Drawings 3 of 3 - updated.pdf
PDF 8 MB Posted
- Solicitation number
- N0042120B0003
About this file
This solicitation notice seeks proposals for the construction of an approximately 11,400 square foot office building to house the Combat Integration & Identification Systems (CI&IDS) Lab at Webster Outlying Field in St. Inigoes, Maryland. The Naval Air Warfare Center - Aircraft Division Procurement Group at Patuxent River, Maryland will issue the contract on behalf of the Department of the Navy Naval Air Systems Command. Construction will include a single story structure to revitalize the CI&IDS Lab. Proposals are due in response to solicitation number N0042120B0003.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LUMINAIRES
120/277V TOGGLE SWITCH. SINGLE POLE, SUBSCRIPTS DENOTES
FIXTURES CONTROLLED.
LED LUMINAIRE
TOGGLE SWITCH. SUBSCRIPT "3" = 3 WAY, "4" = 4 WAY.
TOGGLE SWITCH. SUBSCRIPT "D" = DIMMER SWITCH 600 WATTS.
WALL MOUNT VANITY FIXTURE.
SURFACE/WALL MOUNT LUMINAIRE
SWITCH AND OCCUPANCY SENSOR, WALL MOUNTED UON.
SURFACE/SUSPENDED MOUNT LUMINAIRE
D
OCCUPANCY SENSOR, CEILING MOUNTED UON.OS
OC
F1E
LUMINAIRE TYPE
'E' DENOTES EMERGENCY
a
LOWER CASE LETTER DENOTES SWITCH
'LEG'. THE SWITCH WITH THE SAME LETTER
OPERATES THE FIXTURE
LP-1
PANELBOARD - CIRCUIT NUMBER
a
EXTERIOR POLE-MOUNTED LIGHT FIXTURE (W/O ARM, W ARM)
P3 = FIXTURE TAG/TYPE
LED EMERGENCY LUMINAIRE. EMERGENCY BATTERY DRIVER, 1400
LUMENS MINIMUM FOR 90 MINUTES, UON (NOTE: ALL FIXTURES
NOTED ON PLAN WITH HATCH AND/OR LABELED WITH AN 'E' AFTER
THE FIXTURE TYPE INDICATES EMERGENCY)
RECESSED / SURFACE LED DOWNLIGHT LUMINAIRE, OR
SUSPENDANT DECORATIVE LUMINARE.
EXIT LUMINAIRE. CEILING / WALL MOUNT. ARROW WHEN USED
INDICATES DIRECTION. HATCHED AREAS INDICATES NUMBER OF
FACES.
POWER
RECESSED DUPLEX CONVENIENCE RECEPTACLE. 20A, 120V. GFI
DENOTES GROUND FAULT INTERRUPTER, AC DENOTES ABOVE
COUNTER, WP DENOTES WEATHER PROOF ENCLOSURE, TV
DENOTES TELEVISION AND OC DENOTES OCCUPANCY CONTROLLED.
RECESSED QUAD RECEPTACLE. 20A, 120V. GFI DENOTES GROUND
FAULT INTERRUPTER.
HOMERUN TO PANEL. PANEL & CIRCUIT DESIGNATIONS AS
INDICATED.
MOTOR RATED SWITCH OR MANUAL MOTOR STARTER WITH
OVERLOADS.
PANELBOARD.
DRY-TYPE TRANSFORMER. T DENOTES TRANSFORMER
IDENTIFICATION
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. 2-#12
CONDUCTORS & 1-#12 GND. IN 1/2" CONDUIT, UON. CONDUIT LARGER
THAN 1/2" & WIRE LARGER THAN #12 SHALL BE INDICATED.
JUNCTION BOX. MINIMUM 4" SQUARE X 2 1/8" / SIZE PER NEC.
TV
GFI
M
ELECTRICAL CONNECTION FOR MECHANICAL EQUIPMENTM
SURFACE MOUNTED DUPLEX CONVENIENCE RECEPTACLE. 20A,
120V. GFI DENOTES GROUND FAULT INTERRUPTER, AC DENOTES
ABOVE COUNTER, WP DENOTES WEATHER PROOF ENCLOSURE AND
C DENOTES CEILING MOUNT (FLUSH).
SURFACE MOUNTED QUAD RECEPTACLE. 20A, 120V. GFI DENOTES
GROUND FAULT INTERRUPTER.
SPECIAL RECEPTACLE. SUBSCRIPT INDICATES TYPE.
A NEMA L5-20
B NEMA L5-30
C NEMA 6-20R
SYSTEMS FURNITURE. RECESSED FLOOR. POWERED FURNITURE
CONNECTION. PROVIDE THE JUNCTION BOX IN (OR ON, FOR RAF)
THE FLOOR SLAB. ALL ASSOCIATED 'WHIP' CONNECTIONS ARE
PROVIDED WITH THE FF&E PACKAGE.
R CEILING MOUNTED RECEPTACLE ON CORD REEL.
J
GROUND ROD, SUBSCRIPT INDICATES TYPE
T = TEST WELLT
AIR TERMINAL
EQUIPMENT CONNECTION OR BONDING CONNECTION
SYSTEMS FURNITURE. RECESSED WALL.
J
J
SF
SF
POWER (CONT')
DISCONNECT SWITCH. 208V IN NEMA 1 ENCL. UON. SLASH
INDICATES VARIABLE FREQUENCY DRIVE, CROSS INDICATES
COMBINATION STARTER/DISCONNECT
30A 15A
DISCONNECT RATING
FUSE SIZE, IF NO FUSE SIZE LISTED,THEN
IT IS NON-FUSED
FLOOR BOX
MAIN GROUNDING BUS (MGB)MGB
RECEPTACLES CONTROLLED BY OCCUPANCY SENSORS PER ASHRAE
90.1 SECTION 8.4.2. PROVIDE MARKINGS ON CONTROLLED
RECEPTACLES PER NEC 406.3(E). SEE DETAIL C2, SHEET E-505.
OC
EMERGENCY POWER OFF PUSHBUTTON. BUTTON MUST SHUNT
POWER TO THE MAIN CIRCUIT BREAKERS IN EACH OF THE
PANELBOARDS SERVING THE EQUIPMENT IN THE SPACE. PROVIDE
WITH CLEAR PLASTIC SAFETY COVERING. INSTALL 6" FROM THE
ROOM'S LIGHT SWITCH. COORDINATE LOCATIONS.
EP
ABBREVIATIONS
Ø PHASE
AC ABOVE COUNTER
AFF ABOVE FINISHED FLOOR
ARF ABOVE RAISED FLOOR
AHU AIR HANDLING UNIT
BKR BREAKER
CONDUIT
CURRENT TRANSFORMER
DRAWING
EACH
EMPTY CONDUIT
ELECTRICAL
ELECTRICAL METALLIC TUBING
ENCLOSURE
EQUIPMENT
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXISTING
EXPLOSION PROOF EQUIPMENT
FAN COIL UNIT
FEET
GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GOVERNMENT FURNISHED EQUIPMENT
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GROUND FAULT INTERRUPTER
GROUND
HIGH INTENSITY DISCHARGE
HORSEPOWER
LIGHT EMITTING DIODE
LIQUID TIGHT CONNECTION
MAIN CIRCUIT BREAKER
MAIN DISTRIBUTION PANEL
MECHANICAL
MAIN LUGS ONLY
MOUNTED
NATIONAL ELECTRICAL CODE
NON FUSIBLE
NOT IN CONTRACT
NIGHT LIGHT
NOT TO SCALE
OUTLET BASE INFEED
OCCUPANCY SENSOR
PANEL
PANELBOARD
POLYVINYL CHLORIDE CONDUIT
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL
ROOM
SHEET
STANDARD OPERATING PROCEDURE
SWITCHBOARD
TELEPHONE
TYPICAL
UNLESS OTHERWISE NOTED
VOLTAGE OR VOLTS
WIRE
WEATHERPROOF
WIREWAY (TROUGH)
IN SCHEDULES, ITEM NOT APPLICABLE
BFG BELOW FINISHED GROUND
C
CT
DWG
EA
EC
ELEC
EMT
ENCL
EQUIP
EWC
EWH
EXIST
EXP
FCU
FT
GFCI
GFE
GFGI
GFI
GND
HID
HP
LED
LTC
MCB
MDP
MECH
MLO
MTD
NEC
NF
NIC
NL
NTS
OBI
OC
PNL
PNLBD
PVC
REC
REQ'D
RGS
RM
SHT
SOP
SWBD
T
TYP
UON
V
W
WP
WW
X
TRANSFORMERXFMR
VARIABLE FREQUENCY DRIVEVFD
A AMPERAGE OR AMPS
CIRCUITCKT
WEATHERPROOF IN USEWPIU
GENERAL
NEW WORK NOTE TAG - REFER TO "WORK NOTES" FOR EACH SHEET?
SYMBOLS - RISER DIAGRAM
CONNECTION
SEPARABLE CONNECTOR OR CONNECTION FOR
DRAWOUT ASSEMBLIES
MANHOLE
FUSED DISCONNECT SWITCH
TRANSFORMER
GROUND
DELTA - WYE TRANSFORMER CONNECTION
METER
DIGITAL METER
SURGE PROTECTION DEVICE
VARIABLE FREQUENCY DRIVE
SHUNT TRIP
CIRCUIT BREAKER
SWITCH
DISCONNECT SWITCH
PANELBOARD (PANELBOARD NAMED 'M')
MOTOR
GENERATOR
CURRENT TRANSFORMER
MH
M
DM
SPD
VFD
ST
M
M
CT
G
BID OPTIONS
ADD 1600 GROSS SQUARE FOOT (BETWEEN GRID 4 AND 5)1.
ADD OFFICE (PLAN NORTH) PARTITIONS WITH SIDE LIGHTS2.
PROVIDE LOW PROFILE RAISED ACCESS FLOOR3.
ADD GENERATOR4.
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:3
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-001
LE
G
E N
D , A
B B
R E
V
IA
TI
O
N S
A N
D G
E N
E R
A L
N O
TE
S
KMSJCH JLJ
13128786
INTERIOR LEGEND
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth Stephen So
Cierra Kinchen
EXIT
NOTE 4
N O
T E
NOTE 2
SINK OR
BASIN
CEILING
FINISHED
FLOOR
DEVICE MOUNTING NOTES:
1.
2.
3.
4.
5.
COORDINATE ABOVE COUNTER DEVICES AND RECEPTACLES WITH CASEWORK OR COUNTERS SUCH THAT THE DEVICES AND RECEPTACLES ARE LOCATED AT +42" AFF OR 9" ABOVE THE COUNTERTOP OR BACKSPLASH, WHICHEVER IS HIGHER.
ALL RECEPTACLES INSTALLED WITHIN 6'-0" OF ANY SINK OR BASIN SHALL HAVE GFI PROTECTION. DO NOT INSTALL
RECEPTACLES WITHIN 12" OF THE EDGE OF A SINK OR BASIN.
COORDINATE WITH THE COMMUNICATIONS DRAWINGS TO ENSURE THAT A DUPLEX RECEPTACLE IS INSTALLED
WITHIN 18" HORIZONTAL TO ALL SIGNAL AND DATA DEVICE LOCATIONS.
SWITCHES AND OTHER FLUSH WALL-MOUNTED DEVICES SHALL BE MOUNTED WITHIN 16" OF DOOR FRAME.
COORDINATE WITH ARCHITECTURAL DRAWINGS FOR DOORS WITH ADJACENT SIDELIGHTS. WHERE DEVICES ARE SHOWN ADJACENT TO THE DOOR ON THE HINGE-SIDE OF THE DOOR, AND THE DOOR SWINGS IN A MANNER THAT SHALL BLOCK THE DEVICE, MOUNT THE DEVICE 12" BEYOND THE DOOR SWING. COORDINATE ROUGH-IN LOCATIONS WITH DIV. 27 AND 28 DEVICES AS WELL. COORDINATE MOUNTING LOCATION WITH OTHER TRADES TO ENSURE A
UNIFORM MOUNTING AND AESTHETICALLY-PLEASING APPEARANCE.
MOUNTING HEIGHT INDICATED IN LEGEND AND ON THE DRAWINGS SHALL BE THE DISTANCE MEASURED FROM THE
CENTER OF THE DEVICE TO THE FINISHED FLOOR. NOTE 3
S
TYPICAL DEVICE MOUNTING DETAIL
NOTE 5
TYPICAL DEVICE MOUNTING HEIGHTS:
REF
CO
AC
REFRIGERATOR, +36" AFF
COPIER, +18" AFF
ABOVE COUNTER, SEE "DEVICE MOUNTING NOTES", NOTE 1 ABOVE
J
AC AC
PANEL LP1A
100A, 208Y/120V-30, 4W
FEEDS FROM PANEL MDP
INSTALLED 2016
DRAWING NO. 15,350,896
DEVICE ID
DEVICE RATING
POWER SOURCE
INSTALLATION DATE
NAVFAC DRAWING NUMBER
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:3
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-002
G E
N E
R A
L E
LE
C
TR
IC
A L
N O
TE
S
KMSJCH JLJ
13128787
GENERAL NOTES
CONSTRUCTION NOTES
1. CONTRACTOR SHALL PROVIDE A MINIMUM OF 2 WEEKS NOTICE OF POWER
OUTAGES TO ACTIVITY AND GOVERNMENT OFFICIAL.
1. AN EQUIPMENT GROUND WIRE MUST BE RUN WITH FEEDERS AND BRANCH
CIRCUITS.
2. WIRING SHALL BE AS PER NATIONAL ELECTRICAL CODE (NEC).
3. ELECTRICAL EQUIPMENT MUST BE IDENTIFIED AND LABELED.
4. FEEDERS/CIRCUITS MUST BE IDENTIFIED AT EACH END OF THE WIRE AND AT
EVERY SPLICE OR JUNCTION/PULL BOX.
5. PROVIDE NAMEPLATES ON THE EXTERIOR OF ELECTRICAL PANELS AND
ENCLOSURES AS FOLLOWS:
6. FOR DISCONNECT SWITCHES AND MOTOR STARTERS, THE TOP LINE SHALL
BE THE NAME/DESIGNATION OF EQUIPMENT BEING FED BY SAME.
7. PROVIDE TYPED DIRECTORIES FOR PANELS (NEW OR EXISTING).
INCLUDED IN THIS PROJECT.
8. INTERIOR WIRING SYSTEMS MUST BE CONCEALED WITH FLUSH MOUNTED
BOXES/DEVICES, UON.
9. DRAWINGS ARE BASED ON EXISTING BUILDING PLANS AND FIELD
INVESTIGATIONS. VISIT THE EXISTING BUILDING AND ACQUAINT
HIMSELF/HERSELF WITH THE EXISTING CONDITIONS. EXAMINE EXISTING
DRAWINGS TO AVOID CONFLICTS.
10. COORDINATE LOCATION AND POWER REQUIREMENTS OF ELECTRICAL
DEVICES WITH MECHANICAL, PLUMBING, ARCHITECTURAL AND FIRE
PROTECTION DRAWINGS.
11. ELECTRICAL DEVICES SHOWN BUT NOT CIRCUITED MUST REMAIN ON THEIR
EXISTING CIRCUIT.
12. PROVIDE ARC-FLASH LABELS ON ALL SWITCHBOARDS / SWITCHGEAR /
PANELS / DISCONNECT SWITCHES / MOTOR STARTS / VFDs PER UFC 3-560-01
AND NFPA 70E.
13. SINGLE PHASE (120/208V) BRANCH CIRCUITS SHALL CONSIST OF 2 #12 & 1 #1
GND. IN 1/2" C UON. THREE PHASE BRANCH CIRCUITS CONSIST OF 3 #12 & 1 #
12 GND IN 1/2" C UON.
14. REFER TO PLANS FOR CONDUCTOR SIZING. COMPLY WITH THE
FOLLOWING GUIDELINES FOR CONDUCTOR RUN LENGTHS:
20A,120V CIRCUITS LONGER THAN 100' - USE #10 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
20A, 120V CIRCUITS LONGER THAN 150' - USE #8 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
20A, 277V CIRCUITS LONGER THAN 150' - USE #10 AWG TO
LIMIT VOLTAGE DROP ON BRANCH CIRCUITS TO 3%
15. COORDINATE ELECTRICAL WORK WITH ARCHITECTURAL, MECHANICAL AND
FIRE PROTECTION WORK PRIOR TO FABRICATION AND INSTALLATION TO
PREVENT CONFLICTS. NOTIFY THE CONTRACTING OFFICER WHERE
CONFLICTS ARE DISCOVERED PRIOR TO CONSTRUCTION AND BEFORE
BEGINNING WORK IN THOSE AREAS. ALL CONFLICTS THAT ARISE DUE TO
LACK OF COORDINATION MUST BE RECTIFIED AT NO COST TO THE
GOVERNMENT.
16. ELECTRICAL CONTRACTOR MUST HAVE A ST. MARY COUNTY ELECTRICAL
LICENSE.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
M S
B
UTILITY
TRANSFORMER
GEN
(BY SMECO)
GENERATOR
ATS
LP
T1
MLV
LB
T2
T3 F
GP1
GP2
23678
E
C
A
B
D
ELEC
5 4
ACCU-1A
MHV
BID OPTIONS
ADD 1600 GROSS SQUARE FOOT (BETWEEN GRID 4 AND 5)1.
ADD OFFICE (PLAN NORTH) PARTITIONS WITH SIDE LIGHTS2.
PROVIDE LOW PROFILE RAISED ACCESS FLOOR3.
ADD GENERATOR4.
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:5
P
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-100
E
LE
C
TR
IC
A
L S
IT
E
P
LA
N
KMSJCH JLJ
13128788
1/8" = 1'-0" A1
ELECTRICAL SITE PLAN
1. PROVIDE (NEMA-4X STAINLESS STEEL) CT CABINET ON EXTERIOR WALL IN
CLOSE PROXIMITY TO THE ATS. PROVIDE WIRING FROM ATS TO CT
CABINET. PROVIDE AND LOOP SUFFICIENT WIRE IN CT CABINET THAT
WILL REACH THE 5' LINE FROM THE BUILDING. PROVIDE SMECO
APPROVED METER BASE NEXT TO CT CABINET (EXTERIOR WALL). METER
ENCLOSURE SHALL BE LOCATED A MINIMUM OF 4" FROM CT CABINET.
CONDUIT SHALL A MINIMUM OF 1-1/4". BOTTOM OF CT CABINET AND
METER SHALL BE MIN. OF 3'-6" ABOVE GRADE. TOP OF CT CABINET SHALL
BE MAX OF 6'-6" ABOVE GRADE. TOP OF METER SHALL BE MAX. OF 6'-0"
ABOVE GRADE. PROVIDE SLIP RISER ON CONDUITS AT BOTTOM OF CT
CABINET.
2. PROVIDE FOUR (4) 4" PVC CONDUIT AND CABLING (PER SHEET E-600)
FROM CT CABINET TO 5' FROM BUILDING. STUB UP CONDUITS ABOVE
GRADE AND CAP FOR EASY FINDING. SMECO WILL PROVIDE CONDUIT
AND CONDUCTORS FROM SMECO PROVIDED UTILITY TRANSFORMER AND
CONNECT TO THE STUB UPS AT THE 5' LINE. COORDINATE INSTALLATION
WITH SMECO. TWO OF THE CONDUITS ARE SPARE. SEE SHEET E-501 FOR
DUCT BANK CROSS SECTION.
3. BID OPTION: PROVIDE ATS WITH NEMA-1 ENCLOSURE INSIDE ELECTRICAL
ROOM.
4. ELECTRICAL PRIMARY DUCT BANK PROVIDED AND SIZED BY SMECO.
5. BID OPTION: PROVIDE GENERATOR IN A SOUND ATTENUATED,
WEATHERPROOF ENCLOSURE AND A 24 HOUR SUB-BASE DIESEL TANK.
GROUND BELLY TANK SHALL BE UL-142 LISTED.
6. PROVIDE CONCRETE ENCASED 2X2 DUCT BANK BETWEEN GENERATOR
AND ATS. TWO OF THE CONDUITS ARE SPARE. SEE SHEET E-501 FOR
DUCT BANK CROSS SECTION.
7. LIMITS OF CONSTRUCTION TO BEGIN AT THE 5' LINE FROM BUILDING
(SMECO TO PROVIDE UTILITY TRANSFORMER, FIBERGLASS PAD AND
CONDUIT/CONDUCTOR TO 5' LINE). SMECO TO ENSURE UTILITY
TRANSFORMER HAS A MINIMUM OF 10' CLEAR WORKSPACE IN FRONT OF
EQUIPMENT FOR HOT STICK WORK.
8. 1" DIRECT BURIED CONDUIT FOR ATS CONTROL. REFER TO DETAIL C4,
SHEET E-501.
WORK NOTES
PLAN
NORTH
1. CONTRACTOR WILL REVIEW UTILITY SOP'S PRIOR TO ANY UTILITY WORK
BEGINS.
2. CONTRACTOR WILL REVIEW SMECO HANDBOOK PRIOR TO PURCHASE
OF CT CABINET AND METER.
GENERAL NOTES
4' 8' 16'0'
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
4 5
4 5
TT
T T
2TYP. 23678
E
C
A
B
D
TYP.
TYP.
3TYP.
BID OPTION
ELEC
TR
5 4
TYP.
TYP.
LAB <TOP SEC>
T
LAB <SECRET>
M G
B
GEN
T
ACCU-1A
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:3
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-101
G R
O U
N D
IN
G
P
LA
N
KMSJCH JLJ
13128789
1/8" = 1'-0" A1
GROUNDING PLAN
1. GROUND ALL SITE EQUIPMENT IN ACCORDANCE WITH MIL-HDBK-419A,
NEC AND APPLICABLE UFC CRITERIA.
2. ALL BONDING AND GROUNDING CONNECTIONS WILL BE EXOTHERMIC
TYPE, UON. SEE DETAILS, SHEET E-500.
1. TYPICAL GROUND ROD. "T" INDICATES TEST WELL. ADDITIONAL GROUND
RODS SHALL BE ADDED AS REQUIRED FOR LIGHTNING PROTECTION AND
GROUNDING.
2. PROVIDE BARE COPPER #4/0 AWG GROUND COUNTERPOISE AT MINIMUM
OF 18" BFG AND 24" OUTSIDE THE FOOT PRINT OF BUILDING OR
CONCRETE PAD.
3. PROVIDE BARE COPPER #4/0 GROUNDING ELECTRODE CONDUCTOR FOR
PAD MOUNTED EQUIPMENT. GROUND EQUIPMENT TO EQUIPMENT
GROUND COUNTERPOISE.
4. PROVIDE EQUIPMENT GROUNDING BAR. COORDINATE WITH TN SHEETS
FOR LOCATION. SEE SHEET E-601 FOR GROUNDING RISER.
5. PROVIDE RAF GROUNDING BAR. SEE GROUNDING RISER FOR DETAILS.
6. GROUND BAR UNDER RAISED FLOOR.
7. SMECO WILL PROVIDE ITS OWN GROUNDING MEASURES FOR THE
SERVICE TRANSFORMER.
GROUND COUNTERPOISE
LINE STYLE LEGEND
WORK NOTES
GENERAL NOTES
4' 8' 16'0'
PLAN
NORTH
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
2TYP.
TYP.
23678
E
C
A
B
D
15 49
3TYP.
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:5
P
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-102
LI
G
H
TN
IN
G
P R
O
TE
C
TI
O N
P
LA
N
KMSJCH JLJ
13128790
1/8" = 1'-0" A1
LIGHTNING PROTECTION PLAN
4' 8' 16'0'
PLAN
NORTH
LINE STYLE LEGEND
1. PROVIDE A FRANKLIN ROD TYPE LIGHTNING PROTECTION SYSTEM IN
ACCORDANCE WITH NFPA 780 AND UL96. ALL LIGHTNING PROTECTION
DOWN CONDUCTORS WILL BE CONCEALED. INSTALLATION PER
APPLICABLE STANDARDS AND SPECIFICAITONS.
2. ALL SYSTEM MATERIALS WILL BE UL LISTED FOR LIGHTNING
PROTECTION SYSTEMS.
3. ENSURE THAT MATERIALS USED ARE COMPATIBLE WITH THE ROOFING
SYSTEM, DOES NOT CAUSE DAMAGE TO THE ROOF WHEN INSTALLED OR
VOID THE ROOF WARRANTY. DISSIMILAR METALS SHALL NOT BE USED.
4. PROVIDE STRANDED COPPER CONDUCTOR WITH A MINIMUM CROSS
SECTIONAL AREA OF 133,100 CIRCULAR MILS FOR ALL MAIN ROOF
CONDUCTORS, BONDING CONDUCTORS, CROSS CONDUCTORS AND
DOWN CONDUCTORS.
5. GROUND ALL SITE EQUIPMENT IN ACCORDANCE WITH MIL-HDBK-419A,
NEC AND APPLICABLE UFC CRITERIA.
6. ALL BONDING AND GROUNDING CONNECTIONS WILL BE EXOTHERMIC
TYPE, UON. SEE DETAILS, SHEET E-500.
1. DOWN CONDUCTOR TO GROUND COUNTERPOISE. SEE DETAIL C4, SHEET
E-500.
2. AIR TERMINAL. SEE DETAIL A4, SHEET E-500.
3. BONDING CONDUCTOR TO MATCH ROOF MAIN CONDUCTOR. SEE SHEET
DETAIL B1, SHEET E-502 (TYPICAL).
WORK NOTES
GENERAL NOTES
ROOF MAIN CONDUCTOR
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
DSDS
DS DSDSDS
DSDS
U G
U G
UG
UG
UG
UG
U G
U G
UG UGUG
U G
U G
U G
U G
U G
U G
T2
LP-11
T5
T5
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:4
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-103
P A
R K
IN
G
L O
T P
LA
N
KMSJCH JLJ
13128791
1" = 20'-0" A1
PARKING LOT PLAN
PLAN
NORTH
0" 20' 60'40'
1. PROVIDE (1) 1" SCHEDULE 40 PVC CONDUIT MINIMUM OF 18" BFG FOR
SITE LIGHTING CIRCUIT, TYPICAL.
WORK NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
J J J
J J
J
JJ J
J
J
J J J
M
J
J
J
JJ
JJ
J
M
M
JJ
JJ JJ JJ
JJ JJ
JJ
JJ
J
J
J
J
J
J
J
J
OFFICE
ELEC
MECH
G P
,3
,5
E-400 A3
E-400 A2
E-400 A4
LS
LT1
(SEE SITE PLAN)
PRINTER
P R
IN
T
E R
S
H R
E D
D E
R
GP2 -1
G P
,4
,6
GP2 -2
G P
,9
,1
1 GP2 -3
G P
,1
,1
2 GP2 -4
G P
,1
,1
GP2 -5
G P
,1
,1
GP2 -6
G P
,2
,2
GP2 -7
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
GP1 -34GP1 -34
GP1 -34
GP1 -34
GP1 -32
GP1 -32
GP1 -32
MLV-5
LS -2
GP1 -30
EWC
GP2 -11
G P
GP2 -15
TV
A
BID OPTION
SF
SF SF
SF
SF
SF SF
C
C
C
5LT1 -1
LS -1 5
ROLL-UP DOOR
SF
LS -22,24,26
LS -28
DSS-1
23678
E
C
A
B
D
15 4
A1 E-400
GP2 -29
REF
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STOR
TR
BREAK
JAN
WOMEN
MEN
CORRIDOR
CONFERENCE
OFFICE
ENGINEERING
TV
VESTIBULE
C O
P
IE
R
G P
,2
,2
GP2 -8
MOTHER'S
GP2 -35
GP2 -37
LAB <TOP SEC>
AV
110A
GFI
GP2 -27
GFI
AC
GFI
AC
GP2 -31
GP2 -28 OFFICE
GP2 -33
OC
OC
OC
OC
OC
OC
OC
OC OC
OC
OC
OC OC
OC
OC OC
OC
OC
OC
OC
OC
GP2 -30
GP2 -32
F -1
FACP F -2
AV RACK
OC OCOCOCOCOCOC
UTILITY
TRANSFORMER
GP1 -32
WP
GFI
GP2 -26
MLV-13
MLV-12
GEN WATER JACKET HEATER
GEN BATTERY CHARGER
G P
,4
,6
GP2 -2
G P
,9
,1
GP2 -3
G P
,1
,1
GP2 -4
G P
,1
,1
GP2 -5
G P
,1
,1
GP2 -6
G P
,2
,2
GP2 -7
SFSFSF
SF
SFSFSF
LAB <SECRET>
OC
OC
OC
OC
GP2 -38
G P
G P
LT1 -27,29,31
LT1 -30
SF
AC
GP1 -33
AC
S M
E P
E P
GP2 -34
GEN
ACCU-1A
3 (TYP.)
3 (TYP.)
C
C C
J
C I
LS -23,25
C J
C D
LS -17 H
B1 E-400
LS -18 C
LS -20C
LT1 -2
LT1 -3
LT1 -4
K
L
M
LT1 -18
LT1 -19
LT1 -20
LT1 -21
K
L
M
N
LT1 -5 N
L T
O
LT1 -6
LT1 -16
LT1 -28
Q
Q
LT1 -7
LT1 -17
R
R
LT1 -12 S
C1 E-400
LT1 -22
LT1 -25 T
T
LT1 -26 U
LT2 -1,3V
LT2 -2,4V
LT2
L T
,7
LT2 -6,8
V
V
C
C
LS -19,21
LS -27,29
LS -23,25
I
JI
C
C
C C
LT2 -9
LT2 -10
LT2 -11
LT2 -12
L T
L T
K
L
M
N
R
S
L T
P
L T
Q
L T
U
C3 E-400
LS -30
COPIER
GP2 -10
REF
GP2 -12
REF
GP2 -1
G P
,3
,5
SF
LT2 -20
LT2 -217
L T
LT2 -19 7
LS -327
LS -31
LS -34 7
LS -337
GP2 -24 GP2 -23 GP2 -22 GP2 -21 GP2 -20 GP2 -19 GP2 -18 GP2 -17
9 9
GP1-27
GP1-29
LAB EQUIPMENT RECEPTACLE VOLTAGE (V) LOAD (W)MARK
A APX-123(V)(1)
UPX-29 SYSTEMS--
C D E F G H I
RTDE SYSTEMS
B1 B2 B3 B4 B5 B6 B7
CP-1273/UPX-24(V) 1078
C-10064/UPX-24(V)+BZ 75
C-10065/UPX-24(V)+BZ 15
C-10063/UPX 300
AN/UPX-41(C) 890
LAB EQUIPMENT SCHEDULE - LAB <SECRET> 132
NOTE:
CV-3372/UPX 550
AUX EQUIP. (SG841/DAGR/IRIG) 600
OSCILLOSCOPE
SIGNAL GENERATOR
SPECTRUM ANALYZER
45TS
TEST EQUIPMENT
SPARE 20A/240V RECEPTACLE
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 6-20R
-- -- N/A 120V
120V 120V 120V 120V 120V 120V 120V 120V 120V 120V 120V 120V 120V 240V
J TDE SYSTEM NEMA 6-20R 240V 500
NOTE: NO MARK INDICATES GENERAL POWER / GENERAL RECEPTACLE.
LAB EQUIPMENT RECEPTACLE VOLTAGE (V) LOAD (W)MARK
K 34A RX/TX SETS
34B RX/TX SETSL
T U V
TEST EQUIPMENT
M N O P Q R S
LAB EQUIPMENT SCHEDULE - LAB <TOP SECRET> 131
NOTE:
SPECTRUM ANALYZER
SPARE 20A/240V RECEPTACLE
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
120V
120V 120V 120V 120V 120V 120V 120V 120V 120V 240V
500NEMA 6-20R
NEMA 5-20R 120V 1400
RF GENERATOR
RF GENERATOR
MAC CLUSTER (IN RACK)
DEVELOPMENT CHASSIS
ZONE-D MACHINES
NIPR MACHINES
SIPR MACHINES
NOTE: NO MARK INDICATES GENERAL POWER / GENERAL RECEPTACLE.
BID OPTIONS
ADD 1600 GROSS SQUARE FOOT (BETWEEN GRID 4 AND 5)1.
ADD OFFICE (PLAN NORTH) PARTITIONS WITH SIDE LIGHTS2.
PROVIDE LOW PROFILE RAISED ACCESS FLOOR3.
ADD GENERATOR4.
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:4
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-104
P O
W E
R P
LA
N
KMSJCH JLJ
13128792 1/8" = 1'-0"
A1
POWER PLAN
4' 8' 16'0'
PLAN
NORTH
1. MOUNTED ABOVE CABINET / RACK.
2. PROVIDE GROUNDING BAR BENEATH RAISED FLOOR. COORDINATE WITH
TN SHEETS FOR LOCATION. SEE SHEET E-601 FOR GROUNDING RISER.
3. ALL RECEPTACLES LOCATED AT WORKBENCHES ARE A MINIMUM OF 3'-6"
AFF (TYP.). LABEL ALL RECEPTACLES PER SCHEDULE THIS SHEET. ALL
RECEPTACLES IN SECRET LAB AND TOP SECRET LAB ARE SURFACE
MOUNTED, UNLESS OTHERWISE NOTED.
4. COORDINATE DEVICE LOCATION WITH AV DRAWINGS. MOUNT TV REC
6'-0" AFF.
5. J-BOX POWER FOR PREMISE CONTROL UNIT (PCU). SEE DETAIL ON TY
SHEETS.
6. COORDINATE WITH FIRE PROTECTION SUPPLIER REGARDING POWER
RECEPTACLE REQUIREMENTS FOR THE LED BOARD. SEE SHEET FA101
FOR LED BOARD LOCATIONS. RECEPTACLES LOCATED 7'-6" AFF.
7. PROVIDE SURFACE MOUNTED J-BOXES UNDER RAISED ACCESS FLOOR
FOR CONNECTION TO FUTURE LOADS/FLOOR BOXES.
8. FLOOR BOXES LOCATION TO BE DETERMINED, ORDERED WITH RAISED
ACCESS FLOOR. FOR REFERENCE ONLY. SEE NOTE 7 ABOVE.
9. PROVIDE RECEPTACLES AND SYSTEMS FURNITURE BETWEEN GRID 4
AND 5 (AS INDICATED) ONLY IF BID OPTION 1 AWARDED.
10. PROVIDE RECEPTACLES IN HATCHED AREA ONLY IF BID OPTION 2
AWARDED.
WORK NOTES
1. SEE SHEET E-105 FOR THE MECHANICAL EQUIPMENT CONNECTION PLAN.
2. TOP SECRET LAB 131 AND SECRET LAB 132 HAS RAISED FLOORS
(FINISHED FLOOR). MOUNTING HEIGHT OF ELECTRICAL ASSETS SHALL
BE THE DISTANCE MEASURED FROM THE CENTER OF THE DEVICE TO
THE FINISHED FLOOR. SEE MOUNTING DETAIL ON SHEET E-002.
3. POWER PLAN SHOWS BID OPTIONS 1, 2 AND 4 AWARDED.
GENERAL NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
M
M M
M M
M
M
M
M
M
M
M
M
M
M
M
M
M
23678
E
C
A
B
D
15 4
OFFICE
ELEC
MECH
DSS-1
MLV-8,10
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STOR
TR
BREAK
JAN
WOMEN
MEN
CORRIDOR
CONFERENCE
OFFICE
ENGINEERING
VESTIBULE
MOTHER'S
EF-1
VAV-01A
VAV-08A
VAV-02A
VAV-03A
VAV-07
VAV-06
VAV-04
VAV-05
EF-3
MLV-7,9
UH-2
DSS-1A
E-400 A2
MLV-1
S M
MLV-3
S M
MHV-7 MHV-8
MHV-9
MHV-10
MHV-11
MHV-123
MHV-133
MHV-14
60A 35A
MSB-4
AV
110A
LAB <TOP SEC>
OFFICE
LAB <SECRET>
VAV-09A
MHV-1530A
NF
30A
NF
H-3
H-2
MHV-22
MHV-24
SZVAV-2
SZVAV-1
60A
NF
60A
NF
MHV-2,4,6
MHV-1,3,5
30A
NF
ACCU-1A
S M
S M
MLV-14,16
CUH-1
BID OPTIONS
ADD 1600 GROSS SQUARE FOOT (BETWEEN GRID 4 AND 5)1.
ADD OFFICE (PLAN NORTH) PARTITIONS WITH SIDE LIGHTS2.
PROVIDE LOW PROFILE RAISED ACCESS FLOOR3.
ADD GENERATOR4.
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:4
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-105
P O
W E
R P
LA
N
M
E C
H A
N
IC
A L
E Q
U
IP
M E
N T
KMSJCH JLJ
13128793
1. PROVIDE NEUTRAL CONDUCTOR TO EACH VAV FAN PER BASIS OF
DESIGN.
2. MECHANICAL EQUIPMENT POWER PLAN SHOWS BID OPTIONS 1 AND 2
AWARDED.
GENERAL NOTES
1/8" = 1'-0" A1
MECHANICAL EQUIPMENT CONNECTION PLAN
4' 8' 16'0'
PLAN
NORTH
1. PROVIDE NEMA-4X, STAINLESS STEEL SAFETY SWITCH.
2. CONNECT EXTERIOR UNIT DSS-1 TO INTERIOR UNIT DSS-1A LOCATED IN
ROOM TR 202.
3. THERMAL MOTOR SWITCH / DISCONNECT / VFD INTEGRAL TO EQUIPMENT
AND PROVIDED BY DIV 23/DIV 22. SEE MECHANICAL AND PLUMBING
SCHEDULES.
4. IF BID OPTION 1 IS NOT AWARDED, MECHANICAL EQUIPMENT
ELECTRICAL LOADING WILL CHANGE. SEE SCHEDULES FOR LOADING
CHANGES. SEE MECHANICAL PLANS (SHEET M-101) FOR NEW VAV
LOCATIONS, IF APPLICABLE.
WORK NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
OS
OS
OS
OS
OS
OS OS
OS
OS OS
OS
OS
OS
OS
OS
O
S
O S
O S
O S
O S
O S
D
O S
OS
OS
Da Db
O S
O S
OS
D
O S
OFFICE
OFFICE
D2
D2
D2 D2
D2E
D2 D2E D2
D2
D2D2
D2
ELEC
MECH
U1
U1
S1
S1
S1
S1
LP-10
LP-10
LP-10
LP-10
8'-6" (TYP. UON)
23678
E
C
A
B
D
ENGINEERING
CORRIDOR
5 4
LAB <TOP SEC>
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STOR
TR
WOMEN
MEN
MOTHER'S
BREAK
JAN
OFFICE
AV
110A
OFFICE
CONFERENCE
VESTIBULE
LP-10 LP-10
S1 S1
10'-0"
12'-0"
10'-0" a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a a a a a a a a
D2E
D2
D2
D2E
D2D2D2D2E
D2 D2 D2 X2
X2
D2
D2E
D2
X2
D2
D2
D2
D2D2
D2
D2E
D2D2
D2
D2
D2
LP-2 LP-8
LP-4
X1X1
LP-9
O1
O1
O1
O1E
O1
O1
O1
O1
O1
O1E
O1
O1
O1
O1 O1
O1
O1
O1
O1
O1
O1
O1E
O1
O1
O1
O1
O1
O1 O1
O1
O1E
O1
O1
O1
O1
O1
O1
O1
O1
O1E
O1
O1 O1
O1
O1
O1
O1
O1E
O1
O1
O1
O1
O1
O1
O1
O1 O1
O1
O1
O1
O1
O1
O1
O1
D1
D1
D1
A1E
A1
A1E
A1
A1
A1E
A1 A1 A1E
X2
A1
C1E X2
A1E
A1
X2
LP-6
D1
X2
C8 C8
C8E
C8
V1
V1 V1
V1
C8
C8E
C8
C8
X2
LP-7
LP-5
B1 B1
B1
B1
B1
B1
B2
B2 B2
B2B2E
B2 B2
D3
D3E
D3 D1
D1E
D1
D1D1
D1 D1E
D1D1
D3
LP-3
B1
B1
B1
B1 B1
B1 B1
B1 B1
B1 B1
B1 B1
B1
X1
10'-0" AFF
10'-0" AFF
S1
LP-10
OFFICE
LAB <SECRET>
D2E
D2
D2
D2E
LP-10
S1
D2E
D2
D2
D2
D2E
B1
B1
8'-6" TYP.
O1
O1
O1
O1
O1
O1E
O1
O1
O1
O1
O1
O1
O1E
O1b b b b b b b b b b b b b b
D2
D2
D2
LP-1
D2
D2
D2 D2E
C8
C8
C8 C8
C8 C8
2 TYP.
7'-0"
7'-0"
11'-0"11'-0"11'-0"
X2
V1 V1
D1
53 54 4 4 4 4 4 4
BID OPTIONS
ADD 1600 GROSS SQUARE FOOT (BETWEEN GRID 4 AND 5)1.
ADD OFFICE (PLAN NORTH) PARTITIONS WITH SIDE LIGHTS2.
PROVIDE LOW PROFILE RAISED ACCESS FLOOR3.
ADD GENERATOR4.
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:5
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-106
LI
G
H
TI
N G
P
LA
N
KMSJCH JLJ
13128794
1/8" = 1'-0" A1
LIGHTING PLAN
4' 8' 16'0'
PLAN
NORTH
1. CIRCUIT UNDERCABINET LIGHTS TO NEAREST 120V CIRCUIT. SEE SHEET
E-400.
2. EXTERIOR LIGHTING CONTROLLED BY LIGHTING CONTROL PANEL (LCP).
SEE SHEET E-504.
3. PROVIDE LIGHTING FIXTURES AND LIGHTING CONTROL SWITCHES
BETWEEN GRID 4 AND 5 ONLY IF BID OPTION 1 AWARDED.
4. PROVIDE ABOVE CEILING MOUNTED JBOX FOR LIGHTING CONTROL
SWITCHING. IF BID OPTION 2 IS NOT AWARDED, THEN ALL LIGHTING
CONTROL SWITCHES IN PLAN NORTH OFFICES WILL BE JETTISONED AND
PROVIDE LIGHTING CONTROL SWITCHING ON SAME CIRCUIT AND PLACE
SWITCH AS INDICATED.
5. IF BID OPTION 1 IS AWARDED AND BID OPTION 2 IS NOT AWARDED, THEN
PLACE LIGHTING FIXTURES IN OFFICES 125 AND 126 ON SAME CIRCUIT AS
REMAINING PLAN NORTH OFFICES. MAKE CIRCUIT LP-8 A SPARE CIRCUIT.
WORK NOTES
1. LIGHTING ROOM CONTROLLERS TO BE LOCATED IN EACH INDIVIDUALLY
CONTROLLED ROOM.
2. LIGHTING CONTROL SCHEMES ARE DEFINED ON SHEETS E-504 AND
E-505.
3. EACH SPACE SHALL HAVE DEDICATED LOCAL CONTROLS USING
STANDARD "OFF-THE-SHELF" COMPONENTS.
4. LIGHTING CONTROL PANEL (LCP) SHALL HAVE THE ABILITY TO
COMMUNICATE WITH THE FIRE ALARM SYSTEM RECEIVING A
SIGNAL/INPUT TO INDICATE A FIRE ALARM INITIATION. THIS SIGNAL
SHALL INITIATE ALL LIGHTING TO INCREASE TO 100% FOR ALL SPACES
AND SHALL OVERRIDE ALL CONTROLS. SHEET E-504 FOR LCP DETAIL.
5. SPACES MAY HAVE MULTIPLE CONTROL TYPES.
6. OCCUPANCY SENSORS SHALL BE PLACED IN CENTER OF ACT, OR IN
LOCATION ORTHOGONAL TO LIGHTING FIXTURES.
7. LIGHTING PLAN SHOWS BID OPTIONS 1 AND 2 AWARDED.
GENERAL NOTES
LIGHTING CONTROLS SCHEDULE
NAME RM # CONTROLS
VESTIBULE 100 OS2
CORRIDOR 101 OS2
MEN 102 OS1
WOMEN 103 VS2
JAN 104 OS1
MOTHER'S 105 SW
BREAK 106 OS2
STOR 107 OS3
CONFERENCE 110 DIM
AV 110A SW
OFFICE 120 VS2
OFFICE 121 VS2
OFFICE 122 VS2
OFFICE 123 VS2
OFFICE 124 VS2
OFFICE 125 VS2
OFFICE 126 VS2
OFFICE 127 VS2
OFFICE 128 VS2
OFFICE 129 VS2
ENGINEERING 130 OS3
LAB <TOP SEC> 131 OS1
LAB <SECRET> 132 OS1
MECH 200 SW
ELEC 201 SW
TR 202 SW
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
J M
M
M
M M
MM
UH-1
DWH-1
MLV-4,6
GP1 -28
MLV-11
D
S M
EF-2
DDC
S M
MLV-2
H -1
30A
NF
MHV-16,18,20
60A
NF
MHV-17,19,21
AHU-1A
(CKT1)
DH-1
S M
AHU-1A
(CKT2)
60A
NF
MHV-23,25,27
GP1 -25
GP1 -25
MSB
ATS
MLV
MHV T3
T1
LP
F
LB
GP1
GP2
T2 4
BID OPTION
E
GP1 -26
GP1 -26
GP1 -26
MGB5
TPP
TPP -6
(C A
B -1
(RK-1)
(C A
B -2
(R
K -1
A
A
A
A
TPP -1
TPP -2
TPP -3
TPP -4
N M
C I/D
I C
O -L
O
D2/D3
TERM
RACK
TELEPHONE
RACK
TPP-10
TPP-9
PBB
TPP -5
E
DSS-1A
TPP -8
TPP -8
TPP -7
MICRO
GP2 -14
GP2 -25
GFI
AC
U1 U1
6 S
GP2 -16
MICRO
GP2 -25
GFI
AC
LS -16 LS -15 LS -14 LS -13 LS -12 LS -11 LS -10 LS -9 LS -8 LS -7 LS -6 LS -5 LS -4 LS -3LS-19,21LS-27,29LS-23,25
A
B1
B2
B3
B6
B5
B5
I
J
C
C
D
D
E
B4
B7
F
GH
A
B1
B2
B3
B6
B5
B5
I
J
C
C
D
D
E
B4
B7
F
GH
A
B1
B2
B3
B6
B5
B5I
C
C
D
D
E
B4
B7
F
G
TYP.7
LAB EQUIPMENT RECEPTACLE VOLTAGE (V) LOAD (W)MARK
A APX-123(V)(1)
UPX-29 SYSTEMS--
C D E F G H I
RTDE SYSTEMS
B1 B2 B3 B4 B5 B6 B7
CP-1273/UPX-24(V) 1078
C-10064/UPX-24(V)+BZ 75
C-10065/UPX-24(V)+BZ 15
C-10063/UPX 300
AN/UPX-41(C) 890
LAB EQUIPMENT SCHEDULE - LAB <SECRET> 132
NOTE:
CV-3372/UPX 550
AUX EQUIP. (SG841/DAGR/IRIG) 600
OSCILLOSCOPE
SIGNAL GENERATOR
SPECTRUM ANALYZER
45TS
TEST EQUIPMENT
SPARE 20A/240V RECEPTACLE
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 6-20R
-- -- N/A 120V
120V 120V 120V 120V 120V 120V 120V 120V 120V 120V 120V 120V 120V 240V
J TDE SYSTEM NEMA 6-20R 240V 500
NOTE: NO MARK INDICATES GENERAL POWER / GENERAL RECEPTACLE.
LAB EQUIPMENT RECEPTACLE VOLTAGE (V) LOAD (W)MARK
K 34A RX/TX SETS
34B RX/TX SETSL
T U V
TEST EQUIPMENT
M N O P Q R S
LAB EQUIPMENT SCHEDULE - LAB <TOP SECRET> 131
NOTE:
SPECTRUM ANALYZER
SPARE 20A/240V RECEPTACLE
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
NEMA 5-20R
120V
120V 120V 120V 120V 120V 120V 120V 120V 120V 240V
500NEMA 6-20R
NEMA 5-20R 120V 1400
RF GENERATOR
RF GENERATOR
MAC CLUSTER (IN RACK)
DEVELOPMENT CHASSIS
ZONE-D MACHINES
NIPR MACHINES
SIPR MACHINES
NOTE: NO MARK INDICATES GENERAL POWER / GENERAL RECEPTACLE.
LT1 -26
LT1 -24
LT1 -17
LT1 -16
LT1 -11 LT1 -15
LT1 -14
LT1 -26
LT1 -13
LT1 -12
LT1 -23
LT1 -7
LT1 -6
LT1 -11 LT1 -21
LT1 -10
LT1 -9
LT1 -8LT2-2,4 LT2-1,3
U T R Q P V M L U K S T R Q P V N M L K
7 TYP.
MAC CLUSTER RACK
S Y
S T
E M
S F
U R
N
IT
U R
E
LT2 -14
LT2 -13
LT1 -28
LT2 -17
LT1 -35 LT1 -35
LT2-6,8
O O V S R T
TYP.7
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:5
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-400
E N
LA
R
G E
D P
LA
N
S
KMSJCH JLJ
13128795
1. CONNECT INTERIOR UNIT DSS-1A TO EXTERIOR UNIT DSS-1 LOCATED
OUTSIDE PLAN NORTH NEAR ELECTRIC ROOM. SEE SHEET E-105.
2. SPECIAL RECEPTACLE MOUNTED INSIDE CABINET RACK. PROVIDE WHIP
FROM ABOVE CEILING WITH SUFFICIENT LENGTH TO REACH THE FLOOR.
3. POWER TO LOCKS POWER SUPPLY AND ACS/IDS PANEL. SEE DETAIL ON
TY SHEETS.
4. PROVIDE LIGHTING CONTROL PANEL. LOCATE ABOVE PANEL LP.
PROVIDE POWER TO THE LIGHTING CONTROL PANEL (CIRCUIT GP2-40).
5. LOCATE MGB ABOVE PANEL MHV.
6. CIRCUIT UNDERCABINET LIGHTS TO NEAREST 120V CIRCUIT (CIRCUIT
GP2-18). PROVIDE SWITCH FOR MANUAL CONTROL.
7. LABEL ALL RECEPTACLES AS INDICATED, PER SCHEDULE THIS SHEET.
WORK NOTES
1. SEE TY, TN AND TA SHEETS FOR TELECOMM EQUIPMENT DETAILS AND
EQUIPMENT NAMING CONVENTION.
2. MECHANICAL ENLARGED POWER PLAN SHOWS BID OPTION 1 AWARDED.
GENERAL NOTES
1/4" = 1'-0" A2
MECHANICAL ROOM ENLARGED
2' 4' 8'0' 1/4" = 1'-0"
A3
ELECTRICAL ROOM ENLARGED PLAN
1/4" = 1'-0" A4
TELECOMM ROOM ENLARGED PLAN
2' 4' 8'0' 2' 4' 8'0'1/2" = 1'-0"
A1
BREAK 106 SOUTH WALL
1' 2' 4'0'
1/2" = 1'-0" B1
SECRET LAB 132 WEST WALL
2' 4' 8'0'
1/2" = 1'-0" C1
TOP SECRET LAB 131 WEST WALL
2' 4' 8'0' 1/2" = 1'-0"
C3
TOP SECRET LAB 131 EAST WALL
2' 4' 8'0'
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
GROUND ROD
GROUND ROD
EXOTHERMIC WELD COPPER GROUND CABLE
BUTT WELD
TEE WELD
WELD TO ROD
WELD RING TO ROD
EITHER BUTT WELD
CONDUCTOR OR 'THRU WELD'
CONNECTION
JUNCTION WELD
7' -0
A B
O V
E F
LO
O
R
WITH NUT AND LOCK WASHERS
SIZE AS REQUIRED. LUGS TO BE
HEX HEAD BOLT
COORDINATE MOUNTING HARDWARE
BUILDING WALL
2 HOLE LUG
LOCKWASHER
GROUNDING CONNECTION
1/4" EXTERIOR TOOTH
1/4"-20 HEX NUT
1/4" FLAT WASHER
1/4"-20 HEX BOLT
TOP VIEW
2-HOLE TYPE.
GROUND BAR OR
METAL ENCLOSURE
GROUND BAR MINIMUM SIZE
12" LONG X 3" WIDE X 1/4" THICK SOLID
COPPER, SEE NOTE 1
3/8" DIA BOLTS LENGTH
AS REQUIRED WITH LOCK
WASHERS
INSULATED MOUNT, 2" DEEP
GROUND CONDUCTOR
GREEN STRANDED
IRREVERSIBLE CRIMP GREEN STRANDED
COPPER WIRE TO GROUND
MAIN GROUND BUS IN
ELECTRICAL ROOM BOX
NOTES:
1. PROVIDE NUMBER AND SIZE OF CONNECTORS AND GROUND CONDUCTORS AND LENGTH OF GROUND BAR AS
REQUIRED FOR EACH GROUND BAR LOCATION.
2. PROVIDE GROUND BUS IN ACCORDANCE WITH EIA/TIA-607 GROUNDING STANDARDS.
3. DETAIL IS USED AN EXAMPLE. HOLE SIZE, SPACING AND PATTERN SHALL BE IN ACCORDANCE WITH TIA-607C.
4. PROVIDE UL LISTED GROUND BUS.
5. REFER TO TN SHEETS FOR PBB AND SBB DIMENSIONS.
NOTES:
1. THE COUNTERPOISE GROUND RING OF THE FACILITY
SHALL HAVE A RESISTANCE OF 5 OHMS OR LESS PER
IEEE STANDARD #143, "GREEN BOOK". ADDITIONAL
GROUND RODS SHALL BE DRIVEN AS REQUIRED TO
ACHIEVE THE PROPER RESISTANCE.
12"
THROAT DIA
12"
GROUND
24"
3/4 " x 10'-0" GROUND ROD
COUNTERPOISE, #4/0
BARE COPPER CABLE
GROUND ROD BOX
SCHEDULE 80 PVC
BODY
CAST IRON LID, WITH
LOCKING BOLT
COUNTERPOISE
#4/0 COPPER CABLE
BOLTED
CONNECTION (TYP)
MAIN CONDUCTOR
CONDUCTOR
SPLICER
"T" TYPE
(TYP.)
BOLT
STEEL GROUND ROD
10'x3/4" DIA. COPPER CLAD
COPPER GROUND
CABLE
GROUND LEVEL
EXOTHERMIC WELD OR
COMPRESSION TYPE
M
IN
M
IN
PIGTAIL LENGTH AND
SIZE PER PLAN
FOUNDATION,
CONCRETE PAD,
OR PAVING
GROUND CONDUCTOR TO GROUND
GRID. SIZE AS INDICATED ON PLAN
DRAWING OR SPECIFICATIONS
M
IN
S E
E N
O T
E
NOTES:
1. PROVIDE 8" MINIMUM SLEEVE. FOR CONCRETE SLAB, FOUNDATION OR
PAVING, EXTEND SLEEVE 3" BELOW CONCRETE OR PAVING.
2. PROVIDE 1.5" SCHEDULE 40 PVC SLEEVE. FILL SLEEVE WITH RTV COMPOUND
AND CAULK WITH TWO COMPONENT POLYURETHANE SYSTEM SEALANT.
CONDUIT SLEEVE. SEE
NOTE 2
1/2" X 12" COPPER
SAFETY TIPPED
AIR TERMINAL
CLASS I
COPPER MAIN CONDUCTOR
COPPER CABLE HOLDER
COPPER STANDING SEAM
POINT BASE
BRONZE ONE BOLT
PARALLEL SPLICER
BRONZE FLANGE
BONDING CLAMP
CLASS I
COPPER MAIN CONDUCTOR
1-1/4" PVC CONDUIT FOR
DOWNLEADS
1'-6" MIN. BELOW GRADE
2'-0" MIN OFF DRIP LINE
B4
E-500
A4
E-500
#4/0 CLAMP FOR GROUND
CONDUCTORS
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:0
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-500
D E
T A
IL
S
KMSJCH JLJ
13128796
NOT TO SCALE
D1
EXOTHERMIC WELDS
NOT TO SCALE
C2
GROUND BUS DETAIL
NOT TO SCALE
B1
GROUND TEST WELL
NOT TO SCALE
A1
TYPICAL "T" CABLE SPLICER
NOT TO SCALE
A2
GROUND ROD CONNECTION
NOT TO SCALE
A3
GROUNDING CONDUIT STUB UP
NOT TO SCALE
A4
STANDING SEAM METAL AIR TERMINAL
NOT TO SCALE
B4
STANDING SEAM METAL THROUGH ROOF CONNECTOR
NOT TO SCALE
C4
STANDING SEAM METAL ROOF DOWN CONDUCTOR
NOT TO SCALE
B2
TYPICAL CLAMP
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
3"
WARNING TAPE, 12" BELOW
GRADE
SELECT BACKFILL
NOTES:
1. USE PLASTIC CONDUIT SPACERS
AT 5'-0" OC.
3"
M
IN
3"
3"
PVC CONDUIT
SIZE AS INDICATED
MULTIPLEX
POLYESTER ROPE
3000 PSI CONCRETE
TOP OF PAVEMENT SUBGRADE OR GRADE
3"
FOR MEDIUM VOLTAGE DUCTBANKS.
PROVIDE #4/0 AWG
BARE COPPER CONDUCTOR IN
BOTTOM OF DUCTBANK.
TRACER WIRE
3"
M
IN
3" 3"
WARNING TAPE, 12" BELOW
GRADE
PVC CONDUIT
SIZE AS INDICATED
3" 3"
3"
MULTIPLEX POLYESTER
ROPE
SELECT BACKFILL
3000 PSI CONCRETE
TOP OF PAVEMENT SUBGRADE OR GRADE
NOTES:
1. USE PLASTIC CONDUIT SPACERS
AT 5'-0" OC.
FOR MEDIUM VOLTAGE DUCTBANKS.
PROVIDE #4/0 AWG
BARE COPPER CONDUCTOR IN
BOTTOM OF DUCTBANK.
TRACER WIRE
YELLOW WARNING TAPE, 12"
BELOW GRADE
PVC CONDUIT SIZE AND QUANTITY AS INDICATED
GREENLEE MULTIPLEX POLYESTER ROPE OR
EQUIVALENT
SELECT BACKFILL
TOP OF PAVEMENT SUBGRADE OR GRADE
M
IN
. U O
N
3" 3"
3" 3"
3"
NOTES:
1.
2.
3.
USE PLASTIC CONDUIT SPACERS
AT 5'-0" OC.
DUCTBANK IS IDENTIFIED AS FOLLOWS:
2 X 2. FIRST NUMBER INDICATES COLUMNS.
SECOND NUMBER INDICATES ROWS. PROVIDE
DUCTBANK AS INDICATED. DETAIL ALSO APPLIES TO
OTHER DUCTBANK SIZES.
ALTER DUCTBANK CONFIGURATIONS AS REQUIRED
TO PROPERLY ENTER HANDHOLES.
ROWS
C O
LU
M
N S
TRACER WIRE
SAND
2" X 8" PRESSURE TREATED PLANK
SCHED 80 TO PVC COATED GRS CONDUIT
ADAPTER
18" MIN BELOW SLAB
40" MIN BELOW GRADE
INCREASE DEPTH AS REQD
TO ALLOW FOR NEC MIN.
BEND RADIUS
PROVIDE MIN BEND
RADIUS FOR CONDUIT
IAW NEC.
4" MAX
TRANSITION COUPLING
PVC COATED GRS ELBOW
SCHED 80 PVC CONDUIT
TOP OF
CONCRETE
OR GRADE
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:0
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-501
D E
TA
IL
S
KMSJCH JLJ
13128797
NOT TO SCALE
C1
TYPICAL 2-WAY CONCRETE ENCASED DUCTBANK
NOT TO SCALE
C2
TYPICAL 4- WAY CONCRETE ENCASED DUCTBANK
NOT TO SCALE
C4
TYPICAL DIRECT BURIED DUCTBANK
NOT TO SCALE
A4
TYPICAL DIRECT BURIED CONDUIT AND DUCTBANK RISER DETAIL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
NOTES:
PROVIDE KNOCKOUTS AS
REQUIRED.
PROVIDE ACTIVATION COVER
ASSEMBLY
1.
2.
3.
4.
PROVIDE GANGS, FACEPLATES AND CONDUIT PER DRAWINGS.
ROUTE ALL CONDUITS TO/FROM FLOOR BOX AT MINIMUM OF 24" BELOW SLAB. AVOID
ROUTING CONDUITS HORIZONTALLY THRU SLAB. COORDINATE WITH STRUCTURAL
DRAWINGS FOR SLAB DEPTHS.
CAST IN PLACE BOXES MUST MAINTAIN FIRE RATING OF FLOOR ASSEMBLY.
PROVIDE ACTIVATION COVER THAT COORDINATES WITH USE. ACTIVATION COVERS
SHALL HAVE INSERT TO MATCH ARCHITECTURAL FINISHES.
NOTE: TO BE USED DURING
POUR-IN-PLACE; PREFERRED
METHOD.
FLEX LTC, TYP.
FLEXIBLE CONNECTION PROVIDED BY FURNITURE
SUPPLIER. FINAL CIRCUITING AND CONNECTION AT
JUNCTION BOX IN WALL SHALL BE BY ELECTRICAL
CONTRACTOR.
4" X 4" X 1-1/2"JUNCTION BOX
FOR FURNITURE
POWER CONNECTION MOUNT
18" AFF.
CONDUIT WITH CIRCUITING
AS INDICATED ON PLANS
SEE TELECOM DRAWINGS
FOR REQUIREMENTS.
120 VOLT POWER
CONNECTION TO BE
DETERMINED BY
FURNITURE SUPPLIER
NOTES:
COORDINATE CONNECTIONS WITH OWNERS FINAL
FURNITURE PLAN AND SELECTION.
1.
BASE
BONDING CONDUCTOR
TYPICAL 2 PLACES.
SIZE TO MATCH MAIN CONDUCTOR
ROOF
SPD1
WIDTH: 30 INCHES WIDTH: 45 INCHES
H E
IG
H
T : 9
IN
C H
E S
LGE
MAIN BREAKER, 3P, 800AF/600AT, LSI
1. SURGE PROTECTIVE DEVICE
2. FEEDER BREAKER, 3P, 225AF/20AT
3. FEEDER BREAKER, 3P, 225AF - PROVISIONS FOR BREAKER
4. FEEDER BREAKER, 3P, 225AF/80AT
5. FEEDER BREAKER, 3P, 225AF/45AT
6. FEEDER BREAKER, 3P, 250AF/100AT
7. FEEDER BREAKER, 3P, 250AF - PROVISIONS FOR BREAKER
8. FEEDER BREAKER, 3P, 400AF/250AT
9. FEEDER BREAKER, 3P, 400AF/225AT
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
W
A S
H
IN
G T
O N
P W
D P
A T
U X
E N
T R
IV
E
R P
A T
U X
E N
T R
IV
E
R
M D
AS NOTED
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
S T
IN
IG
O
E S
M
D W
E B
S T
E R
O U
T L Y
IN
G
F
IE
L D
R E
V D
A T
E
F
IL
E N
A M
E
U N
C
LA
S S
IF
IE
D
DRAWFORM REVISION: 12 APRIL 2018
GMP
CHIEF ENG/ARCH
IPT TECH. BRANCH HEAD
PROJECT MANAGER
A/E INFO
APPROVED
1610271
/1
/2
:0
:0
A
M C
U s e rs \r a k e m p \D o c u m e n ts
\1
ID
S
E
C e n tr a l_ ra k e m p b u rn s m c d
.c o m
.r v t
E-502
D E
TA
IL
S
KMSJCH JLJ
13128798
NOT TO SCALE
A1
TYPICAL FLOOR BOX DETAIL
NOT TO SCALE
B3
SYSTEMS FURNITURE FLOOR FEED POUR-IN-PLACE
NOT TO SCALE
A3
SYSTEMS FURNITURE WALL FEED
NOT TO SCALE
B1
TYPICAL MECHANICAL EQUIPMENT BONDING DETAIL
NOT TO SCALE
C1
SWITCHBOARD (MSB) ELEVATION
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E F
O R
C O
N S
T R
U C
T
IO
N
/2 1/
2850 EISENHOWER AVENUE
SUITE 200
ALEXANDRIA, VA 22314
C I&
ID
S
E N
G
IN
E E
R
IN
G S
U P
P O
R T
F A
C
IL
IT
Y
.1
.2
GMP
CHIEF ENG/ARCH
DESIGN TEAM LEAD
PROJECT MANAGER
ELF
FPE
Ehan Weech Craig Guth
RECESSED
2' X 2' LED VOLUMETRIC TROFFER
RCR
REVISED: JANUARY 2014 TYPE: A1
CU
LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
NOMINAL 30W INPUT/
3,200 LUMENS
LPW - 108
MINIMUM
TYPE A1
HOUSING - DIE-FORMED, COLD-ROLLED STEEL. REFLECTOR SHALL BE PAINTED
WITH A HIGHLY REFLECTIVE PAINT.
FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT
FINISHED WITH HIGH REFLECTANCE (MINIMUM 85%), BAKED WHITE ENAMEL FINISH.
LENS - 100% IMPACT MODIFIED ACRYLIC THAT ATTACHES TO THE LUMINAIRE
END CAPS.
6.
5.
4.
3.
2.
1.
1.03 0.89 0.78 0.69
7.
2-3/8"
ELECTRONIC DRIVER - IES LM-80 PERFORMANCE FOR 60,000 HOURS MINIMUM.
SOUND RATING "A" WITH LESS THAN 20% THD, MINIMUM 0.9 POWER FACTOR,
INHERENT THERMAL PROTECTION, SHORT-CIRCUIT AND OVERLOAD PROTECTION,
AND COMPLIES WITH ANSI C62.41 CATEGORY A TRANSIENT PROTECTION. PROVIDE
0-10V DIMMING DRIVER FOR 5-100% DIMMING RANGE OR BI-LEVEL STEP-DIMMING IF
INDICATED.
8.
CERTIFICATION - UL LISTED AND LAVELED
MOUNTING - END CAPS SHALL HAVE T-BAR CLIPS FOR MOUNTING TO
STANDARD 15/16" AND 9/16" T-GRID CEILING SYSTEMS.
OPTION - EMERGENCY BATTERY PACK.
PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU), GIVEN
INTERIOR CAVITY REFLECTANCES OF 80-50-20:
6" LED RECESSED DOWNLIGHT
REVISED: JANUARY 2014 TYPE: C1,C8LIGHTING PLATE:
HOUSING - DIE-FORMED, COLD-ROLLED STEEL, OR FORGED ALUMINUM WITH HEAT SINK. DRIVER MUST BE ACCESSIBLE FROM BOTTOM OF LUMINAIR. PROVIDE T-BAR HANGERS FOR INSTALLATION IN ACOUSTICAL TILE
CEILINGS OR TABS WHEN MOUNTING IN HARD CEILINGS.
7.
6.
4.
3.
2.
1.
LUMINAIRE REQUIREMENTS:
REFLECTOR AND TRIM - SPECIFICATION GRADE, LOW IRRIDESCENT, SPECULAR ALUMINUM REFLECTOR WITH
METALLIC OR PAINTED TRIM RING.
LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500K CCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FOR COLOR CONSISTENCY. INITIAL LUMEN
OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING.
OPTIONS - EMERGENCY BATTERY BACK-UP, WALL-WASH TRIM, IC RATED FOR DIRECT CONTACT
WITH INSULATION, VARIOUS APERTURE DIAMETERS, AND VARIOUS GLASS LENSES.
PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU), GIVEN INTERIOR
CAVITY REFLECTANCES OF 80-50-20:
8.
7-5/8"
CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT. COMPLIES WITH LM79, LM80, AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED WITH EMERGENCY BATTERY
BACK-UP.
ELECTRONIC DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, <20% TOTAL HARMONIC DISTORTION. ON-
OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
5.
RCR
CU
1.11 1.03 0.96 0.90
NOMINAL 12W INPUT/
1,075 LUMENS
LPW - 91
MINIMUM
TYPE C8
RCR
CU
1.11 1.03 0.96 0.90
NOMINAL 23W INPUT/
1,650 LUMENS
LPW - 72
MINIMUM
TYPE C1
4' LED LENSED STRIP LIGHT
RCR
REVISED: JANUARY 2014 TYPE: D1,D2,D3
CU
1.04 0.91 0.80 0.70
LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
NOMINAL 44W INPUT/
3,300 LUMENS
LPW - 75
MINIMUM
TYPE D2
HOUSING - DIE-FORMED, COLD-ROLLED STEEL. REFLECTOR SHALL BE PAINTED
WITH A HIGHLY REFLECTIVE PAINT.
FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT
FINISHED WITH HIGH REFLECTANCE (MINIMUM 85%), BAKED WHITE ENAMEL FINISH.
LENS - 100% ACRYLIC, MEDIUM DIFFUSE.
CERTIFICATION - UL LISTED AND LABELED6.
5.
4.
3.
2.
1.
MOUNTING - PENDANT/STEM MOUNTED FROM CEILING.
PROVIDE AN EMERGENCY BATTERY PACK.
7.
PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU),
GIVEN INTERIOR CAVITY REFLECTANCES OF 80-50-20:
8.
ELECTRONIC DRIVER - PROVIDE 0-10V DIMMING DRIVER FOR 5-100% DIMMING RANGE
OR BI-LEVEL STEP-DIMMING AS INDICATED.
IES L80 PERFORMANCE PER LM-80 CALCULATED IAW TM-21 FOR 50,000 HOURS
MINIMUM.
9.
VAR.
V A
R
RCR
CU
1.04 0.91 0.80 0.70
NOMINAL 32W INPUT/
2,000 LUMENS
LPW - 62
MINIMUM
TYPE D1
RCR
CU
1.04 0.91 0.80 0.70
NOMINAL 68W INPUT/
5,000 LUMENS
LPW - 73
MINIMUM
TYPE D3
LUMINAIRE REQUIREMENTS:
REVISED: JANUARY 2014 TYPE: S1LIGHTING PLATE:
4 0.72
RCR
1.06
0.82 0.93
CU
LED WALL / MULLION
HOUSING - ALUMINUM EXTRUDED HOUSING AND MILLED ENDCAPS.
FINISH - ELECTROSTATICALLY APPLIED POWDER COATED FINISH.
LENS - 100% ACRYLIC, FROSTED.
MOUNTING - LUMINAIRE SHALL HAVE A "FLANGELESS" AND FLUSH APPEARANCE.
MULLION MOUNT OPTION.
OPTICS - LUMINAIRE SHALL PROVIDE A SYMMETRICAL DISTRIBUTION PATTERN.
1.
2.
3.
4.
5.
6.
NOMINAL 12W INPUT/
3,500 LUMENS
TYPE S1
LPW - 140
MINIMUM
CERTIFICATION - UL LISTED AND LABELED FOR WET LOCATIONS.
ELECTRONIC DRIVER - IES LM-80 PERFORMANCE FOR 60,000 HOURS MINIMUM.
SOUND RATING "A" WITH LESS THAN 20% THD, MINIMUM 0.9 POWER FACTOR,
INHERENT THERMAL PROTECTION, SHORT-CIRCUIT AND OVERLOAD PROTECTION,
AND COMPLIES WITH ANSI C62.41 CATEGORY A TRANSIENT PROTECTION. PROVIDE
0-10V DIMMING DRIVER FOR 5-100% DIMMING RANGE OR BI-LEVEL STEP-DIMMING IF
INDICATED.
7.
PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU), GIVEN
INTERIOR CAVITY REFLECTANCES OF 80-50-20:
9.
OPTION - EMERGENCY BATTERY PACK - 90 MINUTES. PHOTOCELL8.
2' UNDERCABINET LED
RCR
REVISED: JANUARY 2014 TYPE: U1
CU
1.04 0.90 0.79 0.70
LIGHTING PLATE:
HOUSING - LOW PROFILE DURABLE PLASTIC
FINISH - WHITE
LENS - 100% UV STABALIZED ACRYLIC, CLEAR
CERTIFICATION - UL LISTED AND LABELED
PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU) GIVEN
INTERIOR CAVITY REFLECTANCES OF 80-50-20:
7.
5.
4.
3.
2.
1.
LUMINAIRE REQUIREMENTS:
NOMINAL 24W INPUT/
427 LUMENS
LPW - 53
MINIMUM
TYPE U1
4.37"
0.72"
OPTIONS - SPLICE BOX
6.
ELECTRONIC DRIVER - PROVIDE 0-10V DIMMING DRIVER FOR 5-100% DIMMING RANGE
OR BI-LEVEL STEP-DIMMING AS INDICATED.
IES L80 PERFORMANCE PER LM-80…
This is the start of the file's text. The full file is on GovTribe.