BEAM LEGEND
W18X40 C=1"
CAMBERBEAM SIZE
20K20K
BEAM REACTION,
TYP
(8) (8)(4)
QUANTITY OF SHEAR STUDS,
UNIFORMLY SPACED BETWEEN
ADJACENT FRAMING, TYP
(COMPOSITE CONSTRUCTION
ONLY)
NOTES:
1) REACTION VALUE IS ASD (KIPS), UNO.
2) WHERE NO VALUE IS SHOWN, DESIGN CONNECTION FOR A MINIMUM REACTION OF 10 KIPS.
3) SPACE STUDS PER TYPICAL SHEAR STUD PLACEMENT DETAIL. MINIMUM NUMBER OF STUDS
PER GENERAL NOTES.
4) "M" IN PLACE OF BEAM SIZE INDICATES W10X12 WITH MINIMUM CONNECTION.
5) HSS IN PLACE OF SHAPE INDICATES HSS10X4X5/16, UNO.
6) BEAMS ARE PRIMARY MEMBERS FOR FIREPROOFING UNLESS NOTED AS SECONDARY.
7) POSITIVE CAMBER UPWARDS, NEGATIVE CAMBER DOWNWARDS. CAMBER SHOWN
ON CANTILEVERS IS AT END OF CANTILEVER.
MOMENT CONNECTION
CANT BM, SAME SIZE AND
END REACTION AS
BACKSPAN, UNO
C=1/2" CAMBER
SUPPLEMENTAL LOAD LEGEND
JOIST GIRDER
(##K)
ADDITIONAL VERT
LOAD AT INDICATED
JOIST GIRDER PANEL
POINT
NOTES:
1) LOAD IS ASD LIVE LOAD (KIPS), UNO.
2) LOAD IS IN ADDITION TO TYPICAL PANEL POINT LOADS, UNO.
3) LATERAL FORCE TO BE TRANSFERED THROUGH SUPPORT BY CONNECTIONS, IN
ADDITION TO VERTICAL REACTION FORCES. FORCE MAY ACT IN EITHER DIRECTION.
4) TOP CHORD AXIAL FORCE IN ADDITION TO CHORD FORCES PRODUCED BY VERTICAL
LOADS. FORCE MAY BE EITHER COMPRESSION OR TENSION.
##K
J O
IS
T
T
Y P
K
NOTE 3
NOTE 4
MISCELLANEOUS SYMBOLS
NORTH ARROW GRIDLINES
EARTH
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
A
ELEVATION
REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
C# COLUMN NOTATION
Z# PRECAST/ BRICK SUPPORT
L# LINTEL NOTATION
F ## COLUMN FOOTING NOTATION
GB ## GRADE BEAM NOTATION
P ## PIER NOTATION
B ## CONCRETE BEAM NOTATION
PB ## POST-TENSIONED CONCRETE
BEAM NOTATION
PC ## PILE CAP NOTATION
WF ## WALL FOOTING NOTATION
SHEAR WALL NOTATIONSW ##
BW ## BEARING WALL NOTATION
GRAVEL
Name
Elevation
WALL PIER NOTATIONWP ##
W ## WALL NOTATION
CONCRETE SYMBOLS
POST-TENSION TENDON
ANCHOR DEAD END
LOCATION
POST-TENSION TENDON
ANCHOR JACKING
LOCATION
REBAR
CHANGE OF SLAB
ELEVATION
SLOPING SLAB
CHANGE OF SLAB
THICKNESS
MECHANICAL COUPLER
REBAR SPLICE
LIMIT OF MEMBER OR
SPAN MARK
DIRECTION OF SPAN
OPENING
SELF-EXPANDING
WATERSTOP
CONTROL JOINT LOCATION
IN CONCRETE WALLS
REBAR TERMINATOR
INTENTIONALLY
ROUGHENED
CONSTRUCTION JOINT
TO 1/4" AMPLITUDE
WELDED WIRE FABRIC
PVC WATERSTOP
COLUMN CONTINUES
COLUMN TERMINATED
FORM-SAVER
SLAB ON GRADE MARKSOG#
CONNECTORS
HEADED STUD
CONNECTOR SECTION END/ALT VIEW
CAST-IN ANCHOR
ROD
POST-INSTALLED
MECHANICAL ANCHOR
BOLT
POST INSTALLED
ADHESIVE ANCHOR
STEEL MEMBERS
W-SHAPE BEAM
SHAPE SECTION PLAN VIEWELEVATION
CHANNEL
ANGLE
DOUBLE ANGLE
HOLLOW STRUCTURAL
SECTION
-RECTANGULAR
LLV LLH
HOLLOW STRUCTURAL
SECTION
-CIRCULAR (PIPE)
OPEN WEB STEEL
JOIST
STEEL SYMBOLS
STEEL DECK
STEEL DECK MARK AND
SPAN DIRECTION
BEAM SPLICE
CONNECTION
BEAM MOMENT CONNECTION
AT COLUMN
BEAM SHEAR CONNECTION
AT COLUMN
BEAM CONTINUOUS OVER
COLUMN
SLAB ON STEEL
DECK
SLAB ON STEEL
DECK
WWF
COLUMN STARTS HERE
DIAGONAL BRACING
BRACING
HANGER OR POST
HANGER OR POST
BELOW FLOOR
SLAB-ON-DECK MARK AND
SPAN DIRECTION
OR
D#
S#
MASONRY MEMBERS
CMU SECTION
CMU BOND BEAM SECTION
(FULLY GROUTED)
CMU LINTEL SECTION
(FULLY GROUTED)
SINGLE REINFORCEMENT
(FULLY GROUT REINFORCED
CELLS)
DOUBLE REINFORCEMENT
(FULLY GROUT REINFORCED
CELLS)
PLAN
PLAN
JST JOIST
JT JOINT
KB KNEE BRACE
KIP, K 1,000 POUNDS
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE OR LENGTH
LAB LABRATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONGIT LONGITUDINAL
LP LOW POINT
LSL LAMINATED STRAND LUMBER
LSLT LONG SLOTTED HOLE
LTWT LIGHT WEIGHT
LVL LAMINATED VENEER LUMBER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL/ PLUMBING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MULT MULTIPLE
N/A NOT APPLICABLE
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
ORIG ORIGINAL
OVS OVERSIZED HOLE
OWJ PRE-MANUFACTURED OPEN WEB JOIST
PC PRECAST CONCRETE
PEMB PRE-ENGINEERED METAL BUILDING
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PREP PREPARATION, PREPARE
PROJ PROJECTION
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT POST-TENSIONED
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
RO ROUGH OPENING
RTU ROOFTOP MECHANICAL UNIT
S SLOPE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SPA SPACES, SPACE
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
T/ TOP OF
T/GB TOP OF GRADE BEAM
TBS MECHANICAL TENSION BUTT SPLICE
TEMP TEMPERATURE
THRU THROUGH
TJI PREFABRICATED WOOD I-JOIST
TRANS TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS' LABORATORY INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRA-SONIC TEST
VERT VERTICAL
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WH WEEP HOLE
WP WORK POINT
WT WEIGHT, STRUCTURAL T
WWF WELDED WIRE FABRIC
XS EXTRA STRONG (PIPE)
XXS DOUBLE EXTRA STRONG (PIPE)
& AND
A/E ARCHITECT/ENGINEER
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BD BOARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BRKT BRACKET
BTWN BETWEEN
BU BUILT UP
C STANDARD CHANNEL
CANT CANTILEVER
CC CENTER TO CENTER
CF COLD FORMED
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONTROL JOINT OR CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEARANCE, CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTRD CENTERED
CU FT CUBIC FEET
CU IN CUBIC INCH
CYD CUBIC YARD
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DN DOWN
DO DITTO
DP DEEP
DWG DRAWING
DWL DOWELS
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
ENCL ENCLOSURE
ENGR ENGINEER
EOD EDGE OF DECK
EOJ EDGE OF JOIST
EOS EDGE OF SLAB
EQ EQUAL
EQPT EQUIPMENT
ES EACH SIDE
EW EACH WAY
EX EXISTING
EXP EXPANSION
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FT FEET
FTG FOOTING
FTGD FOOTING DRAIN
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GL GLUED LAMINATED TIMBER (GLULAM)
GRND GROUND
GT GIRDER TRUSS
HAS HEADED ANCHOR STUD
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HIP TRUSS
HVAC HEATING, VENTILATION, AIR CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J/BRG JOIST BEARING
STRUCTURAL DRAWINGS ABBREVIATIONS
SHEET # SHEET NAME
5-SS-001 ABBREVIATIONS AND SYMBOLS
5-SS-002 GENERAL NOTES
5-SS-003 SPECIAL INSPECTION REQUIREMENTS
5-SS-004 LOAD MAPS
5-SS-101 PHASE 1 - FOUNDATION PLAN
5-SS-102 PHASE 1 - SLAB-ON-GRADE CONTROL JOINT PLAN
5-SS-201 PHASE 1 - SECOND FLOOR FRAMING PLAN
5-SS-202 PHASE 1 - ROOF FRAMING PLAN
5-SS-202A PHASE 1 - ROOF FRAMING PLAN ALTERNATE
5-SS-203 PHASE 1 - HIGH ROOF FRAMING PLAN
5-SS-301 FOUNDATION SECTIONS AND DETAILS
5-SS-302 FOUNDATION SECTIONS AND DETAILS
5-SS-310 PILE/PILE CAP DETAILS/SCHEDULES
5-SS-401 MASONRY SECTIONS AND DETAILS
5-SS-402 MASONRY SECTIONS AND DETAILS
5-SS-501 FRAMING SECTIONS AND DETAILS
5-SS-601 FRAMING ELEVATIONS
5-SS-602 BRACED FRAME DETAILS
5-SS-701 COLUMN SCHEDULE
STRUCTURAL INDEX
FULLY SPRINKLERED
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Office of Construction and Facilities Management th re e e ig h th s in c h o n e fo o t
EXPAND SPECIALTY
CARE
SUBMISSIONS
REVISIONS
ARCHITECT/ENGINEERS:
7260 SHADELAND STATION
INDIANAPOLIS, IN 46256-3957
TEL 317.547.5580 FAX 317.543.0270
www.structurepoint.com
United States Department of Veterans Affairs R. L. Roudebush VAMC 1481 West 10th Street Indianapolis, Indiana 46202
65% DESIGN DEVELOPMENT 01-23-15
95% CONSTRUCTION DOCUMENTS 02-25-15
11FY14
100% SUBMITTAL DOCUMENTS 05-29-15
BID DOCUMENTS 05-10-17
/5
/2
:3 :2
A
M C
U s e rs
\k m u d d \D o c u m e n ts
\2 .0
.0
S
T V
A I n d y B u ild in g
R
S T
R k m u d d .r v t
ABBREVIATIONS AND SYMBOLS
05-10-17
VA 583-331
R. L. Roudebush VAMC, Indianapolis, IN
5-SS-001
JMK EMS
BIDDING DOCUMENTS
Revision # Description Date
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE
METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE
RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE
SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING
ERECTION. THIS INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
TEMPORARY BRACING, GUYS, AND TIEDOWNS.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL,
ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS AND
SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH
THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A
DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE
MORE STRINGENT REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN
ON THE DRAWINGS, SHALL BE MADE WITHOUT THE APPROVAL OF THE STRUCTURAL
ENGINEER.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER
A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL
BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE
CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETE
OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING
INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION
OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION,
AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND
LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION
OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
9. DESIGN SLUMP RANGE.
10. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
11. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN
ACCORDANCE WITH "STANDARD DEVIATION" DETERMINATION OUTLINED IN
ACI 318.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO
FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE
WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE
REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE
CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO
SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS SUBMITTED WITHOUT
CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF SHOP DRAWINGS. FOR HARD
COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF SHOP DRAWINGS TO THE
STRUCTURAL ENGINEER FOR REVIEW (ONE COPY SHALL BE RETAINED BY THE
STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT SHOP DRAWINGS IN
ADOBE PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. CONCRETE MASONRY REINFORCEMENT (INCLUDING PLANS AND ELEVATIONS
FOR EACH WALL INDICATING ALL CMU REINFORCING REQUIREMENTS,
INCLUDING SHEAR WALLS)
3. CONCRETE MASONRY CONTROL JOINT LOCATIONS
4. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE
PROJECT IS CONSTRUCTED FOR ALL CONNECTIONS NOT SPECIFICALLY
DETAILED ON THE DRAWINGS)
5. STEEL DECK
6. GLASS CURTAIN WALL SYSTEM (INCLUDING DESIGN CALCULATIONS AND
CONNECTION DETAILS SEALED BY A PROFESSIONAL ENGINEER REGISTERED
IN THE STATE WHERE THE PROJECT IS CONSTRUCTED)
7. PILE LAYOUT (INCLUDING TOP AND TIP ELEVATIONS AS WELL AS PILE
REINFORCING)
8. LIGHT GAUGE STEEL FRAMING (INCLUDING DESIGN CALCULATIONS, MEMBER
PROPERTIES, FASTENER REQUIREMENTS, ASSEMBLY DETAILS AND
CONNECTION DETAILS SEALED BY A PROFESSIONAL ENGINEER REGISTERED
IN THE STATE WHERE THE PROJECT IS CONSTRUCTED)
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC
ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE
SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF PRODUCT DATA. FOR HARD
COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF PRODUCT DATA TO THE
STRUCTURAL ENGINEER FOR REVIEW (ONE COPY SHALL BE RETAINED BY THE
STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT PRODUCT DATA IN
ADOBE PDF FORMAT.
1. DIAMOND PLATE DOWELS FOR SLABS ON GRADE
2. CONCRETE CURING COMPOUND
3. CONCRETE JOINT SEALANT
4. WATER STOPS
5. MASONRY JOINT REINFORCEMENT
6. EXPANSION ANCHORS
7. ADHESIVE ANCHORS
8. NON-SHRINK GROUT
FOUNDATIONS
FOUNDATION EXCAVATIONS AND SOIL RELATED WORK SHALL BE PERFORMED IN
ACCORDANCE WITH THE GEOTECHNICAL REPORT NUMBER 86.00481.0321
PREPARED BY CARDNO ATC DATED 10/24/2014.
FOUNDATIONS AND SOILS RELATED WORK SHALL BE INSPECTED BY A LICENSED
GEOTECHNICAL ENGINEER. WRITTEN FIELD REPORTS SHALL BE FORWARDED TO THE
STRUCTURAL ENGINEER AS SOON AS THEY BECOME AVAILABLE.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM
THOSE DESCRIBED IN THE GEOTECHNICAL REPORT, SHALL BE REPORTED TO THE
STRUCTURAL ENGINEER AND GEOTECHNICAL ENGINEER BEFORE FURTHER
CONSTRUCTION IS ATTEMPTED.
EXCAVATIONS FOR SPREAD FOOTINGS, GRADE BEAMS, PILE CAPS, COMBINED FOOTINGS,
CONTINUOUS FOOTINGS AND MAT FOUNDATIONS SHALL BE CLEANED AND HAND TAMPED
TO UNIFORM SURFACE AND SHALL BE PROTECTED AND MAINTAINED UNIFORM UNTIL
CONCRETE IS PLACED.
DESIGN ALLOWABLE PILE LOADS:
16" DIA WITH PILE TIP ELEVATIONS OF 660.00'
COMPRESSION: 100 KIPS
TENSION: 30 KIPS
LATERAL: 12 KIPS
PILE LENGTHS ARE FOR BIDDING PURPOSES ONLY. SEE SPECIFICATIONS FOR
DELEGATED DESIGN CRITERIA.
BELOW-GRADE WALLS
DO NOT BACKFILL AGAINST BELOW-GRADE CONCRETE (OR MASONRY) WALLS UNTIL
THE CONCRETE (OR MASONRY ASSEMBLAGE) HAS REACHED ITS 28-DAY
COMPRESSIVE STRENGTH.
WHERE BACKFILL IS REQUIRED ON BOTH SIDES OF BELOW-GRADE WALLS, BACKFILL
EVENLY ON EACH SIDE OF EACH WALL TO PREVENT UNBALANCED SOIL LOADS
AGAINST THE WALL.
PERIMETER INSULATION
PERIMETER INSULATION SHOWN ON THE STRUCTURAL DRAWINGS IS FOR GENERAL
VISUAL REFERENCE ONLY. SEE THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS
FOR EXACT LOCATION, PLACEMENT, THICKNESS AND MATERIAL REQUIREMENTS.
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING
CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318) AND COMMENTARY
(ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE
LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301).
READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94.
IN CASE OF A DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT
(BY WEIGHT) OF FLY ASH TO TOTAL CEMENTITIOUS MATERIALS IN THE MIX SHALL NOT
EXCEED 25 PERCENT.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE
CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN
0.1 PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON
THE DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL BE USED IN THE FOLLOWING AREAS AND SHALL
HAVE THE PROPERTIES AS SHOWN BELOW:
FOOTINGS, PILE CAPS, MAT FOUNDATIONS, WALLS, AND GRADE BEAMS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING
ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS ADDED TO CONCRETE WITH
2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCHES
7. AIR CONTENT: N/A
ENTRANCE PLATFORMS, RETAINING WALLS, AND CURBS/SIDEWALKS/SLABS EXPOSED
TO DE-ICERS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 517 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING
ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS ADDED TO CONCRETE WITH
2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.45
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: 5.5% +/- 1%
INTERIOR SLABS ON GRADE
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING
ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS ADDED TO CONCRETE WITH
2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: N/A
INTERIOR SLABS ON METAL DECK
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING
ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS ADDED TO CONCRETE WITH
2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: N/A
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM A185.
FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND LAPPED A MINIMUM OF ONE SPACE
PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED AS FOLLOWS, UNLESS NOTED OTHERWISE:
SLABS ON GRADE: 2 INCHES DOWN FROM TOP OF SLAB.
SLABS ON METAL DECK: 3/4 INCH DOWN FROM TOP OF SLAB.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH
DAY'S POUR AND FOR EACH 100 CUBIC YARDS. EACH SET SHALL INCLUDE ONE
SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT 28 DAYS AND ONE SPECIMEN
RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION OF THE STRUCTURAL
ENGINEER. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER CASTING UNLESS
DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST
CYLINDERS SHALL BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES
DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN
ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED.
THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED
UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL CURING BOXES
ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER,
READY-MIX SUPPLIER AND CONTRACTOR WITHIN 24 HOURS AFTER TESTING.
CONCRETE UNIT MASONRY
CONCRETE MASONRY HAS BEEN DESIGNED IN ACCORDANCE WITH THE LATEST
EDITION OF THE BUILDING CODE REQUIREMENTS FOR CONCRETE MASONRY
STRUCTURES (ACI 530).
CONCRETE MASONRY SHALL CONSIST OF HOLLOW UNITS CONFORMING TO THE
REQUIREMENTS OF ASTM C90, WITH A MINIMUM NET AREA COMPRESSIVE STRENGTH
OF 1900 PSI. CONCRETE MASONRY ASSEMBLAGES SHALL HAVE A MINIMUM
COMPRESSIVE STRENGTH (F'M) OF 1,500 PSI AT 28 DAYS.
MORTAR SHALL BE TYPE S PROPORTIONED IN ACCORDANCE WITH ASTM C270.
GROUT FOR REINFORCED MASONRY SHALL BE PROPORTIONED IN ACCORDANCE WITH
ASTM C476. COARSE AND FINE AGGREGATES SHALL CONFORM TO ASTM C404. USE
COARSE GROUT FOR ALL GROUTING EXCEPT HIGH-LIFT POURS DEFINED BY ACI 530-05
TABLE 1.16.1, WHERE FINE GROUT SHALL BE USED.
PROVIDE 9-GAUGE GALVANIZED STEEL WIRE JOINT REINFORCEMENT IN ALL MASONRY
CONSTRUCTION. REINFORCEMENT SHALL BE CONTINUOUS AND BE LAPPED EIGHT
INCHES AT SPLICES. CUT REINFORCEMENT AT ALL CONTROL AND EXPANSION JOINTS.
SPACE REINFORCEMENT AT 8" ON CENTER FOR PARAPETS AND BELOW GROUND
FLOOR ELEVATION. ELSEWHERE SPACE REINFORCEMENT AT 16 INCHES ON CENTER.
BEAMS AND LINTELS SHALL BEAR A MINIMUM OF 8 INCHES ONTO SUPPORTING
MASONRY, UNLESS NOTED OTHERWISE. BEARING FOR ALL BEAMS, LINTELS, AND
JOISTS. SHALL BE GROUTED SOLID A MINIMUM OF ONE COURSE (8 INCHES)
BELOW BEARING ELEVATION, UNLESS NOTED OTHERWISE.
PROVIDE MASONRY CONTROL JOINTS AT 30'-0" OC MAXIMUM, UNO. LOCATE JOINTS IN
ACCORDANCE WITH NCMA TEK 10-2C "CONTROL JOINST FOR CONCRETE MASONRY
WALLS - EMPIRICAL METHOD" AT OFFSETS, SETBACKS, WALL INTERSECTIONS, CORNERS,
CHANGES IN THICKNESS, CHANGES IN HEIGHT, OR EDGE OF OPENINGS.
STRUCTURAL STEEL - ASD
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO
THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST
EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE
SHAPES SHALL CONFORM TO ASTM A36, UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
STRUCTURAL STEEL ROD HANGERS AND BRACING SHALL CONFORM TO ASTM A36,
UNLESS NOTED OTHERWISE.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED
OTHERWISE.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL
JOINTS USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL
ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED
CONNECTIONS FOR STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4"
DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE. BOLTED CONNECTIONS SHALL BE
TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN
BRACE ELEMENTS ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN
WELDING SOCIETY'S STRUCTURAL WELDING CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE
WITH E70XX LOW HYDROGEN ELECTRODES. UNLESS OTHERWISE SHOWN OR NOTED
ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD
E70XX ELECTRODES.
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A
RUST-INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM
SPECIFIED BY THE ARCHITECT. COORDINATE FINISH PAINTING REQUIREMENTS
WITH THE ARCHITECT.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN
CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN
ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE.
FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT.
FOR GALVANIZED STEEL, USE A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION
AND MANUAL OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE ON THE
DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM OF A
10 KIP SHEAR REACTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF
BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
PROVIDE L4X4X1/4 FRAMED OPENINGS FOR ALL ROOF PENETRATIONS 12 INCHES OR
LARGER ALONG ANY SIDE, UNLESS LARGER FRAMING IS INDICATED. REFER TO
MECHANICAL AND PLUMBING DRAWINGS FOR PENETRATIONS. COORDINATE FRAMED
OPENING SIZES AND LOCATIONS WITH THE MECHANICAL AND PLUMBING
CONTRACTORS.
STEEL ROOF DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE
STEEL DECK INSTITUTE'S SPECIFICATIONS AND CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL ROOF DECK ACCESSORIES, INCLUDING
CLOSURES, SUPPLEMENTARY FRAMING, AND SUMP PANS, WHETHER OR NOT SUCH
ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN ROOF DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS.
PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
ROOF DECK SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION.
PROVIDE STEEL ROOF DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
STEEL FLOOR DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE
STEEL DECK INSTITUTE'S SPECIFICATIONS AND CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL FLOOR DECK ACCESSORIES, SUCH AS
EDGE FORMS, CLOSURES, FILLERS AND POUR STOPS FOR A COMPLETE INSTALLATION,
WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN FLOOR DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS.
PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
STEEL FLOOR DECK IS INTENDED TO BE INSTALLED IN AN UNSHORED CONDITION
UNLESS NOTED OTHERWISE. DECK SUPPLIER SHALL REVIEW ALL SPAN CONDITIONS
AND CONFIRM THAT THE SUPPLIED PRODUCT IS SUFFICIENT TO SAFELY SUPPORT THE
WET WEIGHT OF CONCRETE AND ASSOCIATED CONSTRUCTION LIVE LOADS WITHOUT
THE NEED FOR SHORING.
FLOOR DECK UNITS SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION.
PROVIDE INTERIOR STEEL FLOOR DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
PROVIDE FLOOR DECK SUPPORTING EXTERIOR SLABS WITH A GALVANIZED FINISH IN
ACCORDANCE WITH ASTM A924 G90.
CONCRETE SLABS ON METAL DECK
UNLESS INDICATED OTHERWISE ON THE DRAWINGS, CONCRETE SLABS ON METAL
DECK SHALL BE PLACED AS REQUIRED TO MAINTAIN A CONSTANT
SLAB THICKNESS.
CONTRACTOR SHALL ALLOW FOR THE DEFLECTION OF THE FLOOR ASSEMBLY DUE TO
THE WET WEIGHT OF THE CONCRETE WHEN CALCULATING CONCRETE QUANTITIES
AND SHALL INCLUDE THE COST OF ALL REQUIRED SLAB-ON-DECK CONCRETE IN THE
BID PRICE.
PRIOR TO PLACEMENT OF CONCRETE SLABS ON METAL DECK, THE CONTRACTOR
SHALL CAREFULLY REVIEW THE ELEVATIONS OF THE STRUCTURAL STEEL FRAMING,
INCLUDING CAMBERED MEMBERS, FOR CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS. CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY
DISCREPANCIES (SUCH AS IMPROPER CAMBER, AND IMPROPER STEEL ELEVATIONS)
IMMEDIATELY AND SHALL NOT BEGIN CONCRETE PLACEMENT WITHOUT PRIOR
REVIEW BY THE STRUCTURAL ENGINEER.
ACTUAL CONCRETE SLAB THICKNESS SHALL NOT BE LESS THAN THE INDICATED
NOMINAL THICKNESS AT ANY LOCATION. IF ANY CONDITION IS DISCOVERED THAT
WOULD PREVENT PLACEMENT OF CONCRETE TO THE NOMINAL THICKNESS;
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL
NOT PROCEED WITH CONCRETE PLACEMENT WITHOUT PRIOR REVIEW BY THE
STRUCTURAL ENGINEER.
SLABS ON METAL DECK SHALL RECEIVE A SMOOTH TROWEL FINISH, AND BE PLACED
TO ACHIEVE THE FOLLOWING MINIMUM TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX.
DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST
SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON
THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A
SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO
ASTM C309. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE
RECOATED DAILY. OTHER CURING METHODS MAY BE USED WITH APPROVAL BY THE
STRUCTURAL ENGINEER.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND
SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE
LATEST EDITION OF THE FOLLOWING STANDARDS: ACI 301, ACI 315, ACI 318 AND
ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE
THE FOLLOWING MINIMUM CONCRETE COVER OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 INCHES
#6 BARS AND LARGER EXPOSED TO EARTH OR WEATHER: 2 INCHES
#5 BARS AND SMALLER EXPOSED TO EARTH OR WEATHER: 1-1/2 INCHES
BEAM AND COLUMN TIES, STIRRUPS AND SPIRALS: 1-1/2 INCHES
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 3/4 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT
UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR APPROVED BY THE
STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE
STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT
CORNERS OF ALL WALLS AND GRADE BEAMS. LAP SPLICE CORNERS BARS WITH
STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE)
AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE
BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
DESIGN DATA
THE BUILDING STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE
2012 INTERNATIONAL BUILDING CODE.
FLOOR LOADS
OFFICE SPACE
SEE LOAD MAPS
STAIRS AND PUBLIC AREAS
SEE LOAD MAPS
UNLESS OTHERWISE NOTED, FLOOR FRAMING HAS BEEN DESIGNED UTILIZING LIVE
LOAD REDUCTIONS TO THE EXTENT ALLOWED BY THE BUILDING CODE.
ROOF LOADS
SEE LOAD MAPS
SNOW LOAD DESIGN DATA
1. GROUND SNOW LOAD (PG) = 20 PSF
2. LOW-SLOPE ROOF SNOW LOAD (PF) = 20.0 PSF
3. SNOW EXPOSURE FACTOR (CE) = 1.0
4. THERMAL FACTOR (CT) = 1.0
5. SNOW LOAD IMPORTANCE FACTOR (IS) = 1.0
WIND LOAD DESIGN DATA
1. BASIC WIND SPEED (3-SECOND GUST) = 115 MPH
2. RISK CATEGORY = II
3. WIND EXPOSURE = C
4. WIND DESIGN PRESSURE (P) = VARIES WITH HEIGHT AND LOCATION
EARTHQUAKE DESIGN DATA
1. SHORT PERIOD SPECTRAL RESPONSE (SS) = 0.159
2. 1-SECOND SPECTRAL RESPONSE (S1) = 0.086
3. SEISMIC IMPORTANCE FACTOR (IE) = 1.00
4. RISK CATEGORY = II
5. SEISMIC DESIGN CATEGORY = B
6. SITE CLASSIFICATION = C
7. SHORT PERIOD SPECTRAL RESPONSE COEFFICIENT (SDS) = 0.127
8. 1-SECOND SPECTRAL RESPONSE COEFFICIENT (SD1) = 0.097
9. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM:
a. BEARING WALL / ORDINARY REINFORCED MASONRY SHEAR WALLS
b. STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE
10. ANALYSIS PROCEDURE UTILIZED = EQUIVALENT LATERAL FORCE PROCEDURE
11. RESPONSE MODIFICATION COEFFICIENT: (R) = 2.0 (ORDINARY REINFORCED
MASONRY SHEAR WALLS)
(R) = 3.0 (STEEL SYSTEMS NOT
SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE)
12. SEISMIC RESPONSE COEFFICIENT (CS) = 0.064 (R=2) (LONG DIRECTION)
(CS) = 0.042 (R=3) (SHORT DIRECTION)
CONCRETE SLABS ON GRADE
SLABS ON GRADE SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST
EDITION OF THE GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION (ACI 302.1R).
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX.
DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST
SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON
THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A
SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO
ASTM C309, UNLESS NOTED OTHERWISE. ALL SCUFFS OR ABRASIONS TO THE CURING
MEMBRANE SHALL BE RECOATED DAILY. OTHER CURING METHODS MAY BE USED
WITH APPROVAL BY THE STRUCTURAL ENGINEER.
SLABS ON GRADE SHALL RECEIVE A SMOOTH TROWEL FINISH, AND BE PLACED TO
ACHIEVE THE FOLLOWING MINIMUM TOLERANCES:
OVERALL VALUES: FF = 25 FL = 20
LOCAL VALUES: FF = 20 FL = 15
THE MINIMUM LOCAL AREA SHALL BE ANY BAY DEFINED BY COLUMN LINES.
UNLESS SHOWN OR NOTED OTHERWISE, PROVIDE CONTROL OR CONSTRUCTION
JOINTS IN SLABS-ON-GRADE AT A MAXIMUM SPACING OF 36 TIMES THE SLAB
THICKNESS. PROVIDE JOINTS AT ALL COLUMN LOCATIONS. LOCATE JOINTS TO
ELIMINATE RE-ENTRANT CORNERS AND TO CREATE SQUARE OR RECTANGULAR
SECTIONS WITH MAXIMUM LONG SIDE TO SHORT SIDE RATIO OF 1.5 TO 1.
CONTROL JOINTS IN SLABS ON GRADE SHALL NOT RECEIVE JOINT FILLER MATERIAL
UNLESS NOTED OTHERWISE.
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE HILTI “KWIK BOLT TZ” OR AN EQUIVALENT SUBSTITUTE
APPROVED BY THE STRUCTURAL ENGINEER, UNO.
ANCHOR FINISH SHALL BE CARBON STEEL FOR INTERIOR EXPOSURES AND
AISI 316 STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER’S REPRESENTATIVE.
ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR MASONRY UNTIL IT HAS
ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE STRENGTH.
ADHESIVE ANCHORS FOR SOLID SUBSTRATES
ADHESIVE ANCHORS FOR SOLID SUBSTRATES SHALL BE HILTI "HIT-HY 200" OR AN
EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNO.
ANCHORS SHALL BE ASTM A36 THREADED RODS FOR INTERIOR EXPOSURES AND
AISI 316 STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
ADHESIVE ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR MASONRY UNTIL IT
HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE STRENGTH.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED
OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN
ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED,
NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA
SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS.
GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF 5,000 PSI IN
28 DAYS.
WATERSTOPS
SELF-EXPANDING STRIP WATER STOPS SHALL BE 101 UNLESS NOTED OTHERWISE.
INSTALL IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
ADHESIVE ANCHORS FOR HOLLOW SUBSTRATES
ADHESIVE ANCHORS FOR HOLLOW SUBSTRATES SHALL BE HILTI "HIT-HY 70" WITH
HILTI “HIT-SC” SCREEN TUBE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE
STRUCTURAL ENGINEER, UNO.
ANCHORS SHALL BE ASTM A36 THREADED RODS FOR INTERIOR EXPOSURES AND
AISI 316 STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
BRICK VENEER MASONRY
PROVIDE EXPANSION JOINTS IN ACCORDANCE WITH THE ARCHITECTURAL
DRAWINGS AND SPECIFICATIONS.
IF BRICK EXPANSION JOINT LOCATIONS ARE NOT INDICATED ON THE
ARCHITECTURAL DRAWINGS OR IN THE SPECIFICATIONS, SUBMIT PROPOSED
EXPANSION JOINT LOCATIONS TO THE ARCHITECT AND STRUCTURAL ENGINEER
FOR REVIEW PRIOR TO CONSTRUCTION. UNLESS INDICATED OTHERWISE,
PROVIDE EXPANSION JOINTS AT 20'-0" OC MAXIMUM. LOCATE JOINTS IN
ACCORDANCE WITH BIA TECHNICAL NOTE 18A "ACCOMMODATING EXPANSION OF
BRICKWORK" AT OFFSETS, SETBACKS, WALL INTERSECTIONS, CORNERS,
CHANGES IN THICKNESS, CHANGES IN HEIGHT, OR EDGES OF OPENINGS.
SEPARATION OF DISSIMILAR METALS
DISSIMILAR METALS SHALL BE ELECTRICALLY ISOLATED TO PREVENT GALVANIC
CORROSION VIA NON-CONDUCTIVE WASHERS, GASKETS, COATINGS, OR EQUIVALENT
SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNO.
GLASS CURTAIN WALLS
SUPPLIER OF GLASS CURTAIN WALL IS RESPONSIBLE FOR THE DESIGN, DETAILING
AND INSTALLATION OF THE CURTAIN WALL SYSTEM.
STEEL REQUIRED TO TRANSMIT THE GRAVITY AND/OR LATERAL LOADS TO THE
STRUCTURE NOT DETAILED ON THE STRUCTURAL DRAWINGS IS THE RESPONSIBILITY
OF THE CURTAIN WALL SUPPLIER TO DESIGN, DETAIL AND INSTALL.
CONNECTIONS TO TRANSMIT LATERAL LOADS TO THE STRUCTURE SHALL NOT BE
MADE TO THE BOTTOM FLANGES OF BEAMS, BOTTOM CHORDS OF JOIST GIRDERS OR
BOTTOM CHORDS OF JOISTS WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER.
ELEVATORS
CONTRACTOR SHALL COORDINATE ELEVATOR PITS, SHAFTS, SLAB OPENINGS,
FRAMING LOCATIONS, GUIDE RAIL SUPPORTS, DIVIDER BEAMS, HOIST BEAMS AND
SUMP PITS WITH ELEVATOR SUPPLIER PRIOR TO CONSTRUCTION AS REQUIRED FOR
PROPER INSTALLATION AND OPERATION.
COORDINATE ANY REQUIRED STRUCTURAL MODIFICATIONS WITH THE STRUCTURAL
ENGINEER PRIOR TO FABRICATION AND/OR INSTALLATION OF ANY STRUCTURAL
ELEMENTS.
FULLY SPRINKLERED
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Office of Construction and Facilities Management th re e e ig h th s in c h o n e fo o t
EXPAND SPECIALTY
CARE
SUBMISSIONS
REVISIONS
ARCHITECT/ENGINEERS:
7260 SHADELAND STATION
INDIANAPOLIS, IN 46256-3957
TEL 317.547.5580 FAX 317.543.0270
www.structurepoint.com
United States Department of Veterans Affairs R. L. Roudebush VAMC 1481 West 10th Street Indianapolis, Indiana 46202
65% DESIGN DEVELOPMENT 01-23-15
95% CONSTRUCTION DOCUMENTS 02-25-15
11FY14
100% SUBMITTAL DOCUMENTS 05-29-15
BID DOCUMENTS 05-10-17
/5
/2
:3 :2
A
M C
U s e rs
\k m u d d \D o c u m e n ts
\2 .0
.0
S
T V
A I n d y B u ild in g
R
S T
R k m u d d .r v t
GENERAL NOTES
05-10-17
VA 583-331
R. L. Roudebush VAMC, Indianapolis, IN
5-SS-002
JMK EMS
BIDDING DOCUMENTS
AUGER CAST PILES
SEE SPECIFICATION SECTION 316316 - AUGER CAST GROUT PILES FOR MORE
INFORMATION.
SPECIAL INSPECTION SERVICES SCHEDULE - CONCRETE CONSTRUCTION
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK
TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION
APPLICABLE TO
PROJECT (Y/N)
FREQUENCY
MATERIAL TESTING
QUALITY CONTROL
REINFORCING STEEL
CAST-IN-PLACE
BOLTS AND
ANCHOR RODS
CONCRETE MIX
DESIGN
FORMWORK
MATERIAL SAMPLING
AND TESTING
CONCRETE
PLACEMENT
CURING AND
PROTECTION
CONSTRUCTION
JOINTS
TEST
REFERENCE CAST-IN-PLACE CONCRETE SPECIFICATION FOR EXTENT OF TESTING
REQUIRED
INSPECTION VERIFY THAT QUALITY CONTROL TESTING IS PROVIDED IN ACCORDANCE WITH THE
PROJECT REQUIREMENTS.
INSPECTION
INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS (WHEN
USED) AND PLACEMENT AS FOLLOWS:
VERIFY THAT REINFORCEMENT SURFACES ARE FREE OF EXCESS RUST OR OTHER
COATINGS THAT MAY ADVERSELY AFFECT BONDING CAPACITY. IF OILING OF FORMS
IS REQUIRED, VERIFY THAT IT IS APPLIED BEFORE REINFORCING IS PLACED.
VERIFY REINFORCING BARS FOR COMPLIANCE WITH CONTRACT DOCUMENTS AND
APPROVED SHOP DRAWINGS AS FOLLOWS:
MATERIAL GRADE, SIZE, QUANTITY, SPACING, AND LAYERING; BARS ARE
ADEQUATELY TIED AND SUPPORTED ON CHAIRS OR BOLSTERS; PROPER HOOK
TYPE AND LOCATION; SPLICE LOCATIONS AND REQUIRED LENGTH OF LAP;
PROPER CLEARANCE AND COVER REQUIREMENTS FROM CONCRETE SURFACES;
SUFFICIENT SPACING BETWEEN REINFORCEMENT FOR CONCRETE PLACEMENT;
VERIFY THAT UNSCHEDULED/ADDITIONAL REINFORCING BARS SHOWN ON
PLAN, IN DETAIL, OR SPECIFIED IN NOTES ARE PROVIDED AND ARE IN
COMPLIANCE WITH CONTRACT DOCUMENTS AND APPROVED SHOP DRAWINGS.
MECHANICAL SPLICES:
(TENSION AND/OR COMPRESSION) ON THE PROJECT. VERIFY COMPLIANCE
WITH SPECIFICATIONS AND CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS FOR INSTALLATION. VERIFY THAT THE MANUFACTURER IS
PRESENT FOR THE FIRST INSTALLATION OF EACH TYPE OF SPLICE ON THE
PROJECT.
VERIFY THAT WELDED WIRE REINFORCEMENT IS COMPOSED OF FLAT SHEETS, HAS
PROPER WIRE GAUGE AND SPACING, IS PROPERLY SUPPORTED, AND IS PROPERLY
LAPPED.
INSPECT HEADED STUD SHEAR REINFORCEMENT TO ENSURE THAT IT CONFORMS
TO THE PROJECT REQUIREMENTS:
REVIEW TYPE AND SPACING; VERIFY THAT REINFORCING IS ADEQUATELY
SUPPORTED TO RESIST DISPLACEMENT OR SHIFTING DURING CONCRETE
PLACEMENT; VERIFY WELDING OF REINFORCEMENT IS PERFORMED ACCORDING
TO AWS REQUIREMENTS AND THAT IT IS INSPECTED BY THE TESTING
LABORATORY.
INSPECT BOLTS AND ANCHOR RODS TO BE CAST IN CONCRETE PRIOR TO PLACEMENT OF
CONCRETE FOR SIZE, QUANTITY, LOCATION, POSITION AND EMBEDMENT. INSPECT
DURING PLACEMENT FOR PROPER CONCRETE CONSOLIDATION AROUND BOLTS AND
ANCHORS.
ALLOWABLE LOADS HAVE BEEN INCREASED PER PLAN NOTESINSPECTION
BOLTS AND/OR ANCHOR RODS USED IN LATERAL FORCE RESISTING SYSTEM AT THE
FOLLOWING LOCATIONS: A1, A2, C1, E1, G1, AND G2
20% OF BOLTS AND/OR ANCHOR RODS USED ELSEWHERE.
INSPECTION
REVIEW AND BECOME FAMILIAR WITH THE MIX DESIGNS SPECIFIED ON THE
PROJECT. VERIFY MIX DESIGN PROVIDED BY THE CONTRACTOR IS CONSISTENT WITH
PROJECT SPECIFICATIONS AT LOCATION INDICATED. REVIEW CONCRETE BATCH
TICKETS TO PROPER MIX ID, TYPE OF CONCRETE AND STRENGTH FOR THE PLACEMENT
LOCATION. VERIFY THAT WATER ADDED AT SITE (IF PERMITTED), DOES NOT EXCEED
THAT ALLOWED BY THE MIX DESIGN.
INSPECTION OF
FORMED AREA
INSPECTION VERIFY THAT ALL DEBRIS AND FOREIGN MATTER HAVE BEEN REMOVED BEFORE
CONCRETE IS PLACED
INSPECTION
INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE
MEMBER BEING FORMED. VERIFY FORMWORK USED IN COMPLIANCE WITH THE
SPECIFICATIONS AND APPROVAL SHOP DRAWINGS (WHEN REQUIRED).
TEST
AT THE TIME FRESH CONCRETE IS SAMPLED TO FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE
INSPECTION
INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES AS FOLLOWS:
VERIFY THE CONCRETE IS NOT OVER 90 MINUTES OLD AT TIME OF PLACEMENT;
HOT-WEATHER OR COLD-WEATHER TECHNIQUES ARE BEING APPLIED AS
REQUIRED; CONCRETE BEING DEPOSITED IN UNIFORM, THAT THE VERTICAL DROP
DOES NOT EXCEED SIX FEET, AND THAT CONCRETE IS NOT PERMITTED TO DROP
FREELY OVER REINFORCEMENT CAUSING SEGREGATION; CONCRETE IS PROPERLY
VIBRATED; EMBEDDED ITEMS AND REINFORCING STEEL ARE NOT ADVERSELY
ALTERED DURING PLACEMENT. NOTE IF ANYTHING WAS DISPLACED OR
OTHERWISE ALTERED DURING PLACEMENT; VERIFY THAT THERE ARE NO COLD
JOINTS WITHIN THE AREA OF THE POUR
INSPECTION
VERIFY THE CURING PROCESS IS AS SPECIFIED IN THE CONTRACT DOCUMENTS AND
THAT ANY CURING COMPOUND USED IS APPLIED IN ACCORDANCE WITH
MANUFACTURER'S PRINTED APPLICATION INSTRUCTIONS.
INSPECTION
VERIFY THAT LOCATION OF VERTICAL AND HORIZONTAL CONSTRUCTION JOINTS FOR
COMPLIANCE WITH THE CONSTRUCTION JOINT LOCATION PLAN SUBMITTED BY THE
CONTRACTOR TO ENGINEER OF RECORD. VERIFY THAT REINFORCEMENT, DOWELS, KEYS,
AND BULKHEADS AT CONSTRUCTION JOINTS ARE IN CONFORMANCE WITH THE
CONTRACT DOCUMENTS.
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
PERIODIC
PERIODIC
PERIODIC
CONTINUOUS
PERIODIC
PERIODIC
CONTINUOUS
CONTINUOUS
PERIODIC
PERIODIC
PERIODIC
PERIODIC
CONTINUOUS
CONTINUOUS
PERIODIC
PERIODIC
N
CONTINUOUS
SPECIAL INSPECTION SERVICES SCHEDULE - FOUNDATION WALLS AND PITS
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK
TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION APPLICABLE TO
PROJECT (Y/N)
FREQUENCY
CONCRETE
PLACEMENT
FORMWORK
DIMENSIONS
EMBEDDED ITEMS
REINFORCEMENT
BACKFILL
OPERATIONS
CONCRETE
INSPECTION
THE INSPECTOR MUST BE PRESENT FULL TIME DURING THE ENTIRE PLACEMENT
OF THE FIRST 2 SHALLOW FOUNDATION CONCRETE POURS AND THEN MUST BE
PRESENT AT THE START OF 100% OF OTHER CONCRETE POURS.
INSPECTION VERIFY THAT FORMS ARE PLUMB AND STRAIGHT, BRACED AGAINST MOVEMENT,
AND LUBRICATED FOR REMOVAL.
INSPECTION
INSPECTION
INSPECTION
WATERSTOPS INSPECTION
INSPECTION
INSPECTION
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
VERIFY WALL/PIT DIMENSIONS.
VERIFY ANCHOR RODS AND/OR DOWELS ARE INSTALLED WITH THE EMBEDMENT
AND PROJECTED LENGTHS AND IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
VERIFY PIT/WALL REINFORCEMENT PRIOR TO PLACEMENT OF CONCRETE
VERIFY WATER STOPS ARE PROPERLY INSTALLED AND ANCHORED INTO POSITION
PRIOR TO PLACEMENT OF CONCRETE.
VERIFY THAT FOUNDATION AND PIT WALLS WITH UNEVEN BACKFILL CONDITIONS
ARE NOT BACKFILLED UNTIL FLOOR CONSTRUCTION AT TOP OF WALL IS COMPLETE
OR TEMPORARY BRACING IS PROVIDED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
VERIFY CONCRETE PLACEMENT AS OUTLINED IN THIS INSPECTION PLAN.
Y
Y
Y
Y
Y
Y
Y
Y
SPECIAL INSPECTION SERVICES SCHEDULE - MASONRY CONSTRUCTION
(LEVEL 1 INSPECTION)
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK
TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION
APPLICABLE TO
PROJECT (Y/N)
FREQUENCY
MATERIAL TESTING
QUALITY CONTROL
TEST REFERENCE MASONRY SPECIFICATION FOR EXTENT OF TESTING REQUIRED
INSPECTION
VERIFY THAT QUALITY CONTROL TESTING IS PROVIDED IN ACCORDANCE WITH THE
PROJECT REQUIREMENTS.
Y PERIODIC
CONTINUOUS
MATERIALS
WALL LOCATIONS
CONTROL JOINTS
OPENINGS
CONNECTIONS
REINFORCING STEEL
MORTAR AND GROUT
PROTECTION
EMBEDDED ITEMS
VERIFY THE MATERIALS ARE STORED PROPERLY BEFORE PLACEMENT IN THE STRUCTURE
VERIFY THE WALL LOCATIONS AND THICKNESSES
VERIFY THE PROPER INSTALLATION OF CONTROL JOINTS, TYPE AND LOCATION
VERIFY THE PROPER INSTALLATION OF STRUCTURAL ELEMENTS AROUND OPENINGS
INCLUDING LINTELS, SILLS, AND DOOR OR WINDOW JAMBS INCLUDING MASONRY UNIT
TYPE AND REINFORCEMENT
VERIFY THE MASONRY IS PROPERLY CONNECTED TO THE SUPPORTING STRUCTURE(S)
INSPECTION OF REINFORCING STEEL AND PLACEMENT AS FOLLOWS:
VERIFY THAT REINFORCEMENT SURFACES ARE FREE OF EXCESS RUST OR OTHER
COATINGS THAT MAY ADVERSELY AFFECT BONDING CAPACITY.
VERIFY REINFORCING BARS AND HORIZONTAL JOINT REINFORCEMENT FOR COMPLIANCE
WITH CONTRACT DOCUMENTS AND APPROVED SHOP DRAWINGS AS FOLLOWS:
MATERIAL GRADE, SIZE, QUANTITY, SPACING, AND LAYERING; BARS ARE ADEQUATELY
TIED AND SUPPORTED ON CHAIRS AND CENTERED AS REQUIRED; PROPER HOOK TYPE
AND LOCATION; SPLICE LOCATIONS AND REQUIRED LENGTH OF LAP; PROPER
CLEARANCE AND COVER REQUIREMENTS FROM MASONRY SURFACES; SUFFICIENT
SPACING BETWEEN REINFORCEMENT FOR GROUT PLACEMENT; VERIFY THAT
UNSCHEDULED/ADDITIONAL REINFORCING BARS SHOWN ON PLAN, IN DETAILS, OR
SPECIFIED IN NOTES ARE PROVIDED AND ARE IN COMPLIANCE WITH CONTRACT
DOCUMENTS AND APPROVED SHOP DRAWINGS.
INSPECT EMBEDDED ITEMS TO BE CAST IN MASONRY PRIOR TO PLACMENT OF GROUT
FOR SIZE, QUANTITY, LOCATION, POSITION AND EMBEDMENT. INSPECT DURING
PLACEMENT FOR PROPER GROUT CONSOLIDATION EMBEDDED ITEMS.
INSPECT THE MORTAR AND GROUT USED ON THE PROJECT AS FOLLOWS:
VERIFY THAT MORTAR AND GROUT MATERIALS COMPLY WITH THE CONTRACT
DOCUMENTS AND APPROVED SUBMITTALS.
SITE-MIXED MORTAR: VERIFY THE MORTAR IS MIXED IN ACCORDANCE WITH SPECIFIED
PROPORTIONS.
BAG-MIX MORTAR: VERIFY THE MORTAR IS MIXED ACCORDING TO THE
MANUFACTURER’S INSTRUCTIONS.
VERIFY PROPER MORTAR PLACEMENT.
GROUT BAG MIX: VERIFY THAT THE GROUT IS MIXED ACCORDING TO THE
MANUFACTURER’S INSTRUCTIONS.
READY-MIX GROUT: VERIFY THE MIX NUMBER AND GROUT STRENGTH.
PRIOR TO ANY GROUTING PROCEDURE, INSPECT THE GROUT SPACE TO VERIFY THAT
IT IS CLEAN AND THAT CLEANOUTS, IF REQUIRED, ARE IN PLACE AND CONFORM TO
REQUIREMENTS OF THE CONTRACT DOCUMENTS.
VERIFY THE PROPER GROUT PLACEMENT AND CONSOLIDATION.
VERIFY THAT GROUT TESTING IS PERFORMED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
VERIFY THE PROPER CONSTRUCTION TECHNIQUES ARE FOLLOWED FOR PROTECTION
OF MASONRY DURING HOT-WEATHER AND/OR COLD-WEATHER CONSTRUCTION.
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
INSPECTION
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
PERIODIC
SPECIAL INSPECTION SERVICES SCHEDULE - STEEL CONSTRUCTION
REFERENCED STANDARDS PER IBC, CHAPTER 17
VERIFICATION AND
INSPECTION TASK TEST / INSPECTION DESCRIPTION OF TEST / INSPECTION
APPLICABLE TO
PROJECT (Y/N) FREQUENCY
FABRICATOR QUALITY
CONTROL PROCESS
QUALITY
MILL TEST REPORTS
WELDED
CONNECTIONS
BOLTED
CONNECTIONS
STEEL FRAMING,
DETAILS AND
CONNECTORS
COMPOSITE BEAM
SHEAR CONNECTORS
GRATING
INSPECTION
VERIFY THE FABRICATOR MEETS AISC CERTIFIED FABRICATOR REQUIREMENT LISTED IN
THE PROJECT SPECIFICATIONS.
INSPECTION
VISUALLY INSPECT STEEL AS IT IS RECEIVED FOR POSSIBLE DAMAGE IN SHIPPING,
WORKMANSHIP, AND PIECE MARKING.
INSPECTION REVIEW CERTIFIED MILL TEST REPORTS AND IDENTIFICATION MARKINGS ON WIDE-FLANGE
SHAPES, HIGH-STRENGTH BOLTS, NUTS AND WELDING ELECTRODES.
INSPECT FIELD WELDED CONNECTIONS AS FOLLOWS:
INSPECT 100% OF COMPLETE JOINT PENETRATION FIELD WELDS. ULTRASONIC
TESTING OF ALL COMPLETE PENETRATIONS WELDS.
INSPECT 100% OF PARTIAL JOINT PENETRATION FIELD WELDS.
INSPECT 100% OF MULTI-PASS FILLET FIELD WELDS.
INSPECT 100% OF FILLET FIELD WELDS IN LATERAL-LOAD-RESISTING BRACED
FRAMES AND MOMENT FRAMES.
INSPECT 10% OF OTHER FILLET FIELD WELDS.
PERFORM PRE-WELDING INSPECTIONS TO VERIFY THAT MATERIALS (I.E. STRUCTURAL
STEEL, OR WELD FILLER MATERIAL), WELDING PROCEDURES, AND WELDING
PERSONNEL QUALIFICATIONS ARE APPROPRIATE.
VISUALLY INSPECT FIELD WELDS ACCORDING TO AWS D1.1/D1.1M.
VERIFY WELDING PROCEDURES ARE IN ACCORDANCE WITH AWS REQUIREMENTS.
INSPECT PRE-HEAT, POST-HEAT AND SURFACE PREPARATION BETWEEN PASSES.
INSPECTION
VERIFY SIZE AND LENGTH OF FILLET WELDS.
VERIFY THAT WELDS ARE CLEAN; WELDER IDENTIFICATION IS LEGIBLE; SIZE, LENGTH
AND LOCATION OF WELDS; VERIFY THAT WELDS MEET ACCEPTANCE CRITERIA;
PLACEMENT OF REINFORCEMENT FILLETS; REMOVAL OF BACKING BARS AND WELD
TABS AS REQUIRED; AND REPAIR ACTIVITIES.
INSPECTION
INSPECT BOLTED CONNETIONS AS FOLLOWS:
MEMBERS SIZES
AND GRADE INSPECTION
VERIFY THAT STEEL MEMBER SIZES AND STEEL GRADE CONFORM TO THE CONTRACT
DOCUMENTS AND APPROVED SHOP DRAWINGS.
INSPECTION
INSPECT STEEL FRAME FOR COMPLIANCE WITH STRUCTURAL DRAWINGS, INCLUDING
BRACING, MEMBER CONFIGURATION AND CONNECTION DETAILS AS FOLLOWS:
TEST
INSPECT COMPOSITE STEEL BEAM SHEAR CONNECTORS AS FOLLOWS:
INSPECTION
INSPECT STEEL GRATING AS FOLLOWS:
VISUALLY INSPECT THE GRATING FOR DAMAGE DURING SHIPPING.
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
ONE-TIME
PERIODIC
CONTINUOUS
PERIODIC
PERIODIC
CONTINUOUS
PERIODIC
PERIODIC
PERIODIC
PERIODIC
CONTINUOUS
CONTINUOUS
INSPECT 100% OF ALL PRE-TENSIONED AND SLIP-CRITICAL BOLTED CONNECTIONS.
INSPECT 100% OF BOLTED CONNECTIONS IN LATERAL-LOAD-RESISTING BRACED
FRAMES AND MOMENT FRAMES
INSPECT 20% OF ALL OTHER BOLTED CONNECTIONS.
FOR SLIP-CRITICAL BOLTED CONNECTIONS, VERIFY INSTALLATION IS PERFORMED IN
ACCORDANCE WITH ONE OF THE FOLLOWING METHODS:
TURN-OF-NUT: ACCORDING TO RCSC'S "SPECIFICATION FOR STRUCTURAL JOINTS
USING ASTM A 325 OR A 490 BOLTS."
CALIBRATED WRENCH: ACCORDING TO RCSC'S "SPECIFICATION FOR STRUCTURAL
JOINTS USING ASTM A 325 OR A 490 BOLTS."
TWIST-OFF TENSION CONTROL BOLT: ASTM F 1852.
DIRECT-TENSION CONTROL BOLT: ASTM F 1852.
FOR ALL BOLTED CONNECTIONS, VERIFY QUANTITY, SIZE AND GRADE OF BOLTS,
REQUIRED SURFACE PREPARATION AND PROPER FIT-UP OF CONNECTED ELEMENTS.
CHECK THE INSTALLATION OF BASE PLATES FOR PROPER LEVELING AND VERIFY
PROPER GROUT TYPE AND INSTALLATION…