Att._3_GATE201069C_Final_CD-SPECIFCIATIONS-DIV_21-33_VL03_1509021.pdf

PDF 2 MB Posted

Attached to
GATE 201069C - Building 102 Repairs Federal contract opportunity
Solicitation number
P16PS00037
Issued by
Department of the Interior National Park Service National Office

About this file

Attachment 3

View the file

Other files for this federal contract opportunity

Other files attached to GATE 201069C - Building 102 Repairs, newest first.
File Type Posted
Att._6_General_Decision_Number_NJ150037_11062015__NJ37.pdf PDF
Amendment_000005_P16PS00037.pdf PDF
Att._5_B102-Existing_Pressed_Tin_Ceiling-2.JPG JPG image
Att._4_B102-Existing_Pressed_Tin_Ceiling-1.JPG JPG image
Att._3_2015-0528_FINAL_Building_102_HFS.pdf PDF
P16PS00037_Amendment_000004.pdf PDF
Att._1_Compiled_Bid_Questions_Complete_11.25.15.pdf PDF
Att._2_01_27_00_DEFINITION_OF_CONTRACT_LINE_ITEMS_Revised_.pdf PDF
P16PS00037_Amendment_000003.pdf PDF
Amendment_000002_P16PS00037.pdf PDF
Amendment_000001_P16PS00037.pdf PDF
Att._2_GATE201069C_Final_CD-SPECIFCIATIONS-DIV_02-12_VL02_1509021.pdf PDF
Att._9_Proposal_Submission_Package.docx DOCX document
102615_RFP_P16PS00037.pdf PDF
Att._7_GATE201069C_Final_CD-ContractPriceSchedule-Blank_151019.xls XLS spreadsheet
Att._4_Combined_Set_-GATE_646_124865_A.pdf PDF
Att._1_GATE201069C_Final_CD-SPECIFICATIONS-DIV_01_VL01_1509021_rev.pdf PDF
Att._8_Map _GATE-SAHO _Fort_Hancock.pdf PDF
Att._5_Combined_Set_-_GATE_646_41068.pdf PDF
Att._6_General_Decision_Number_NJ150037_10092015__NJ37.pdf PDF
P16PS00037_Presolicitation_Notice.pdf PDF
Amended_Presolicitation_P15PS01047.pdf PDF
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

This page intentionally left blank

National Park Service Gateway National Recreational Area Sandy Hook, NJ

GATE-201069C

092115

TABLE OF CONTENTS

Division Section Title

Volume 3 of 3 - SPECIFICATIONS GROUP

Facility Services Subgroup

DIVISION 21 – FIRE SUPPRESSION

211313 SPRINKLER SYSTEMS

DIVISION 22 - PLUMBING

220513 COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

220516 EXPANSION FITTINGS AND LOOPS FOR PLUMBING PIPING

220517 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

220518 ESCUTCHEONS FOR PLUMBING PIPING

220519 METERS AND GAGES FOR PLUMBING PIPING

220523 GENERAL-DUTY VALVES FOR PLUMBING PIPING

220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

220548.13 VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT

220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

220716 PLUMBING EQUIPMENT INSULATION

220719 PLUMBING PIPING INSULATION

221116 DOMESTIC WATER PIPING

221119 DOMESTIC WATER PIPING SPECIALTIES

221123 DOMESTIC WATER PUMPS

221316 SANITARY WASTE AND VENT PIPING

221319 SANITARY WASTE PIPING SPECIALTIES

223400 FUEL-FIRED, DOMESTIC WATER HEATERS

224213 COMMERCIAL PLUMBING FIXTURES

DIVISION 23 - HEATING VENTILATING AND AIR CONDITIONING

230500 COMMON WORK RESULTS FOR HVAC

230529 HANGERS AND SUPPORTS FOR HVAC PIPING

230548.13 VIBRATION CONTROLS FOR HVAC

230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC

230713 DUCT INSULATION

230923 HVAC PIPING INSULATION

231313 FACILITY UNDERGROUND FUEL STORAGE TANKS

232300 REFRIGERANT PIPING

233113 METAL DUCTS

233300 AIR DUCT ACCESSORIES

092115

233713 DIFFUSERS, REGISTERS, AND GRILLES

237200 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT

238000 VARIABLE REFRIGERANT VOLUME SPLIT-SYSTEM AIR-CONDITIONERS

238239.19 WALL AND UNIT CEILING HEATERS

DIVISION 26 - ELECTRICAL

260000 BASIC ELECTRICAL REQUIREMENTS

260519 260523

LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

CONTROL-VOLTAGE ELECTRICAL POWER CABLES

260526 260529

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

260533.10 RACEWAYS

260533.20 BOXES, ENCLOSURES AND CABINETS

260536 CABLE TRAYS FOR ELECTRICAL SYSTEMS

260543 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS

260544 SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND

CABLING

260548 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

260553 ELECTRICAL SYSTEMS IDENTIFICATION

260573 SHORT CIRCUIT, OVERCURRENT PROTECTIVE DEVICE

COORDINATION STUDY AND ARC FLASH HAZARD ANALYSIS

260583 EQUIPMENT WIRING SYSTEMS

260593 ELECTRICAL SYSTEMS FIRESTOPPING

262416 PANELBOARDS

262417 ROLL-UP GENERATOR TERMINATION CABINET

262713 ELECTRICTY METERING

262726 WIRING DEVICES

262813 FUSES

262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS

263601 MANUAL TRANSFER SWITCHES

264113 LIGHTNING PROTECTION

264300 TRANSIENT VOLTAGE SUPPRESSION

265100 INTERIOR AND EXTERIOR LIGHTING

DIVISION 27 - COMMUNICATIONS

271000 COMMUNICATIONS AND SECURITY GENERAL REQUIREMENTS

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

281611 INTRUSION DETECTION SYSTEM

283111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

092115

Site and Infrastructure Subgroup

DIVISION 31 - EARTHWORK

311000 SITE CLEARING

312000 312319 315000

EARTH MOVING

DEWATERING

EXCAVATION SUPPORT AND PROTECTION

DIVISION 32 - EXTERIOR IMPROVEMENTS

321216 ASPHALT PAVING

321313 CONCRETE PAVING

321373 CONCRETE PAVING JOINT SEALANTS

321713 PARKING BUMPERS

321723 PAVEMENT MARKINGS

329200 TURF AND GRASSES

DIVISION 33 - UTILITIES

334100 STORM UTILITY DRAINAGE PIPING

337173 ELECTRICAL UTILITY SERVICES

END OF TABLE OF CONTENTS

092115

21 13 13 - 1

SPRINKLER SYSTEMS

SECTION 21 13 13 – SPRINKLER SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Pipes, fittings, and specialties.

2. Fire-protection valves.

3. Sprinklers.

4. Pressure gages.

1.2 DEFINITIONS

A. Standard-Pressure Sprinkler Piping: Wet-pipe and dry-pipe sprinkler system piping designed to operate at working pressure of 175 psig (1200 kPa) maximum.

1.3 SYSTEM DESCRIPTIONS

A. Wet-Pipe Sprinkler System: Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device.

B. Dry-Pipe Sprinkler System: Automatic sprinklers are attached to piping containing air which is held in the piping by a dry-pipe control valve. On the other side of the dry-pipe control valve is water that is connected to water supply. Water enters the system when air pressure in the system drops as a result of a sprinkler activation. Sprinklers open when heat melts fusible link or destroys frangible device.

C. System Summary: The Basement Level will be protected by a new dry-pipe sprinkler system.

All piping and hanging assemblies for the dry-pipe sprinkler system on the Basement Level shall be galvanized. A new dry-pipe control valve for the Basement system will be located on the First Floor in the Sprinkler Room. The First and Second Floors will be protected by a retrofitted wet-pipe sprinkler system. New floor control assemblies will be provided for the First and Second Floors. New supply mains will be provided from the sprinkler control room to the existing mains on the First and Second Floors. The re-use of existing mains is recommend on the First and Second Floor. Rerouting is required in the core area to avoid architectural features. See architectural drawings for coordination. New branch lines and sprinklers will connected to the existing mains. The existing dry-pipe control valve will be relocated to the Sprinkler Room on the First Floor to supply the existing Attic dry-pipe sprinkler system. The existing mains, branch lines, and sprinklers within the attic will remain. The connection to the attic system will be made on the Second Floor at the existing riser.

21 13 13 - 2

D. Water Supply: The water supply will enter the East Wing at the existing location. A new double check backflow preventer will be installed at the entry point.

1.4 PERFORMANCE REQUIREMENTS

A. Standard-Pressure Piping System Component: Listed for 175-psig (1200-kPa) minimum working pressure.

B. Sprinkler system design shall be approved by authorities having jurisdiction.

1. Margin of Safety for Available Water Flow and Pressure: 5 percent, including losses through water-service piping, valves, and backflow preventers.

2. Sprinkler Occupancy Hazard Classifications:

a. Electrical Equipment Rooms: Ordinary Hazard, Group 1.

b. General Storage Areas: Ordinary Hazard, Group 1.

c. Mechanical Equipment Rooms: Ordinary Hazard, Group 1.

d. Public Areas: Light Hazard.

3. Minimum Density for Automatic-Sprinkler Piping Design:

a. Light-Hazard Occupancy: 0.10 gpm over 1500-sq. ft. (4.1 mm/min. over 139-

sq. m) area.

b. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. (6.1 mm/min.

over 139-sq. m) area.

c. Dry-Pipe Sprinkler Systems: Remote area shall be increased by 30% without revising the density.

4. Maximum Protection Area per Sprinkler: Per UL listing.

5. Total Combined Hose-Stream Demand Requirement: According to NFPA 13 unless otherwise indicated:

a. Light-Hazard Occupancies: 100 gpm (6.3 L/s) for 30 minutes.

b. Ordinary-Hazard Occupancies: 250 gpm (15.75 L/s) for 60 to 90 minutes.

6. Dry System Sprinkler Requirements: According to NFPA 13, the dry sprinkler systems shall be sized such that initial water is discharged from the system test connection in 60 seconds or less, unless the system size is less than 500 gallons.

1.5 SUBMITTALS

A. Product Data: For each type of product indicated. Where more than one product is shown on any data sheet, indicate the applicable product.

B. Shop Drawings: For sprinkler systems. Include plans, elevations, sections, details, and attachments to other work.

1. Wiring Diagrams: For power, signal, and control wiring.

21 13 13 - 3

C. Coordination Drawings: Sprinkler systems, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:

1. Domestic water piping.

2. Compressed air piping.

3. HVAC hydronic piping.

4. Items penetrating finished ceiling include the following:

a. Lighting fixtures.

b. Air outlets and inlets.

D. Qualification Data: For qualified Installer. The installer shall demonstrate it has successfully installed automatic sprinkler systems for the last 5 years.

E. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, that have been approved by authorities having jurisdiction, including hydraulic calculations if applicable.

F. Welding certificates.

G. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for Aboveground Piping."

H. Field quality-control reports.

I. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and maintenance manuals.

1. Comply with the "System Acceptance" Section of the NFPA 13.

2. Provide "Record of Completion Documents" according to NFPA 13.

3. Provide "Maintenance, Inspection and Testing Records" according to NFPA 25:

a. Frequency of testing of installed components.

b. Frequency of inspection of installed components.

c. Requirements and recommendations related to results of maintenance.

d. Manufacturer's user training manuals.

4. Manufacturer's required maintenance related to system warranty requirements.

1.6 QUALITY ASSURANCE

A. Installer Qualifications:

1. Installer's responsibilities include designing, fabricating, and installing sprinkler systems and providing professional engineering services needed to assume engineering responsibility. Base calculations on results of fire-hydrant flow test.

a. Engineering Responsibility: Preparation or review of working plans, calculations, and field test reports by a minimum NICET Level III Technician.

21 13 13 - 4

B. Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

D. NFPA Standards: Sprinkler system equipment, specialties, accessories, installation, and testing shall comply with the following:

1. NFPA 13, "Installation of Sprinkler Systems," 2013 edition.

2. NFPA 25, “Standard for the Inspection, Testing, and Maintenance of Water-Based Fire

Protection Systems,” 2014 Edition.

3. NFPA 72, “National Fire Alarm and Signaling Code,” 2013 edition.

E. System design and Installation shall comply with National Park Services (NPS) Directives

1.7 WARRANTY

A. The Contractor shall warranty all materials and workmanship during the installation period and a period of one (1) year, beginning from the date of final acceptance by the NPS. The Contractor shall be responsible during the design, installation, testing and warranty periods for any damage caused by him or his subcontractors or by defects in his or his subcontractors' work, materials, or equipment.

1.8 PROJECT CONDITIONS

A. Interruption of Existing Sprinkler Service: Do not interrupt sprinkler service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary sprinkler service according to requirements indicated:

1. Notify NPS no fewer than two days in advance of proposed interruption of sprinkler service.

2. Do not proceed with interruption of sprinkler service without NPS’ written permission.

1.9 COORDINATION

A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light fixtures, HVAC equipment, and partition assemblies.

1.10 EXTRA MATERIALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Sprinkler Cabinets: Finished, wall-mounted, steel cabinet with hinged cover, and with space for minimum of six spare sprinklers plus sprinkler wrench. Include number of sprinklers required by NFPA 13 and sprinkler wrench. Include separate cabinet with

21 13 13 - 5 sprinklers and wrench for each type of sprinkler used on Project. Provide a list of spare sprinklers in accordance with NFPA 25.

PART 2 - PRODUCTS

2.1 GENERAL

A. All components shall be a product of the USA.

2.2 PIPING MATERIALS

A. Pressure ratings of all fittings shall meet or exceed maximum working pressures available within the system.

B. All piping and hangers in the Basement Level shall be protected against corrosion. Piping and hangers in this area shall be hot dipped, galvanized pipe. Piping having an external only galvanized finish is unacceptable.

2.3 STEEL PIPE AND FITTINGS

A. Standard Weight, Black-Steel Pipe: ASTM A 53/A 53M, Type E, Grade B. Pipe ends may be factory or field formed to match joining method.

B. Hot-dipped, Galvanized Pipe: ASTM A 123/A 123M. Pipe ends may be factory or field formed to match joining method.

C. Black-Steel Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M, standard-weight, seamless steel pipe with threaded ends.

D. Uncoated, Steel Couplings: ASTM A 865, threaded.

E. Uncoated, Gray-Iron Threaded Fittings: ASME B16.4, Class 125, standard pattern.

F. Malleable- or Ductile-Iron Unions: UL 860.

G. Cast-Iron Flanges: ASME 16.1, Class 125.

H. Steel Flanges and Flanged Fittings: ASME B16.5, Class 150.

I. Steel Welding Fittings: ASTM A 234/A 234M and ASME B16.9.

J. Grooved-Joint, Steel-Pipe Appurtenances:

1. Pressure Rating: 175 psig (1200 kPa) minimum.

2. Uncoated, Grooved-End Fittings for Steel Piping: ASTM A 47/A 47M, malleable-iron casting or ASTM A 536, ductile-iron casting; with dimensions matching steel pipe.

21 13 13 - 6

2.4 PIPING JOINING MATERIALS

A. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch (3.2 mm) thick or ASME B16.21, nonmetallic and asbestos free.

1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges: Full-face gaskets.

B. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise indicated.

C. Welding Filler Metals: Comply with AWS D10.12M/D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded.

2.5 LISTED FIRE-PROTECTION VALVES

A. General Requirements:

1. Valves shall be UL listed or FM approved.

2. Minimum Pressure Rating for Standard-Pressure Piping: 175 psig (1200 kPa).

B. Backflow Preventer

1. Standard: AWWA C510.

2. Pressure Rating: 250 psig (1725 kPa) minimum.

3. Type: Double Check Valve assembly or reduced pressure zone assembly.

4. Body Material: Cast iron or steel, lined with brass, bronze, epoxy resin or stainless steel.

5. End Connections: Flanged or grooved.

C. Ball Valves:

1. Standard: UL 1091 except with ball instead of disc.

2. Valves NPS 1-1/2 (DN 40) and Smaller: Bronze body with threaded ends.

3. Valves NPS 2 and NPS 2-1/2 (DN 50 and DN 65): Bronze body with threaded ends or ductile-iron body with grooved ends.

4. Valves NPS 3 (DN 80): Ductile-iron body with grooved ends.

D. Iron Butterfly Valves:

1. Standard: UL 1091.

2. Pressure Rating: 175 psig (1200 kPa).

3. Body Material: Cast or ductile iron.

4. Style: Lug or wafer.

5. End Connections: Grooved.

E. Check Valves:

1. Standard: UL 312.

2. Pressure Rating: 250 psig (1725 kPa) minimum.

3. Type: Swing check.

4. Body Material: Cast iron.

5. End Connections: Flanged or grooved.

21 13 13 - 7

F. Riser Check Valve Assembly:

1. Standard: UL 312.

2. Pressure Rating: 250 psig (1725 kPa) minimum.

3. Type: Swing check.

4. Body Material: Cast iron or ductile iron.

5. End Connections: Flanged or grooved.

6. Shall be completed with trim that includes gauges, gauge valves, check valves and drain valves, G. Iron OS&Y Gate Valves:

1. Standard: UL 262.

2. Pressure Rating: 250 psig (1725 kPa) minimum.

3. Body Material: Cast or ductile iron.

4. End Connections: Flanged or grooved.

H. Iron Dry-Pipe Valve:

1. Standard: UL 260.

2. Pressure Rating: 250 psig (1725 kPa) minimum.

3. Body Material: Cast or ductile iron.

4. End Connections: Flanged or grooved.

I. Indicating-Type Butterfly Valves:

1. Standard: UL 1091.

2. Pressure Rating: 175 psig (1200 kPa) minimum.

3. Valves NPS 2 (DN 50) and Smaller:

a. Valve Type: Ball or butterfly.

b. Body Material: Bronze.

c. End Connections: Threaded.

4. Valves NPS 2-1/2 (DN 65) and Larger:

a. Valve Type: Butterfly.

b. Body Material: Cast or ductile iron.

c. End Connections: Flanged, grooved, or wafer.

5. Valve Operation: Integral electrical, 115-V ac, prewired, two-circuit, supervisory switch indicating device.

2.6 AIR COMPRESSOR

A. General Requirements:

1. Compressor shall be tank mounted, single stage oil-free type, air-cooled, electric-motor driven, equipped with two air maintenance devices, a check valve, shutoff valve, automatic drain on drip leg, and pressure switch for automatic starting and stopping.

21 13 13 - 8

Pressure switch settings to start and stop the compressor shall be as required by system conditions.

2. Shall include vibration isolators.

3. Shall include installation of a desiccant dryer, ISO Class 3, 10 max SCFM @ 100 PSI, min. total capacity 4400.

4. A safety relief valve shall be provided.

2.7 TRIM AND DRAIN VALVES

A. General Requirements:

1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.

2. Pressure Rating: 175 psig (1200 kPa) minimum.

2.8 SUPERVISORY AND ALARM EQUIPMENT

A. All waterflow and valve supervisory switches shall be furnished, installed and properly adjusted by the sprinkler contractor. Alarm monitoring of these devices will be by others.

B. Contacts: All waterflow and valve supervisory switches shall be provided with two "Form C" (D.P.D.T.) contacts for monitoring. Specific contact rating shall be coordinated with the fire alarm contractor.

C. Waterflow Switches: Vane-type water flow indicators shall be provided to indicate waterflow in each sprinkler system zone and shall by UL listed and/or FM approved. All water flow switches shall be equipped with an adjustable retard setting that can be varied from 0 to 60 (minimum) seconds.

D. Supervisory Switches: Valve supervisory (tamper) switches shall be provided for all valves controlling the water supply to the sprinkler systems. Valve supervisory switches for OS&Y type valves shall be the yoke mounted or integral type. Supervisory switches for butterfly style valves shall be factory installed and integral to the valve assembly.

E. High/Low Pressure Supervisory Switches: Provide pressure switches for the dry sprinkler systems. The pressure switch shall be UL Listed or FM Approved and contain two single pole double throw contacts. Each switch shall be adjustable from 10 to 60 psi. The low pressure switch shall supervise pressure in the system and shall be set to activate at 10 psi above the dry-pipe valve trip point pressure. The high pressure switch shall supervise pressure in the system and shall be set to activate at 10 psi above the normal dry-pipe supervisory pressure. Activation of either high or low pressure switch shall cause a supervisory alarm on the fire alarm system control unit.

2.9 SPRINKLER SPECIALTY PIPE FITTINGS

A. Branch Outlet Fittings:

21 13 13 - 9

1. Standard: UL 213.

2. Pressure Rating: 175 psig (1200 kPa) minimum.

3. Body Material: Ductile-iron housing with EPDM seals and bolts and nuts.

4. Type: Mechanical-T and -cross fittings.

5. Configurations: Snap-on and strapless, ductile-iron housing with branch outlets.

6. Size: Of dimension to fit onto sprinkler main and with outlet connections as required to match connected branch piping.

7. Branch Outlets: Grooved, plain-end pipe, or threaded.

B. Adjustable Drop Nipples:

1. Standard: UL 1474.

2. Pressure Rating: 250 psig (1725 kPa) minimum.

3. Body Material: Steel pipe with EPDM-rubber O-ring seals.

4. Size: Same as connected piping.

5. Length: Adjustable.

6. Inlet and Outlet: Threaded.

2.10 SPRINKLERS

A. General Requirements:

1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.

2. Pressure Rating for Automatic Sprinklers: 175 psig (1200 kPa) minimum.

3. Standard: UL 199.

B. Automatic Sprinklers with Heat-Responsive Element:

1. Residential Sprinklers

a. Shall be concealed, horizontal sidewall type.

b. Nominal 1/2-inch (12.7-mm) orifice with Discharge Coefficient K of 4.0, and for

"Ordinary" temperature classification rating unless otherwise indicated or required by application.

c. Manufacturer: Viking VK4800, or similar.

2. Dry-type Sprinklers

a. Shall be horizontal sidewall type.

b. Nominal 1/2-inch (12.7-mm) orifice with Discharge Coefficient K of 5.6 or greater, and for "Ordinary" temperature classification rating unless otherwise indicated or required by application.

3. Standard sprinklers

a. Concealed or upright.

b. Nominal 1/2-inch (12.7-mm) orifice with Discharge Coefficient K of 5.6 or greater, and for "Ordinary" temperature classification rating unless otherwise indicated or required by application.

C. Sprinkler Finishes:

21 13 13 - 10

1. Chrome plated.

2. Bronze.

3. Painted.

D. Special Coatings:

1. Wax.

2. Lead.

3. Corrosion-resistant paint.

E. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers.

1. Ceiling Mounting: Chrome-plated steel, two piece, with 1-inch (25-mm) vertical adjustment.

2. Sidewall Mounting: Chrome-plated steel, one piece, flat.

PART 3 - EXECUTION

3.1 PIPING INSTALLATION

A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical.

1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. File written approval with Architect before deviating from approved working plans.

B. Piping Standard: Comply with requirements for installation of sprinkler piping in NFPA 13.

C. Use listed fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes.

D. Install unions adjacent to each valve in pipes NPS 2 (DN 50) and smaller.

E. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 (DN 65) and larger end connections.

F. Install sprinkler piping with drains for complete system drainage.

G. Install alarm devices in piping systems.

H. Install hangers and supports for sprinkler system piping according to NFPA 13. Comply with requirements for hanger materials in NFPA 13.

I. Fill sprinkler system piping with water.

J. Install escutcheons for piping penetrations of walls, ceilings, and floors.

21 13 13 - 11

3.2 JOINT CONSTRUCTION

A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special fittings that have finish and pressure ratings same as or higher than system's pressure rating for aboveground applications unless otherwise indicated.

B. Install unions adjacent to each valve in pipes NPS 2 (DN 50) and smaller.

C. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 (DN 65) and larger end connections.

D. Ream ends of pipes and tubes and remove burrs.

E. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings before assembly.

F. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable for water service. Join flanges with gasket and bolts according to ASME B31.9.

G. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows:

1. Apply appropriate tape or thread compound to external pipe threads.

2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged.

H. Welded Joints: Construct joints according to AWS D10.12M/D10.12, using qualified processes and welding operators according to "Quality Assurance" Article.

1. Shop weld pipe joints where welded piping is indicated. Do not use welded joints for galvanized-steel pipe.

I. Steel-Piping, Cut-Grooved Joints: Cut square-edge groove in end of pipe according to AWWA C606. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for steel-pipe joints.

J. Steel-Piping, Roll-Grooved Joints: Roll rounded-edge groove in end of pipe according to AWWA C606. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for steel-pipe grooved joints.

K. Dissimilar-Material Piping Joints: Make joints using adapters compatible with materials of both piping systems.

3.3 VALVE AND SPECIALTIES INSTALLATION

A. Install listed fire-protection valves, trim and drain valves, specialty valves and trim, controls, and specialties according to NFPA 13 and authorities having jurisdiction.

21 13 13 - 12

B. Install listed fire-protection shutoff valves supervised open, located to control sources of water supply except from fire-department connections. Install permanent identification signs indicating portion of system controlled by each valve.

C. Specialty Valves:

1. General Requirements: Install in vertical position for proper direction of flow, in main supply to system.

3.4 SPRINKLER INSTALLATION

A. Install sprinklers in suspended ceilings in center of acoustical ceiling panels.

B. Install dry-type sprinklers with water supply from heated space. Do not install pendent or sidewall, wet-type sprinklers in areas subject to freezing.

3.5 IDENTIFICATION

A. Install labeling and pipe markers on equipment and piping according to requirements in

NFPA 13.

3.6 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Tests and Inspections:

1. Leak Test: After installation, charge systems and test for leaks. Repair leaks and retest until no leaks exist.

2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

3. Flush, test, and inspect sprinkler systems according to NFPA 13, "Systems Acceptance" Chapter.

4. Energize circuits to electrical equipment and devices.

5. Coordinate with fire-alarm tests. Operate as required.

6. Verify that equipment hose threads are same as local fire-department equipment.

C. Sprinkler piping system will be considered defective if it does not pass tests and inspections.

D. Prepare test and inspection reports.

3.7 CLEANING

A. Clean dirt and debris from sprinklers.

B. Remove and replace sprinklers with paint other than factory finish.

21 13 13 - 13

3.8 DEMONSTRATION

A. Train Owner's maintenance personnel to adjust, operate, and maintain specialty valves.

3.9 PIPING SCHEDULE

A. Sprinkler specialty fittings may be used, downstream of control vales, instead of specified fittings.

B. Standard-pressure, wet-pipe sprinkler system, NPS 2 (DN 50) and smaller, shall be the following:

1. Schedule 40, black-steel pipe with threaded ends; uncoated, gray-iron threaded fittings;

and threaded joints.

C. Standard-pressure, wet-pipe sprinkler system, NPS 2-1/2 to NPS 4 (DN 65 to DN 100), shall be one of the following:

1. Schedule 40, black-steel pipe with threaded ends; uncoated, gray-iron threaded fittings;

and threaded joints.

2. Schedule 40, black-steel pipe with cut- or roll-grooved ends; uncoated, grooved-end fittings for steel piping; grooved-end-pipe couplings for steel piping; and grooved joints.

D. Standard-pressure, dry-pipe sprinkler system NPS 2 (DN 50) and smaller shall be the following:

1. Schedule 40, hot-dipped galvanized pipe with threaded ends; hot-dipped galvanized threaded fittings; and threaded joints.

E. Standard-pressure, dry-pipe sprinkler system, NPS 2-1/2 to NPS 4 (DN 65 to DN 100), shall be one of the following:

1. Schedule 40, hot-dipped galvanized pipe with threaded ends; hot-dipped galvanized threaded fittings; and threaded joints.

2. Schedule 40, hot-dipped galvanized with cut ends; hot-dipped galvanized, grooved-end fittings for steel piping; grooved-end-pipe couplings for steel piping; and grooved joints.

3.10 SPRINKLER SCHEDULE

A. Use sprinkler types in subparagraphs below for the following applications:

1. Rooms without Ceilings: Upright sprinklers.

2. Rooms with Suspended Ceilings: Concealed sprinklers.

3. Dorm Rooms: Concealed residential sprinklers.

4. Cloud Feature in Corridor: Concealed sprinklers.

5. Wall Mounting: Sidewall sprinklers.

6. Spaces Subject to Freezing: Sidewall, dry sprinklers.

Sprinklers within in the dorm rooms shall be concealed, residential sidewall style heads. All other sprinklers, including corridors and the Basement level, shall be quick response.

21 13 13 - 14

B. Provide sprinkler types in subparagraphs below with finishes indicated.

1. Concealed Sprinklers: Rough brass, with factory-painted white cover plate.

2. Upright Pendent and Sidewall Sprinklers: Chrome plated in finished spaces exposed to view; rough bronze in unfinished spaces not exposed to view; wax coated on the Basement Level.

END OF SECTION 211313

GATE – 201069C 22 05 13 - 1

092115 COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

SECTION 22 05 13 - COMMON MOTOR REQUIREMENTS FOR PLUMBING

EQUIPMENT

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes general requirements for single-phase, general-purpose, horizontal, small and medium, squirrel-cage induction motors for use on ac power systems up to 600 V and installed at equipment manufacturer's factory.

1.3 COORDINATION

A. Coordinate features of motors, installed units, and accessory devices to be compatible with the following:

1. Motor controllers.

2. Torque, speed, and horsepower requirements of the load.

3. Ratings and characteristics of supply circuit and required control sequence.

4. Ambient and environmental conditions of installation location.

PART 2 - PRODUCTS

2.1 GENERAL MOTOR REQUIREMENTS

A. Comply with NEMA MG 1 unless otherwise indicated.

2.2 MOTOR CHARACTERISTICS

A. Duty: Continuous duty at ambient temperature of 40 deg C and at altitude of 3300 feet above sea level.

B. Capacity and Torque Characteristics: Sufficient to start, accelerate, and operate connected loads at designated speeds, at installed altitude and environment, with indicated operating sequence, and without exceeding nameplate ratings or considering service factor.

GATE – 201069C 22 05 13 - 2

092115 COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

2.3 SINGLE-PHASE MOTORS

A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and requirements of specific motor application:

1. Permanent-split capacitor.

2. Split phase.

3. Capacitor start, inductor run.

4. Capacitor start, capacitor run.

B. Bearings: Pre-lubricated, antifriction ball bearings or sleeve bearings suitable for radial and thrust loading.

C. Motors 1/20 HP and Smaller: Shaded-pole type.

D. Thermal Protection: Internal protection to automatically open power supply circuit to motor when winding temperature exceeds a safe value calibrated to temperature rating of motor insulation. Thermal-protection device shall automatically reset when motor temperature returns to normal range.

PART 3 - EXECUTION (Not Applicable)

END OF SECTION 22 05 13

GATE – 201069C 22 05 16 - 1

092115 EXPANSION FITTINGS AND LOOPS FOR PLUMBING PIPING

SECTION 22 05 16 - EXPANSION FITTINGS AND LOOPS FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes: Pipe loops and swing connections.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Compatibility: Products shall be suitable for piping service fluids, materials, working pressures, and temperatures.

PART 3 - EXECUTION

3.1 PIPE LOOP AND SWING CONNECTION INSTALLATION

A. Install pipe loops cold-sprung in tension or compression as required to partly absorb tension or compression produced during anticipated change in temperature.

B. Connect risers and branch connections to mains with at least five pipe fittings, including tee in main.

C. Connect risers and branch connections with at least four pipe fittings, including tee in riser.

D. Connect mains and branch connections with at least four pipe fittings, including tee in main.

END OF SECTION 22 05 16

GATE – 201069C 22 05 17 - 1

092115 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

SECTION 22 05 17 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Sleeves.

2. Grout.

PART 2 - PRODUCTS

2.1 SLEEVES

A. Galvanized-Steel-Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc coated, with plain ends.

2.2 GROUT

A. Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.

B. Characteristics: Non-shrink; recommended for interior and exterior applications.

C. Design Mix: 5000-psi, 28-day compressive strength.

D. Packaging: Premixed and factory packaged.

PART 3 - EXECUTION

3.1 SLEEVE INSTALLATION

A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls.

B. Install sleeves in concrete floors, concrete roof slabs, and concrete walls.

1. Cut sleeves to length for mounting flush with both surfaces.

a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches above finished floor level.

GATE – 201069C 22 05 17 - 2

092115 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

2. Using grout, seal the space outside of sleeves in slabs and walls without sleeve-seal system.

C. Install sleeves for pipes passing through interior partitions.

1. Cut sleeves to length for mounting flush with both surfaces.

2. Install sleeves that are large enough to provide 1/4-inch annular clear space between sleeve and pipe or pipe insulation.

3. Seal annular space between sleeve and piping or piping insulation; use joint sealants appropriate for size, depth, and location of joint. Comply with requirements for sealants specified in Section 079200 "Joint Sealants."

D. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for firestopping specified in Section 078413 "Penetration Firestopping."

3.2 SLEEVE SCHEDULE

A. Use sleeves and sleeve seals for the following piping-penetration applications:

1. Concrete Slabs above Grade: Galvanized-steel-pipe sleeves.

2. Interior Partitions: Piping Smaller Than NPS 6: Galvanized-steel-pipe sleeves.

END OF SECTION 22 05 17

GATE – 201069C 22 05 18 - 1

092115 ESCUTCHEONS FOR PLUMBING PIPING

SECTION 22 05 18 - ESCUTCHEONS FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Escutcheons.

2. Floor plates.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product indicated.

PART 2 - PRODUCTS

2.1 ESCUTCHEONS

A. One-Piece, Cast-Brass Type: With polished, chrome-plated or rough-brass finish and setscrew fastener.

B. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with chrome-plated finish and spring-clip fasteners.

C. Split-Casting Brass Type: With polished, chrome-plated or rough-brass finish and with concealed hinge and setscrew.

D. Split-Plate, Stamped-Steel Type: With chrome-plated finish, concealed hinge, and spring-clip fasteners.

2.2 FLOOR PLATES

A. One-Piece Floor Plates: Cast-iron flange with holes for fasteners.

B. Split-Casting Floor Plates: Cast brass with concealed hinge.

GATE – 201069C 22 05 18 - 2

092115 ESCUTCHEONS FOR PLUMBING PIPING

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install escutcheons for piping penetrations of walls, ceilings, and finished floors.

B. Install escutcheons with ID to closely fit around pipe, tube, and insulation of insulated piping and with OD that completely covers opening.

1. Escutcheons for New Piping:

a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-pattern type.

b. Chrome-Plated Piping: One-piece, cast-brass type with polished, chrome-plated finish.

c. Insulated Piping: One-piece, stamped-steel type.

d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, cast-brass type with polished, chrome-plated finish.

e. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece, cast-brass type with polished, chrome-plated finish.

f. Bare Piping in Unfinished Service Spaces: One-piece, cast-brass type with polished, chrome-plated or rough-brass finish.

g. Bare Piping in Equipment Rooms: One-piece, cast-brass type with polished, chrome-plated or rough-brass finish.

2. Escutcheons for Existing Piping:

a. Chrome-Plated Piping: Split-casting brass type with polished, chrome-plated finish.

b. Insulated Piping: Split-plate, stamped-steel type with concealed hinge.

c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: Split-casting brass type with polished, chrome-plated finish.

d. Bare Piping at Ceiling Penetrations in Finished Spaces: Split-casting brass type with polished, chrome-plated finish.

e. Bare Piping in Unfinished Service Spaces: Split-casting brass type with polished, chrome-plated or rough-brass finish.

f. Bare Piping in Equipment Rooms: Split-casting brass type with polished, chrome-plated or rough-brass finish.

C. Install floor plates for piping penetrations of equipment-room floors.

D. Install floor plates with ID to closely fit around pipe, tube, and insulation of piping and with OD that completely covers opening.

1. New Piping: One-piece, floor-plate type.

2. Existing Piping: Split-casting, floor-plate type.

3.2 FIELD QUALITY CONTROL

A. Replace broken and damaged escutcheons and floor plates using new materials.

END OF SECTION 22 05 18

GATE – 201069C 22 05 19 - 1

092115 METERS AND GAGES FOR PLUMBING PIPING

SECTION 22 05 19 - METERS AND GAGES FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Liquid-in-glass thermometers.

2. Dial-type pressure gages.

3. Gage attachments.

4. Meters.

B. Related Sections:

1. Section 221116 "Domestic Water Piping" for water meters inside the building.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product indicated.

1.4 INFORMATIONAL SUBMITTALS

A. Product Certificates: For each type of meter and gage, from manufacturer.

1.5 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For meters and gages to include in operation and maintenance manuals.

PART 2 - PRODUCTS

2.1 LIQUID-IN-GLASS THERMOMETERS

A. Metal-Case, Industrial-Style, Liquid-in-Glass Thermometers:

1. Standard: ASME B40.200.

2. Case: Cast aluminum; 9-inch nominal size.

3. Case Form: Adjustable angle.

4. Tube: Glass with magnifying lens and blue or red organic liquid.

GATE – 201069C 22 05 19 - 2

5. Tube Background: Non-reflective aluminum with permanently etched scale markings graduated in deg F.

6. Window: Glass.

7. Stem: Aluminum and of length to suit installation.

a. Design for Thermowell Installation: Bare stem.

8. Connector: 1-1/4 inches, with ASME B1.1 screw threads.

9. Accuracy: Plus or minus 1 percent of scale range or one scale division, to a maximum of

1.5 percent of scale range.

2.2 THERMOWELLS

A. Thermowells:

1. Standard: ASME B40.200.

2. Description: Pressure-tight, socket-type fitting made for insertion into piping tee fitting.

3. Material for Use with Copper Tubing: CNR or CUNI.

4. Material for Use with Steel Piping: CSA.

5. Type: Stepped shank unless straight or tapered shank is indicated.

6. External Threads: NPS 1/2, NPS 3/4, or NPS 1, ASME B1.20.1 pipe threads.

7. Internal Threads: 1/2, 3/4, and 1 inch, with ASME B1.1 screw threads.

8. Bore: Diameter required to match thermometer bulb or stem.

9. Insertion Length: Length required to match thermometer bulb or stem.

10. Lagging Extension: Include on thermowells for insulated piping and tubing.

11. Bushings: For converting size of thermowell's internal screw thread to size of thermometer connection.

B. Heat-Transfer Medium: Mixture of graphite and glycerin.

2.3 PRESSURE GAGES

A. Direct-Mounted, Metal-Case, Dial-Type Pressure Gages:

1. Standard: ASME B40.100.

2. Case: Liquid-filled, sealed type; cast aluminum or drawn steel; 4-1/2-inch nominal diameter.

3. Pressure-Element Assembly: Bourdon tube unless otherwise indicated.

4. Pressure Connection: Brass, with NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe threads and bottom-outlet type unless back-outlet type is indicated.

5. Movement: Mechanical, with link to pressure element and connection to pointer.

6. Dial: Non-reflective aluminum with permanently etched scale markings graduated in psi.

7. Pointer: Dark-colored metal.

8. Window: Glass or plastic.

9. Ring: Stainless steel.

10. Accuracy: Grade A, plus or minus 1 percent of middle half of scale range.

2.4 GAGE ATTACHMENTS

A. Snubbers: ASME B40.100, brass; with NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe threads and surge-dampening device. Include extension for use on insulated piping.

GATE – 201069C 22 05 19 - 3

B. Valves: Brass ball, with NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe threads.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install thermowells with socket extending to center of pipe and in vertical position in piping tees.

B. Install thermowells of sizes required to match thermometer connectors. Include bushings if required to match sizes.

C. Install thermowells with extension on insulated piping.

D. Fill thermowells with heat-transfer medium.

E. Install direct-mounted thermometers in thermowells and adjust vertical and tilted positions.

F. Install direct-mounted pressure gages in piping tees with pressure gage located on pipe at the most readable position.

G. Install valve and snubber in piping for each pressure gage for fluids.

H. Install thermometers in the following locations: Inlet and outlet of each water heater.

I. Install pressure gages in the following locations:

1. Building water service entrance into building.

2. Suction and discharge of each domestic water pump.

3.2 CONNECTIONS

A. Install meters and gages adjacent to machines and equipment to allow service and maintenance of meters, gages, machines, and equipment.

3.3 ADJUSTING

A. Adjust faces of meters and gages to proper angle for best visibility.

3.4 THERMOMETER SCHEDULE

A. Thermometers at inlet and outlet of each domestic water heater shall be: Industrial-style, liquid-in-glass type.

B. Thermometer stems shall be of length to match thermowell insertion length.

GATE – 201069C 22 05 19 - 4

3.5 THERMOMETER SCALE-RANGE SCHEDULE

A. Scale Range for Domestic Cold-Water Piping: 0 to 100 deg F.

B. Scale Range for Domestic Hot-Water Piping: 0 to 250 deg F.

3.6 PRESSURE-GAGE SCALE-RANGE SCHEDULE

A. Scale Range for Water Service Piping: 0 to 100 psi.

B. Scale Range for Domestic Water Piping: 0 to 100 psi.

END OF SECTION 22 05 19

GATE – 201069C 22 05 23 - 1

092115 GENERAL-DUTY VALVES FOR PLUMBING PIPING

SECTION 22 05 23 - GENERAL-DUTY VALVES FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Bronze ball valves.

2. Bronze swing check valves.

B. Related Sections:

1. Section 220553 "Identification for Plumbing Piping and Equipment" for valve tags and schedules.

2. Section 221116 "Domestic Water Piping" for valves applicable only to this piping.

1.3 DEFINITIONS

A. CWP: Cold working pressure.

B. EPDM: Ethylene propylene copolymer rubber.

C. NBR: Acrylonitrile-butadiene, Buna-N, or nitrile rubber.

D. NRS: Nonrising stem.

E. SWP: Steam working pressure.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of valve indicated.

1.5 QUALITY ASSURANCE

A. Source Limitations for Valves: Obtain each type of valve from single source from single manufacturer.

B. ASME Compliance: ASME B31.9 for building services piping valves.

C. NSF Compliance: NSF 61 for valve materials for potable-water service.

GATE – 201069C 22 05 23 - 2

1.6 DELIVERY, STORAGE, AND HANDLING

A. Prepare valves for shipping as follows:

1. Protect internal parts against rust and corrosion.

2. Protect threads and flange faces.

3. Set ball valves open to minimize exposure of functional surfaces.

4. Block check valves in either closed or open position.

B. Use the following precautions during storage:

1. Maintain valve end protection.

2. Store valves indoors and maintain at higher than ambient dew point temperature. If outdoor storage is necessary, store valves off the ground in watertight enclosures.

C. Use sling to handle large valves; rig sling to avoid damage to exposed parts. Do not use handwheels or stems as lifting or rigging points.

PART 2 - PRODUCTS

2.1 GENERAL REQUIREMENTS FOR VALVES

A. Refer to valve schedule articles for applications of valves.

B. Valve Pressure and Temperature Ratings: Not less than indicated and as required for system pressures and temperatures.

C. Valve Sizes: Same as upstream piping unless otherwise indicated.

D. Valve Actuator Types: Handlever: For quarter-turn valves NPS 6 and smaller.

E. Valves in Insulated Piping: With 2-inch stem extensions and the following features:

1. Ball Valves: With extended operating handle of non-thermal-conductive material, and protective sleeve that allows operation of valve without breaking the vapor seal or disturbing insulation.

F. Valve-End Connections:

1. Solder Joint: With sockets according to ASME B16.18.

2. Threaded: With threads according to ASME B1.20.1.

G. Valve Bypass and Drain Connections: MSS SP-45.

2.2 BRONZE BALL VALVES

A. Two-Piece, Full-Port, Bronze Ball Valves with Stainless-Steel Trim:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Conbraco Industries, Inc.; Apollo Valves.

b. Crane Co.; Crane Valve Group; Crane Valves.

GATE – 201069C 22 05 23 - 3

c. Hammond Valve.

d. Lance Valves; a division of Advanced Thermal Systems, Inc.

e. Milwaukee Valve Company.

f. NIBCO INC.

g. Watts Regulator Co.; a division of Watts Water Technologies, Inc.

2. Description:

a. Standard: MSS SP-110.

b. SWP Rating: 150 psig.

c. CWP Rating: 600 psig.

d. Body Design: Two piece.

e. Body Material: Bronze.

f. Ends: Threaded.

g. Seats: PTFE or TFE.

h. Stem: Stainless steel.

i. Ball: Stainless steel, vented.

j. Port: Full.

2.3 BRONZE SWING CHECK VALVES

A. Class 125, Bronze Swing Check Valves with Bronze Disc:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. American Valve, Inc.

b. Crane Co.; Crane Valve Group; Crane Valves.

c. Crane Co.; Crane Valve Group; Jenkins Valves.

d. Crane Co.; Crane Valve Group; Stockham Division.

e. Hammond Valve.

f. Kitz Corporation.

g. Milwaukee Valve Company.

h. NIBCO INC.

i. Powell Valves.

j. Red-White Valve Corporation.

k. Watts Regulator Co.; a division of Watts Water Technologies, Inc.

l. Zy-Tech Global Industries, Inc.

2. Description:

a. Standard: MSS SP-80, Type 3.

b. CWP Rating: 200 psig.

c. Body Design: Horizontal flow.

d. Body Material: ASTM B 62, bronze.

e. Ends: Threaded.

f. Disc: Bronze.

GATE – 201069C 22 05 23 - 4

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove special packing materials, such as blocks, used to prevent disc movement during shipping and handling.

B. Operate valves in positions from fully open to fully closed. Examine guides and seats made accessible by such operations.

C. Examine threads on valve and mating pipe for form and cleanliness.

D. Do not attempt to repair defective valves; replace with new valves.

3.2 VALVE INSTALLATION

A. Install valves with unions at each piece of equipment arranged to allow service, maintenance, and equipment removal without system shutdown.

B. Locate valves for easy access and provide separate support where necessary.

C. Install valves in horizontal piping with stem at or above center of pipe.

D. Install valves in position to allow full stem movement.

E. Install swing check valves for proper direction of flow and in horizontal position with hinge pin level.

3.3 ADJUSTING

A. Adjust or replace valve packing after piping systems have been tested and put into service but before final adjusting and balancing. Replace valves if persistent leaking occurs.

3.4 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS

A. If valve applications are not indicated, use the following:

1. Shutoff Service: Ball valves.

2. Throttling Service: Ball valves.

3. Pump-Discharge Check Valves: NPS 2 and Smaller: Bronze swing check valves.

B. If valves with specified SWP classes or CWP ratings are not available, the same types of valves with higher SWP classes or CWP ratings may be substituted.

C. Select valves with the following end connections:

1. For Copper Tubing, NPS 2 and Smaller: Threaded ends except where solder-joint valve-end option is indicated in valve schedules below.

GATE – 201069C 22 05 23 - 5

2. For Copper Tubing, NPS 2-1/2 to NPS 4: Flanged ends except where threaded valve-end option is indicated in valve schedules below.

3.5 DOMESTIC, HOT- AND COLD-WATER VALVE SCHEDULE

A. Bronze Valves: May be provided with solder-joint ends instead of threaded ends.

B. Ball Valves: Two piece, full port, bronze with stainless-steel trim.

C. Bronze Swing Check Valves: Class 125, bronze disc.

END OF SECTION 22 05 23

GATE – 201069C 22 05 29 - 1

092115 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION 22 05 29 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND

EQUIPMENT

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification…

This is the start of the file's text. The full file is on GovTribe.