This is a construction plan document prepared by The Wilson T. Ballard Company for the Washington Suburban Sanitary Commission (WSSC) Water in Montgomery County, Maryland, detailing the replacement of water infrastructure at 1200 W. University Boulevard in Silver Spring. The project involves replacement of approximately 87 linear feet of 30-inch water main (48 feet replacement and 39 feet relocation), 48 linear feet of 72-inch water main, and installation of one new 30-inch horizontal valve and associated vault. The existing infrastructure comprises three sections: a 24-inch to 30-inch PCCP main (39 feet for relocation), a 30-inch PCCP main (48 feet for replacement), and a 72-inch PCCP main (48 feet for replacement to be replaced with 72-inch steel pipe). The project is located within the Sligo Creek Stream Valley Park on MNCPPC property and along University Boulevard (MD 193), with construction anticipated to commence in summer 2025 and be completed by fall 2025. The contract number is BT7370A22, site number BT7370A22, located in the Wheaton Election District No. 13 within the Sligo Creek Mini Drainage Basin. The design was certified by licensed Maryland Professional Engineer Shawn T. Burnett (License No. 20615, expiration 10/21/2026) and approved by John Marshall (License No. 12679, expiration 10/27/2025).
The project specifications require all 30-inch ductile iron water mains to be Class 54 with external coating and cathodic protection, and all 72-inch steel water mains to have 7/8-inch wall thickness with external coating and cathodic protection per WSSC standards, with no polyethylene encasing permitted. Compaction testing must be performed by a licensed geotechnical engineer following ASTM standards at minimum rates of one test per 100 linear feet of fill. All pipe work must pass hydrostatic testing at 200 PSI for 2 hours and bacterial testing prior to connection. The contractor is responsible for tree protection and restoration, including replacement of removed trees at a 1:1 diameter breast height ratio (79 inches total), installation of temporary pedestrian trail access to maintain Sligo Creek Trail usage during construction, and full restoration of the trail upon completion. Environmental controls include silt fence installation, sediment control measures per WSSC standards, daily street sweeping, and proper management of excavated materials and slurry. The contractor must coordinate with multiple WSSC divisions including Systems Control Division, Water/Wastewater Systems Assessment Division, and Pipeline Construction Division at minimum 60 days in advance, and must maintain water service to affected properties through temporary water service connections limited to maximum 8-hour shutdowns. Additional coordination is required with MNCPPC for park property work and with Maryland utilities via Miss Utility (811) notification at least 72 hours prior to any ground disturbance.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S l i g o C r e e k
BE
LG
R
AD
E C
T
NORTHWOOD FOREST
GLENVIEW
UNIVERSITY BLVD W
G
LE
N H
AV
EN
D R
YESHIVA OF
GREATER
WASHINGTON
KEMP
MILL
E.S.
E.S.
ARCOLA
SCHOOL
ST ANDREWS
APOSTLE
KEMP
MILL
ARCOLA
AVE
LAMBERTO
N
DR
LO
VE
JO
Y
ST
N
BELGRADE
RD
RD
KERSEY
AV
E
M O
N
TI
CE
LL
OFRANWALL AVE
HYDE
RD
RD
N
AI
RN
G
LS
AN
FULHAM
ST
SISSON ST
AV
E
O R
EB
AU
G H
C HARLTON
ST
O
CLINTWOOD
C H
AN
N
IN
G
D R
HILLSBORO
DR
BR
O
M
LE
Y
ST
HO
RTO
N
DR
LA
SA
D
VENTURA
AVE
RO
CKBRIDGE
RD
RE
ED
IE DR
YE
AT
M
AN
TE
R R
LADD
ST
LO
CK
HA
RT
PL
ST
BROMLEY
YA
TE
S
ST
CLO
VERH
ILL
D R
C O
LT
TE
R R
H OLBORN
ST
DAFFO
D
IL
LA
HEATHER
CRESTLA
CLARA
ST
ALM
A
ST
YE
AT
MAN
CT
RIDGE AVE
LAM
BERTO
N
CT
FILLM
ORE
DR
CLINTWOOD PL
KWY
AN
CREST
TERR
HEATHER
N
AI
R N
R D
CT
F
U
LHAM
GILSA
CT
SISSO
N
C T
H
YDECT
SLIGO CREEK
STREAM
VALLEY PARK
ARCOLOA
PARK
SLIGO
M.S.
NORTHWOOD H.S.
HAVEN
E.S.
GLEN
FOREST
KNOLL
E.S.
KEMP MILL
CHESTNUT
RIDGE
SLIGO
WOODS
T N
BLVD
W.
SLIGO
CREEK
PKW
Y
DENNIS
AVE
D R
IN
W
O O
D
AVE
LO
LO
XFO RD
TERR
EDGEW
OOD
AVE
KERWIN RD
CADDINGTON
AV
E
HANNES
KENBRO O K
DR
LAGRIDLEY
BU
CKN
ELL
DR
DIEDR
AVE
ARCO
LA
PR
O
C
TER
ST
LA
WINDHAM
CAVAL
BELTON
R
LA
AVE
H U
N
TLEY
C
AL
UMET DR
ST
H
AY
ES
AV
E
NORTHWOOD
TERR
S
BELGRADE
RD
RD
ALBERTI
DR
HILLSBORO
ST
N
PKWY
LADD
ST
ST
BYBEE
WESTCHESTER
DR
WHITEHALL
RD
ST
EISNER
GILM
O
URE
D
R
MALTA
AV
E
JU
LE
P
H O
RD
E
ST
ASCADE
RD
EASECREST
DR
N
IC
HOLA
S
DR
H
ILLSBORO
DR
C
H ISWELL
LA
ST
G ABEL
EAST
LE
S T
ER
ST
LA
PLAYFO
RD
REPUBLIC
RD
WHEATON
LA
DAYTON
ST
H U
N
TLEY
PL
LUTTRELL
LA
MCM AH O N RD
MAR
KW
OOD
D R
BREEW
O
O D
RD
CONSTAN CE ST
ORDW
AY
DR
IRWIN
ST
JASPER
ST
ON
RD
ROBIN RD
M
AL
O N
E
ST
ST
GLEASON
DR
LAPOINTE
LAREDO RD
ORANG E
DR
G
RA
N D
IN
R
D
CREST
RD
FLORIN
ST
S BELGRADE RD
DR
GLEN PA RK
ST
HANBY
SNURE
RD
HELENA DR
N O
RL
EE
DR
A
D O
D
SO
N
LA
M
AR
VI
N
RDCASCADE
PL
LA
DD
ST
D
UN
KIRK
DR
NO
TERR
BE
NSO
N
H E M
LE
Y
LA
LA
DS
O N
RD
H
EALY
ST
M O
N
TICELLO
AVE
R
EE
D
IE
D R
KO RTH LA
CONTI
PL
GRE
G
O
RY
ST
M
AY
HE
W
DR
HOYT
ST
DONALD PL
JEW
ETT
ST
CARMODYDR
VIVIAN
PL
PLGLENKARNEY
AVE
CLIN
TO
N
AVE
BAR
R
IE
AM
H
ER
ST
WAY
JUSTIN
JAM
AIC
A
D R
KE
LL
ER
ST
W
HITTIN
GTON
TERR
R U
N D
R
PEBBLE
DUKEDR
ETNA PL
FIE
ST
A
RD
WIN O N A CT
D R
FR
AN
C
IS
G
LEN
H
AVEN
PKW
Y
HORDERD
ELDON
LA
PL
GLENHAVEN
HA
NN
ES
CT
TERR
ROYALTON
C
LO
V E
RH
IL
L
KENBRO OK
CT
HAVENPARK
DR
TENBROOK
CT
VIV IA N
CT
W
HITEHALL
CT
CTCAV
AL
IE
R
G
AB
EL C T
BREEWOOD
CT
H
EN
LO
PEN
C T
SLYE
CT
BELTO
N
CT
M
AR
KW
O
O D
C T
C
LA
R A
ST
EASTW
O
O D
AVE
KERW
IN
CT
C T
BE
LG
R
AD
E
CO
NT
I
CT
CT
BY
BE
E
GLEN HAVEN PARK
MILL
PARK
KEMP
WHEATON
FOREST
PARK
BREEWOOD
PARK
SLIGO
DENNIS
CREEK
EVANS PARK
CHESTNUT
HILLS
30" WATER VALVE
1200 W. UNIVERSITY BOULEVARD
SILVER SPRING, MONTGOMERY COUNTY, MARYLAND
CONTRACT NO. BT7370A22
SITE NO.
BT7370A22
GENERAL NOTES
1. AT THE END OF CONSTRUCTION, CONTRACTOR SHALL RESTORE THE SLIGO CREEK
TRAIL, AND ALL ASSOCIATED LANDSCAPING, CHANNELS, SWALES, DITCHES, ETC. TO
THE ORIGINAL CONDITION (PRIOR TO CONSTRUCTION.)
2. ALL 30" DUCTILE IRON WATER MAINS AND FITTINGS TO BE CLASS 54 WITH EXTERNAL
COATING AND CATHODIC PROTECTION FOR CORROSION CONTROL PER SPECIFICATIONS
AND AS SHOWN ON PLANS. DO NOT POLYETHYLENE ENCASE THE WATER MAINS.
3. ALL 72" STEEL WATER MAINS AND FITTINGS SHALL HAVE A WALL THICKNESS OF 7 8" WITH
EXTERNAL COATING AND CATHODIC PROTECTION FOR CORROSION CONTROL PER
SPECIFICATIONS AND AS SHOWN ON PLANS. DO NOT POLYETHYLENE ENCASE THE
WATER MAINS.
4. SEE CORROSION CONTROL NOTES ON SHEET CP-1.
5. LICENSED GEOTECHNICAL ENGINEER TO PERFORM COMPACTION TESTING FOLLOWING
ASTM D1556, ASTM D6938 OR ASTM D2937 AT A MINIMUM RATE OF 1 TEST FOR EVERY 100
FEET OF FILL ALONG MAIN TRENCH AND AT EVERY LATERAL TRENCH, STRUCTURE AND
VALVE BOX IN TYPE I AREAS.
6. CONTRACTOR SHALL TEST PIT TO LOCATE PIPE JOINTS FOR THE EX. 30" PCCP WATER
MAIN AND EX. 72" PCCP WATER MAIN USING VAC-TRUCK PRIOR TO CONSTRUCTION.
CONTRACTOR SHALL TEST PIT EXISTING WATER MAIN CONNECTION LOCATIONS AND ALL
UTILITY CROSSINGS PRIOR TO BEGINNING CONSTRUCTION OF WATER MAIN, AND MAKE
ANY ADJUSTMENTS AS NECESSARY WITH PRIOR APPROVAL OF WSSC WATER. THERE IS
THE POSSIBILITY OF ENCOUNTERING POURED LEAD JOINTS. IF POURED JOINT PIPE IS
FOUND, REPLACE WITH MECHANICAL JOINT PIPE AND FITTINGS. REMOVAL OF THE JOINT
IS INCIDENTAL TO THE CONTRACT. SEE SPECIAL CONSTRUCTION REQUIREMENTS FOR
WORK PERFORMED IN VICINITY OF EXISTING PCCP MAINS ON SHEET 2.
7. ALL PIPE WORK TO BE TESTED AT 200 PSI FOR 2 HOURS AND PASSING TEST FOR
HYDROSTATIC AND BACTERIAL PRIOR TO CONNECTION.
8. NEW 30" VALVE MUST BE TESTED ABOVE GROUND PRIOR TO CONSTRUCTION.
9. CONTRACTOR SHALL VERIFY THE TYPE, SIZE AND LOCATION OF EXISTING FITTINGS ON
THE WATER MAIN TO BE REPLACED.
10. FOR SAME TRENCH REPLACEMENT, ALL EXISTING VALVES, FIRE HYDRANTS, VALVE
BOXES, COPPER, BRASS, FITTINGS AND PIPE MUST BE REMOVED FOR SALVAGE AND
RETURNED TO WSSC ANACOSTIA WAREHOUSE, AT NO COST TO WSSC WATER. FOR PIPE
RELOCATION, FIRE HYDRANTS AND VALVE BOXES MUST BE REMOVED FOR SALVAGE
AND RETURNED TO WSSC ANACOSTIA WAREHOUSE, AT NO COST TO WSSC WATER.
EXISTING LARGE VALVE TO BE REMOVED FOR SALVAGE AS ONE OPERATING PIECE
(UNLESS ALREADY BROKEN) TO WSSC ANACOSTIA WAREHOUSE AT NO ADDITIONAL
COST TO WSSC WATER.
11. FOR MAINS SMALLER THAN 16 INCHES, OPERATE VALVES UNDER DIRECT SUPERVISION
OF CERTIFIED WSSC WATER EMPLOYEE. FOR MAINS 16 INCHES AND LARGER, WSSC
WATER WILL OPERATE VALVES FOR SHUTDOWNS.
12. CONTRACTOR SHALL PROVIDE ALL MATERIALS AND MATERIAL CERTIFICATIONS FOR
THIS CONTRACT IN ACCORDANCE WITH APPROVED DRAWINGS AND SPECIFICATIONS.
13. CONTRACTOR SHALL NOT SHUT DOWN EXISTING WATER MAIN UNTIL THE NEW VALVE IS
ON SITE AND HAS BEEN TESTED.ONCE THE CONTRACTOR STARTS TO REMOVE THE
EXISTING VALVE, THE CONTRACTOR MUST CONTINUE TO WORK UNTIL THE NEW VALVE
HAS BEEN INSTALLED IN ITS PLACE AND WATER MAIN IS READY TO BE PLACED BACK IN
SERVICE.
14. INSTALL ALL WATER MAINS AND TEMPORARY CAPS/PLUGS ON BOTH THE REPLACEMENT
AND EXISTING MAINS AND TEST, AS SHOWN ON THESE DRAWINGS.
15. CONTRACTOR SHALL NOTIFY MISS UTILITY AT LEAST 72 HOURS IN ADVANCE OF ANY
WORK IN THIS AREA, SO APPROPRIATE MARKING OF EXISTING UTILITIES CAN BE MADE.
CALL 811 OR 1-800-257-7777 OR LOG ON TO WWW.CALL811.COM OR
HTTP://WWW.MISSUTILITY.NET
16. 1"=10' SCALE DRAWINGS ARE BASED ON TOPOGRAPHIC SURVEY DATA COLLECTED BY
THE WILSON T. BALLARD COMPANY DURING MARCH 2023. HORIZONTAL DATUM = NAD
83/91 AND VERTICAL DATUM = NGVD 29.
17. CONTRACTOR SHALL NOT STOCKPILE MATERIALS OR EQUIPMENT WITHIN THE DRIP-LINE
OF ANY TREES.
18. PROVIDE TREE TRUNK PROTECTION FOR ALL TREES WITHIN 15 FEET OF ANY WORK. SEE
STANDARD DETAIL SC/19.0, EXCEPT NOMINAL 2"X10" OR 2"X12"; PINE BOARDS MAY BE
USED.
19. CONTRACTOR SHALL LOCATE ALL WHC'S IN THE FIELD. THE CONTRACTOR, AT NO COST
TO WSSC WATER, SHALL REPAIR ANY DAMAGE TO HOUSE CONNECTIONS AND WATER
MAINS THEY MAY CAUSE.
20. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING STAGING AREA(S) AND FOR
MOBILIZATION TO AND FROM SUCH AREA(S) AT NO ADDITIONAL COST TO THE WSSC
WATER. CONTRACTOR IS NOT ALLOWED TO USE MNCPPC PROPERTY AS A STAGING
AREA.
21. CONTRACTOR SHALL PROVIDE STAKEOUT FOR THE PROPOSED RELOCATIONS.
22. PROVIDE TEMPORARY WATER SERVICE DURING CONSTRUCTION FOR WATER SERVICES
AFFECTED BY THE WATER MAIN REPLACEMENTS. TEMPORARY WATER SERVICE
CONNECTIONS SHALL BE AS PER STANDARD DETAILS W/5.16 AND W/5.16a. ALL
SHUTDOWNS SHALL BE LIMITED TO NO LONGER THAN 8 HOURS. NO VALVES ARE TO BE
OPERATED WITHOUT A WSSC WATER INSPECTOR ON SITE.
23. INSTALL REPLACEMENT WATER MAINS WITH A MINIMUM OF 42" COVER, AND RELOCATED
WATER MAINS WITH MINIMUM OF 48" COVER UNLESS OTHERWISE NOTED ON THE
DRAWING.
24. ALL VALVE EXTENSIONS ARE TO BE INSTALLED PER STD. DETAIL W/2.2.
25. ANY YARD WITH ZOYSIA GRASS THAT IS DISTURBED OUTSIDE OF PARK PROPERTY MUST
BE REPLACED WITH ZOYSIA GRASS. FOLLOW RECOMMENDED TIME FOR PLANTING
ZOYSIA GRASS.
26. IN ACCORDANCE WITH CODE OF MARYLAND REGULATIONS (COMAR) 26.04.01.33, DIRECT
AND INDIRECT ADDITIVES, SUPPLIERS OF WATER SHALL ONLY USE PRODUCTS (AND
MATERIALS THAT COME IN CONTACT WITH WATER INTENDED FOR USE IN PUBLIC WATER
SUPPLY) THAT MEET THE APPLICABLE AMERICAN NATIONAL STANDARDS INSTITUTE / NSF
INTERNATIONAL (ANSI/NSF) STANDARDS FOR DIRECT OR INDIRECT DRINKING WATER
ADDITIVES. THE PRODUCTS CAN ALSO BE CERTIFIED BY AN ORGANIZATION ACCREDITED
BY THE ANSI FOR SUCH TESTING (I.E., INTERNATIONAL ASSOCIATION OF PLUMBING AND
MECHANICAL OFFICIALS RESEARCH AND TESTING, ONTARIO CA, UNDERWRITERS
LABORATORY, NORTHBROOK IL, AND WATER QUALITY ASSOCIATION, LISLE IL).
27. IN COMPLIANCE WITH COMAR 09.20.01.03 AND THE SAFE DRINKING WATER ACT (SECTION
1417(A)(4)(8), MATERIALS THAT COME IN CONTACT WITH WATER INTENDED FOR USE IN
PUBLIC WATER SUPPLY SHALL COMPLY WITH THE REDUCTION OF LEAD IN DRINKING
WATER ACT, WHICH WENT INTO EFFECT IN MARYLAND IN JANUARY 2012.
28. NOTIFY KAREN WRIGHT, SYSTEMS CONTROL DIVISION MANAGER, AT 301-206-8416 TWO
(2) WEEKS PRIOR TO WATER MAIN SHUTDOWN.
29. SEE NOTIFICATION REQUIREMENTS IN THE EXISTING PCCP SHUTDOWN NOTES ON
SHEET 2. IN ADDITION, CONTRACTOR MUST CONTACT THE FOLLOWING
PERSONS/AGENCIES AT LEAST SEVEN (14) DAYS PRIOR TO START OF ANY WORK UNDER
THIS CONTRACT:
A. KEVIN LETHBRIDGE, CONSTRUCTION MANAGER, PIPELINE CONSTRUCTION
DIVISION OF WSSC, LYTTONSVILLE DEPOT, (301) 206- 7339.
B. MARYLAND NATIONAL CAPITAL PARKS AND PLANNING COMMISSION
(MNCPPC), SEE PERMIT FOR CONTACT INFORMATION.
DESIGNED BY: _______________________________________ DATE: ________________________
FIELD REVIEW BY: ____________________________________ DATE: ________________________
AND VALVE VAULT REPLACEMENT
INDEX OF SHEETS
SHEET NO. DESCRIPTION
1 TITLE SHEET, GENERAL NOTES
2 BLOCKING NOTES, SEDIMENT
CONTROL NOTES, SPECIAL
CONSTRUCTION NOTES
3 1"=10' SCALE PLAN
4 1"=5' PROFILES
5 SITE ACCESS PLAN
6 SPECIAL DETAILS
7-8 MNCPPC SPECIAL DETAILS
FOR CONSTRUCTION
9 TEMPORARY BY-PASS PLAN/
SUGGESTED SEQUENCE OF
CONSTRUCTION
CP-1 CATHODIC PROTECTION PLAN
SC-1 SEDIMENT CONTROL DETAILS
EXISTING WATER MAINS TO BE REPLACED/ RELOCATED
(SHEET 3)
SHEET
NO. STREET EX. WATER
MAIN SIZE
NEW WATER
MAIN SIZE LENGTH RENEWAL
METHOD FROM TO PIPE ID
3 W UNIVERSITY
BOULEVARD 24"/30" PCCP 30" DIP 39' RELOCATION VALVE
VV14D02127
JOINT
PJM16000
WS00087787 /
WS00087788
3 W UNIVERSITY
BOULEVARD 30" PCCP 30" DIP 48' REPLACEMENT - - WS00122845
3 W UNIVERSITY
BOULEVARD 72" PCCP 72" STEEL 48' REPLACEMENT - - WS00087747
WSSC Erosion and Sediment Control Approval Note:
This plan has been approved per requirements in the:
Standard Procedures of the WSSC Regulations for Utility Erosion and Sediment Control, Section V. Paragraph A.
Reviewed by: __________________________________________ Date: _________________ Plan No.: _______________________BT7370A22
TOTAL 30" REPLACEMENT= 48'
TOTAL 30" RELOCATION= 39'
TOTAL 72" RELOCATION= 48'
TOTAL REPLACEMENT = 135' = 0.03 MILES
ENGINEER:
MONTGOMERY CO.
ADEQUATE SURVEY
NO
200'S OF
CONTRACT
DATE
DATE STARTED
DATE FINALED
Drawing No.
FINALED BY
DATE COMPLETED
TYPE MANHOLES
TYPE PIPE W.
1 thru 9 Plans/Profiles/Details
Description
P.G.CO.D.P.W.&T.
SED. CONTROL
CONTRACT MANAGER
INSPECTOR
CONTRACTOR
L & G
AS BUILT DATA
TOWN NOTIFICATION
STATE HGWY. ADM.
STATE BD. HEALTH
PERMIT REQUIREMENTS
M.N.C.P.&P.C.
WETLANDS / WATERWAYS
TREE
DATE REVISIONS
PAGECo. GRID
VICINITY MAP
SCALE
ON PROP. R/W REQ'D
OFF PROP. R/W REQ'D
S.
THESE DOCUMENTS CONTAIN
PRIVILEGED AND CONFIDENTIAL
INFORMATION WHICH SHALL NOT
BE REDISTRIBUTED WITHOUT
PRIOR WSSC APPROVAL
FOR LOCATION OF UTILITIES CALL 8-1-1 OR 1-800-257-7777
OR LOG ON TO www.call811.com or www.missutility.net 72
HOURS IN ADVANCE OF ANY WORK IN THIS VICINITY
OTHER UTILITIES
*TO BE ACQUIRED BY APPLICANT
1" = 2,000'
MONTGOMERY 5286 F05
DRAWING INDEX
IS REQUIRED
NOT REQUIRED
IS REQUIRED
IS REQUIRED
NOT REQUIRED
NOT REQUIRED
IS REQUIRED
NOT REQUIRED
DRAWN
CHECK
PIPELINE DESIGN DIVISION
XXX
XXX
DATE DIVISION MANAGER
VE
R
IF
Y
SC
AL
E
- B
AR
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
S
H
EE
T, A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
M.D. D.O.E. - WMA NOT REQUIRED
SECTION MANAGER
10/16/2024 9:14 AM - PLOT DATE
BT7370A22
214NW02
WHEATON ELECTION DISTRICT NO. 13
30" WATER VALVE AND VALVE VAULT REPLACEMENT
1200 W. UNIVERSITY BOULEVARD
SILVER SPRING, MONTGOMERY COUNTY, MARYLAND
SLIGO CREEK MINI DRAINAGE BASIN NOS. 064
HHG: 530'
LHG: 460'
PRESSURE ZONE= 495A
PROFESSIONAL CERTIFICATION
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE
OF MARYLAND.
NAME: SHAWN T. BURNETT
LICENSE NO.: 20615
EXP. DATE: 10/21/2026
NAME: THE WILSON T. BALLARD COMPANY
ADDRESS: 17 GWYNNS MILL COURT, OWINGS MILLS, MD 21117
PHONE: (410) 363-0150
CONTACT : SHAWN BURNETT
EMAIL: SBURNETT@WTBCO.COMPA
TH
T:
\W
SS
C
\P M
A2 0\
0-
1.
B
T7
0A
B
T7
3A
\D W
G s\
BT
A2
2\
G -0
.d w g
WSSC
WASHINGTON SUBURBAN SANITARY COMMISSION
M.D.E. CONST. IS REQUIRED
HHG: 670'
LHG: 598'
PRESSURE ZONE (72" W, V019) = 660A
UNIVERSITY BOULEVARD W (MD 193)
2022 AADT=25,771 POSTED 35 MPH
SC-1 Sediment Control Details
CP-1 Cathodic Protection Plan
DATE REVISIONS
NO
200'S OF
CONTRACT
ENGINEER:THESE DOCUMENTS CONTAIN
PRIVILEGED AND CONFIDENTIAL
INFORMATION WHICH SHALL NOT
BE REDISTRIBUTED WITHOUT
PRIOR WSSC APPROVAL VE
R
IF
Y
SC
AL
E
- B
AR
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IF
N O
T O
N E
IN
C
H O
N T
H
IS
S H
EE
T, A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
10/16/2024 9:15 AM - PLOT DATE
DATE
BT7370A22
214NW02
WHEATON ELECTION DISTRICT NO. 13
30" WATER VALVE AND VALVE VAULT REPLACEMENT
1200 W. UNIVERSITY BOULEVARD
SILVER SPRING, MONTGOMERY COUNTY, MARYLAND
WATER INFRASTRUCTURE SECTION
PROJECT MANAGER
PROFESSIONAL CERTIFICATION
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE
OF MARYLAND.
NAME: SHAWN T. BURNETT
LICENSE NO.: 20615
EXP. DATE: 10/21/2026
NAME: THE WILSON T. BALLARD COMPANY
ADDRESS: 17 GWYNNS MILL COURT, OWINGS MILLS, MD 21117
PHONE: (410) 363-0150
CONTACT : SHAWN BURNETT
EMAIL: SBURNETT@WTBCO.COM
SLIGO CREEK MINI DRAINAGE BASIN NOS. 064
PA
TH
T:
\W
SS
C \P
M
A2
0\
0-
1.
B T7
0A
B T7
3A
\D
W G s\
BT
A2 2\
G
-0
.d w g
WASHINGTON SUBURBAN SANITARY COMMISSION
WSSC
HHG: 530'
LHG: 460'
PRESSURE ZONE= 495A
HHG: 670'
LHG: 598'
PRESSURE ZONE (72" W, V019) = 660A
BLOCKING NOTES
1. RESTRAIN ALL PIPE JOINTS AND FITTINGS, SEE SPECIFICATIONS.
ENVIRONMENTAL SEDIMENT CONTROL NOTES
1. CONTACT WSSC WATER ENVIRONMENTAL PROGRAMS SECTION AT (301)
206-8077, 48 HOURS PRIOR TO STARTING ANY UTILITY WORK UNDER THIS
CONTRACT.
2. ANY GROUND WATER OR SURFACE WATER PUMPED DURING THIS PROJECT
SHOULD BE DISCHARGED THROUGH AN APPROVED DE-WATERING DEVICE. SEE
STANDARD DETAIL SC/15.0, SC/15.1.
3. STREETS AND PAVED WALKWAYS SHALL BE BROOM SWEPT DAILY.
4. INSTALL CURB INLET OR AT-GRADE INLET PROTECTION AS NEEDED OR AS
DIRECTED BY WSSC ENVIRONMENTAL STAFF. SEE STANDARD DETAIL SC/16.0,
SC/16.1.
5. PLACE SILT FENCE PER STANDARD DETAIL SC/1.0 ALONG LOW SIDE OF
EXCAVATED AREA WHEN WORKING IN NON-PAVED AREAS OR AS SHOWN ON THE
PLANS, OR AS DIRECTED BY WSSC ENVIRONMENTAL STAFF IN THE FIELD.
CONTRACTOR SHALL PROVIDE DAILY TEMPORARY STABILIZATION FOR ALL
DISTURBED NON-PAVED AREAS.
6. ANY EXCAVATED OR STOCKPILES MATERIAL LEFT OVERNIGHT SHALL BE
COVERED WITH AN IMPERMEABLE (PLASTIC) MATERIAL. PROVIDE SEDIMENT
CONTROL FOR ALL OFFSITE STAGING/STOCKPILE AREAS.
7. WHEN WORKING IN PAVED SURFACES, PLACE EXCAVATED MATERIAL ON HIGH
SIDE OF TRENCH.
8. ANY SLURRY GENERATED BY PAVEMENT SAW CUTTING SHALL BE CONTAINED BY
THE CONTRACTOR TO PREVENT SLURRY FROM ENTERING THE EXISTING STORM
DRAIN SYSTEM OR WATERWAY BY USING APPROVED METHODS, DEVICES, OR AS
DIRECTED BY THE WSSC ENVIRONMENTAL STAFF. CONTRACTOR SHALL
PROPERLY REMOVE AND DISPOSE OF CONTAINED SLURRY AT THE END OF EACH
WORK DAY.
9. FOR AREAS WITHIN THE LIMIT OF DISTURBANCE WHICH DO NOT DRAIN TO AN
APPROVED EROSION AND SEDIMENT CONTROL MEASURE AND/OR WHERE THE
INSTALLATION OF CONTROLS IS NOT FEASIBLE (ROADWAY, SIDEWALK, ETC.)/
CONTRACTOR SHALL ONLY DISTURB AREA WHICH CAN BE COMPLETED AND
STABILIZED BY THE END OF EACH WORKING DAY. STABILIZATION SHALL BE AS
FOLLOWS:
A. FOR AREAS TO BE PAVED: STONE BASE SHALL BE APPLIED.
B. FOR AREAS TO BE VEGETATIVELY STABILIZED:
i. PERMANENT SEED AND SOIL STABILIZATION MATTING FOR
SOD FOR ALL STEEP SLOPES, CHANNELS, OR SWALES
ii. PERMANENT SEED AND MULCH FOR ALL OTHER AREAS. ANY
AREAS WHICH CAN NOT BE STABILIZED BY THE END OF EACH
WORKING DAY MUST HAVE SILT FENCE SC/1.0 INSTALLED ON
THE DOWN SLOPE SIDE.
MDE NOTES
1. IN ACCORDANCE WITH TEN STATE STANDARDS, A MINIMUM OF TEN (10) FOOT
HORIZONTAL AND EIGHTEEN (18) INCH VERTICAL SEPARATION MUST BE
MAINTAINED BETWEEN WATER MAINS AND SANITARY SEWER. WHEN IT IS
IMPOSSIBLE TO OBTAIN THE MINIMAL HORIZONTAL 10 FOOT HORIZONTAL
SEPARATION AND/OR 18 INCH VERTICAL SEPARATION BETWEEN WATER MAINS
AND SANITARY SEWER, MDE MUST SPECIFICALLY APPROVE ANY VARIANCE
SUPPORTED BY DATA FROM THE DESIGN ENGINEER.
2. ALL WATER LINES SHALL BE DISINFECTED ACCORDING TO AWWA STANDARD
C651. BACTERIOLOGICAL TESTS SHALL BE SUBMITTED TO MDE WATER SUPPLY
PROGRAM FOR APPROVAL PRIOR TO PLACING THE MAIN INTO SERVICE.
SPECIAL CONSTRUCTION REQUIREMENTS FOR WORK
PERFORMED IN THE VICINTIY OF EXISTING PCCP
WATER MAINS
1. CONSTRUCTION VEHICLES GENERATING LIVE LOADS GREATER THAN AASHTO
HS20 (APPROX. 40,000 LBS OR GREATER), AND ANY VIBRATORY ROLLER
COMPACTION EQUIPMENT, SHALL NOT BE PERMITTED WITHIN 10 FEET CLEAR OF
THE OUTER EDGE OF EX. PCCP WATER MAIN UNLESS APPROVED BY WSSC.
2. THE CONTRACTOR SHALL SUBMIT CONSTRUCTION VEHICLE SPECIFICATIONS
FOR ALL VEHICLES PROPOSED FOR USE CLOSER THAN 10 FEET CLEAR, OR IF
PROPOSED TO CROSS EX. PCCP WATER MAINS, TO THE WSSC PROJECT
MANAGER/CONTACT PERSON FOR APPROVAL PRIOR TO COMMENCING WORK.
ANY VEHICLE NOT PREVIOUSLY IDENTIFIED DURING THE DESIGN REVIEW OF
THESE PLANS WILL REQUIRE AN ADDITIONAL LOADING ANALYSIS REVIEW.
3. IF NECESSARY, HARDWOOD TIMBER MATS OF APPROPRIATE SIZE AND
THICKNESS (SUFFICIENT TO FIT THE LARGEST CONSTRUCTION VEHICLE
PROPOSED AND 1-FOOT THICK) SHALL BE PLACED OVER THE EXISTING PCCP
MAIN TO ALLOW WSSC APPROVED CONSTRUCTION VEHICLE TRAFFIC TO CROSS
OVER THE PIPELINE AND SAFELY DISTRIBUTE LIVE LOADS.
4. STOCKPILING OF SOIL OR OTHER MATERIAL IS NOT PERMITTED WITHIN 10 FEET
CLEAR OF THE EDGE OF THE ROW OF THE EX. MAINS, TO PREVENT ROW
ENCROACHMENT.
5. THE CONTRACTOR SHALL LOCATE AND STAKEOUT THE EX. PCCP WATER MAINS
AND EDGE OF THE ROW AND MAINTAIN THE MARKERS DURING CONSTRUCTION.
UNLESS OTHERWISE APPROVED BY WSSC PROJECT MANAGER/ CONTACT
PERSON, CONSTRUCTION VEHICLES ARE NOT PERMITTED WITHIN 10 FEET
CLEAR OF EX. PCCP WATER MAIN AT ANY TIME, WHEN LESS THAN 6 FEET OF
COVER EXISTS OVER THE MAIN. THE CONTRACTOR IS RESPONSIBLE FOR
IDENTIFYING AREAS WHERE LESS THAN 6 FEET OF COVER EXISTS OVER THE
MAINS DURING CONSTRUCTION VIA VACUUM TEST PITTING.
6. ALL BACKFILL AND COMPACTION OVER THE EX. PCCP MAINS, AT ANY DEPTH OF
COVER, SHALL BE PERFORMED MANUALLY AND/OR WITH VEHICLES POSITIONED
A MINIMUM OF 10 FEET CLEAR OF THE OUTER EDGE OF THE MAIN.
7. ALL ROCKS, BROKEN PAVEMENT, CURBING AND OTHER DEBRIS HAVING ANY
DIMENSION GREATER THAN 3 INCHES SHALL BE REMOVED FROM ABOVE AND
AROUND THE MAIN(S) PRIOR TO PLACING AND COMPACTING FILL, SUB GRADE
MATERIAL OR PAVING OVER THE MAIN (INCLUDING PIPE BEDDING).
8. THE CONTRACTOR SHALL NOTIFY THE APPROPRIATE PIPELINE CONSTRUCTION
DIVISION INSPECTOR ASSIGNED TO THE PROJECT AT LEAST 72 HOURS IN
ADVANCE OF ANY GRADING OR PAVING IN THE VICINITY OF THE EX. PCCP MAINS.
ALL GRADING AND PAVING OVER THE MAINS SHALL BE COORDINATED AND
PERFORMED UNDER THE SUPERVISION OF A WSSC INSPECTOR.
9. THE CONTRACTOR SHALL USE SPECIAL CARE WHILE PERFORMING WORK IN THE
VICINITY OF THE EX. PCCP WATER MAINS AND SHALL STRICTLY ADHERE TO
THESE SPECIAL CONSTRUCTION REQUIREMENTS. THE CONTRACTOR IS
RESPONSIBLE FOR ANY DAMAGE AND/OR REPLACEMENT REQUIRED AS A
RESULT OF HIS WORK OVER THE MAINS AT NO ADDITIONAL COST TO WSSC.
10. IF SHUTDOWN AND DE-WATERING OF THE EX. PCCP WATER MAIN IS REQUIRED,
COORDINATION WITH SYSTEMS CONTROL DIVISION (SCD) IS MANDATORY. A
MINIMUM OF 60 DAYS ADVANCE NOTICE TO SCD IS REQUIRED TO COORDINATE
WATER MAIN SHUTDOWN, DE-PRESSURIZATION, AND DE-WATERING OF EX. PCCP
WATER MAINS AND REMOVAL OF THE ACOUSTIC FIBER OPTIC (AFO) MONITORING
CABLE. SCD SHALL PERFORM THE SHUTDOWN SCHEDULING AND THE UTILITY
SERVICES DEPARTMENT SHALL EXECUTE THE SHUTDOWN, DE-PRESSURIZATION
AND DE-WATERING.
11. TEST PITS TO VERIFY THE HORIZONTAL AND VERTICAL ALIGNMENT OF THE PCCP
MAINS SHALL BE VIA VACUUM TEST PITTING RATHER THAN OPEN-CUT
TRENCHING ON LIVE PCCP MAINS. VACUUM TEST PITTING IS PERFORMED ONLY
TO THE CROWN OF THE EXISTING PCCP WATER MAINS. BACKFILL THE VACUUM
TEST PIT IMMEDIATELY AFTER THE PERTINENT INFORMATION IS GATHERED.
ANY DAMAGE TO THE EX. WATER MAIN COATING RESULTING FROM THE
CONTRACTOR'S OPERATIONS SHALL BE REPAIRED AT THE CONTRACTOR'S
EXPENSE. DAMAGE AND REPAIRS SHALL BE INSPECTED BY WSSC ENGINEERS
AND/OR THE PIPE MANUFACTURER'S TECHNICAL FIELD REPRESENTATIVE, AND
BE REPAIRED ACCORDINGLY PRIOR TO BACKFILLING.
12. DURING BACKFILLING, COMPACTED CR-6 OR #57 STONE SHALL BE USED TO 12
INCHES ABOVE THE CROWN OF THE PCCP MAIN. THE REMAINING EXCAVATION
SHALL BE BACKFILLED AND COMPACTED WITH SUITABLE MATERIAL IN
ACCORDANCE WITH STANDARD SPECIFICATION SECTION 02315.
SPECIAL CONSTRUCTION REQUIREMENTS FOR WORK
PERFORMED IN THE VICINTIY OF EXISTING PCCP
WATER MAINS
NOTIFICATIONS:
1. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE PIPELINE
CONSTRUCTION DIVISION INSPECTOR ASSIGNED TO THE PROJECT.
NOTIFICATIONS ARE REQUIRED AT A MINIMUM OF 60 DAYS IN ADVANCE OF
WORK TO ARRANGE SHUTDOWN AND INSPECTION OF THE EX. PCCP WATER
MAINS.
2. THE CONTRACTOR AND/OR THE APPROPRIATE PIPELINE CONSTRUCTION
DIVISION INSPECTOR SHALL CONTACT KAREN WRIGHT, SYSTEMS CONTROL
DIVISION - DIVISION MANAGER, AT 301-206-8416 A MINIMUM OF 60 DAYS IN
ADVANCE OF WORK TO COORDINATE THE SHUTDOWN AND DE-WATERING OF
THE EX. PCCP WATER MAINS.
3. THE CONTRACTOR AND/OR THE APPROPRIATE PIPELINE CONSTRUCTION
DIVISION INSPECTOR SHALL NOTIFY ARTURO ACEVEDO AT 301-206-8478 OF THE
WATER/WASTEWATER SYSTEMS ASSESSMENT DIVISION 60 DAYS IN ADVANCE OF
WORK TO COORDINATE THE REMOVAL AND REPLACEMENT OF ANY PCCP PIPE
SECTIONS. FURTHER COORDINATION IS REQUIRED TO REMOVE AND REINSTALL
THE ACOUSTIC FIBER OPTIC (AFO) MONITORING SYSTEM WITHIN THE PCCP
PIPELINE. COORDINATION INCLUDES PLANNING WITH THE INSPECTION
CONSULTANT(S), WSSC WATER/WASTEWATER SYSTEMS ASSESSMENT DIVISION,
AND WSSC UTILITY SERVICES TEAM STAFF. THE PCCP MAIN MAY HAVE AN AFO
MONITORING CABLE INSTALLED INSIDE, AND THIS CABLE MUST NOT BE CUT OR
DAMAGED. THE WATER/WASTEWATER SYSTEMS ASSESSMENT DIVISION MUST
BE NOTIFIED 60 DAYS IN ADVANCE OF WORK TO COORDINATE AND PLAN THE
AFO CABLE REMOVAL PRIOR TO REMOVING ANY PIPE SECTIONS AND TO
COORDINATE REINSTALLATION OF THE CABLE FOLLOWING THE PIPE
REPLACEMENT. IF THE PCCP PIPELINE DOES NOT HAVE AN AFO MONITORING
SYSTEM INSTALLED, 60-DAY ADVANCE NOTIFICATION IS STILL REQUIRED TO
COORDINATE THE REMOVAL & REPLACEMENT OF ANY PCCP PIPE SECTIONS, TO
DOCUMENT THE EXTERNAL CONDITIONS, AND TO COLLECT SAMPLES OF THE
PIPE SECTION FOR FORENSIC ANALYSIS.
GENERAL NOTES FOR WORKING ON M-NCPPC PROPERTY
1. A PRE-CONSTRUCTION MEETING MUST BE HELD PRIOR TO START OF WORK
WITH 72-HOURS PRIOR NOTICE. THE M-NCPPC PARK MANAGER, INSPECTOR, AND
ARBORIST SHALL BE REPRESENTED AT THE MEETING.
2. M-NCPPC RESERVES THE RIGHT TO ADJUST AND MODIFY THE LIMITS OF
DISTURBANCE IN THE FIELD TO MINIMIZE IMPACTS OF WORK.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING SAFE FACILITY
ACCESS THROUGHOUT CONSTRUCTION AND PROVIDE ANY APPROPRIATE
DETOURS, TEMPORARY FACILITIES, AND SIGNAGE AS REQUESTED BY THE PARK
MANAGER.
4. SITE RESTORATION AND REPAIR/REPLACEMENT OF DAMAGED INFRASTRUCTURE
SHALL BE IN ACCORDANCE WITH M-NCPPC DETAILS, STANDARDS, AND
SPECIFICATIONS AT THE DIRECTION OF THE M-NCPPC INSPECTOR AT NO COST
TO M-NCPPC.
5. TREE PROTECTION FENCING SHOULD BE 14-GAUGE WELDED WIRE TYPE (WITH
METAL STAKES AT 10 FEET O.C.) AND MUST BE MAINTAINED THROUGHOUT
CONSTRUCTION. TREE SAVE AREA SIGNAGE SHOULD BE POSTED EVERY 30 FEET
ALONG FENCING. TREE PROTECTION FENCE SHOULD BE INSTALLED BY THE
CONTRACTOR AND INSPECTED BY M-NCPPC ARBORIST PRIOR TO START OF
CONSTRUCTION.
6. THE ENTIRE L.O.D. SHALL BE FENCED AS DIRECTED BY THE PARK INSPECTOR.
WHERE SILT FENCE , SUPER SILT FENCE, OR TREE PROTECTION FENCE IS NOT
REQUIRED, ORANGE BLAZE SAFETY FENCE MAY BE USED.
7. ALL PLANTING SUBSTITUTIONS MUST BE APPROVED BY M-NCPPC
HORTICULTURIST. PLANT MATERIALS AND LOCATIONS SHOULD BE INSPECTED
BY M-NCPPC HORTICULTURIST PRIOR TO INSTALLATION.
8. PROVIDE 4-FOOT HIGH (1-FOOT MINIMUM DIAMETER) 14-GAUGE WELDED WIRE
DEER PROTECTION CAGES WITH MINIMUM OF ONE SUPPORT STAKE FOR ALL
REFORESTATION TRESS AND SHRUBS TO PREVENT DAMGAGE BY DEER. DO NOT
USE TUBEX AS A SUBSTITUTE.
9. STAGING AREAS AND ACCESS ROUTES SHALL BE DETERMINED IN FIELD TO
MINIMIZE IMPACTS.
10. SPECIAL PROTECTION MEASURES, INCLUDING BUT NOT LIMITED TO 12-INCH
THICK MULCH LAYER ACCESS BEDDING, MATTING, TREE PROTECTION FENCING,
AND SEDIMENT CONTROLS SHALL BE PROVIDED AS DIRECTED IN THE FIELD BY
M-NCPPC. M-NCPPC RESERVES THE RIGHT TO INSPECT CONDITION OF TREES
THROUGHOUT CONSTRUCTION AND MAY REQUIRE REPAIR, REMOVAL, AND/OR
REPLACEMENT OF ANY DAMAGED TREES AT NO COST TO M-NCPPC.
11. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR UTILITY CLEARANCE
PRIOR TO WORK AND MUST CONTACT M-NCPPC SMARTPARKS SERVICE CENTER
AT (301) 670-8080 ONCE MISS UTILITY CLEARANCE IS OBTAINED AND
FORTY-EIGHT HOURS PRIOR TO THE START OF CONSTRUCTION FOR LOCATION
OF ALL M-NCPPC UNDERGROUND UTILITIES.
12. THE CONTRACTOR WILL NOT DISCHARGE POTABLE WATER DIRECTLY INTO
STREAMS OR STORM DRAINS THAT FLOW INTO MONTGOMERY COUNTY PARK
PROPERTY.
EXISTING PCCP SHUTDOWN NOTES
1. THE EXISTING 30" PCCP MAIN SHALL BE [SHUTDOWN, DEPRESSURIZED,
DEWATERED, INSPECTED] FOR ALL CONSTRUCTION ACTIVITIES WITHIN 20'-0" OF
EXISTING PCCP INCLUDING INSTALLATION OF NEW TEE.
2. VALVES TO FACILITATE SHUTDOWN:
A. V083 ON SHEET 214NW02
B. V175 ON SHEET 214NW02
C. V125 ON SHEET 214NW02
CONTRACTOR TO VERIFY SHUTDOWN OPERATION WITH THE WSSC WATER CONTRACT
MANAGER A MINIMUM OF 60 DAYS IN ADVANCE OF SHUTDOWN.
3. THE EXISTING 72" PCCP MAIN SHALL BE [SHUTDOWN, DEPRESSURIZED,
INSPECTED ISOLATED AND DEWATERED AND AFO CABLE REMOVED] FOR ALL
CONSTRUCTION ACTIVITIES WITHIN 20'-0" OF EXISTING PCCP INCLUDING
INSTALLATION OF NEW OUTLET.
4. VALVES TO FACILITATE SHUTDOWN:
A. V019 ON SHEET 214NW02 (WITHIN PRESSURE ZONE 660A)
B. V111 ON SHEET 214NW01
C. V097 ON SHEET 214NW01, V098 ON SHEET 214NW01
D. V170 ON SHEET 214NW01
E. V101 ON SHEET 214NW01
CONTRACTOR TO VERIFY SHUTDOWN OPERATION WITH THE WSSC WATER
CONTRACT MANAGER A MINIMUM OF 60 DAYS IN ADVANCE OF SHUTDOWN.
5. CONTRACTOR MUST REMOVE AFO CABLE MONITORING THE 72" PCCP WATER
MAIN. CONTACT WATER CONDITION ASSESSMENT SECTION FOR COORDINATION.
6. CONTRACTOR SHALL PROVIDE TEMPORARY WATER SERVICE FOR ALL
PROPERTIES AFFECTED BY SHUTDOWN DURING CONSTRUCTION AS DIRECTED
BY THE WSSC WATER CONTRACT MANAGER.
EXISTING PCCP SHUTDOWN NOTES
NOTIFICATIONS:
1. THE APPLICANT'S CONTACT PERSON AT WSSC WATER SHALL BE THE PROJECT
MANAGER FOR PROJECTS UP TO AND INCLUDING DESIGN PHASE. DURING
CONSTRUCTION PHASE, THE APPLICANT'S CONTACT PERSON AT WSSC WATER
SHALL BE THE PIPELINE CONSTRUCTION DIVISION INSPECTOR.
2. THE APPLICANT SHALL COMMENCE COORDINATION OF THE PCCP PIPELINE
SHUTDOWN PROCESS WITH THE WSSC WATER CONTACT PERSON AT A
MINIMUM OF 60 DAYS IN ADVANCE OF BEGINNING WORK TO COORDINATE THE
PCCP ISOLATION VALVE INSPECTION, PIPELINE ISOLATION AND DEWATERING,
AND/OR AFO MONITORING CABLE REMOVAL, AND RECHARGE OF THE PIPELINE.
3. APPROVAL OF THE PCCP PIPELINE SHUTDOWN IS SUBJECT TO WATER MAIN
TRANSMISSION SYSTEM CONDITIONS AT THE TIME OF REQUEST.
RESCHEDULING OF THE PROPOSED SHUTDOWN TIME AND DURATION MAY BE
REQUIRED AND IS AT THE DISCRETION OF WSSC.
4. THE APPLICANT'S CONTACT PERSON AT WSSC SHALL COORDINATE THE PCCP
SHUTDOWN A MINIMUM OF 60 DAYS IN ADVANCE OF WORK WITH THE SYSTEMS
CONTROL DIVISION MANAGER (KAREN WRIGHT @ 301-206-8416), THE
WATER/WASTEWATER SYSTEM ASSESSMENT DIVISION (ARTURO ACEVEDO @
301-206-8478), THE PIPELINE CONSTRUCTION DIVISION INSPECTOR, AND THE
UTILITY SERVICES DIVISION MANAGER (NADIR AL-SALAM, (301) 206- 7337).
5. THE PCCP PIPELINE MAY HAVE AN ACOUSTIC FIBER OPTIC (AFO) MONITORING
SYSTEM INSTALLED INSIDE THE PIPELINE. COORDINATION WITH THE
WATER/WASTEWATER SYSTEM ASSESSMENT DIVISION IS REQUIRED (AS
SPECIFIED IN ITEM 2) TO REMOVE THE INTERNAL AFO CABLE PRIOR TO
BEGINNING WORK. IF COORDINATION IS NOT ACCOMPLISHED, THE APPLICANT IS
RESPONSIBLE FOR ANY DAMAGE AND/OR REPLACEMENT OF THE AFO CABLE AS
RESULT OF THEIR WORK AT NO ADDITIONAL COST TO WSSC.
6. IF THE PCCP PIPELINE DOES NOT HAVE AN AFO MONITORING SYSTEM
INSTALLED, 60-DAY ADVANCE NOTIFICATION IS STILL REQUIRED TO COORDINATE
THE REMOVAL & REPLACEMENT OF ANY PCCP PIPE SECTIONS, TO DOCUMENT
THE EXTERNAL CONDITIONS, AND TO COLLECT SAMPLES OF THE PIPE SECTION
FOR FORENSIC ANALYSIS.
7. PCCP PIPELINE RECHARGE EFFORTS SHALL BE COORDINATED WITH WSSC
STAFF SPECIFIED IN ITEM 4. THE PIPELINE RECHARGE EFFORTS AND AFO CABLE
RE-INSTALLATION SHALL FOLLOW THE ADVANCE NOTIFICATION AS SPECIFIED IN
ITEM 2 AND WILL BE UNDER THE DIRECTION OF THE UTILITY SERVICES DIVISION
MANAGER (NADIR AL-SALAM, (301) 206- 7337).
8. THE APPLICANT IS RESPONSIBLE FOR ANY DAMAGE TO THE PCCP MAIN AT THE
LOCATION OF WORK EFFORT AND SHALL BE RESPONSIBLE FOR REPLACEMENT
OF ANY DAMAGED PCCP PIPE SECTIONS PER WSSC DIRECTION AT NO
ADDITIONAL COST TO WSSC WATER.
12345 001-U
LEGEND
LIMITS OF SLIGO CREEK TRAIL
REPLACEMENT/RESTORATION
TO BE PERFORMED BY
CONTRACTOR
EXISTING WATER (TO BE ABANDONED)
EXISTING WATER (TO BE REMOVED)
EXISTING SEWER
EXISTING GAS
EXISTING ELECTRIC
EXISTING OVERHEAD ELECTRIC
EXISTING TELEPHONE
EXISTING CABLE TV
EXISTING FIBER OPTIC
EXISTING STORM DRAIN
ROADWAY R/W LINE
LINE OF DIVISION
EXISTING WSSC EASEMENT
PROPOSED WSSC EASEMENT
PROPOSED CONSTRUCTION STRIP
SILT FENCE
EDGE OF TRAIL
WETLAND
WETLAND BUFFER
TEMPORARY TRAIL LINE
TREE PROTECTION FENCE/LOD
FILTER LOG
TEMPORARY WATER BY-PASS
NEW VALVE
NEW FIRE HYDRANT
NEW CURB STOP
NEW WATER METER
NEW WATER MANHOLE
EXISTING VALVE
EXISTING FIRE HYDRANT
EXISTING CURB STOP
EXISTING WATER METER
EXISTING WATER MANHOLE
EXISTING METER VAULT
EXISTING UTILITY POLE
EXISTING TREE
TEST PIT LOCATION
SOIL BORING LOCATION
PAVEMENT CORE LOCATION
SMH FROM AS-BUILT
SMH FROM WERI
TREE REMOVAL
TP-#
SB-#
PC-#
T.B.A.
T.B.R.
NEW WATER (SMALLER THAN 24")
EXISTING WATER (SMALLER THAN 24")
EXISTING WATER (24" AND LARGER)
NEW WATER (24" AND LARGER WITH
PIPE JOINTS)
LIMITS OF TEMPORARY
ACCESS ROAD
TEMPORARY SLIGO
CREEK TRAIL LIMITS
TPF TPF TPF TPF TPF
X
EGIN
WP001-02
T-402
WP001-03
WP001-04
WP001-WET
WP001-05
WP001-06 END
L SAMPLE PLOT
T-383 T-382
T-389 T-390
T-403
T-391
T-399
T-404
T-415
T-413
T-414
T-416
T-417
T-420
T-418
T-419
T-421
T-422
T-425
T-424 T-423
T-427
T-426
T-428 T-432
T-431
T-429 T-430
T-436
T-437
T-397
T-433 T-434
T-435
T-438
T-398
T-408
T-395
T-375
T-376
T-378
T-377
T-380
T-357
T-356
T 358
T-379
T-353
T-354
T-355
T-352
T-350
T-351
T-381
T-450
T-209
T-106
T-107 T-108
T-105
T-104
T-103
T-102
T-100
T-101
T-97
T-98
T-99
T-96
T-123
T-89
T-62
T-72
T-73
T-77
T-76 T-74
T-95
T-78
T-79
T-87 T-88
T-81
T-82 T-84
T-83
T-85
T-86
T-80
7"
N. RED
OAK
8"
SWAMP
WHITE
21" SILVER
MAPLE
10" RED
MAPLE
2" AMERICAN
HOLLY TREE
1" AMERICAN
HORNBEAM
2" AMERICAN
HOLLY TREE
4" RED
MAPLE
15" RED
MAPLE
10" RED
MAPLE
4" RED
MAPLE
4"-6" TWIN
RED MAPLE
5"
WHITE
OAK
6"
BLACK
GUM
4" RED
MAPLE
6"
AMERICAN
SYCAMORE
3"
BLACK
OAK
13" RED
MAPLE
14" RED
MAPLE
5" S.
RED OAK
5"
BLACK
OAK
1"
BLACK
OAK
5" BLACK
OAK5" BLACK
GUM
2"
BLACK
GUM
6" RED
MAPLE
2"
BLACK
OAK
6" RED
MAPLE
TRAV PT
WTB102
WSSC
C
WSSC
E
EX. 1
8" S
D HDPE
EX. 72" W
PCCP (66-2621J)
(LOCKJOINT NO. PE-67-119)
EX. 30" W
PCCP (61-5411) (LOCKJOINT CO-62-60)
GRASS
GRASS
GRASS
GRASS
GRASS
EX. 30" W
PCCP (61-5411)
EX. 30" W
PCCP
(66-2621J)
EX. 72" W
PCCP (66-2621J)
EX. FIBER OPTICS
EX. FIBER OPTICS
MARYLAND NATIONAL CAPITAL
LIBER: 02706 FOLIO: 0359
THE WARWICK APARTMENTS
1131 W. UNIVERSITY BOULEVARD
LIBER: 64043 FOLIO: 0389LINE OF DIVISION
ASPHALT
EX. 30"X24"
REDUCER
ASPHALT
GRASS
GRASS
GRASS
PARKING GARAGE
EX. BOTTOM
SIDE DITCH
BM 'B'
N
AD
3/
N
G
VD
SC
AL
E:
TP-02
SB-01
TP-01
PC-01
REMOVE EX. 24" VALVE AND
EX. VAULT AND REPLACE
DISTURBED SOIL WITH
STRUCTURAL BACKFILL
REMOVE
EX. 30" W
REMOVE THREE 16 L.F. SECTIONS
OF EX. 30" PCCP WATER MAIN AND
EX. 30"X30" TEE. REPLACE WITH
APPROX. 48 L.F. OF NEW 30" DIP
AND NEW 30"X30" TEE.
TO
UNIVERSITY
BO
ULEVARD W
(M D 193)
NEXT VALVE (V083)
APPROX. 1,215'
NEXT VALVE (V125)
APPROX. 445'
NEXT VALVE (V101)
APPROX. 5,530'
NEXT VALVE (V019)
APPROX. 3,675'
SLIG
O
CREEK TRAIL
SLIG
O
CREEK TRAIL
V127
TO TRAV W
TB101
APPROX. 300'
10'
10'
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TP
F
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF TPF
TPF
TPF
ENTRY PORT 'A001'
0+00
CONNECT TO EX. 30" PCCP W WITH M.J. SOLID
SLEEVE, PCCP X DIP ADAPTER, AND INSULATING
FLANGE (PER STD. DET. C/3.0 AND C/3.3), SEE
PCCP TO DIP CONNECTION DETAIL ON SHEET 6.
CONNECTION MUST BE MADE AT JOINT. PER LAY
SCHEDULE FOR AS-BUILT 61-5411, JOINT IS
LOCATED AT STA. 96+04.
X
X
X
0+10
INSTALL NEW 30"-132 H.B.
ROTATE UP 2°30'
INSTALL NEW
30" W D.I.P.
LIMIT OF
EXCAVATION
0+35=0+00
INSTALL NEW 30"X30" TEE
ROTATE DOWN 2°30'
REMOVE THREE 16 L.F. SECTIONS OF EX. 72"
PCCP WATER MAIN AND EX. 72"X24" OUTLET.
REPLACE WITH APPROX. 48 L.F. OF NEW 72"
STEEL PIPE AND NEW 72"X30" STEEL OUTLET.
REPLACE ANY DISTURBED SOIL WITH
STRUCTURAL FILL WHERE 72" STEEL PIPE IS
INSTALLED. SEE WSSC STD. SPEC. 02315.
0+00
CONNECT TO EX. 72" PCCP W WITH PCCP X STEEL
ADAPTER, AND INSULATING FLANGE (PER STD. DET. C/3.0),
SEE PCCP TO STEEL CONNECTION DETAIL ON SHEET 6.
CONNECTION MUST BE MADE AT JOINT. PER LAY
SCHEDULE FOR AS-BUILT 66-2621J, JOINT IS LOCATED AT
STA. 659+99.
LIMIT OF
EXCAVATION
INSTALL TREE
PROTECTION
PER STD.
DET. SC/19.0
INSTALL TREE PROTECTION
PER STD. DET. SC/19.0
E
N 499050
E
N 499050
E
N 499235
PROPOSED LANDSCAPE TREE
TRANSPLANTING LOCATIONS
X
0+48
CONNECT TO EX. 30" PCCP W WITH M.J. SOLID
SLEEVE, PCCP X DIP ADAPTER, AND INSULATING
FLANGE (PER STD. DET. C/3.0 AND C/3.3), SEE
PCCP TO DIP CONNECTION DETAIL ON SHEET 6.
CONNECTION MUST BE MADE AT JOINT. PER LAY
SCHEDULE FOR AS-BUILT 61-5411, JOINT IS
LOCATED AT STA. 96+52.
0+48
CONNECT TO EX. 72" PCCP W WITH PCCP X STEEL
ADAPTER, AND INSULATING FLANGE (PER STD. DET.
C/3.0), SEE PCCP TO STEEL CONNECTION DETAIL ON
SHEET 6. CONNECTION MUST BE MADE AT JOINT. PER
LAY SCHEDULE FOR AS-BUILT 66-2621J, JOINT IS
LOCATED AT STA. 660+31.
0+32=0+39
INSTALL NEW 72"X30" STEEL
OUTLET, SEE SPECIAL
DETAIL ON SHEET 6
0+34
INSTALL NEW
INSULATED
FLANGE PER
STD. DET. C/3.0
CONTRACTOR SHALL USE
HEAVY DUTY MULCH MAT
ON MNCPPC PROPERTY
PER DETAIL ON SHEET 7
20'
0+23.8 = 30" VALVE
0+25.5 = VAULT
INSTALL NEW 30" HORIZONTAL
VALVE IN VAULT
PER STD. DETS. W/2.4 AND W/2.4a
CONTRACTOR SHALL ADD
MULCH UP TO 20' FROM
FACE OF FILTER LOGS
INSTALL FILTER LOGS
PER STD. DET. SC/20.0
SEE DETAIL ON SHEET 8
CONTRACTOR TO MAINTAIN
EX. DRAINAGE ON NORTHEAST SIDE
OF TRAIL DURING CONSTRUCTION
CONTRACTOR TO INSTALL TEMPORARY PEDESTRIAN TRAIL
USING MEDIUM DUTY MULCH MAT. SEE DETAIL ON SHEET 7
X X
X
X
X
X X
X
X
CONTRACTOR SHALL REPLACE/
RESTORE SLIGO CREEK TRAIL
PER DETAIL ON SHEET 7
INSTALL TREE PROTECTION
PER STD. DET. SC/19.0
INSTALL TREE PROTECTION
PER STD. DET. SC/19.0
NEW
72-INCH STEEL
NEW
30-INCH DIP
INSTALL FILTER LOGS
PER STD. DET. SC/20.0
SEE DETAIL ON SHEET 8
REMOVE AND REPLANT
LANDSCAPE TREE
PROPOSED LANDSCAPE TREES
TRANSPLANTING LOCATIONS
REMOVE AND REPLANT
LANDSCAPE TREES
INSTALL TREE
PROTECTION
PER STD.
DET. SC/19.0
REMOVE AND REPLANT
LANDSCAPE TREE
0+32
INSTALL NEW 30"
M.J. SOLID SLEEVE
0+18
INSTALL NEW 30"
M.J. SOLID SLEEVE
0+05
INSTALL NEW 30"
M.J. SOLID SLEEVE
0+43
INSTALL NEW 30"
M.J. SOLID SLEEVE
W21-7 30"X30" ON TEMPORARY
WOOD POST PER CHAPTER
9B MD-MUTCD
WORK
AREA
AHEAD
WORK
AREA
AHEAD
W21-7 30"X30" ON TEMPORARY
WOOD POST PER CHAPTER
9B MD-MUTCD
INSTALL FILTER LOGS
PER STD. DET. SC/20.0
SEE DETAIL ON SHEET 8
ADDITIONAL TREE PROTECTION FENCE
SEE DETAIL SHEET 7
INSTALL FILTER LOGS PER STD. DET. SC/20.0
SEE DETAIL ON SHEET 8
INSTALL FILTER LOGS PER STD. DET. SC/20.0
SEE DETAIL ON SHEET 8
CONTRACTOR SHALL USE HDPE
MAT GROUND PROTECTION
OUTSIDE OF MNCPPC PROPERTY
PER DETAIL ON SHEET 7
6" TEMPORARY
WATER BY-PASS
GRAPHIC SCALE
5 1010
SCALE: 1"=10'
DATE REVISIONS
NO
200'S OF
CONTRACT
ENGINEER:THESE DOCUMENTS CONTAIN
PRIVILEGED AND CONFIDENTIAL
INFORMATION WHICH SHALL NOT
BE REDISTRIBUTED WITHOUT
PRIOR WSSC APPROVAL VE
R
IF
Y
SC
AL
E
- B
AR
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IF
N O
T O
N E
IN
C
H O
N T
H
IS
S H
EE
T, A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
10/16/2024 9:15 AM - PLOT DATE
DATE
BT7370A22
214NW02
WHEATON ELECTION DISTRICT NO. 13
30" WATER VALVE AND VALVE VAULT REPLACEMENT
1200 W. UNIVERSITY BOULEVARD
SILVER SPRING, MONTGOMERY COUNTY, MARYLAND
WATER INFRASTRUCTURE SECTION
PROJECT MANAGER
PROFESSIONAL CERTIFICATION
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE
OF MARYLAND.
NAME: SHAWN T. BURNETT
LICENSE NO.: 20615
EXP. DATE: 10/21/2026
NAME: THE WILSON T. BALLARD COMPANY
ADDRESS: 17 GWYNNS MILL COURT, OWINGS MILLS, MD 21117
PHONE: (410) 363-0150
CONTACT : SHAWN BURNETT
EMAIL: SBURNETT@WTBCO.COM
SLIGO CREEK MINI DRAINAGE BASIN NOS. 064
PA
TH
T:
\W
SS
C \P
M
A2
0\
0-
1.
B T7
0A
B T7
3A
\D
W G s\
BT
A2 2\
C
-1
.d w g
WASHINGTON SUBURBAN SANITARY COMMISSION
WSSC
HHG: 530'
LHG: 460'
PRESSURE ZONE= 495A
HHG: 670'
LHG: 598'
PRESSURE ZONE (72" W, V019) = 660A
TRAVERSE SCHEDULE
POINT NORTHING EASTING DESCRIPTION
WTB101 498945.44 1303739.68 R/C SET
WTB102 499218.64 1303630.29 R/C SET
PLAN OF 30" VALVE VAULT
SCALE: 1"=10'
- RESTRAIN ALL JOINTS AND FITTINGS BETWEEN
NEW 30"X30" TEE AND NEW 72"X30" STEEL
OUTLET
WATER STAKEOUT DATA
30" WATER REPLACEMENT
LOCATION ITEM NORTHING EASTING
0+00, 30" W CONNECT TO EX. 499138.43 1303670.84
0+35, 30" W 30"X30" TEE 499108.50 1303688.51
0+48, 30" W CONNECT TO EX. 499096.73 1303694.54
WATER STAKEOUT DATA
72" WATER REPLACEMENT
LOCATION ITEM NORTHING EASTING
0+00, 72" W CONNECT TO EX. 499155.57 1303697.94
0+32, 72" W 72"X30" OUTLET 499131.58 1303719.12
0+48, 72" W CONNECT TO EX. 499119.60 1303729.72
WATER STAKEOUT DATA
30" WATER INTERCONNECT
LOCATION ITEM NORTHING EASTING
0+00, 30" W 30"X30" TEE 499108.50 1303688.51
0+10, 30" W 30"-1/32 H.B. 499113.10 1303697.44
0+25.5, 30" W CENTER VAULT AT WATER
MAIN 499123.14 1303709.23
0+39, 30" W 72"X30" OUTLET 499131.58 1303719.12
- RESTRAIN ALL JOINTS AND FITTINGS
ALONG 30" DIP WATER MAIN REPLACEMENT
RESTORATION SCHEDULE
AREA GRADING TYPE RESTORATION
ALL AREAS I "A" OR PAVING
BM 'A'
BOX CUT CONC.
ELEV. = 345.26
BM 'B'
BOX CUT HDWL
ELEV. = 348.38
BM 'C'
BOX CUT CONC.
ELEV. = 349.28
- RESTRAIN ALL JOINTS AND FITTINGS ALONG
72" STEEL WATER MAIN REPLACEMENT
CONTRACTOR SHALL CONSTRUCT TEMPORARY
PEDESTRIAN TRAIL PRIOR TO INSTALLING
TEMPORARY WATER BY-PASS. TEMPORARY
WATER BY-PASS TO CROSS UNDER TREE
PROTECTION FENCE AND OVER FILTER LOGS.
0+200+00
PROFILE OF 30" W
SCALE: 1"=5' HORZ.
1"=5' VERT.
325 325
330 330
335 335
340 340
345 345
350 350
355 355
0+40 0+60
0+00
CONNECT TO EX. 30" PCCP W
SEE DETAIL ON SHEET 6.
INV.= 337.9
(AS-BUILT)
0+35=0+00
30"X30" TEE
ROTATE DOWN 2°30'
INV.= 337.6
0+48
CONNECT TO EX. 30" PCCP W
SEE DETAIL ON SHEET 6.
INV.= 337.5
(AS-BUILT)
NEW 30" W DIPEX. 30" W PCCP
(61-5411) EX. 30" W PCCP
(61-5411)
EX. GRADE
0+200+00
PROFILE OF 30" W INTERCONNECT
SCALE: 1"=5' HORZ.
1"=5' VERT.
335 335
340 340
345 345
350 350
355 355
0+40
NEW 30" W DIP
EX. GRADE
0+00=0+35
30"X30" TEE
ROTATE DOWN 2°30'
INV.= 337.6
0+10 30"-132 H.B.
ROTATE UP 2°30'
INV.= 337.2 0+25.5
VALVE
VAULT
FLOOR
ELEV.= 334.7
0+34
INSULATING
FLANGE
INV.= 337.2
0+39=0+32
72"X30" STEEL
OUTLET
INV.= 335.4 (72" W)0+23.8
30" HORIZONTAL VALVE
INV.= 337.2
RESTRAIN ALL JOINTS AND FITTINGS
0+200+00
PROFILE OF 72" W
SCALE: 1"=5' HORZ.
1"=5' VERT.
0+40 0+60
340 340
345 345
350 350
355 355
EX. GRADE
EX. 72" W PCCP
(66-2621J)
NEW 72" W STEEL
EX. 72" W PCCP
(66-2621J)
0+00
CONNECT TO EX. 72" PCCP W
SEE DETAIL ON SHEET 6.
INV.= 335.5
(AS-BUILT)
0+32=0+39
72"X30" OUTLET
INV.= 335.4 (72" W)
0+48
CONNECT TO EX. 72" PCCP W
SEE DETAIL ON SHEET 6.
INV.= 335.4
(AS-BUILT)
0+20 335.5
0+40 335.4
RESTRAIN ALL JOINTS AND FITTINGS
GRASS
0+20 337.7
0+40 337.5
V V-1
8.0%
EX. GRD
SLIGO CREEK TRAIL GRASS
RESTRAIN ALL JOINTS AND FITTINGS
SLIGO CREEK TRAIL GRASS
0+02
INSULATING FLANGE
INV.= 337.9 0+46
INSULATING FLANGE
INV.= 337.5
0+02
INSULATING FLANGE
INV.= 335.5
0+46
INSULATING FLANGE
INV.= 335.4
2.
7'
CO
VE
R
0+43
30" M.J. SOLID SLEEVE
INV.=337.5
0+05
30" M.J. SOLID SLEEVE
INV.= 337.8
0+18 30" M.J.
SOLID SLEEVE
INV.=337.2
0+32
30" M.J. SOLID SLEEVE
INV.=337.2
DATE REVISIONS
NO
200'S OF
CONTRACT
ENGINEER:THESE DOCUMENTS CONTAIN
PRIVILEGED AND CONFIDENTIAL
INFORMATION WHICH SHALL NOT
BE REDISTRIBUTED WITHOUT
PRIOR WSSC APPROVAL VE
R
IF
Y
SC
AL
E
- B
AR
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IF
N O
T O
N E
IN
C
H O
N T
H
IS
S H
EE
T, A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
10/16/2024 9:16 AM - PLOT DATE
DATE
BT7370A22
214NW02
WHEATON ELECTION DISTRICT NO. 13
30" WATER VALVE AND VALVE VAULT REPLACEMENT
1200 W. UNIVERSITY BOULEVARD
SILVER SPRING, MONTGOMERY COUNTY, MARYLAND
WATER INFRASTRUCTURE SECTION
PROJECT MANAGER
PROFESSIONAL CERTIFICATION
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE
OF MARYLAND.
NAME: SHAWN T. BURNETT
LICENSE NO.: 20615
EXP. DATE: 10/21/2026
NAME: THE WILSON T. BALLARD COMPANY
ADDRESS: 17 GWYNNS MILL COURT, OWINGS MILLS, MD 21117
PHONE: (410) 363-0150
CONTACT : SHAWN BURNETT
EMAIL: SBURNETT@WTBCO.COM
SLIGO CREEK MINI DRAINAGE BASIN NOS. 064
PA
TH
T:
\W
SS
C \P
M
A2
0\
0-
1.
B T7
0A
B T7
3A
\D
W G s\
BT
A2 2\
C
-2
.d w g
WASHINGTON SUBURBAN SANITARY COMMISSION
WSSC
HHG: 530'
LHG: 460'
PRESSURE ZONE= 495A
HHG: 670'
LHG: 598'
PRESSURE ZONE (72" W, V019) = 660A
WP001-01 BEGIN WP001-02
T-402
WP001-03
WP001-04
WP001-WET
WP001-05
WP001-06 END
WP001-UPL SAMPLE PLOT
T-383 T-382
T-384
T-385
T-386
T-387
T-388
T-389
T-390
T-403
T-391
T-399
T-404
T-415
T-413
T-414
T-416
T-417
T-405
T-420 T-418
T-419
T-421
T-422
T-425
T-424 T-423 T-406
T-427
T-426
T-428 T-432
T-431
T-429 T-430
T-436
T-437 T-407
T-397
T-433 T-434
T-435
T-438 T-398
T-439 T-400
T-396
T-408
T-395
T-445
T-444 T-443
T-446 T-447
T-441
T-440
T-442
T-449
T-448
T-409
T-411
T-410
T-365 T-366
T-367
T-369
T-373
T-374 T-371 T-370
T-372
T-364 T-361 T-368
T-362
T-330
T-375 T-376
T-378
T-377
T-380
T-357 T-356
T-359
T-358
T-379
T-353
T-354 T-355
T-352
T-350 T-351
T-360
T-347
T-346
T-349
T-381
T-348
T-363
T-343
T-336
T-344
T-341
T-337 T-342
T-340
T-338 T-339
T-335 T-333 T-334
T-332 T-331
T-450
T-209
T-108
T-106
T-107
T-105
T-104
T-103
T-102
T-100
T-101
T-99
T-98
T-97
T-96
T-94
T-93
T-95
T-114 T-111
T-115
T-117
T-116
T-118
T-113 T-112
T-110
T-109
T-122
T-121
T-120
T-119 T-123
T-89
T-90
T-91
T-92
T-304
T-412
T-60
T-401
T-305 T-301
T-302
T-303
T-61
T-62
T-73
T-72
T-67
T-68 T-82
T-66 T-64
T-63 T-71
T-65
T-76 T-74 T-77
T-75
T-79
T-78
T-87 T-88
T-80
T-81 T-84
T-86 T-85
T-83
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TP
F
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
SCE
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
TPF
N
AD
3/
N
G
VD
SC
AL
E:
TO
UNIVERSITY BO
ULEVARD W
(M
D 193)
SLIG
O
CREEK TRAIL
SLIG
O
CREEK TRAIL
V127
10'
UNIVERSITY BOULEVARD (MD 193) WB
PROP.
TP-02
PROP.
SB-01
PROP.
TP-01
PROP.
PC-01
TRAV
PT
WTB102
TRAV
PT
WTB101
12"
WSSC
COMCAST
10"
VERIZON
PEPCO 791438-210200
PEPCO NO NUMBER
WSSC
EX. 8
" S
D
EX. 12" SD RCP
EX. 24" SD CMP
EX. 72" W
PCCP
(66-2621J)
EX. 30" W
PCCP
(61-5411)
GRASS
GRASS
GRASS
GRASS
GRASS
EX. 30" W
PCCP
(61-5411)
EX. 30" W
PCCP
(66-2621J)
EX. 72" W
PCCP
(66-2621J)
EX. FIBER OPTICS
EX. FIBER OPTICS
MARYLAND NATIONAL CAPITAL
LIBER: 02706 FOLIO: 0359
THE WARWICK APARTMENTS
1131 W. UNIVERSITY BOULEVARD
LIBER: 64043 FOLIO: 0389
LI
NE
O F
DI
VI
SI
O
N
LINE OF DIVISION
LIN
E O
F D
IVISIO
N
ASPHALT
EX. 30"X24"
REDUCER
ASPHALT
EX. SHA R/W LINE
EX. SHA R/W LINE
EX. 1
8" S
D
HDPE
ASPHALT PARKING LOT
PARKING GARAGE
GRASS
GRASS
GRASS
GRASS
EX.
BOTTOM
SIDE
DITCH
ASPHALT
ASPHALT
UNIVERSITY BOULEVARD (MD 193) EB
X
X
REMOVE AND TRANSPLANT
2" AMERICAN HOLLY TREE
REMOVE AND TRANSPLANT
1" AMERICAN HORNBEAM TREE
REMOVE AND TRANSPLANT
2" AMERICAN HOLLY TREE
X
ACCESS ROAD FOR
W
ARW
ICK APARTMENTS
(PRIVATE)
364 T-361
TTTTT-3-3-3-3- 30
T
T-3-3-3-3-333333333 T-3344444
T-332
T-117
T-116
WORK
AREA
AHEAD
WWPWWW 001-01 BEGIN WP001-02
WP001-0333
WP000111-11 04
WPPPP00000000001 WET
T-4T
T
LI
NE
O
WORK
AREA
AHEAD
X X
X X
X X
XX
X X
PROPOSED LANDSCAPE
TREES TRANSPLANTING
LOCATIONS
PROPOSED LANDSCAPE
TREES TRANSPLANTING
LOCATIONS
INSTALL FILTER LOGS PER STD. DET.
SC/20.0 SEE DETAIL ON SHEET 8
W21-7 30"X30" ON TEMPORARY
WOOD POST PER CHAPTER
9B MD-MUTCD
W21-7 30"X30"
ON TEMPORARY
WOOD POST PER
CHAPTER
9B MD-MUTCD
CONTRACTOR SHALL USE MEDIUM
DUTY MULCH MAT TO INSTALL
TEMPORARY PEDESTRIAN TRAIL
SEE DETAIL ON SHEET 7
CONTRACTOR SHALL USE HEAVY DUTY
MULCH MAT ON MNCPPC PROPERTY
PER DETAIL ON SHEET 7
CONTRACTOR SHALL USE HDPE
MAT GROUND PROTECTION
OUTSIDE OF MNCPPC PROPERTY
PER DETAIL ON SHEET 7
INSTALL STABILIZED
CONSTRUCTION ENTRANCE
PER STD. DET. SC/7.0.
SEE DETAIL ON SHEET 8
E
N 499025
E
N 499025
E
N 499225
6" TEMPORARY
WATER BY-PASS
12345 001-U
LEGEND
LIMITS OF TRAIL
REPLACEMENT/RESTORATION
TO BE PERFORMED BY
CONTRACTOR
EXISTING WATER (TO BE ABANDONED)
EXISTING WATER (TO BE REMOVED)
EXISTING SEWER
EXISTING GAS
EXISTING ELECTRIC
EXISTING OVERHEAD ELECTRIC
EXISTING TELEPHONE
EXISTING CABLE TV
EXISTING FIBER OPTIC
EXISTING STORM DRAIN
ROADWAY R/W LINE
LINE OF DIVISION
EXISTING WSSC EASEMENT
PROPOSED WSSC EASEMENT
PROPOSED CONSTRUCTION STRIP
SILT FENCE
EDGE OF TRAIL
WETLANDS
WETLAND BUFFER
TEMPORARY TRAIL LINE
TREE PROTECTION FENCE/LOD
FILTER LOG
TEMPORARY WATER BY-PASS
TREE REMOVAL
NEW VALVE
NEW FIRE HYDRANT
NEW CURB STOP
NEW WATER METER
NEW WATER MANHOLE
EXISTING VALVE
EXISTING FIRE HYDRANT
EXISTING CURB STOP
EXISTING WATER METER
EXISTING WATER MANHOLE
EXISTING METER VAULT
EXISTING UTILITY POLE
EXISTING TREE
TEST PIT LOCATION
SOIL BORING LOCATION
PAVEMENT CORE LOCATION
SMH FROM AS-BUILT
SMH FROM WERI
TP-#
SB-#
PC-#
T.B.A.
T.B.R.
NEW WATER (SMALLER THAN 24")
EXISTING WATER (SMALLER THAN 24")
EXISTING WATER (24" AND LARGER)
NEW WATER (24" AND LARGER WITH
PIPE JOINTS)
LIMITS OF TEMPORARY
ACCESS ROAD
TEMPORARY TRAIL LIMITS
TPF TPF TPF TPF TPF
X
INSTALL TREE PROTECTION
PER STD. DET. SC/19.0
GRAPHIC SCALE
SCALE : 1"=20'
20 10 20
DATE REVISIONS
NO
200'S OF
CONTRACT
ENGINEER:THESE DOCUMENTS CONTAIN
PRIVILEGED AND CONFIDENTIAL
INFORMATION WHICH SHALL NOT
BE REDISTRIBUTED WITHOUT
PRIOR WSSC APPROVAL VE
R
IF
Y
SC
AL
E
- B
AR
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IF
N O
T O
N E
IN
C
H O
N T
H
IS
S H
EE
T, A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
10/16/2024 9:16 AM - PLOT DATE
DATE
BT7370A22
214NW02
WHEATON ELECTION DISTRICT NO. 13
30" WATER VALVE AND VALVE VAULT REPLACEMENT
1200 W. UNIVERSITY BOULEVARD
SILVER SPRING, MONTGOMERY COUNTY, MARYLAND
WATER INFRASTRUCTURE SECTION
PROJECT MANAGER
PROFESSIONAL CERTIFICATION
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE
OF MARYLAND.
NAME: SHAWN T. BURNETT
LICENSE NO.: 20615
EXP. DATE: 10/21/2026
NAME: THE WILSON T. BALLARD COMPANY
ADDRESS: 17 GWYNNS MILL COURT, OWINGS MILLS, MD 21117
PHONE: (410) 363-0150
CONTACT : SHAWN BURNETT
EMAIL: SBURNETT@WTBCO.COM
SLIGO CREEK MINI DRAINAGE BASIN NOS. 064
PA
TH
T:
\W
SS
C \P
M
A2
0\
0-
1.
B T7
0A
B T7
3A
\D
W G s\
BT
A2 2\
C
-1
.d w g
WASHINGTON SUBURBAN SANITARY COMMISSION
WSSC
HHG: 530'
LHG: 460'
PRESSURE ZONE= 495A
HHG: 670'
LHG: 598'
PRESSURE ZONE (72" W, V019) = 660A ACCESS PLAN OF 30" VALVE VAULT
SCALE: 1"=20'
MITIGATION FOR MNCPPC PROPERTY
1. ALL TREES REMOVED WILL BE REPLACED AT 1:1 (ONE INCH TO ONE INCH DIAMETER
BREAST HEIGHT) RATIO (TOTAL 79 INCHES) PREFERABLY AT THE LOCATIONS AS CLOSE
AS POSSIBLE TO WHERE THEY WERE REMOVED, OR WHERE THE EXISTING PIPE AND
VALVE VAULT ARE TO BE TAKEN OUT OF SERVICE. SEE TREE REMOVAL LIST AND
PLANTING SCHEDULE. REQUIRED TREE PLANTING THAT CANNOT TAKE PLACE ON-SITE
DUE TO PROXIMITY TO WSSC WATER FACILITIES WILL TAKE PLACE OUTSIDE THE
PROJECT AREA IN THE VICINITY OF THE PROJECT AT LOCATIONS TO BE IDENTIFIED BY
MONTGOMERY PARKS STAFF.
2. LANDSCAPE TREES WILL NEED TO BE PLANTED/REPLANTED DURING MNCPPC
PRESCRIBED PLANTING TIME FRAME (OCTOBER TO APRIL). CONTRACTOR TO
COORDINATE WITH MONTGOMERY COUNTY PARK STAFF TO DETERMINE IF LANDSCAPE
TREES CAN BE SALVAGED.
3. RESEEDING DISTURBED AREAS WITHIN PARK WITH MNCPPC APPROVED SEED MIXES.
AREAS THAT ARE NOT TURF GRASS SHOULD BE SEEDED WITH THE RIPARIAN SEED
MIXES ON SHEET 8.
4. FULL DEPTH SLIGO CREEK TRAIL REPLACEMENT ALONG ENTIRE LENGTH OF DISTURBED
AREA PER PARKS STANDARD DETAIL TO BE IN PLACE THE MINIMUM TIME NEEDED AND
MUST BE MAINTAINED IN A SAFE MANNER.
5. SILT FENCE INSTALLATION.
6. MULCH MAT (HEAVY DUTY) TEMPORARY ACCESS ROAD WITHIN PARK PROPERTY. SEE
DETAIL ON SHEET 7.
7. TEMPORARY TRAIL INSTALLATION TO MAINTAIN TRAIL ACCESS FOR USERS PER MULCH
MAT (MEDIUM DUTY). SEE DETAIL ON SHEET 7.
8. TREE PROTECTION FENCE INSTALLATION AS NOTED, USING SC 19.0 FOR INDIVIDUAL
TREES.
9. TEMPORARY WATER LINE WILL BE HAND INSTALLED TO CROSS UNDER TREE
PROTECTION FENCING AND OVER FILTER LOGS.
10. PARKING OF VEHICLES, STAGING EQUIPMENT, AND/OR STORING SUPPLIES OUTSIDE LOD
WILL NOT BE ALLOWED. THESE ACTIONS DURING CONSTRUCTION WILL RESULT IN
ADDITIONAL SITE RESTORATION AND MITIGATION.
11. LOD FENCE AROUND PERIMETER WILL BE MONTGOMERY COUNTY PARKS APPROVED
TPF (TREE PROTECTION FENCE). SEE DETAIL ON SHEET 7.
12. PROJECT CONSTRUCTION IS PLANNED TO BEGIN SUMMER 2025 WITH COMPLETION
ANTICIPATED FALL 2025.
PARK TREES TO BE REMOVED
COMMON NAME DBH (INCHES)
SILVER MAPLE 21
RED MAPLE 10
RED MAPLE 4
RED MAPLE 4
TWIN RED MAPLE 4,6
RED MAPLE 15
WHITE OAK 5
RED MAPLE 4
BLACK GUM 6
TOTAL DBH (INCHES) 79
PLANTING SCHEDULE FOR
TREE REPLACEMENT
(ASSUMING 2-INCH REPLACEMENT TREES ARE PLANTED)
SPECIES NUMBER
AMERICAN SYCAMORE 8
SWAMP WHITE OAK 8
RIVER BIRCH 8
REDBUD 8
CARPINUS 8
TOTAL 40
CONTRACTOR SHALL CONSTRUCT TEMPORARY
PEDESTRIAN TRAIL PRIOR TO INSTALLING
TEMPORARY WATER BY-PASS. TEMPORARY
WATER BY-PASS TO CROSS UNDER TREE
PROTECTION FENCE AND OVER FILTER LOGS.
72"X30" STEEL OUTLET DETAIL
N.T.S.
30" DIP WATER MAIN
30" INSULATED
FLANGE JOINT
30" STEEL
FLANGED END
72" STEEL WATER MAIN
30" STEEL
OUTLET
30" DIP
(PE X FLG)
5'
DATE REVISIONS
NO
200'S OF
CONTRACT
ENGINEER:THESE DOCUMENTS CONTAIN
PRIVILEGED AND CONFIDENTIAL
INFORMATION WHICH SHALL NOT
BE REDISTRIBUTED WITHOUT
PRIOR WSSC APPROVAL VE
R
IF
Y
SC
AL
E
- B
AR
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IF
N O
T O
N E
IN
C
H O
N T
H
IS
S H
EE
T, A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
10/16/2024 9:17 AM - PLOT DATE
DATE
BT7370A22
214NW02
WHEATON ELECTION DISTRICT NO. 13
30" WATER VALVE AND VALVE VAULT REPLACEMENT
1200 W. UNIVERSITY BOULEVARD
SILVER SPRING, MONTGOMERY COUNTY, MARYLAND
WATER INFRASTRUCTURE SECTION
PROJECT MANAGER
PROFESSIONAL CERTIFICATION
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE
OF MARYLAND.
NAME: SHAWN T. BURNETT
LICENSE NO.: 20615
EXP. DATE: 10/21/2026
NAME: THE WILSON T. BALLARD COMPANY
ADDRESS: 17 GWYNNS MILL COURT, OWINGS MILLS, MD 21117
PHONE: (410) 363-0150
CONTACT : SHAWN BURNETT
EMAIL: SBURNETT@WTBCO.COM
SLIGO CREEK MINI DRAINAGE BASIN NOS. 064
PA
TH
T:
\W
SS
C \P
M
A2
0\
0-
1.
B T7
0A
B T7
3A
\D
W G s\
BT
A2 2\
C
-5
.d w g
WASHINGTON SUBURBAN SANITARY COMMISSION
WSSC
HHG: 530'
LHG: 460'
PRESSURE ZONE= 495A
HHG: 670'
LHG: 598'
PRESSURE ZONE (72" W, V019) = 660A
NOTES:
1. FIELD VERIFY EXISTING END CONDITIONS AT CONNECTING POINT AND
PROVIDE APPROPRIATE PCCP TO DIP ADAPTER.
2. JOINT BETWEEN PCCP AND DIP X PCCP ADAPTER SHALL BE
MORTAR-COATED AFTER ASSEMBLY (FOR NEW DIP BOND PIPE).
3. SEE DETAILS C/3.0 AND C/3.3 FOR INSULATING FLANGE JOINT.
NEW 30" M.J. SOLID SLEEVE
(LONG TYPE), SEE STD.
DETAIL W/11.0
NEW 30" M.J.
SOLID SLEEVE
(LONG TYPE), SEE
STD. DETAIL
W/11.0NEW 30"X30" TEE
(PUSH-ON x PUSH-ON)
EXISTING 30" PCCP
CONNECT TO EX. PCCP BELL END
(CONNECTION MUST BE MADE AT
EXISTING PIPE JOINT)
NEW 30" PCCP X DIP ADAPTER
(PCCP SPIGOT X DIP FLANGE)
NEW 30" DIP
(PE x PE)
NEW 30" DIP
(PE x PE)
NEW 30" PCCP X DIP…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .