N32205-18-R-4006
USNS JOHN LENTHALL (TAO-189)
REQUEST FOR SPECIFICATION CLARIFICATION
RFC 013
NAME OF CONTRACTOR: ______________________
SPECIFICATION ITEM NO.: _616____________________
PARAGRAPH / SECTION NO:____________________
TITLE: ______AFFF Conversion__________________
QUESTION:
Item 616 paragraph 5.4 references verifying the forward Foam Tank is either coated or stainless steel lined. If not lined or coated, it is to be blasted per 7.3.2.b.1. That paragraph references the Fwd and Aft tank but only gives a square footage for the Fwd Tank. Are both tanks to be blasted? Is so, what is the aft tank square footage?
Also, 7.3.2.b.2 calls out removal of pitting. Please provide an estimated square footage.
ANSWER:
See Amendment 0004 and ARMDEC for revised Item 616A
The Aft Tank Is 75SqFt.
The contractor shall Bid to Clad weld 10 2”X2” areas of pitting and corrosion and grind smooth.