N32205-18-R-4006
USNS JOHN LENTHALL (TAO-189)
REQUEST FOR SPECIFICATION CLARIFICATION
RFC 010
NAME OF CONTRACTOR: ______________________
SPECIFICATION ITEM NO.: _103____________________
PARAGRAPH / SECTION NO:____________________
TITLE: _Contaminated DFM Tank Blasting & Recoating__________________
QUESTION:
Item 103 – Paragraph 4.2 lists the product and directs for two (2) full coats and one (1) stripe coat (Buff, Off White and Off White) to be applied but 7.6.5 says to apply two (2) full coats and two (2) stripe coats (Buff, Off White, Buff and Off White); which is correct?
Item 103 – Paragraph 7.3 directs the contractor to “hand scrape tank to remove large blisters”; can some idea of the amount of effected area be provided i.e. 10% of the tank interior, 25%, more, less?
ANSWER:
See Amendment 0004 and ARMDEC for revised work item 103A. The tank is to be blasted 100% to Sp-11.
ATTACHMENT J - 8