This is a solicitation for a construction project to make improvements to the Georgeville Wastewater System owned by the Yakama Nation. The Indian Health Service intends to award a firm fixed price construction contract to support improvements to the sewer system in Goldendale, Washington. The project has a performance period of 120 calendar days from issuance of the notice to proceed. The estimated value of the construction contract is between $500,000 and $1,000,000. The solicitation is set aside 100% for small businesses and will use lowest price technically acceptable source selection procedures. Proposals are due by March 26, 2020 at 2:00pm Pacific Time and shall be submitted electronically to the specified contracting officer. An organized site visit is planned and attendance must be confirmed as instructed.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
8350 W. Grandridge Blvd, Suite 200
Kennewick, WA 99336 509|205-4111 208|676-0100 Fax
SPECIFICATION STAMP PAGE
DATE: 7/13/2018
CLIENT: Century West Engineering PROJECT: IHS Georgeville Wastewater System Upgrades
1110 W. Park Place, Ste.
TEI PROJECT#: 17166
Coeur d’Alene, ID 83814 ENGINEER: Zachary B. McMackin, P.E.
Section Specification Description
26 01 26 ELECTRICAL TESTING
26 05 19 WIRE AND CABLE
26 05 26 GROUNDING
26 05 33 RACEWAYS
26 28 00 OVERCURRENT PROTECTIVE DEVICES
26 28 16 DISCONNECTS AND SAFETY SWITCHES
26 60 00 ELECTRICAL GENERAL PROVISIONS
26 60 01 ELECTRICAL SCOPE OF WORK
26 60 02 BASIC MATERIAL AND METHODS
26 90 25 CONTROL COMPONENTS
The technical specification sections listed above have been prepared under the direction of the Professional Engineer, registered in the State of Washington, whose seal and signature appear below:
zmcmackin Typewritten Text 7/13/18
IHS Georgeville Wastewater System Upgrades SECTION 26 01 26 - PAGE 1 7/13/18
Trindera Engineering, Inc.
SECTION 26 01 26
ELECTRICAL TESTING
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Material and installation requirements for:
1. Testing of Electrical Systems.
1.2 DESCRIPTION OF WORK
A. Provide testing of electrical work installed under Division 26, as specified herein and in other
Division 26 sections. Feeders and equipment shall not be placed in service until they have been checked and tested, as applicable.
1.3 RELATED SECTIONS
A. Related Sections include but are not necessarily limited to:
1. Section 26 60 00 – Electrical: General Provisions
2. Section 26 60 01 – Electrical Scope of Work
3. Section 26 60 02 – Basic Materials and Methods
4. Section 26 05 19 – Wire and Cable
5. Section 26 05 26 – Grounding
1.4 STANDARDS AND REFERENCES
A. All materials and equipment specified herein shall, within the scope of UL Examination
Services, be approved by the Underwriter's Laboratories for the purpose for which they are used and shall bear the UL label.
B. All materials and equipment specified herein shall conform with all applicable NEMA, ANSI and IEEE Standards
C. All materials and equipment specified herein and their installation methods shall conform to the latest published version of the National Electrical Code, NEC.
1.5 SUBMITTALS
A. Shop Drawings
1. See Section 26 60 00.
B. Testing Procedures: Submit four copies of all proposed testing procedures to the Engineer for review at least 10 working days prior to conducting any testing on the project.
C. Reporting Forms: Submit four copies of the proposed forms to be used in recording testing data and results to the Engineer for review at least 10 working days prior to conducting any testing on the project.
D. Test Data and Results: Submit four copies of complete data and certified test results for each test performed, including, but not limited to:
1. Test performed,
2. Test procedure,
3. System and area tested, ELECTRICAL TESTING
IHS Georgeville Wastewater System Upgrades SECTION 26 01 26 - PAGE 2 7/13/18
4. Date(s) and time(s) of test,
5. Weather conditions,
6. Test criteria,
7. Test results,
8. Additional pertinent information.
E. Operational Certification: Submit four certified copies of an operational certification which documents that all equipment and systems have been fully tested to verify proper operation in accordance with the design shown in the Contract documents and manufacturer’s recommendations.
F. Certification: Certifications stating that submitted test data and results are true and correct shall be provided for all submittals under this section. Certification shall be executed by an authorized officer if the Contractor is a corporation, by a partner if the Contractor is a partnership, by the owner if the Contractor is a sole proprietorship or by the authorized representative if the Contractor is a joint venture.
G. Calibration List: Submit four copies of a listing of testing devices to be used for the project to the Engineer for approval. Listing shall include documentation that the devices are properly calibrated.
H. Test Log: The Contractor shall maintain a test log at the site to document the results of all successful and unsuccessful testing as it is performed. This log shall be available for review by the Engineer and a copy of the log shall be submitted to the Engineer prior to the Substantial Completion inspection. A space shall be provided on the test log signoff by the Engineer or Owners representative.
1.6 NOTICE
A. Notify the Engineer in writing 10 working days prior to all scheduled testing to allow time for
Engineer to schedule witnessing of testing, where elected by Engineer.
PART 2 PRODUCTS
2.1 TESTING MATERIALS
A. General: Provide all materials and test equipment required for testing of specified electrical systems, including re-testing until acceptable results are obtained.
B. Products: Tested products which fail to provide acceptable test results shall be repaired or replaced with suitable materials as required to obtain acceptable results.
PART 3 EXECUTION
3.1 TESTING
A. General: Test shall be made during the course of the construction as specified and as required by authorities having jurisdiction. Such test shall be conducted by this Division as part of the Work and shall include all personnel, material, and equipment required to perform test until satisfactory results are obtained. Any defects detected during testing shall be satisfactorily repaired or the equipment involved shall be replaced and the test re-executed.
B. Testing shall include but not be limited to all items in other Sections of this Division and the following:
1. Feeders: Refer to Section 26 05 19.
2. Ground Rods: Refer to Section 26 05 26.
IHS Georgeville Wastewater System Upgrades SECTION 26 01 26 - PAGE 3 7/13/18
C. Test Reports (Attached)
1. ELECTRICAL SYSTEM TEST REPORT - 600V CABLE
2. ELECTRICAL GROUND ROD TEST REPORT
END OF SECTION
IHS Georgeville Wastewater System Upgrades SECTION 26 01 26 - PAGE 4 7/13/18
26 01 26 ELECTRICAL SYSTEM TEST REPORT - 600V CABLE
ELECTRICAL SYSTEM
DESCRIPTION DATA
SERVICE DESCRIPTION:
nominal voltage, phase to phase phase to neutral - single or three phase-number of conductors
SERVICE CONDUCTORS:
phase size and insulation type neutral size and insulation type ground size and insulation type
SERVICE DISCONNECT DESCRIPTION:
circuit breaker or disconnect switch size (amps) fuse (amps)
MEASURED CONDITIONS DATA
Operating Load Voltage Volts Vab Vbc Vca
Van Vbn Vcn
Operating Load Feeder Current Amps Ia Ib Ic
Conductor Insulation Megohms a-b b-c c-a Resistance (record the indicated measurement for each of the Megohms a-g b-g c-g following circuits:)
1. Service Feeder
IHS Georgeville Wastewater System Upgrades SECTION 26 01 26 - PAGE 5 7/13/18
26 01 26 - ELECTRICAL GROUND ROD TEST REPORT
PROCEDURE:
To measure ground resistance, two additional temporary grounds, consisting of short rods 2 or 3 feet long, shall be driven in the ground at least 20 feet away from the rod being tested. A direct-reading ground resistance tester shall then be connected to the three ground rods by means of insulated leads. The battery operated ground resistance tester reads the resistance of the ground rod being tested directly in ohms. The ground rod location / designation and its measured ohm value shall be recorded in chart below.
GROUND ROD LOCATION / DESIGNATION OHM VALUE
1. *
2. *
3. *
COMPOSITE GROUND *
*Ohm value of a single ground rod shall not exceed 25 Ohms. If additional ground rod(s) are added, the "composite" ground electrode shall have a maximum acceptable reading of 15 Ohms which shall be recorded in chart above.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 19 - PAGE 1 7/13/18
SECTION 26 05 19
WIRE AND CABLE
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Material and installation requirements for:
1. Building wire
2. Power and control cable
3. Instrumentation cable
4. Wire connectors
5. Insulating tape
6. Pulling lubricant
1.2 DESCRIPTION OF WORK
A. This section covers furnishing and installation of all wiring and connections used in the construction of this facility.
B. All wiring shall be in raceways.
1.3 RELATED SECTIONS
A. Related Sections include but are not necessarily limited to:
1. Section 26 60 00 – Electrical: General Provisions
2. Section 26 60 02 – Basic Materials and Methods
3. Section 26 05 33 – Raceways
1.4 STANDARDS AND REFERENCES
A. All materials and equipment specified herein shall, within the scope of UL Examination
Services, be approved by the Underwriter's Laboratories for the purpose for which they are used and shall bear the UL label.
B. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:
1. Insulated Cable Engineers Association:
a) S-58-679, Control Cable Conductor Identification
2. Institute of Electrical and Electronic Engineers (IEEE):
a) 518, Guide for the Installation of Electrical Equipment to Minimize Electrical Noise Inputs to Controllers from External Sources
3. National Electrical Manufacturers Association (NEMA):
a) ICS 4, Terminal Blocks for Industrial Use
4. National Electrical Manufacturers Association/Insulated Cable Engineers Association
(NEMA/ICEA):
a) WC 70/ICEA S-95-658, Standard for Nonshielded Power Cables Rated 2000 Volts or
Less for the Distribution of Electrical Energy
5. National Fire Protection Association (NFPA):
a) 70, National Electrical Code (NEC)
6. Underwriters Laboratories, Inc. (UL):
WIRE AND CABLE
IHS Georgeville Wastewater System Upgrades SECTION 26 05 19 - PAGE 2 7/13/18
a) 44, Thermoset-Insulated Wires and Cables
b) 83, Thermoplastic-Insulated Wires and Cables
c) 467, Grounding and Bonding Equipment
d) 486A, Wire Connectors and Soldering Lugs for use with Copper Conductors
e) 486C, Splicing Wire Connectors
f) 510, Insulating Tape
g) 1581, Reference Standard for Electrical Wires, Cables, and Flexible Cords
C. All materials and equipment specified herein and their installation methods shall conform to the latest published version of the National Electrical Code, NEC.
1.5 DEFINITIONS
A. Cable: Multi-conductor, insulated, with outer sheath containing either building wire or instrumentation wire.
B. Instrumentation Cable: Multiple conductor, insulated, twisted or untwisted, with outer sheath.
The following are specific types of instrumentation cables:
1. Analog signal cable: Used for the transmission of low current (e.g., 4-20mA DC) or low voltage (e.g., 0-10 V DC) signals, using No. 16 AWG and smaller conductors. Commonly used types are defined in the following:
a) UTP: Unshielded twisted pair,
b) TSP: Twisted shielded pair, (or STP: Shielded twisted pair),
c) TST: Twisted shielded triad.
2. Digital signal cable: Used for the transmission of digital signals between computers, PLC’s, RTU’s, etc.
C. Power Cable: Multi-conductor, insulated, with outer sheath containing building wire, AWG No.
8 and larger.
D. Control Cable: Multi-conductor, insulated, with outer sheath containing building wires, AWG No. 16, AWG No. 14, AWG No. 12 or AWG No. 10.
E. Building Wire: Single conductor, insulated, with or without outer jacket depending upon type.
1.6 SUBMITTALS
A. Shop Drawings
1. See Section 26 60 00.
PART 2 PRODUCTS
2.1 CONDUCTORS
A. Conductors shall be stranded copper. Sizes AWG No. 14, 12 and 10 for general purpose lighting and receptacle wiring and all wiring within circuit breaker panels may be solid. All other conductors shall be stranded. Insulation shall be THW-2, THWN-2, or THHN, (90˚F) chosen to satisfy environmental conditions. Conductors used for power circuits shall not be smaller than AWG No. 12. Control conductors may be AWG No. 14.
2.2 CONNECTORS
A. Ideal Industries “Wing Nut” or 3M Company “SCOTCHLOCK” pre-insulated connectors may be used for lighting and receptacle circuits for splices and taps in conductors AWG No. 10 and smaller. For AWG No. 8 and larger conductors, utilize Thomas & Betts compression connectors. Compress using recommended die and tools.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 19 - PAGE 3 7/13/18
B. For connections of wire to cord to removable equipment provided with integral cords (such as floats, transmitters, limit switches, aerators, submersible pump motors, etc.) provide junction box with terminals and spade/lug type terminations and coat with liquid insulation.
C. For connections of wire to cord for submersible motors of all size wire use a water proof motor stub insulator: Thomas & Betts multi splice insulator MSLT112-4 or equal.
2.3 SPLICE INSULATION
A. Splice insulation shall be equal to the conductor utilized.
B. Insulate all permanent splices that are underground or in damp or corrosive environments with cast epoxy type insulation which covers the jacket of all cords and the insulation on all wire. Epoxy splice shall be Scotch #3570 or equal.
2.4 MOTOR TERMINAL SPLICE INSULATION
A. Provide motor terminal splice insulation in the motor connection box that will withstand constant vibration and abrasion without degrading the insulation of the splice. A product shall be used that is specifically designed for the purpose of motor terminations.
B. For motor splices in general purpose areas use a bolted splice with a TY-RAP boot type insulator, Thomas & Betts splice insulator series MSC. For splices using wire larger than AWG No. 8 it is also acceptable to use a heat shrinkable motor connection stub splices, RAYCHEM, MCK-V series or equal.
C. For motors in outdoor, damp, or corrosive environments, use a water proof motor stub insulator, Thomas & Betts multi splice insulator MSLT112-4 or equal. For splices using wire larger than AWG No. 8 it is also acceptable to use a heat shrinkable motor connection stub splices, RAYCHEM, MCK-V series or equal.
PART 3 EXECUTION
3.1 GENERAL
A. Splicing of power and control and signal wires or cables is not allowed. All wire transitions shall be done on terminals.
B. Keep all conductors within the allowable tension limits during installation. Lubricants for wire pulling, if used, shall be approved for the insulation and raceway material. Observe cable manufacturer's and industry standard cable bending radius recommendations.
C. Incoming cables in panels and motor control centers, AWG No. 6 and smaller, shall be bundled and laced at intervals not greater than 6 inches and neatly spread into trees and connected to their respective terminals.
D. Sufficient slack shall be allowed in cables for alterations in terminal connections. Lacing shall be done with plastic cable ties using a tensioning tool designed for that purpose.
E. Cables crossing hinges shall be made up into groups not exceeding 12 and shall be so arranged that they will be protected from chafing when the hinged member is moved.
F. Cables installed in handholes shall be bundled and neatly racked to the side of the handhole.
All splices (if allowed) shall be a minimum of 6 inches above the bottom of the handhole.
3.2 WIRE AND CABLE TERMINATION
A. Power conductors, AWG No. 8 and larger may be terminated directly in box-type lugs.
B. Solid conductors (when allowed for lighting and receptacle circuits) of AWG No. 10 and AWG No. 12 may be directly terminated to screw terminals.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 19 - PAGE 4 7/13/18
C. For any power, control, or signal wire terminating on screw type terminals; provide spade or ring tongue type terminations.
D. Stranded control conductors may be directly terminated in box type terminals at control panels. Insulated terminals shall be used also on all stranded instrumentation wiring.
E. Special instrumentation cables shall be terminated in accordance with the recommendations of the manufacturer of the equipment and subject to review by the Engineer.
F. No splices shall be used in power, control and/or signal wiring. The wiring shall be continuous from point-to-point.
G. Terminals and connectors shall be installed with the compression tool recommended by the terminal manufacturer. Solid wire shall not be lugged, but shall be terminated with a full ring eye of the wire under the binding-head screw or saddle of the terminal block. Electrical spring connectors may be used only on lighting circuits.
3.3 COLOR CODING
A. Wiring shall conform to the following color code.
B. Insulation on phase conductor sizes AWG No. 10 and smaller shall be colored, No.8 AWG and larger may have black insulation with plastic tape of the appropriate color from the table below.
C. Insulation on the grounded conductor (neutral) sizes AWG No. 8 and smaller shall be colored, AWG No. 6 and larger may have black insulation with plastic tape of white or gray in accordance with the table below.
Description 120/240V Control
Phase A (Left) Black --
Phase B (Center) Red --
Neutral White White
Ground Green Green
120 VAC Control -- Red
120 VAC Control Neutral White
DC Control (+) -- Blue
DC Control (-) -- Gray
External Source -- Yellow
D. All control wiring in control panels or other enclosures that is powered from an external source and is not disconnected by the control panel disconnect shall be terminated at a disconnecting terminal block upon entering the enclosure. The color of the wire shall then be changed to yellow to identify it as being powered from an external source. Provide identification nameplate on exterior of enclosure to indicate sources of external power.
E. All wiring in industrial machines and equipment shall be in accordance with NFPA 79. Notify Owner of any deficiencies noted during installation.
3.4 TERMINAL MARKING
A. All terminals in instrument and relay compartments, motor control centers, control panels, instrument panels, field panels and control stations, as well as connections to mechanical equipment, shall have reference number and letter in accordance to the following:
IHS Georgeville Wastewater System Upgrades SECTION 26 05 19 - PAGE 5 7/13/18
1. h = Control power hot (usually 120V or 24V)
2. n = neutral
3. g = ground
4. x = PLC input (number shall correspond to the program input number)
5. y = PLC output (number shall correspond to the program output number)
6. ax = PLC signal/analog input (number shall correspond to the program input number)
7. ay = PLC signal/analog output (number shall correspond to the program output number)
8. c = control (use if none of the above letters apply)
9. p = power (usually 480V)
10. s = signal (usually 4-20ma or 1-5V) (use if none of the above letters apply)
11. B = DC + and -
3.5 CONDUCTOR SPACING
A. Unless specifically shown otherwise on the drawings, in all areas maintain a minimum 2-inch separation between all conductors of different voltages. For parallel runs over 6 feet maintain the following minimum separation between conductors:
1. Signal (12/24) VDC and 120 VAC 6 inches
2. Signal (12/24) VDC and 480 VAC 12 inches
3. 120 VAC control wire and 480 VAC 2 inches
3.6 WIRE BENDING RADIUS
A. The radius of bends in all wire (conductors and cables) shall not be less than five (5) times the outside diameter of the wire. Any wire installed with bends less than five times the diameter which the Engineer deems has caused that insulation to be damaged shall be removed and new wire shall be installed.
3.7 VISUAL AND MECHANICAL INSPECTIONS
A. Inspect exposed section for physical damage.
B. Verify that cable is supplied and connected in accordance with specifications and one line diagram, and that phases are labeled correctly.
3.8 TESTING
A. See Section 26 01 26 – Electrical Testing.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 26 - PAGE 1 7/13/18
SECTION 26 05 26
GROUNDING
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Material and installation requirements for:
1. Grounding
1.2 DESCRIPTION OF WORK
A. This section covers furnishing and installing all grounding and/or bonding conductors, connectors, ground rods and terminations as required to meet these specifications and to comply with Article 250 of the National Electric Code.
1.3 RELATED SECTIONS
A. Related Sections include but are not necessarily limited to:
1. Section 26 60 00 – Electrical: General Provisions
2. Section 26 60 02 – Basic Materials and Methods
3. Section 26 05 19 – Wire and Cable
4. Section 26 05 33 – Raceways
1.4 STANDARDS AND REFERENCES
A. All materials and equipment specified herein shall, within the scope of UL Examination
Services, be approved by the Underwriter's Laboratories for the purpose for which they are used and shall bear the UL label.
B. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:
C. American National Standards Institute:
a) ANSI/IEEE Standard 142 Recommended Practice for Grounding of Industrial and
Commercial Power Systems.
2. American Society for Testing and Materials (ASTM):
a) B8, Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft.
3. National Fire Protection Association (NFPA):
a) 70, National Electrical Code (NEC).
4. Underwriters Laboratories, Inc. (UL):
a) 467, Electrical Grounding and Bonding Equipment.
D. All materials and equipment specified herein and their installation methods shall conform to the latest published version of the National Electrical Code, NEC.
1.5 SUBMITTALS
A. Shop Drawings
1. See Section 26 60 00.
a) A complete grounding system diagram for special grounding systems.
2. See Section 26 01 26.
GROUNDING
IHS Georgeville Wastewater System Upgrades SECTION 26 05 26 - PAGE 2 7/13/18
a) After installation is complete:
• Test reports
• Ground rod and grid test results
1.6 DELIVERY, STORAGE, AND HANDLING
A. See Section 26 60 00.
PART 2 PRODUCTS
2.1 GENERAL
A. For each electrical grounding connection, provide a complete assembly of materials to construct a completely grounded electrical system.
B. Raceways for grounding conductors shall be as specified in Section 26 05 19.
C. Grounding cable, wire and connectors shall be as specified in Section 26 05 33.
D. Grounding conductors and jumpers shall be connected to each other and to items to be grounded by means of approved type pressure connectors, clamps, and other suitable methods approved by the Engineer. No solder connections shall be made.
2.2 GROUNDING ELECTRODE CONDUCTORS
A. All concrete encased or direct buried underground grounding electrode conductors shall be soft drawn stranded bare copper cable, conforming to ASTM B8.
1. Sized as required by Table 250-66 of the NEC, except where a larger size conductor is shown on the Contract Drawings.
2. Minimum conductor allowed: 2/0.
B. Equipment grounding conductor:
1. Green copper conductor: Identical insulation to phase conductors.
2. Sized as required by Table 250-122 of the NEC, except where a larger size conductor is shown on the Contract Drawings.
2.3 GROUND ROD BOXES
A. Provide ground rod boxes for each ground rod. Ground rod boxes shall be concrete with traffic rate covers, Fogtite SP-1, or approved equal.
2.4 GROUNDING ELECTRODE RODS
A. Grounding electrode rods used shall be a minimum of ¾” diameter by 10’ long, steel core and thick copper jacket (copperclad).
B. Heavy uniform coating of electrolytic copper molecularly bonded to a rigid steel core.
Corrosion resistant bond between the copper and steel. Hard drawn for a scar-resistant surface. UL listed.
1. Blackburn
2. Thomas & Betts
2.5 GROUND CLAMPS
A. Ground clamps for connecting grounding conductors to copper, brass, or lead pipes shall be made of copper. If pipes are of steel or iron, the ground clamps should be made of galvanized iron. These clamps shall be designed to provide permanent and positive pressure
IHS Georgeville Wastewater System Upgrades SECTION 26 05 26 - PAGE 3 7/13/18 and to avoid mechanical injury to the pipe. Use exothermic welds for connecting ground wires to ground rods for all below grade counterpoise grounds, grids, and elsewhere where noted on the Drawings.
B. High copper alloy content, compression type, noncorrosive.
C. UL 467 listed.
1. Burndy
2. ILSCO
3. Thomas & Betts
2.6 EXOTHERMIC WELD CONNECTIONS
A. Use Cadweld or approved equal system of exothermic welding for welded grounding connections where shown on the Drawings or specified.
B. Copper oxide reduction by aluminum process.
C. Molds properly sized for each application.
PART 3 EXECUTION
3.1 INSTALLATION
A. Install products in accordance with manufacturer's instructions.
B. Remove paint, rust, or other nonconducting material from contact surfaces before making ground connections.
C. Where ground conductors pass through floor slabs or building walls, sleeves of intermediate metal conduit of the required size, shape, and length shall be provided, unless otherwise specified or shown on Drawings.
D. Ground Grid
1. Locate ground rods at approximate locations shown on Drawings.
2. Install rods in firm soil outside of excavated areas.
3. Place perimeter rods a minimum of 10 FT from the building foundation.
4. Drive top of rod to minimum depth of 6 IN below grade unless otherwise noted on
Contract Drawings.
5. Use driving studs or other suitable means to prevent damage to threaded ends of sectional rods.
6. Interconnect all ground rods with ground electrode conductor:
7. Size per the NEC unless a larger size is shown on the Drawings.
8. Do not splice grounding electrode conductor.
9. Provide excavation required for installation of ground conductors buried in earth.
10. Allow sufficient slack to prevent conductor breakage during backfill or due to ground movement.
11. Leave taps, junctions, and splices uncovered until inspected by Engineer.
12. Backfill around ground grid completely, thoroughly tamping to provide good contact between backfill materials and ground rods and conductors.
13. Bond underground metal piping to the ground grid in accordance with NEC 250.
Grounding clamps may be utilized on piping if exothermic welds may damage structural integrity.
14. All underground connections shall be exothermically welded.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 26 - PAGE 4 7/13/18
E. Complete grid system:
1. Resistance of 5 ohms or less.
2. Drive additional rods as required.
3.2 RACEWAY GROUNDING-CONDUIT
A. All metallic conduit shall be electrically continuous.
B. Provide grounding-type insulating bushings:
1. For all equipment not supplied with a conduit hub.
2. On ends of metallic ductbank conduit.
C. Bond all conduit, at entrance and exit of equipment, to equipment ground bus or ground lug.
D. Use manufactured conduit hubs at all panels.
E. Provide bonding jumpers if conduit are installed in concentric knockouts.
F. Make all metallic raceway fittings and grounding clamps tight to ensure equipment grounding system will operate continuously at ground potential to provide low impedance current path for proper operation of overcurrent devices during possible ground fault conditions.
G. Provide bonding jumper from equipment ground lug to RGS conduit if flexible conduit is utilized for equipment connections.
H. Provide bonding jumpers identical in conductor size to the largest ground conductor run within the conduit.
3.3 EQUIPMENT GROUNDING
A. Ground all equipment fed from lighting panels through the lighting panel ground bus. Provide ground conductors for all connections.
B. Consider control devices (switches, indicating lights, meters, starters, relays, etc.) mounted in MCC's, switchgear, control panels, or other metal enclosures to be adequately grounded, if the enclosure ground lug or ground bus is properly grounded.
C. Do not splice grounding conductors.
D. Run all equipment grounding conductors in conduit.
E. Bond all lightning protection equipment to the ground grid.
F. Ground unused and spare power and control cable at both ends.
G. Size all grounding conductors in accordance with Article of the NEC unless larger size is shown on the Drawings.
3.4 STRUCTURAL GROUNDING
A. Bond concrete foundation reinforcing steel to the ground at all corners of the structure and at locations along the perimeter. Maximum spacing between bonds shall not exceed 50 FT.
Utilize a bare 2/0 conductor, unless otherwise shown on Contract Drawings. Do not use exothermic welding if it will damage the structural integrity of the foundation.
B. Make all reinforcing steel electrically continuous.
3.5 TESTING
A. Ground Resistance Test:
1. Test resistance of installed ground system after backfilling and before connection to any other grounded system including underground piping, utility services or other building
IHS Georgeville Wastewater System Upgrades SECTION 26 05 26 - PAGE 5 7/13/18 ground systems. Service ground resistance shall not exceed 5ohms. Overall system resistance shall not exceed 15ohms.
2. Test ground grid resistance by fall-of-potential method.
3. The test shall not be performed immediately following wet weather conditions.
B. See Section 26 01 26.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 1 7/13/18
SECTION 26 05 33
RACEWAYS
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Material and installation requirements for:
1. Conduits
2. Conduit fittings
3. Conduit supports
4. Wireways
5. Outlet boxes
6. Pull and junction boxes
1.2 DESCRIPTION OF WORK
A. Provide electrical raceway and fitting work as shown, scheduled, indicated, and specified.
B. All electrical conductors shall be installed in conduit or surface metallic raceways. Conduit shall be as specified herein. In addition, empty conduit shall be installed for the voice/data system and for other systems as indicated on the Drawings and in the Specifications.
C. The types of electrical raceways and fittings required for the project include, but are not limited to, the following.
1. Rigid metallic conduit (RMC) and intermediate metal conduit (IMC),
2. PVC-coated rigid steel conduit,
3. Flexible metal conduit,
4. Liquidtight flexible metal conduit,
5. Rigid nonmetallic conduit.
1.3 RELATED SECTIONS
A. Section 26 60 00 – Electrical: General Provisions
B. Section 26 60 02 – Basic Materials and Methods
1.4 STANDARDS AND REFERENCES
A. All materials and equipment specified herein shall, within the scope of UL Examination
Services, be approved by the Underwriter's Laboratories for the purpose for which they are used and shall bear the UL label.
B. Products and installation shall comply with applicable sections of the following standards:
1. American Iron and Steel Institute (AISI)
2. American National Standards Institute (ANSI):
a) C80.1, Rigid Steel Conduit - Zinc-Coated
3. ASTM International (ASTM):
a) A123, Standard Specification for. Zinc Coating (Hot-Dip Galvanized) Coatings on Iron and Steel Products
b) A153, Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
RACEWAYS
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 2 7/13/18
c) D1784, Standard Specification for Rigid Polyvinyl Chloride (PVC) Compounds and Chlorinated Polyvinyl Chloride (CPVC) Compounds
d) D2564, Solvent Cements for PVC Plastic Pipe, Tubing, and Fittings
e) E84, Standard Test Method for Surface Burning Characteristics of Building Materials
f) F512, Standard Specification for Smooth-Wall PVC Conduit and Fittings for
Underground Installation
4. National Electrical Manufacturers Association (NEMA):
a) FB 1, Fittings and Supports for Conduit and Cable Assemblies
b) OS 1, Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports
c) RN 1, PVC Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal
Conduit
d) TC 2, Electrical Plastic Tubing (EPT) and Conduit (EPC-40 and EPC-80)
e) TC 3, PVC Fittings for Use with Rigid PVC Conduit and Tubing
f) TC 6, PVC Plastic Utilities Duct for Underground Installations
g) 250, Enclosures for Electrical Equipment (1000 Volts Maximum)
5. Underwriters Laboratories, Inc. (UL):
a) 1, Flexible Metal Conduit
b) 6, Rigid Metal Conduit
c) 50, Standard for Safety Enclosures for Electrical Equipment
d) 360, Liquid-Tight Flexible Steel Conduit
e) 467, Grounding and Bonding Equipment
f) 514A, Standard for Safety Metallic Outlet Boxes
g) 514B, Fittings for Cable and Conduit
h) 651, Schedule 40 and 80 Rigid PVC Conduit
i) 870, Wireways, Auxiliary Gutters, and Associated Fittings
j) 886, Outlet Boxes and Fittings for Use in Hazardous (Classified) Locations
k) 1660, Liquid-Tight Flexible Nonmetallic Conduit
C. All materials and equipment specified herein and their installation methods shall conform to the latest published version of the National Electrical Code, NEC.
1.5 SUBMITTALS
A. Shop Drawings
1. See Section 26 60 00.
1.6 DELIVERY, STORAGE, AND HANDLING
A. See Section 26 60 00.
PART 2 PRODUCTS
2.1 GENERAL
A. Provide metal conduit, tubing, and fittings of the type, grade, size, and weight (wall thickness) as shown and required for each service. Where type and grade are not indicated, provide proper selection determined by this Section to fulfill the wiring requirements and complying with the NEC for electrical raceways.
B. For each electrical raceway system indicated, provide a complete assembly of conduit, tubing, or duct with fittings, including, but not necessarily limited to, connectors, nipples, IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 3 7/13/18 couplings, expansion fittings, bushings, locknuts, other components and accessories as needed to form a complete system of the type indicated.
C. Conduit fittings shall be designed and approved for the specific use intended. Conduit fittings, including flexible, shall have insulated throats or bushings. Rigid conduits shall have insulated bushings, except insulated throat grounding bushings shall be used on all conduits without ground conductors and where required by N.E.C. Article 250.
2.2 ACCEPTABLE MANUFACTURERS
A. Provide products complying with these specifications and produced by one of the following:
1. Rigid metallic conduits:
a) Allied Tube and Conduit Corporation
b) Triangle PWC Inc.
c) Western Tube and Conduit Corporation
d) Wheatland Tube Company
e) LTV Steel Company
2. Flexible Metal and Liquidtight Flexible Metal:
a) AFC
b) Anaconda Metal Hose
c) Electri-Flex Company
d) Flexi-Guard, Inc.
e) Triangle PWC, Inc.
f) Wheatland
3. Rigid Nonmetallic Conduit and Innerduct:
a) Carlon
b) Cantex
c) Triangle PWC, Inc.
4. Raceway Fittings:
a) Appleton Electric Company
b) Cantex (PVC)
c) Carlon (PVC)
d) Crouse Hinds
e) Efcor Division
f) ETP-Uni-Couple
g) O.Z. Gedney Company
h) Raco, Inc.
i) Republic Steel Corporation
j) Steel City
k) Thomas and Betts
5. Support systems:
a) Unistrut Building Systems
b) B-Line Systems Inc.
c) Kindorf
d) Minerallac Fastening Systems
e) Caddy
6. Outlet, pull and junction boxes:
a) Appleton Electric Co.
b) Crouse-Hinds
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 4 7/13/18
c) Killark
d) O-Z/Gedney
e) Steel City
f) Raco
g) Bell
h) Hoffman Engineering Co.
i) Wiegmann
j) B-Line Circle AW
k) Adalet
2.3 RIGID METALLIC CONDUITS
A. Rigid Galvanized Steel Conduit (RGS):
1. Mild steel with continuous welded seam,
2. Metallic zinc applied by hot-dip galvanizing or electro-galvanizing; threads galvanized after cutting,
3. Internal Coating: Baked lacquer, varnish or enamel for a smooth surface.
4. Standards: ANSI C80.1, UL 6.
2.4 RIGID NON-METALLIC CONDUIT
A. Schedules 40 (PVC-40) and 80 (PVC-80):
1. Polyvinyl-chloride (PVC) plastic compound which meets, as a minimum, ASTM D1784 cell classification PVC 12233-A, B, or C,
2. Rated for direct sunlight exposure,
3. Fire retardant and low smoke emission,
4. Shall be suitable for use with 90 Deg C wire and shall be marked "maximum 90 Deg C".
5. Standards: ASTM D1784, NEMA TC 2, UL 651.
2.5 FLEXIBLE CONDUIT
A. PVC-Coated Flexible Galvanized Steel (liquid-tight) Conduit (FLEX-LT):
1. Core formed of continuous, spiral wound, hot-dip galvanized steel strip with successive convolutions securely interlocked,
2. Extruded PVC outer jacket positively locked to the steel core,
3. Liquid- and vapor-tight.
4. Standard: UL 360.
2.6 WIREWAY
A. General:
1. Suitable for lay-in conductors,
2. Designed for continuous grounding.
3. Covers:
a) Hinged or removable in accessible areas,
b) Non-removable when passing through partitions.
4. Finish: Rust inhibiting primer and manufacturers standard paint inside and out except for stainless steel type.
5. Standards: UL 870, NEMA 250.
B. Rain-tight (NEMA 3R) Wiring Trough:
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 5 7/13/18
1. 14 or 16 GA galvanized steel without knockouts.
2. Cover: Non-gasketed and held in place by captive screws.
C. Dusttight (NEMA 12 rated) Wireway:
1. 14 GA steel bodies and covers without knockouts and 10 GA steel flanges.
2. Cover: Fully gasketed and held in place with captive clamp type latches.
3. Flanges: Fully gasketed and bolted.
2.7 CONDUIT FITTINGS AND ACCESSORIES
A. Fittings for Use with RGS:
1. In hazardous locations listed for use in Class I, Groups C and D locations.
2. Locknuts:
a) Threaded steel or malleable iron,
b) Gasketed or non-gasketed,
c) Grounding or non-grounding type.
3. Bushings:
a) Threaded, insulated metallic,
b) Grounding or non-grounding type.
4. Hubs: Threaded, insulated and gasketed, metallic, for rain-tight connection.
5. Couplings:
a) Threaded, straight-type: Same material and finish as the conduit with which they are used on.
b) Threadless type: Gland compression or self-threading type, concrete tight.
6. Unions:
a) Threaded galvanized steel or zinc plated malleable iron.
7. Conduit bodies:
a) Body: Zinc plated cast iron or cast copper free aluminum with threaded hubs,
b) Standard and mogul size.
c) Cover: Clip-on type with stainless steel screws. Gasketed or non-gasketed galvanized steel, zinc plated cast iron or cast copper free aluminum.
8. Sealing fittings:
a) Body: Zinc plated cast iron or cast copper free aluminum with threaded hubs,
b) Standard and mogul size, with or without drain and breather.
c) Fiber and sealing compound: UL listed for use with the sealing fitting.
9. Hazardous location flexible coupling (HAZ-FLEX):
a) Bronze braided covering over flexible brass tubing,
b) Liquid tight and arc resistant,
c) Bronze end fittings and zinc-plated steel or malleable iron unions and nipples.
10. Expansion couplings:
a) 2 IN nominal straight-line conduit movement in either direction.
11. Galvanized steel with insulated bushing.
12. Gasketed for wet locations.
13. Internally or externally grounded.
B. Fittings for Use with FLEX:
1. Connector:
a) Zinc plated malleable iron,
b) Squeeze or clamp-type.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 6 7/13/18
2. Standard: UL 514B.
C. Fittings for Use with FLEX-LT
1. Connector:
a) Straight or angle type
b) Metal construction, insulated and gasketed
c) Composed of locknut, grounding ferrule and gland compression nut
d) Liquid-tight.
2. Standard: UL 467, 514B.
D. Fittings for Use with Rigid Non-Metallic Conduit:
1. Coupling and adapters shall be of the same material, thickness, and construction as the conduits with which they are used.
2. Standards: UL 651, NEMA TC 3.
3. Solvent cement for welding fittings shall be supplied by the same manufacturer as the conduit and fittings.
a) Standard: ASTM D2564.
E. Weather and Corrosion Protection Tape:
1. PVC based tape, 10 mils thick,
2. Protection against moisture, acids, alkalis, salts and sewage and suitable for direct burial,
3. Used with appropriate pipe primer.
2.8 OUTLET BOXES
A. Metallic Outlet Boxes:
1. Hot-dip galvanized steel,
2. Conduit knockouts and grounding pigtail,
3. Accessories:
a) Flat blank cover plates,
b) Barriers,
c) Extension, plaster, or tile rings,
d) Box supporting brackets in stud walls,
e) Adjustable bar hangers.
4. Standards: NEMA OS 1, UL 514A.
B. Cast Outlet Boxes:
1. Zinc plated cast iron or die-cast copper free aluminum with manufacturer’s standard finish,
2. Threaded hubs and grounding screw.
3. Styles:
a) "FS" or "FD",
b) "Bell",
c) "EDS" or "EFS" for hazardous locations.
4. Accessories: 40 mil PVC exterior coating and 2 mil urethane interior coating.
5. Standards: UL 514A and 886.
C. See Section 26 27 26 for wiring devices, wallplates, and coverplates.
2.9 PULL AND JUNCTION BOXES
A. NEMA 4 Rated:
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 7 7/13/18
1. Body and cover: 14 GA steel finished with rust inhibiting primer and manufacturers standard paint inside and out,
2. Seams continuously welded and ground smooth,
3. No knockouts,
4. External mounting flanges,
5. Hinged or non-hinged cover held closed with stainless steel screws and clamps,
6. Cover with oil resistant gasket.
B. NEMA 4X Rated (non-metallic):
1. Body and cover: Ultraviolet light protected fiberglass-reinforced polyester boxes,
2. No knockouts,
3. External mounting flanges,
4. Hinged door with quick release latches and padlocking hasp,
5. Door with oil resistant gasket.
C. NEMA 12 Rated:
1. Body and cover: 14 GA steel finished with rust inhibiting primer and manufacturers standard paint inside and out,
2. Seams continuously welded and ground smooth,
3. No knockouts,
4. External mounting flanges,
5. Non-hinged cover held closed with captivated cover screws threaded into sealed wells or hinged cover held closed with stainless steel screws and clamps,
6. Flat door with oil resistant gasket.
2.10 SUPPORT SYSTEMS
A. Multi-conduit surface or trapeze type support and pull or junction box supports:
1. Material requirements.
a) Galvanized steel: ASTM A123 or ASTM A153.
b) Stainless steel: AISI Type 316.
c) PVC coat galvanized steel: ASTM A123 or ASTM A153 and 20 mil PVC coating.
B. Single conduit and outlet box support fasteners:
1. Material requirements:
a) Zinc plated steel
b) Stainless steel
c) Malleable iron
d) PVC coat malleable iron or steel: 20 mil PVC coating
e) Steel protected with zinc phosphate and oil finish.
2.11 OPENINGS AND PENETRATONS IN WALLS AND FLOORS
A. Sleeves, smoke and fire stop fitting through walls and floors:
1. See Section 01800.
PART 3 EXECUTION
3.1 INSTALLATION
A. General:
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 8 7/13/18
1. Install electrical raceways and fittings as shown in accordance with the manufacturer’s written instructions, the applicable requirements of the NEC, and in accordance with recognized industry practices to ensure that products serve the intended function.
Complete electrical raceway installation before starting the installation of wire and cable.
B. Conduit Size:
1. Minimum conduit size for power wiring shall be ¾”, except that 3/8” flexible metallic conduit may be used for fixture whips. Maximum conduit size for EMT shall be 2”.
Minimum conduit size for control wiring shall be ¾”. Minimum conduit size for voice/data wiring shall be 1”.
C. Rigid Steel and Intermediate Metal Conduit:
1. Use rigid steel or intermediate metal conduit to run all electrical raceway systems where exposed to weather; in damp or wet locations; where subject to physical damage; and where cast in concrete walls or floors slabs which have waterproof membranes and where cast in masonry walls. Use rigid steel or IMC conduit for all exposed feeders. IMC conduit shall not be used in sizes larger than 4”. Use threaded type couplings and fittings. Split type couplings and fittings are not acceptable. The interior of all buildings shall be considered a damp or wet area.
D. Liquidtight Flexible Metal:
1. Use liquidtight flexible metal conduit and fittings for all motor connections, and for other electrical equipment connections where subject to movement and vibration and when subject to one or more of the following conditions: (1) exterior locations, moist or humid atmosphere where condensation can be expected to accumulate; (2) corrosive atmosphere, subject to water spray; subject to dripping oil, grease or water. Install internal ground wire in flexible conduit with grounding bushings. Maximum length shall be 6’0” and minimum length shall be 3’0”.
E. Rigid Nonmetallic:
1. Use PVC conduit directly buried in earth, concrete encased, cast in concrete slabs, and where subject to corrosive environment. PVC may be used for all raceways on the interior of the building, which do not contain 480 volt conductors or motor feeders. Use Schedule 40 where direct buried and Schedule 80 where exposed, with size adjusted to have same fill area as if Schedule 40 were used.
3.2 INTERIOR CONDUIT SYSTEM:
A. Ground all metallic conduit in accordance with the requirements of the latest edition of the
NEC.
B. Install all conduit as a complete system without conductors, continuous from outlet to outlet and from fitting to fitting. Make up threaded joints of conduit carefully in such a manner as to ensure a tight joint. Field-cut threads shall be cold-galvanized after cutting. The entire conduit system shall be secured at all joints and boxes in such a manner that each system shall be electrically continuous throughout. Fasten the entire conduit system securely into position. A run of conduit between outlet and outlet, between fitting and fitting, or between outlet and fitting shall not contain more than the equivalent of four quarter bends, including those bends located immediately at the outlet or fitting. Install approved expansion fittings in all conduit runs as specified in paragraph 3.2.P.
C. Ream all ends of conduit properly to remove rough edges. Whenever a rigid steel or IMC conduit enters a switchboard, panelboard, enclosure, or box it shall be securely fastened by the use of a locknut inside and outside and an approved insulating bushing shall be installed.
Insulated grounding bushings shall be installed on all conduits without ground conductors and where required by NEC Article 250. Lay out and install all conduit systems as to avoid all other services or systems, the proximity of which may prove injurious to the conduit or the wires or conductors which the conduit confines.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 9 7/13/18
D. Conceal conduit systems in finished areas. Concealed metallic conduits shall be run in a direct manner, basically parallel to, and at right angles with the lines of the building, and with as long a bend as possible. Conduit may be exposed in mechanical rooms and where otherwise shown or indicated. On exposed systems, run the conduit parallel or perpendicular to the structural features of the building and rigidly support with malleable iron conduit clamps at intervals as required by NEC, or on conduit racks, neatly racked and bent in a smooth radius at corners insofar as practicable. All bends shall be field-made using an approved bending machine designed for the purpose, or using standard ells having a radius not less than that required by the National Electrical Code, and with approved fittings or connectors.
All bends shall be free from dents or flattening.
E. All conduit shall be run without traps. Where traps are unavoidable, a junction or pull box shall be placed at the low point. Metallic conduit systems, which are exposed to the weather or water, shall be made watertight. As soon as conduit has been permanently installed in place, conduit shall be capped or plugged with standard accessories. All metallic conduit shall be swabbed after plaster and drywall is finished and dry.
F. Support exposed raceway or grouped concealed raceways on galvanized channel using compatible galvanized fittings (bolt, beam clamps, and similar items) and galvanized threaded rod pendants to secure raceway to channel and channel to structure. Support single conduit runs using a properly sized galvanized conduit hanger with galvanized closure bolt/nut and threaded rod. Support flexible conduit on maximum 4-1/2’ centers and within one foot (1’) of boxes. All raceway support system materials shall be galvanized and manufactured by Kindorf, Unistrut, Superstrut, Caddy, or Spring Steel Fasteners, Inc.
Provide chrome or nickel-plated escutcheon plates on all conduit passing through walls and ceilings in finished areas.
G. Make all joints and connections to ensure mechanical strength and electrical continuity. PVC conduit shall be joined, or have fittings attached, by using a fusing (solvent) compound recommended by and applied as instructed by, the conduit manufacturer.
H. Run conduit to avoid proximity to heat producing equipment, piping and flues, keeping a minimum of 8” clear. Whenever possible, install horizontal raceway runs above water piping.
Unless shown otherwise, do not install conduit horizontally in concrete slabs without written approval. All roof penetrations shall be made in adequate time to allow the roofer to make proper flashings.
I. Carefully review architectural, structural, mechanical, plumbing, and electrical Drawings and place boxes and conduit to avoid conflicts with structural members or other general construction.
J. Conduit larger than ¾” shall not be embedded in structural slabs without prior written permission from the Engineer. Conduits embedded in structural slabs shall be installed in the middle of the slab below the top and above the bottom reinforcing steel. Maintain a minimum concrete coverage of one (1”) except where penetration is made.
K. Furnish sleeves for timely placing in construction for all conduit passing through concrete walls, partitions, beams, floors, and roofs while same are under construction.
L. All conduit passing through the housing on connected equipment, shall pass through a cleanly cut hole protected with an approved grommet.
M. Metallic conduit installed below grade shall have its entire length painted with two coats of protective finish unless encased in concrete. Each coat shall consist of 5mils of PPG “Coat Cat Epoxy Coating” applied in accordance with the manufacturer’s recommendations. The entire length of metallic conduit, including fittings, shall be protected to a point 6” above finished grade (or concrete slab).
N. Coordinate locations of raceways in fire rated partitions so as not to affect the fire rating of the partition. Notify the Engineer in writing where additional construction is required to maintain the partition fire rating.
IHS Georgeville Wastewater System Upgrades SECTION 26 05 33 - PAGE 10 7/13/18
O. Install expansion fittings in all conduit as follows:
1. All conduits crossing building expansion joints; unless some other form of thermal expansion compensation is approved in writing by the Engineer,
2. All conduit straight runs in excess of 200’, and 400’ centers in all longer conduit runs.
3. Conduit entering environmental rooms,
4. Locations subject to thermal expansion and as required by NEC.
5. Unless expansion fitting has an integral bonding braid, an external braid approved for the purpose shall be installed around the fitting.
3.3 EXTERIOR CONDUIT SYSTEMS
A. Exterior conduit systems shall meet all of the general installation requirements for interior…