This solicitation seeks a contractor to replace an existing heating plant at the Pine Ridge Hospital in Pine Ridge, South Dakota. The contractor shall furnish all labor, equipment, materials, and transportation necessary to demolish the existing heating equipment and boilers and install three new firetube water boilers, associated pumps and controls, new domestic hot water storage tanks, and related mechanical and control systems. The work shall be performed in accordance with the drawings and technical provisions provided. The solicitation was issued by the Department of Health and Human Services Indian Health Service.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER SHEET
INDIAN HEALTH SERVICE
PINE RIDGE COMPREHENSIVE HEALTH CARE CENTER
REPLACE HEATING PLANT DESIGN
100% CONSTRUCTION DOCUMENTS SUBMITTAL
PINE RIDGE HOSPITAL
607 INDIAN HEALTH RD
PINE RIDGE, SD 57770
SITE MAP
SCALE: NTS
TRUE
NORTH
PROJECT
NORTH
PROJECT AREA
VICINITY MAP
SCALE: NTS
TRUE
NORTH
PROJECT
NORTH
S T
A
T E
O F CA L I FOR N
I A
EXP.________
M 34008 3-31-2022
R
EG
IS
TE
RED
PROFESS IONAL
ENG
IN
E
ER
S
H A N E P A R
K
M E C H A N I C A
L www.ihs.gov
Scale
Project number
Date
Drawn by
Checked by
GREAT PLAINS
AREA INDIAN
HEALTH SERVICE
OFFICE OF
ENVIRONMENTAL
HEALTH &
ENGINEERING
115 4TH AVENUE SE, ROOM 309
ABERDEEN, SD 57401
(605) 226-7451 FAX (605) 226-7689
K. F. DAVIS ENGINEERING, INC.
530 LA GONDA WAY,
SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
N.T.S
PE STAMP:
/2
/2
:2
:3
P
M
G-1
C O
V E
R S
H E
E T
R E
P L
A C
E H
E A
T
IN
G P
L A
N T
02/22/2022
A. SHRESTHA
S. PARK
SHEET INDEX
SHEET
NUMBER SHEET NAME
GENERAL
G-1 COVER SHEET
G-2 GENERAL PROJECT NOTES
STRUCTURAL
S-1 STRUCTURAL GENERAL NOTES & IBC TABLES
S-2 FOUNDATION PLAN
MECHANICAL
M-1 MECHANICAL SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES
M-2 MECHANICAL SCHEDULES
M-3 MECHANICAL SCHEDULES
M-4 HEATING PLANT - MECHANICAL DEMOLITION PLAN
M-5 HEATING PLANT - MECHANICAL NEW PLAN
M-6 HEATING PLANT - PLUMBING PLAN
M-7 MECHANICAL DIAGRAMS
M-8 DOMESTIC WATER DIAGRAM
M-9 POINTS LIST
M-10 BACNET SYSTEM ARCHITECTURE AND SEQUENCE OF
OPERATION
M-11 MECHANICAL DETAILS
M-12 MECHANICAL DETAILS
ELECTRICAL
E-1 ELECTRICAL SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES
E-2 HEATING PLANT - ELECTRICAL DEMOLITION PLAN
E-3 HEATING PLANT - ELECTRICAL NEW PLAN
E-4 ELECTRICAL PANEL SCHEDULE DSEMH DEMO
E-5 ELECTRICAL PANEL SCHEDULE CLF1 DEMO
E-6 ELECTRICAL PANEL SCHEDULE LSLF DEMO
E-7 ELECTRICAL PANEL SCHEDULE DSEMH NEW WORK
E-8 ELECTRICAL PANEL SCHEDULE CLF1 NEW WORK
E-9 ELECTRICAL PANEL SCHEDULE DSEMH1 NEW WORK
E-10 ELECTRICAL PANEL SCHEDULE CLF1A NEW WORK
E-11 ELECTRICAL ROOM SITE PLANS
E-12 ELECTRICAL DETAILS
100% SUBMITTAL
No. Description Date
1 100% CD SUBMITTAL 02/22/2022
1. THE CONTRACTORIS RESPONSIBLE FOR OBTAINING ALL NECESSARY APPROVALS AND PERMITS REQUIRED FROM REGULATORY AGENCIES BEFORE STARTING ANY WORK. THE CONTRACTOR WILL BE REQUIRED TO COMPLY WITH THE INDIAN PREFERENCE AND INDIAN PREFERENCE PROGRAM REQUIREMENTS ADMINISTERED BY
THE OGLALA SIOUX TRIBE TRIBAL EMPLOYMENTS RIGHTS OFFICE (TERO).
BEFORE COMMENCING WORK, CONTRACTORS AND SUB-CONTRACTORS ARE REQUIRED TO SUBMIT AN ACCEPTABLE “COMPLIANCE AGREEMENT” TO THE TERO OFFICE COPIES OF THIS FORM CAN BE OBTAINED FROM THE TERO OFFICE. TYPICAL REQUIREMENTS OF TERO INCLUDE A FEE OF 4% ON THE TOTAL CONTRACT PRICE AND
SUBMISSION OF WEEKLY CERTIFIED PAYROLL REPORTS TO TERO.
ADDITIONALLY THE RULES AND REGULATIONS OF THE TERO ORDINANCE REQUIRE THAT NO PERSON WHO IS NOT A LOCAL INDIAN SHALL BE EMPLOYED BY A COVERED EMPLOYER UNTIL A WORK PERMIT HAS BEEN OBTAINED FOR THEM FROM TERO. THE ANNUAL WORK PERMIT FEE FOR EACH EMPLOYEE IS $250.
CONTRACTORS ARE STRONGLY ENCOURAGED TO CONTACT THE TERO OFFICE AT 605-867-5167 FOR AN EXPLANATION OF TRIBAL REQUIREMENTS, REQIRED FEES, AND/OR PERMITS.
2. SUBJECT TO MINOR EXCEPTIONS, GENERALLY THE ITEMS SHOWN IN BOLD LINES ARE NEW AND ITEMS SHOWN IN GRAYSCALE ARE EXISTING.
3. THE WORK ON THESE DRAWINGS IS GENERALLY DIAGRAMMATIC AND IS INTENDED TO CONVEY THE SCOPE OF WORK, INDICATE THE GENERAL ARRANGEMENT OF EQUIPMENT AND FINAL LAYOUT. THE DRAWINGS ARE GENERIC IN NATURE AND ARE INTENDED TO BE SUPPORTED BY SPECIFIC MANUFACTURER AND/OR FABRICATORS SHOP DRAWINGS AND SIMILAR DETAILS TO DETERMINE EXACT SPACING AND/OR INSTALLATION REQUIREMENTS.
4. IF ANY PART OF THE DRAWINGS OR SPECIFICATIONS CONTRADICT THE MANUFACTURER'S RECOMMENDATIONS, APPLICATION OR INSTALLATION INSTRUCTIONS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK, ADVISE THE CONTRACTING OFFICER AND RECEIVE CLEAR, WRITTEN, DIRECTION
BEFORE PROCEEDING.
5. DO NOT SCALE THE DRAWINGS. WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS. IF ANY DISCREPANCIES OR OMISSIONS IN THE DIMENSIONS ARE DISCOVERED, THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IMMEDIATELY. ANY WORK DONE WITHOUT PROPER NOTIFICATION BEING GIVEN TO THE CONTRACTING OFFICER IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
6. PRIOR TO DEMOLITION, CONTRACTOR SHALL VERIFY ALL DIMENSIONS, EXISTING CONDITIONS AND LOCATION OF NEW CONSTRUCTION WITH EXISTING WALLS, FLOORS, CEILINGS, COLUMNS, FURRING, MECHANICAL AND ELECTRICAL EQUIPMENT AND EXISTING CONSTRUCTION.
7. FIELD INVESTIGATION PERFORMED DURING THE DESIGN STAGE IS LIMITED TO WHAT CAN BE REASONABLY SEEN AND DOCUMENTED WHILE THE SPACE IS OPERATIONAL AND OCCUPIED BY PERSONNEL, EQUIPMENT AND FURNITURE. AS SUCH, THE CONTRACTOR IS RESPONSIBLE FOR PERFORMING A THOROUGH REVIEW AND VALIDATING ALL FIELD CONDITIONS PRIOR TO COMMENCEMENT OF WORK. THE CONTRACTOR SHALL REPORT ANY PROBLEMS/CONFLICTS TO THE CONTRACTING OFFICER WITHIN TWO (2) DAYS OF DISCOVERY. ANY CHANGES RESULTING FROM CONDITIONS ARISING IN THE FIELD WHICH ARE NOT BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER ARE TO BE MADE BY THE CONTRACTOR AT NO ADDITIONAL COST TO GOVERNMENT.
8. DRAWINGS SHOWN ARE SCHEMATIC ONLY. THE CONTRACTOR SHALL FIELD VERIFY SITE CONDITIONS AND ENSURE SHOP DRAWINGS ARE PROVIDED BEFORE DETAILING COMPLETE UTILITY LAYOUT AND INSTALLATION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO ROUTE NEW CONDUITS, DUCTS, PIPING AND SIMILAR LINES TO AVOID POTENTIAL INTERFERENCES, AND WHERE THIS CANNOT BE ACCOMPLISHED, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REMOVE, REROUTE, ADJUST REINSTALL THE INTERFERENCE SUCH THAT IT NO LONGER POSES A PROBLEM. THESE ITEMS ARE TO BE ADDRESSED AND
CORRECTED AT NO ADDITIONAL COST TO THE GOVERNMENT.
9. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE AND FINISHED INSTALLATION AND SHALL COORDINATE ALL EQUIPMENT AND WORK BETWEEN TRADES TO
MEET THE REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS.
10. FINAL LOCATION OF MECHANICAL AND ELECTRICAL EQUIPMENT SUCH AS PANELBOARDS, METERS, FLUES, VENTS, ETC., SHALL BE APPROVED BY THE
GOVERNMENT.
11. EACH SUBCONTRACTOR IS CONSIDERED TO BE A SPECIALIST IN HIS RESPECTIVE FIELD AND SHALL, PRIOR TO SUBMISSION OF BID OR PERFORMANCE OF WORK, NOTIFY THE CONTRACTOR AND THE CONTRACTING OFFICER, IN WRITING, OF ANY WORK CALLED FOR IN THE DRAWINGS OR SPECIFICATIONS THAT
CANNOT BE FULLY GUARANTEED.
12. THE CONTRACTOR WARRANTS ALL WORK TO BE PERFORMED AND ALL MATERIALS TO BE FURNISHED UNDER THIS CONTRACT AGAINST DEFECTS IN WORKMANSHIP FOR A PERIOD OF NOT LESS THAN 1 YEAR FROM THE DATE OF FINAL ACCEPTANCE. UPON WRITTEN NOTICE OF ANY DEFECT IN MATERIALS OR WORKMANSHIP, THE CONTRACTOR SHALL, AT THE OPTION OF THE GOVERNMENT, REPAIR OR REPLACE SAID DEFECT WITHOUT COST TO THE
GOVERNMENT.
13. ALL MATERIALS SHALL CONFORM TO THE "BUY AMERICAN ACT".
14. ALL CONSTRUCTION WORK, ARCHITECTURAL, MECHANICAL, ELECTRICAL, FIRE PROTECTION, ETC. SHALL CONFORM TO THE MOST CURRENT ISSUE OF THE NATIONAL FIRE PROTECTION ASSOCIATION LIFE SAFETY CODE (NFPA 101), THE INTERNATIONAL BUILDING CODE, IHS CRITERIA AND ANY APPLICABLE LOCAL, STATE AND FEDERAL CODES AND GUIDELINES. SHOULD THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE CONFLICT WITH THE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION LIFE SAFETY CODE (NFPA 101), THEN THE MORE STRINGENT BETWEEN THE TWO SHALL GOVERN.
15. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR WORKING CONDITIONS AT THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING THE PERFORMANCE OF THE WORK. THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND SHALL NOT BE LIMITED TO WORK HOURS. CONTRACTOR SHALL CONFORM TO ALL SAFETY REGULATIONS ENFORCED AT THE TIME OF CONSTRUCTION. JOB SITE SAFETY IS STRICTLY THE RESPONSIBILITY OF THE CONTRACTOR, AND NOT THE ARCHITECT/ENGINEER
OR THE GOVERNMENT.
16. THE CONTRACTOR SHALL PROVIDE U.L. RATED PORTABLE FIRE EXTINGUISHERS, TYPE 24.10.B.C ON SITE AND IN A LOCATION APPROVED BY THE
GOVERNMENT.
17. THE CONTRACTOR SHALL MAINTAIN THE CONSTRUCTION AREA AND ALL ADJACENT AFFECTED AREAS, IN A CLEAN AND ORDERLY MANNER THROUGHOUT THE
COURSE OF CONSTRUCTION. DO NOT BLOCK ENTRANCES, EXITS, LOBBIES, CORRIDORS, ETC.
18. THE CONTRACTOR SHALL REMOVE ALL DEBRIS ON A DAILY BASIS IN ACCORDANCE WITH IHS AND EPA REGULATIONS. DEBRIS SHALL BE TRANSPORTED ON COVERED CARTS TO THE APPROVED DISPOSAL AREA AS DIRECTED BY THE CONTRACTING OFFICER. THE CONSTRUCTION AREA, AND ALL ADJACENT AREAS, SHALL BE CLEAN AND FREE OF DEBRIS AT THE END OF EACH DAY.
19. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING ALL LEFT-OVER MATERIALS, DEBRIS, TOOLS AND EQUIPMENT INVOLVED IN HIS OPERATIONS AT THE CONCLUSION OF THE PROJECT. ALL PROJECT AREAS AND SURROUNDING AREAS AFFECTED BY CONSTRUCTION SHALL BE LEFT CLEAN AND IN PERFECT
CONDITION.
20. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONARY MEASURES TO ENSURE THAT ALL PROPERTIES, EQUIPMENT AND DEVICES AT THE PROJECT SITE ARE PROTECTED DURING THE CONSTRUCTION PERIOD. ANY DAMAGES TO EXISTING CONSTRUCTION, LANDSCAPING, EQUIPMENT AND DEVICES SHALL BE REPAIRED AND RESTORED TO A CONDITION EQUAL TO THAT EXISTING AT THE COMMENCEMENT OF THE WORK. THE CONTRACTOR SHALL RESTORE ANY DAMAGE AT HIS OWN EXPENSE. THE CONTRACTOR SHALL SUBMIT THE PROCEDURE FOR CONSTRUCTION AND DEMOLITION PRIOR TO COMMENCING WORK.
21. ALL FINISH WORK, EITHER NEW OR EXISTING, WHICH IS DAMAGED OR STAINED AS A RESULT OF CONSTRUCTION ACTIVITIES, SHALL BE REPAIRED OR
REPLACED AS NECESSARY AT NO ADDITIONAL COST TO GOVERNMENT.
22. ALL SURFACES SHALL BE SMOOTH, CONTINUOUSLY FREE OF IMPERFECTIONS AND IN PROPER CONDITION TO RECEIVE THE FINISH AS SPECIFIED. IN AREAS WHERE A FINISH IS NOT SPECIFIED, THEY SHALL MATCH ADJACENT MATERIAL IN CONSTRUCTION, COLOR, TEXTURE AND MANUFACTURER.
23. WORK SHALL NOT BE PERFORMED WHEN WEATHER CONDITIONS MAY CREATE HAZARDOUS WORKING CONDITIONS OR LEAD TO FAILURE IN WORKMANSHIP.
24. ANY ROOF, WALL OR OTHER OPENINGS MADE DURING CONSTRUCTION SHALL BE SEALED AND PROTECTED FROM RAIN, MOISTURE, WIND, DUST AND OTHER
OUTSIDE ELEMENTS.
25. AN APPROPRIATELY QUALIFIED REPRESENTATIVE OF THE CONTRACTOR SHALL BE ON SITE TO SUPERVISE AND COORDINATE CONSTRUCTION AT ALL TIMES WHILE WORK IS IN PROGRESS. SUCH PERSON SHALL BE RESPONSIBLE FOR OSHA COMPLIANCE AND JOB SITE SAFETY. JOB SITE SAFETY IS STRICTLY THE SOLE RESPONSIBILITY OF THE CONTRACTOR. THE GOVERNMENT, ARCHITECTS AND ENGINEERS ARE NOT RESPONSIBLE FOR ANY
ASPECT OF JOB SITE SAFETY.
26. QUALITY CONTROL, INSPECTIONS AND WORKMANSHIP IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. ANY OBSERVATIONS MADE BY THE GOVERNMENT OR ARCHITECT/ENGINEER DURING THE COURSE OF CONSTRUCTION ARE FOR THE BENEFIT OF THE GOVERNMENT AND DO NOT
ALLEVIATE THE CONTRACTOR OF THIS RESPONSIBILITY.
27. THE CONTRACTOR SHALL NOT STORE ANY CHEMICALS ON THE SITE OR WITHIN THE CONFINES OF THE BUILDING.
28. IF THE CONTRACTOR ENCOUNTERS ANY UNKNOWN SUBSTANCE OR MATERIAL THAT MAY BE SUSPECTED HAZARDOUS, THE CONTRACTOR SHALL
IMMEDIATELY STOP WORK AND NOTIFY THE CONTRACTING OFFICER.
29. ASBESTOS CONTAINING MATERIALS ARE NOT PERMITTED.
30. CONTRACTOR SHALL MAINTAIN AND KEEP THE EXISTING FIRE ACCESS LANE AND PEDESTRIAN ACCESS AND EXIT PATHS CLEAR AT ALL TIMES.
31. SOME WORK MAY BE REQUIRED AFTER NORMAL WORKING HOURS, ON HOLIDAYS AND/OR WEEKENDS. THIS INCLUDES ANY WORK WHICH COULD POTENTIALLY BLOCK ACCESS TO THE FACILITY OR CAUSE DISRUPTION TO THE NORMAL OPERATIONS OF THE MEDICAL CENTER. THE WORK WILL HAVE TO BE CAREFULLY PLANNED AND PHASED FOR MINIMAL DISRUPTION TO MEDICAL CENTER ACTIVITIES. ANY WORK AFTER HOURS MUST BE CAREFULLY COORDINATED WITH, AND APPROVED BY THE GOVERNMENT A MINIMUM OF TWO WEEKS IN ADVANCE.
32. CONTRACTOR SHALL DEVELOP AND SUBMIT A DETAILED PHASING PLAN INDICATING THE SEQUENCE OF WORK. A PROPOSED PHASING PLAN HAS BEEN PROVIDED ON M-1. THE POTENTIAL UTILITY CUTOVERS OR OUTAGES, AND SPECIFICALLY LIST ANY POTENTIAL DISRUPTIONS TO THE NORMAL OPERATIONS OF THE MEDICAL CENTER. THIS PLAN SHALL BE SUBMITTED AND APPROVED PRIOR TO MOBILIZING ON THE SITE.
33. ALL UTILITY OUTAGES MUST OCCUR AFTER HOURS OR ON WEEKENDS. UNDER NO CIRCUMSTANCES CAN THERE BE UTILITY OUTAGES, INCLUDING BRIEF CUTOVERS, ANYWHERE ON THE CAMPUS WITHOUT THE EXPRESS WRITTEN CONSENT OF THE GOVERNMENT. THE CONTRACTOR SHALL PLAN AND FORECAST UPCOMING WORK WHICH MAY DISRUPT NORMAL OPERATIONS OR INTERFERE WITH STAFF OR PATIENTS AND IDENTIFY THESE IN THE PHASING PLAN, AS WELL AS REPORT THESE IN THE WEEKLY MEETINGS. IT MAY BE NECESSARY TO POSTPONE OR RESCHEDULE WORK TO ACCOMMODATE THE NEEDS OF THE MEDICAL CENTER. ALL SUCH TIME SHALL BE INCLUDED IN THE BASE BID AND WILL NOT BE BILLABLE TO THE
GOVERNMENT.
34. CONTRACTOR SHALL SUBMIT TO THE GOVERNMENT, FOR APPROVAL, THE LOCATION FOR LOADING AND UNLOADING MATERIALS. CONTRACTOR IS ADVISED THAT THERE WILL BE TIME RESTRICTIONS ASSOCIATED WITH SUCH ACTIVITIES AND SHALL TAKE THIS INTO CONSIDERATION WHEN
PREPARING THE PHASING PLAN.
35. CONTRACTOR SHALL PROVIDE ANCHORING AND/OR BRACING OF ALL CONSTRUCTION, WHETHER OR NOT SPECIFICALLY STATED ON THE DRAWINGS OR SPECIFICATIONS, INCLUDING BUT NOT LIMITED TO, WALLS, PARTITIONS, FIXTURES, SUSPENDED ITEMS, OVERHEAD DUCTWORK, EQUIPMENT, PLUMBING AND ELECTRICAL PIPES AND RACEWAYS, AND FIRE PROTECTION SYSTEMS PER SPECIFICATION SECTION 130541 AND AS SHOWN ON THE
PLANS AND/OR SPECIFIED BY EACH RESPECTIVE DISCIPLINE.
36. WHERE EXTERIOR WORK OCCURS, THE CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTING A WATERTIGHT FACILITY USING THE MEANS AND METHODS ESTABLISHED BY THE NATIONAL FENESTRATION RATING COUNCIL (NFRC), THE NATIONAL ROOFING CONTRACTOR'S ASSOCIATION, WESTERN STATES ROOFING CONTRACTOR'S ASSOCIATION AND ANY ADDITIONAL STANDARD PRACTICES, CODES AND REQUIREMENTS AS NECESSARY TO ENSURE A WATERTIGHT FACILITY FREE OF ANY LEAKS. ANY DETAILS PROVIDED HEREIN ARE PROVIDED FOR GENERAL GUIDANCE TO CONVEY THE INTENTION OF THE DESIGN, AND DOES NOT ALLEVIATE THE CONTRACTOR FROM THE RESPONSIBILITY TO PROVIDE A COMPLETELY WATERTIGHT FACILITY. THE CONTRACTOR SHALL PERFORM WATER TESTS TO DEMONSTRATE TO THE SATISFACTION OF THE CONTRACTING OFFICER THAT THE BUILDING DOES NOT LEAK. ANY DEFECTS OR LEAKS SHALL BE IMMEDIATELY REPAIRED AT THE CONTRACTOR'S EXPENSE.
37. CONTRACTOR SHALL PROVIDE ALL SAFETY AND CAUTION SIGNAGE TO REDIRECT PEDESTRIAN TRAFFIC AND/OR ALERT THEM TO POTENTIAL CONSTRUCTION ACTIVITIES AND HAZARDS. SAFE AND ACCESSIBLE PEDESTRIAN ROUTES SHALL BE MAINTAINED AT ALL TIMES. PROVIDE SIGNAGE IN ACCORDANCE WITH OSHA STANDARD SPECIFICATION FOR ACCIDENT PREVENTION SIGNS AND TAGS 1910.145.
38. FOR IHS-PROVIDED EQUIPMENT TO BE INSTALLED BY THE CONTRACTOR (SHOWN AS "VC" ON THE PLANS OR SCHEDULES), CONTRACTOR SHALL DISCONNECT, REMOVE AND RELOCATE SUCH EQUIPMENT AND SHALL BE RESPONSIBLE FOR RE-CONNECTING AND TESTING PROPER OPERATION (PER MANUFACTURER'S INSTRUCTIONS) OF SUCH EQUIPMENT PRIOR TO TURNING OVER SUCH EQUIPMENT TO THE IHS.
39. FOR UTILITY INTERRUPTIONS, THE CONTRACTOR SHALL SUBMIT A REQUEST TO INTERRUPT ANY SUCH SERVICES TO COR, IN WRITING, FORTY-FIVE (45) WORKING DAYS IN ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE, EXACT TIME OF, AND APPROXIMATE DURATION OF
SUCH INTERRUPTION.
40. CONSTRUCTION IS TAKING PLACE IN AN EXISTING OCCUPIED FACILITY. AS SUCH, DEMOLITION OR CONSTRUCTION THAT PRODUCES EXCESSIVE (60 DB OR GREATER) NOISE OR VIBRATION SHALL BE PERFORMED AT TIMES COORDINATED AND APPROVED BY THE COR. CONTRACTOR IS ADVISED THAT WORK MAY BE STOPPED OR DELAYED AT ANY TIME AT THE DISCRETION OF THE COR SHOULD CONSTRUCTION ACTIVITIES CAUSE ANY DISTURBANCE
OR INTERFERENCE WITH PATIENT CARE.
41. THE CEILING ACCESS PANELS SHOWN ON DRAWINGS ARE FOR MAJOR MECHANICAL EQUIPMENT ACCESS ONLY. ADDITIONAL ACCESS PANELS (NOT SHOWN) WILL BE REQUIRED FOR MAINTENANCE, PLUMBING, ELECTRICAL AND FIRE PROTECTION. CONTRACTOR SHALL PROVIDE ADDITIONAL ACCESS PANELS REQUIRED FOR THE ABOVE SPECIALTIES AT NO ADDITIONAL COST TO THE GOVERNMENT. CONTRACTOR SHALL COORDINATE WITH EACH SPECIALTY TRADE AND LOCATE ADDITIONAL ACCESS PANELS FOR REVIEW AND APPROVAL BY THE IHS PRIOR TO FRAMING THE CEILING.
42. SHORING, BRACING AND PROTECTION OF EXISTING STRUCTURE AND EARTHWORK IS THE CONTRACTORS RESPONSIBILITY. PROVIDE ADEQUATE SHORING OF ANY EXISTING CONDITIONS OR CONDITIONS CAUSED BY CONSTRUCTION RELATED ACTIVITIES, AS NECESSARY TO PROTECT PERSONS AND STRUCTURE FROM POTENTIAL FALLING STRUCTURE, EQUIPMENT OR COLLAPSE OF EARTHWORK. AS A MINIMUM, FOR ANY EARTHWORK RESULTING IN TRENCHES OR EXCAVATIONS EXCEEDING THREE FEET (3') IN DEPTH, THE CONTRACTOR SHALL RETAIN THE SERVICES OF A LICENSED STRUCTURAL ENGINEER TO PROVIDE INSTRUCTIONS, FOR IHS APPROVAL, ON THE METHODS TO BE USED FOR SHORING. ANY OVERHEAD STRUCTURE, EQUIPMENT OR SIMILARLY HEAVY CONDITION TO REMAIN, SHALL BE PROPERLY SHORED WITH INPUT FROM A LICENSED STRUCTURAL ENGINEER, AS REQUIRED, TO ENSURE THE PERSONAL SAFETY AND PROTECTION OF REMAINING STRUCTURE.
43. PROVIDE TEMPORARY CONSTRUCTION BARRIERS AS NECESSARY TO SEPARATE DEMOLITION AREAS FROM ADJACENT OCCUPIED SPACES WHEN
BARRIERS CROSS A REQUIRED EXIT PATH, PROVIDE EXIT DOORS WITHIN BARRIER WALL.
44. THESE DOCUMENTS ARE NOT INTENDED TO SHOW EVERY EXISTING CONDITION OR ITEM. CONTRACTOR SHALL NOTIFY IHS OF MISCELLANEOUS ITEMS FOUND. COORDINATE WITH THE IHS REGARDING THE DISPOSITION OF SUCH ITEMS, AND HANDLE ACCORDINGLY AT NO COST TO THE GOVERNMENT.
45. ALL STRUCTURAL ELEMENTS INCLUDING THEIR FIRE PROTECTION MATERIALS ARE TO REMAIN EXCEPT WHERE FURRING IS INDICATED TO BE
REMOVED.
46. NOT USED.
47. THE GENERAL OR PRIME CONTRACTOR AND ANY SUB-CONTRACTORS WILL BE REQUIRED AND EXPECTED TO ATTEND A PRE CONSTRUCTION RISK ASSESSMENT (PCRA) AND AN INFECTION CONTROL RISK ASSESSMENT (ICRA) MEETING BEFORE ANY CONSTRUCTION WORK TAKES PLACE. PROPER PCRA/ICRA PAPER WORK AND PERMITTING IS EXPECTED TO BE SIGNED BY THE CONTRACTOR(S) AND POSTED IN WORK AREA BEFORE
ANY CONSTRUCTION WORK CAN TAKE PLACE.
GENERAL NOTES
S T
A
T E
O F CA L I FOR N
I A
EXP.________
M 34008 3-31-2022
R
EG
IS
TE
RED
PROFESS IONAL
ENG
IN
E
ER
S
H A N E P A R
K
M E C H A N I C A
L www.ihs.gov
Scale
Project number
Date
Drawn by
Checked by
GREAT PLAINS
AREA INDIAN
HEALTH SERVICE
OFFICE OF
ENVIRONMENTAL
HEALTH &
ENGINEERING
115 4TH AVENUE SE, ROOM 309
ABERDEEN, SD 57401
(605) 226-7451 FAX (605) 226-7689
K. F. DAVIS ENGINEERING, INC.
530 LA GONDA WAY,
SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
PE STAMP:
NTS
/2
/2
:2
:3
P
M
G-2
G E
N E
R A
L P
R O
J E
C T
N O
T E
S
R E
P L
A C
E H
E A
T
IN
G P
L A
N T
02/22/2022
A. SHRESTHA
S. PARK
SPECIAL INSPECTION AND TESTING:
1. SPECIAL INSPECTION AND MINIMUM TESTING SHALL BE PERFORMED IN ACCORDANCE
WITH 2018 IBC AND ALL REFERENCED MATERIALS AND TABLES.
2. INSPECTION SHALL BE PROVIDED BY AN INDEPENDENT TESTING AGENCY HIRED AT THE
OWNER'S EXPENSE. AGENCY INSPECTION PERSONNEL SHALL MEET THE INSPECTOR
QUALIFICATIONS FOR EACH MATERIAL ITEM AS INDICATED IN THE SPECIFICATIONS.
3. ANY MATERIAL OR PLACEMENT DEVIATIONS FROM MINIMUMS SHOWN ON THE DRAWINGS
OR IN SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
4. TESTING - ANY FAILED FIELD TEST SHALL BE REPORTED TO ALBERTSON ENGINEERING
INC IMMEDIATELY.
IBC 2018 TABLE 1705.3 REQUIRED SPECIAL INSPECTION
AND TESTS OF CONCRETE CONSTRUCTION
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE
MEMBERS.b
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
A. APPLICATION OF PRESTRESSING FORCES.
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE
AND TECHNIQUES.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS,
AND DETERMINE THE TEMPERATURE OF THE CONCRETE.
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES
ACI 318: CH. 26.9
ACI 318: 26.10
ACI 318: 26.5.3-26.5.5
ACI 318: 26.5
ASTM C172, ASTM C31,
ACI 318: 26.5, 26.12
ACI 318: 17.8.2.4,
ACI 318: 17.8.2
X
X
X
X
X
X
X
ACI 318: 26.11.2
1908.9
1908.6, 1908.7, 1908.8
1908.10
3. INSPECT ANCHORS CAST IN CONCRETE.
2. REINFORCING BAR WELDING:
1. INSPECTION REINFORCEMENT, INCLUDING PRESTRESSING
TENDONS, AND VERIFY PLACEMENT
TYPE
ACI 318 CH 20, 25.2,
25.3, 26.6.1-26.6.3
REFERENCED
STANDARDa
CONTINUOUS
SPECIAL
INSPECTION
X
AWS D1.4,
ACI 318: 26.6.4
IBC REFERENCE
1908.4
X
ACI 318: 17.8.2
5. VERIFY USE OF REQUIRED DESIGN MIX.
ACI 318: CH. 19,
26.4.3, 26.4.4
X
1904.1, 1904.2, 1908.2, 1908.3
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED.
ACI 318: 26.11.1.2(b)X
9. INSPECT OF PRESTRESSED CONCRETE FOR:
B. GROUTING OF BONDED PRESTRESSING TENDONS.
11. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL
OF SHORES ANDFORMS FROM BEAMS AND STRUCTURAL SLABS.
XA. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM
A706.
X
B. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16".
C. INSPECT ALL OTHER WELDS
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR
UPWARDLLY INCLINED ORIENTATIONS TO RESIST
SUSTAINED TENSION LOADS.
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT
DEFINED IN 4A.
X
X
X
PERIODIC
SPECIAL
INSPECTION
a. WHERE APPLICABLE, SEE SECTION 1705.12, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
b. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSEUD BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK.
MATERIAL TESTS.
IN THE ABSENCE OF SUFFICIENT DATA OR DOCUMENTATION PROVIDING EVIDENCE OF CONFORMANCE TO QUALITY STANDARDS FOR MATERIALS IN CHAPTERS 19 AND 20 OF ACI 318, THE BUILDING OFFICIAL SHALL REQUIRE TESTING OF MATERIALS IN ACCORDANCE WITH THE APPROPRIATE STANDARDS AND CRITERIA FOR THE MATERIAL IN CHAPTERS 19
AND 20 OF ACI 318.
REQUIRED ON
PROJECT
YES
NO
YES
YES
YES
NO
YES
NO
NO
NO
YES
NO
NO
CONCRETE PROPERTIES
4,000 PSI ≤3.0%
5.0% - 7.0%
EXTERIOR SLABS
LOCATION
28 DAY
COMPRESSIVE
STRENGTH
ENTRAINED
AIR
SLUMP MAX W/C
RATIO
INTERIOR SLABS 5,000 PSI
3" ± 1"
3" ± 1"
0.5
0.40
MICHAEL D.
ALBERTSON
O F E IS S
E
T
E R
U O
S
E T
S I
G
D
E R R
PR
E
DA KH
O
T
A
E R
O. NG
L
A
NO
N G
I N
E www.ihs.gov
Scale
Project number
Date
Drawn by
Checked by
GREAT PLAINS
AREA INDIAN
HEALTH SERVICE
OFFICE OF
ENVIRONMENTAL
HEALTH &
ENGINEERING
115 4TH AVENUE SE, ROOM 309
ABERDEEN, SD 57401
(605) 226-7451 FAX (605) 226-7689
02-22-22
12" = 1'-0"
/1
/2
:5
:0
A
M
S-1
S T
R U
C T
U R
A L G
E N
E R
A L
N O
T E
S
I B
C T
A B
L E
S
R E
P L A
C E
H E
A T
IN
G
P L A
N T
D E
S
IG
N
02-22-2022
JAB
MDA
FOUNDATIONS:
FOUNDATIONS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING
PRESSURE OF 2,000 PSF. ON EXISTING SOILS. BEFORE
CONSTRUCTION COMMENCES, SOIL BEARING CAPACITY SHALL BE
VERIFIED BY A SUBSURFACE INVESTIGATION, A CERTIFIED TESTING
LABORATORY, WHOSE REPORT SHALL INCLUDE ANALYSIS AND
RECOMMENDATIONS FOR SITE PREPARATION IN ORDER TO BEAR THE
FOUNDATION LOADS. ABOVE REPORT SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW BEFORE FOUNDATION
CONSTRUCTION BEGINS.
PLUMBING SLEEVES:
MINIMUM SLEEVE SPACING SHALL BE TWO DIAMETERS CENTER TO
CENTER TO THE LARGER SLEEVE OR 6" CLEAR BETWEEN SLEEVES,
WHICHEVER IS GREATER. PRIOR TO CONSTRUCTION SLEEVE
LOCATIONS AND SIZES SHALL BE APPROVED BY THE STRUCTURAL
ENGINEER OF RECORD.
CHEMICAL ANCHORS:
SHALL BE A POLYMER INJECTION SYSTEM SUCH AS RAMSET "EPCON",
MOLLY "PARAMOUNT HVC", SIKA "SIKADUR INJECTION SEL", "HILTI-HIGH
STRENGTH EPOXY", OR APPROVED EQUAL, INSTALLED IN
ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS.
INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
ANCHOR BOLTS:
1. SHALL BE A36 THREADED ROD. PROVIDE HOT DIP GALVANIZE
FINISH ON ALL ANCHOR BOLTS PERMANENTLY EXPOSED TO
EXTERIOR OR IN CONTACT WITH PRESSURE TREATED LUMBER.
2. THREADED ROD EMBEDMENT DEPTH SPECIFIED IN THE DRAWINGS
SHALL BE FROM TOP OF CONCRETE TO TOP OF DOUBLE NUT.
CONCRETE TESTING:
1. CONCRETE TESTING SHALL BE PAID FOR BY THE OWNER. TESTING
LABORATORY SHALL PERFORM THE FOLLOWING TEST ON CAST-IN-
PLACE CONCRETE:
A. ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF
PORTLAND CEMENT CONCRETE."
B. ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVE
STRENGTH OF CYLINDRICAL CONCRETE SPECIMENS. A
SEPARATE TEST SHALL BE CONDUCTED FOR EACH CLASS, FOR
EVERY 50 CUBIC YARDS (OR FRACTION THEREOF), PLACED PER
DAY. REQUIRED CYLINDER(S) QUANTITIES AND TEST AGE AS
FOLLOWS:
a. AT 7 DAYS
b. AT 28 DAYS
C. PROVIDE ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED
UNDER THE DIRECTION OF THE ENGINEER, IF REQUIRED. IF 28
DAY STRENGTH IS ACHIEVED, THE ADDITIONAL CYLINDER(S)
MAY BE DISCARDED.
D. TESTING SHALL BE BASED UPON CONCRETE TAKEN AT POINT OF
PLACEMENT.
E. IN ADDITION TO TYPICAL TESTING REQUIREMENTS, SLUMP AND
AIR CONTENT SAMPLES SHALL BE TAKEN AT BEGINNING OF
FIRST TRUCK PRIOR TO ANY PLACEMENT AND REPEATED AT THE
MIDDLE OF FIRST TRUCK. CONCRETE PLACEMENT SHALL NOT
START IF INITIAL TEST(S) FAIL AND SHALL NOT CONTINUE OF
TEST TAKEN AT MIDDLE OF FIRST LOAD FAILS.
F. IF ANY SLUMP OR AIR CONTENT FAILS DURING PLACMENT, TESTS
SHALL BE IMMEDIATELY REPORTED AND RETAKEN. IF RETAKEN
TESTS FAIL THEN ALL SUBSEQUENT LOADS MUST BE TESTED AT
ARRIVAL AND TEST MUST SHOW COMPLIANCE PRIOR TO THE
CONCRETE IN THAT TRUCK BEING ALLOWED FOR USE ON
PROJECT. ALL COSTS FOR ADDITIONAL TESTING SHALL BE
CREDITED TO THE OWNER.
PENETRATIONS:
NO PENETRATIONS SHALL BE MADE IN ANY STRUCTURAL MEMBERS
OTHER THAN THOSE LOCATED ON THESE DRAWINGS WITHOUT
PREVIOUS APPROVAL OF THE ENGINEER.
CONCRETE MIX DESIGN:
1. SHALL BE MIX DESIGNED BY A RECOGNIZED TESTING
LABORATORY TO ACHIEVE A STRENGTH AT 28 DAYS AS LISTED
BELOW WITH A PLASTIC AND WORKABLE MIX:
2. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDER OR
LAB TESTS FOR REVIEW PRIOR TO USE. MIX SHALL BE UNIQUELY
IDENTIFIED BY MIX NUMBER OR OTHER POSITIVE IDENTIFICATION.
CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF
ASTM STANDARD C94 FOR MEASURING, MIXING, TRANSPORTING,
ETC. CONCRETE TICKETS SHALL BE TIME STAMPED WHEN
CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM THE
TIME THE MIXING WATER IS ADDED UNTIL IT IS DEPOSITED IN ITS
FINAL POSITION SHALL NOT EXCEED ONE AND ONE HALF (1-1/2)
HOURS. IF FOR ANY REASON THERE IS A LONGER DELAY THAN
STATED ABOVE, THE CONCRETE SHALL BE DISCARDED. IT SHALL
BE THE RESPONSIBILITY OF THE TESTING LAB TO NOTIFY THE
OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY
NONCOMPLIANCE WITH THE ABOVE. ALL SLABS SHALL BE CURED
USING CURING COMPOUND MEETING ASTM STANDARD C309 TYPE
1 AND SHALL HAVE A FUGITIVE DYE. THE COMPOUND SHALL BE
PLACED AS SOON AS THE FINISHING IS COMPLETED OR AS SOON
AS THE WATER HAS LEFT THE UNFINISHED CONCRETE. ALL
SCUFFED OR BROKEN AREAS IN THE CURING MEMBRANE SHALL
BE RECOATED DAILY. CALCIUM CHLORIDES SHALL NOT BE
UTILIZED; OTHER ADMIXTURES MAY BE USED ONLY WITH THE
APPROVAL OF THE ENGINEER.
3. COARSE AND FINE AGGREGATES SHALL COMPLY WITH ASTM C33
AND ACI 302.1, CURRENT VERSIONS.
a. COMPLIANCE WITH THE NON-REACTIVE REQUIREMENTS OF
ACI 302.1 SHALL NOT BE PROVIDED FOR BY THE PROVISION OF
ACI 302.1 (SUBSECTION 7.3) THAT EXCLUDES THE
AGGREGATES BEING CLASSIFIED AS DELETERIOUSLY
REACTIVE WITH ALKALIES IF THE AGGREGATE HAS A
SATISFACTORY SERVICE RECORD EVALUATION OR WITH THE
ADDITION OF A MATERIAL THAT HAS SHOWN TO PREVENT
HARMFUL EXPANSION DUE TO ALKALI-AGGREGATE REACTION.
b. CONCRETE MIX DESIGN SHALL INCLUDE TEST RECORDS OF
THE COMPLIANCE OF THE AGGREGATE MEETING THE
REQUIREMENTS OF ASTM C1260, AND THAT THE EXPANSION
OF THE MORTAR SAMPLE SHALL NOT EXCEED 0.10% WHEN
TESTED IN ACCORDANCE WITH ASTM C1260 AT 14 DAYS. USE
OF ADMIXTURES THAT MITIGATE THE EFFECT OF THE
REACTIVE AGGREGATE TO BE PROPOSED IN CONCRETE MIX
SHOP DRAWING MAY BE AN APPROVED APPROACH BY THE
ENGINEER TO ALLOW FOR THE USE OF OTHERWISE REACTIVE
AGGREGATES. IF SUCH MITIGATING MEASURES ARE
PROPOSED, THEY MUST BE INCLUDED WITHIN MIX DESIGN
SUBMITTAL. THE ENGINEER IS GIVEN DISCRETION AS TO
WHETHER OR NOT TO ACCEPT MITIGATING MEASURES OR TO
MAINTAIN REQUIREMENTS THAT NONREACTIVE AGGREGATES
MUST BE USED. AT A MINIMUM, SUCH DOCUMENTATION MUST
SHOW THAT REACTIVE AGGREGATES USED IN COMBINATION
WITH A GIVEN AMOUNT OF ADMIXTURE RESULTS IN THE
EXPANSION OF THE MORTAR SAMPLE BEING LESS THAN 0.10%
WHEN TESTED IN ACCORDANCE WITH ASTM C1567 AT 14 DAYS.
LIABILITY OF THE PERFORMANCE OF THE CONCRETE MIX
REMAINS SOLELY WITH GENERAL CONTRACTOR.
c. IF CONCRETE MIXES ARE APPROVED BY THE ENGINEER THAT
CONTAIN EITHER FINE OR COARSE AGGREGATE, THAT EITHER
SEPARATELY OR IN COMBINATION EXCEED THE 0.10%
EXPANSION WHEN TESTED ACCORDING TO ASTM C1260,
SPECIAL CONSIDERATIONS MUST BE GIVEN TO SLAB CURING
(SLABS ON GRADE AND ELEVATED SLABS). IN SUCH
INSTANCES SLABS SHALL BE CURED USING EITHER A WET
BURLAP OR CONTINUOUS WETTING/FOGGING METHOD FOR
SLABS FOR AT LEAST 10 DAYS. USE OF CURING AND/OR
SEALING COMPOUNDS IS NOT ACCEPTABLE UNTIL THE SLAB
HAS CURED A MINIMUM OF 28 DAYS AND THE CONDITIONS FOR
THE APPLICATION OF THE CURING COMPOUND ON THE
CONCRETE SLAB SET BY THE MANUFACTURER’S
RECOMMENDATIONS HAVE BEEN MET.
d. ENGINEER HAS SOLE DISCRETION IN DETERMINING
ACCEPTABILITY OF A CONCRETE SLAB THAT IS EXHIBITING
ALKALI-SILICA REACTION. FOR SLABS SHOWING AN ALKALI
SILICA REACTION SOLELY WITHIN THE FINE AGGREGATE: A
SLAB SHOWING AN AVERAGE DENSITY OF POPOUTS GREATER
THAN 1 PER 8 SQUARE FEET OVER ANY CONTIGUOUS AREA OF
100 SQUARE FEET OR LARGER, OR ANY AREA WITH A DENSITY
OF 1 POPOUTS PER 2 SQUARE FEET WITHIN ANY AREA UP TO
100 SQUARE FEET WOULD BE CONSIDERED AS A BASIS FOR
THE REJECTION OF THE SLAB FROM WHICH THOSE SAMPLE
AREAS ARE INCLUDED. FOR A ALKALI SILICA REACTION
WITHIN THE COARSE AGGREGATE: THE POPOUT DENSITIES
CONSIDERED FOR REJECTION OF THE CONCRETE SLAB SHALL
BE ½ OF THE DENSITIES GIVEN FOR FINE AGGREGATE. THE
EXTENT OF REJECTED SLAB TO BE DETERMINED BY
ENGINEER. THE TIME FRAME FOR OBSERVATION OF ALKALI
SILICA REACTIONS AND DETERMINATION OF REJECTION OF
THE CONCRETE SLAB SHALL BE AT LEAST 56 DAYS FROM THE
DATE OF POUR.
e. CONCRETE MIXES UTILIZING CRUSHED LIMESTONE AS COARSE
AGGREGATE AND CONTAINING AT LEAST 25% CLASS F FLY ASH
AND HAVING A SATISFACTORY SERVICE RECORD PER ACI 302.1
IS CONSIDERED AN ACCEPTABLE ALTERNATIVE APPROACH TO
THE COMPLIANCE REQUIREMENTS OUTLINED IN PROVISIONS
4a THROUGH 4d ABOVE.
4. THE CONCRETE STRENGTHS SHOWN IN THE SECTION ABOVE AND
IN THE SPECIFICATIONS ARE MINIMUM COMPRESSIVE STRENGTHS.
THE ENGINEER SHALL DETERMINE IF THE CONCRETE IS
ACCEPTABLE, OR TO BE REMOVED, OR TO RECEIVE SPECIAL
CURING IF THE COMPRESSIVE STRENGTHS ARE LESS THAN
SPECIFIED.
5. ALL CONCRETE EXPOSED TO WEATHER OR EARTH SHALL BE AIR
ENTRAINED TO 5% TO 7%.
6. WATER REDUCING AGENTS MAY BE USED IN THE CONCRETE MIX.
PLASTICIZERS AND SUPER-PLASTICIZERS MAY BE USED ONLY
WHEN WRITTEN PERMISSION OF THE ENGINEER IS GIVEN.
7. NO SALTS OF ANY KIND MAY BE USED IN CONCRETE BEFORE
OBTAINING THE ENGINEER'S WRITTEN PERMISSION FOR THEIR
USE.
SPECIAL INSPECTION AND TESTING:
1. SEE DETAILED INSPECTION AND TESTING REQUIREMENTS AS
INDICATED ON THIS SHEET.
DESIGN CODES:
• 2018 INTERNATIONAL BUILDING CODE.
• ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE AND COMMENTARY.
• ASCE 7-16 MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR
BUILDINGS AND OTHER STRUCTURES.
CONCRETE AND REINFORCING PLACEMENT:
1. ALL CONCRETE SHALL BE PLACED IN ACCORDANCE WITH ACI 301
AND ACI 117 EXCEPT AS MODIFIED BELOW:
A. ACI 117 ITEM 4.3.1.1 ELEVATIONS OF SLABS-ON-GRADE TOP OF
SLAB ELEVATION SHALL BE WITHIN A 3/8" ENVELOPE EITHER
SIDE OF THE THEORETICAL DESIGN SURFACE.
B. ACI 117 ITEM 4.5.7 FLOOR FINISH TOLERANCES AS MEASURED
BY PLACING A FREESTANDING (UNLEVELED) 10 FT.
STRAIGHTEDGE ANYWHERE ON THE SLAB AND ALLOWING IT
TO REST UPON TWO HIGH SPOTS WITHIN 28 DAYS AFTER
SLAB CONCRETE PLACEMENT. THE GAP AT ANY POINT
BETWEEN THE STRAIGHT EDGE AND THE FLOOR SHALL NOT
EXCEED 1/4".
2. ALL REINFORCING STEEL TO BE ASTM A615, GRADE 60 (#4 AND
LARGER), EXCEPT WHERE NOTED OTHERWISE. REINFORCING
SHALL NOT BE WELDED
3. WELDED WIRE FABRIC TO CONFORM TO ASTM A185 AND SHALL
BE FREE FROM OIL, SCALE, AND RUST. PLACE WWF IN
ACCORDANCE WITH THE TYPICAL PLACING DETAILS OF ACI
STANDARDS AND THE SPECIFICATIONS. MINIMUM LAPS SHALL BE
ONE SPACE PLUS 2"
4. ALL REINFORCING STEEL BARS TO BE DETAILED AND PLACED IN
ACCORDANCE WITH THE LATEST ACI MANUALS.
5. LAP ALL REINFORCING SPLICES IN CONCRETE A MINIMUM OF 48
BAR DIAMETERS OR 24 INCHES, WHICHEVER IS GREATER,
UNLESS NOTED OTHERWISE ON DRAWINGS (CLASS B SPLICE).
6. PROVIDE CORNER BARS OF SAME BAR DIAMETER AS SPECIFIED
FOR THE WALL, BEAM OR FOOTING. PROVIDE MINIMUM OF 40 BAR
DIAMETER LAP FOR ALL CORNER BARS, UNLESS NOTE
OTHERWISE.
7. PROVIDE FOUNDATION DOWELS AS SHOWN. MINIMUM SIZE
DOWELS TO BE #4, UNLESS OTHERWISE NOTED. ALL VERTICAL
REINFORCING STEEL IN COLUMNS AND PIERS, OR VERTICAL
REINFORCING IN WALLS, SHALL BE DOWELED INTO THE
FOOTINGS WITH SAME SIZE AND QUANTITY DOWEL AS THE
VERTICAL REINFORCING.
8. WHERE SHOWN ON THE DRAWINGS, PROVIDE WELD PLATES,
WELDMENTS, OR CONCRETE INSERTS FOR FASTENING AND
SECURING OTHER COMPONENTS. CONCRETE INSERTS SHALL BE
FURNISHED BY THE CONTRACTOR REQUIRING THEM AND
INSTALLED BY THE CONTRACTOR CASTING THE CONCRETE
AROUND THEM. CLIP ANGLES SHALL BE FURNISHED BY THE
CONTRACTOR REQUIRING THEM.
9. REINFORCING STEEL SHALL RECEIVE CONCRETE COVER AS
FOLLOWS:
DESCRIPTION MINIMUM COVER
CAST AGAINST & PERMANENTLY 3"
EXPOSED TO EARTH
EXPOSED TO EARTH OR WEATHER
#6 THROUGH #18 BARS 2"
#5 BARS OR SMALLER 1 1/2"
NOT EXPOSED TO EARTH OR WEATHER
OR IN CONTACT WITH THE GROUND, SLABS
AND WALLS
#11 BARS OR SMALLER 3/4"
#14 AND #18 1 1/2"
BEAMS AND COLUMNS 1 1/2"
SHELLS, FOLDED PLATE MEMBERS:
NO. 6 BAR AND LARGER 3/4"
NO. 5 BAR, W31 OR D31 WIRE AND SMALLER 1/2"
10. PROVIDE TWO (2) #5'S, ONE AT EACH FACE, UNLESS NOTED
OTHERWISE, AROUND ALL OPENINGS GREATER THAN 12"x12" IN
CAST-IN-PLACE CONCRETE. EXTEND REINFORCING 2'-0" BEYOND
OPENING IN BOTH DIRECTIONS. CONTACT ENGINEER FOR ALL
OPENINGS GREATER THAN 12"x12" FOR DESIGN.
11. COLD WEATHER AND HOT WEATHER PROVISIONS OF ACI 306 AND
305 (CURRENT EDITIONS), RESPECTIVELY, SHALL BE MAINTAINED.
12. UNLESS NOTED OTHERWISE ALL UNDER SLAB VAPOR
RETARDERS SHALL CONFORM TO THE REQUIREMENTS OF ASTM
1745 CLASS A AND SHALL BE INSTALLED AS PER
MANUFACTURER'S RECOMMENDATIONS.
GENERAL NOTES:
1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH
JOB SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL,
ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT THESE
DRAWINGS FOR SLEEVES, DEPRESSIONS AND OTHER DETAILS NOT
SHOWN ON STRUCTURAL DRAWINGS.
2. ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD.
ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF
THE ENGINEER BEFORE PROCEEDING WITH THE AFFECTED PART
OF THE WORK.
3. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND
STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE
CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE ERECTION
PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE
BUILDING AND ITS COMPONENTS DURING ERECTION. THIS
INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
TEMPORARY BRACING (AND ACCOMPANYING FOOTINGS), GUYS OR
TIE-DOWNS.
4. ADDITIONAL OBSERVATIONS AS A RESULT OF REJECTION OF WORK
COMPLETED AND/OR ADDITIONAL OBSERVATIONS DUE TO THE
DEFICIENCIES IN WORK OBSERVED WILL BE AT THE EXPENSE OF
THE CONTRACTOR.
5. ALL STRUCTURAL SHOP DRAWINGS TO BE REVIEWED BY JOB
SUPERINTENDENT IN ADDITION TO ALL PERSONNEL DEEMED
NECESSARY BY CONTRACTOR PRIOR TO SUBMITTAL TO ENGINEER
FOR APPROVAL.
1 100% CD SUBMITTAL 02-02-22
J
J
J.3
J.3
0.1 0.1
1 1
2 2
BOILER EQUIPMENT PAD
PAD TYPE 1
PUMP EQUIPMENT PAD
PAD TYPE 2
F.6 F.6
POT FEEDER EQUIPMENT PAD
PAD TYPE 1
16' - 0"
14' - 8"
14' - 8"
14' - 8"
2' - 0"
(5) #5 LONG DIRECTION
ANCHOR BOLT SIZE &
LOCATIONS BY EQUIPMENT
SUPPLIER, PROVIDE
DOUBLE NUT AT BASE
1/2" ISOLATION
JOINT & CAULK
(E) CONC SLAB-ON-GRADE
TO REMAIN
EQUIPMENT FOOTPRINT
3"⌀x3" DEEEP
SLEEVE, FILL W/
NON-SHRINK GROUT
TYP
6"
MIN
T Y
P
M
IN
W
S E
E P
L A
N F
O R
B O
D
L
SEE PLAN FOR BOD
(16) #5 SHORT DIRECTION
P E
R M
E C
H
3/4"x3/4" CHAMFER
A
A
SECTION A-A
C L R
(5) #5 LONG DIRECTION
TOP & BOT
ANCHOR BOLT SIZE &
LOCATIONS BY EQUIPMENT
SUPPLIER, PROVIDE
DOUBLE NUT AT BASE
1/2" ISOLATION
JOINT & CAULK
(E) CONC SLAB-ON-GRADE
TO REMAIN
EQUIPMENT FOOTPRINT
3"⌀x3" DEEP SLEEVE
FILL W/ NON-SHRINK
GROUT
TYP
6"
MIN
T Y
P
M
IN
W
S E
E P
L A
N F
O R
B O
D
L
SEE PLAN FOR BOD
(13) #5 SHORT DIRECTION
TOP & BOT
P E
R M
E C
H
3/4"x3/4" CHAMFER
A
A
SECTION A-A
C L R
MICHAEL D.
ALBERTSON
O F E IS S
E
T
E R
U O
S
E T
S I
G
D
E R R
PR
E
DA KH
O
T
A
E R
O. NG
L
A
NO
N G
I N
E www.ihs.gov
Scale
Project number
Date
Drawn by
Checked by
GREAT PLAINS
AREA INDIAN
HEALTH SERVICE
OFFICE OF
ENVIRONMENTAL
HEALTH &
ENGINEERING
115 4TH AVENUE SE, ROOM 309
ABERDEEN, SD 57401
(605) 226-7451 FAX (605) 226-7689
02-22-22
As indicated
/1
/2
:5
:0
A
M
S-2
F O
U N
D A
T
IO
N P
L A
N
R E
P L A
C E
H E
A T
IN
G
P L A
N T
D E
S
IG
N
02-22-2022
JAB
MDA
1/4" = 1'-0"
HEATING PLANT CONC PADS
3/4" = 1'-0"
TYP EQUIPMENT PAD TYPE 1 DETAIL
3/4" = 1'-0"
TYP EQUIPMENT PAD TYPE 2 DETAIL
1 100% CD SUBMITTAL 02-22-22
DESCRIPTION
DIAMETER
CONDENSATE DRAIN, DRAIN
⌀, DIA.
BTU(H)
CD
DB
ABBREVIATION
FLEXIBLE CONNECTION
DEGREES FAHRENHEIT
ENTERING DRY BULB
HEATING
GALVANIZED
FULL LOAD AMPS
EDB
°F
FLA
HTG
GALV.
FC
TYPICAL
SQUARE FEET
STAINLESS STEEL
RUNNING LOAD AMPERESRLA
TYP.
SQ FT
BRITISH THERMAL UNITS (PER HOUR)
DRY BULB (DEGREES FAHRENHEIT)
MECHANICAL ABBREVIATIONS
BHP BRAKE HORSEPOWER
CENTRAL CONTROL PANELCCP
ENTERING AIR TEMPERATUREEAT
HORSEPOWERHP
REVOLUTIONS PER MINUTERPM
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ANSI AMERICAN NATIONAL STANDARD INSTITUTE
TOP OF CONCRETETOC
HEATING HOT WATER SUPPLYHHWS
HEATING HOT WATER RETURNHHWR
NATURAL GASG
GLYCOL SUPPLYGS
GLYCOL RETURNGR
UNLESS OTHERWISE NOTEDUON
DIFFERENTIAL PRESSUREDP
INCHES WATER GAUGEIN. W.G.
VARIABLE FREQUENCY DRIVEVFD
DCW DOMESTIC COLD WATER
BFP BACKFLOW PREVENTER
INSTANTANEOUS WATER HEATERIWH
CUBIC FEET PER HOURCFH
EFFICIENCYEFF
EXISTING
ENTERING WET BULB
EXHAUST AIR
EXTERNAL STATIC PRESSURE
EWB
EA
EWT
ESP
(E), EXIST.
ENTERING WATER TEMPERATURE
FEETFT
GALLONS PER MINUTEGPM
POUNDSLBS
MAXIMUM
MINIMUM
NIPPLE PIPE THREAD
OUTSIDE AIR
LOCKED ROTOR AMPERES
POINT OF CONNECTION
MAX.
LWB
LRA
MIN.
OA
NPT
MBH
, POC
LDB
THOUSAND BRITISH THERMAL UNITS PER HOUR
LEAVING DRY BULB IN DEGREES FAHRENHEIT
LEAVING WET BULB IN DEGREES FAHRENHEIT
LEAVING AIR TEMPERATURELAT
MFR MANUFACTURER
NEW(N)
PRESSURE REDUCING VALVEPRV
NET POSITIVE SUCTION HEADNPSH
PRESSURE DIFFERENTIAL TRANSMITTERPDT
POUNDS PER SQUARE INCH GAUGEPSIG
SS
MECHANICAL GENERAL NOTES
COMPRESSED AIRCA
INCHES WATER GAUGEIN. W.C.
1. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, SPECIFICATIONS, LOCAL
ORDINANCES AND INDUSTRY STANDARDS.
2. VERIFY EXACT LOCATION OF ALL EQUIPMENT AND PIPING. NOTIFY COR IMMEDIATELY
OF ANY DISCREPANCIES BETWEEN SYSTEMS AND DRAWINGS.
3. COORDINATE EXACT LOCATION OF EQUIPMENT AND ALL PENETRATIONS THROUGH
ROOF, FLOORS AND WALLS WITH ARCHITECTURAL, STRUCTURAL SYSTEMS PRIOR TO
COMMENCING WORK.
4. DUCT SIZES DENOTE INSIDE DIMENSION UNLESS OTHERWISE INDICATED.
5. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
INTERNATIONAL MECHANICAL CODE.
6. ALL FIRE RATED CONSTRUCTION SHALL MEET THE REQUIREMENTS IN NFPA 90A. FIRE
DAMPERS SHALL HAVE A FIRE RATING OF 1 1/2 HOURS IN ACCORDANCE WITH THE
LATEST EDITION OF UL555, ONLY FOR WALL RATING OF 2 HOURS, PER CODE.
7. CONTRACTOR SHALL MAINTAIN A MINIMUM OF 1 BOILER IN OPERATION AND
ASSOCIATED PIPING DURING CONSTRUCTION. INTENT IS TO HAVE ABILITY OF BOILER
SYSTEM TO PROVIDE 200 °F HEATING SUPPLY WATER AT ALL TIMES DURING
CONSTRUCTION FOR HYDRONIC HEATING REQUIREMENTS AND DOMESTIC HOT
WATER NEEDS.
SEE STRUCTURAL DRAWINGSSSD
FUEL OIL SUPPLY
FUEL OIL RETURNFOR
FOS
NOT TO SCALEN.T.S, NTS
BAS BUILDING AUTOMATION SYSTEM
MCA MINIMUM CIRCUIT AMPACITY
BMS BUILDING MANAGEMENT SYSTEM
MAXIMUM OVERLOAD CURRENT PROTECTIONMOCP
PROPOSED PHASING PLAN
THE FOLLOWING PHASING PLAN OUTLINES ONE APPROACH TO COMPLETION OF THE
REQUIRED SERVICES. THIS IN NO WAY REPRESENTS A COMPLETE, OR DETAILED,
PHASING PLAN. IT IS INTENDED ONLY TO OUTLINE THE HIGH-LEVEL TASKS TO BE
COMPLETED.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A DETAILED PHASING PLAN FOR IHS
REVIEW AND APPROVAL. THE FOLLOWING RESTRICTIONS SHALL BE STRICTLY ADHERED
TO:
A. AT ALL TIMES, AT LEAST ONE BOILER AND ASSOCIATED HYDRONIC ACCESSORIES
MUST REMAIN IN FULL OPERATION TO SERVE THE FACILITY HEATING AND
DOMESTIC HEATING REQUIREMENTS.
B. UNDER NO CIRCUMSTANCES SHALL ANY UTILITY (ELECTRICAL, WATER, FUEL OIL,
ETC) BE DISCONNECTED WITHOUT PRIOR WRITTEN APPROVAL FROM THE IHS
PROJECT MANAGER.
C. THE EXISTING FUEL OIL SYSTEM SHALL REMAIN OPERATIONAL THROUGHOUT THE
PROJECT CONSTRUCTION (WITH THE EXCEPTION OF MINIMAL SCHEDULED
OUTAGES).
D. PRIOR TO PREPARING AND SUBMITTING THE PHASING PLAN, CONTRACTOR SHALL
COORDINATE WITH IHS TO DETERMINE THE NUMBER OF DAYS THEY REQUIRE FOR
OUTAGE NOTICES, ETC., AND INCORPORATE THIS INTO THE DETAILED PHASING
PLAN.
PHASE 1 REMOVE EXISTING BOILERS (B-1 AND B-2) AND INSTALL NEW BOILERS (B-1
THRU B-3)
IT IS SUGGESTED THAT BOILER (E) B-2 IS REMOVED FIRST TO ALLOW ROOM TO INSTALL
THE NEW BOILERS WHILE BOILER (E)B-1, DT-3, REMAIN IN OPERATION.
1. DEMOLISH BOILER (E) B-2. KEEP (E) B-1, DHW HEATER AND ASSOCIATED
CIRCULATION PUMP OPERATIONAL.
2. MODIFY EQUIPMENT PADS AND DRAINS, ONCE BOILER IS COMPLETELY REMOVED.
3. INSTALL BOILER (N) B-3.
4. INSTALL PIPING, FLUES, PRIMARY AND SECONDARY PUMPS. KEEP (E) PUMPS IN
OPERATION UNTIL FINAL TIE-IN. IHS ALLOWS 1 HOUR DOWNTIME OF HOT WATER
SYSTEM FOR TIE-INS. COORDINATE WITH IHS IF MORE TIME IS REQUIRED.
5. INSTALL ELECTRICAL POWER SUPPLIES AND CONTROLS.
6. MODIFY MAKE-UP WATER CONNECTIONS TO THE BOILERS.
7. ISOLATE HWH-2, ISO VALVE, FUEL OIL SUPPLY, BUTTERFLY VALVES, ELECTRICAL
AND CONTROLS, FLUE ETC.. REMOVE DHWS-2 AND ALL ASSOCIATED PIPING. ONCE
(N) HWS IS INSTALLED AND VERIFIED TO BE OPERATIONAL, REPEAT FOR HWH-1
AND ASSOCIATED PIPING.
8. MAKE TIE-IN CONNECTIONS TO BOILER B-3. KEEP (E) B-1 OPERATIONAL.
9. VALVE OFF BOILER (E) B-1. DEMOLISH (E) B-1. SWITCH OVER TO (N) B-3 OPERATION
10. START UP BOILER (N) B-3 AND ASSOCIATED PRIMARY AND SECONDARY PUMPS.
MAKE FINAL CONNECTIONS AND TIE-INS.
11. ONCE SYSTEM IS UP AND RUNNING, PROCEED TO DEMOLISH (E) BOILER B-1 IN
SIMILAR FASHION AS (E) B-2 ABOVE.
12. INSTALL BOILER (N) B-2 AND (N) B-1 SIMILAR TO AS DESCRIBED ABOVE. RUN FUEL
SUPPLY OVER TO BOILER (N) B-2 AND (N) B-1 AND (N) B-3.
PHASE 2: START-UP TESTING AND BALANCING
TEST OPERATION OF EACH BOILER B-1, B-2 AND B-3 AND ASSOCIATED PRIMARY AND
SECONDARY PUMPS. ENSURE BOILERS AND ALL ASSOCIATED CONTROL SYSTEMS ARE
ABLE TO OPERATE UNDER BMS CONTROL. TEST BOILERS THROUGH ALL SEQUENCES AS
INDICATED ON THE DRAWINGS. TESTING OF SECONDARY PUMPS SHALL BE PERFORMED
PER THE SEQUENCE OF OPERATION TO THE SATISFACTION OF THE IHS.
TEST DOMESTIC HOT WATER STORAGE TANKS AND ASSOCIATED CIRCULATING PUMPS
INCLUDING TEMPERATURE SETPOINT CONTROL, PUMP OPERATION AND THREE WAY
VALVES MODULATION AND LEAD LAG & FAIL SEQUENCES.
TEST DDC CONTROLS AND BURNER MANAGEMENT INTEGRATION PER THE SEQUENCE
OF OPERATION.
ADDITIONAL TESTS ARE REQUIRED PER THE SPECIFICATIONS. TESTING SHALL BE
PERFORMED TO THE EXTENT NECESSARY TO DEMONSTRATE TO THE SATISFACTION OF
THE IHS THAT THE SYSTEM IS IN COMPLETE WORKING ORDER.
TOTAL ENCLOSED FAN COOLEDTEFC
METASYS USER INTERFACEMUI.
PRESSURE & TEMPERATURE
VALVE IN RISER (TYPE AS
INDICATED OR NOTED)
VENT , VENT RISER , VENT
THRU ROOF
VALVE WITH MOTOR ACTUATOR
PITCH DOWN IN
DIRECTION OF FLOW
& TEMPERATURE RELIEF VALVE
PLUMBING LEGEND cont'd
EXISTING TO BE REMOVED
FROM BELOW , TO BELOW
FROM ABOVE , TO ABOVE
FLUSH VALVE
FLOW IN DIRECTION OF ARROW
ECCENTRIC REDUCER
FLEXIBLE CONNECTOR
GRADE CLEANOUT
GLOBE VALVE
FLOOR SINK
FIXTURE UNIT
FLOOR DRAIN
FLOOR CLEANOUT
DRINKING FOUNTAIN
DIAMETER
(FB) , (TB)
(FA) , (TA)
FV
GL.V.
GCO
FU
FS
FD
FCO
FC
(E)
ER
DF
TYP. TYPICAL
V , VR , VTR
WCO
V
AV
UN
WALL CLEANOUT
VENT PIPING
UNION OR FLANGE
TWS
TH
TP
TWS
SOV
R , D
THERMOMETER
TRAP PRIMER
TEMPERED WATER SUPPLY
SHUTOFF VALVE, BALL TYPE.
RISE OR DROP
RISER UP (ELBOW)
RISER DOWN (ELBOW)
DEGREES FAHRENHEIT
CONCENTRIC REDUCER
COLD WATER HEADER, HOT WATER
CORRUGATED METAL PIPE
ATMOSPHERIC VENT
(STEAM OR HOT VAPOR)
ACCESS DOOR , ACCESS PANEL
ABOVE FLOOR , BELOW FLOOR
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
CALIBRATED BALANCE VALVE
BACKFLOW PREVENTER
AUTOMATIC AIR VENT
BRANCH - TOP CONNECTION
BRANCH - BOTTOM CONNECTION
BRANCH - SIDE CONNECTION
CAP ON END OF PIPE
PLUMBING LEGEND
CARBON DIOXIDE PIPING
CENTER LINE
DOMESTIC COLD WATER
CHECK VALVE
CLEANOUT PLUG
BUTTERFLY VALVE
BALANCE VALVE, CIRCUIT SETTER
AQUASTAT
AREA DRAIN
ANGLE VALVE
DESCRIPTION
ABOVE CEILING
AQ
CWH, HWH, VH
CMP
CO
CL
CR
DCW
CO
CKV
CO
CO2
or
ATV
CO2
BFV
CBV
COP
BV
BFP
AD
ATV
AAV
AF , BF
SYMBOL
ABC
AFF
AFG
ANV
AD , AP
ABBREVIATION
RET
OR
S
P & TRV
PD
RV or P&TRV
P & TRV
PG
PD
PRV
(NTS)
POC
PT
AN
PG
PRESSURE GAUGE
PUMP DISCHARGE LINE
RELIEF VALVE OR PRESSURE
PRESSURE REDUCING VALVE
RETURN
NOT TO SCALE
PLUGGED TEE
PIPE ANCHOR
POINT OF CONNECTION
PIPE GUIDE
(N) , (E) NEW , EXISTING
DHW
HB
DHWR
HV
SYMBOL ABBREVIATION
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER PIPING
HOSE BIBB
HAND VALVE
DESCRIPTION
CD CONDENSATE DRAIN
°F
PREFABRICATED BEDSIDE PBPU
AMERICAN DISABILITIES ACTA.D.A.
FIRE HOSE CABINETFHC
HEADER, VENT HEADER
PATIENT UNIT
RELIEF VALVE PIPING
GALLONS PER FLUSH
GALLONS PER MINUTE
GAGE COCK
GPF
GPM
GCK
COMPRESSED AIR PIPINGCA CA
TWR TWR TEMPERED WATER RETURN
VAC VAC VACUUM PIPING
LEGEND
EXISTING
DEMOLITION WORK
NEW WORK
T
BALL VALVE
GATE VALVE
DDC SENSOR W/ THERMOWELL
TEMPERATURE GAUGE
MIXING VALVE
MECHANICAL SYMBOLS
S T
A
T E
O F CA L I FOR N
I A
EXP.________
M 34008 3-31-2022
R
EG
IS
TE
RED
PROFESS IONAL
ENG
IN
E
ER
S
H A N E P A R
K
M E C H A N I C A
L www.ihs.gov
Scale
Project number
Date
Drawn by
Checked by
GREAT PLAINS
AREA INDIAN
HEALTH SERVICE
OFFICE OF
ENVIRONMENTAL
HEALTH &
ENGINEERING
115 4TH AVENUE SE, ROOM 309
ABERDEEN, SD 57401
(605) 226-7451 FAX (605) 226-7689
K. F. DAVIS ENGINEERING, INC.
530 LA GONDA WAY,
SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
N.T.S
PE STAMP:
/2
/2
:2
:3
P
M
M-1
M E
C H
A N
IC
A
L S
Y M
B O
L S
A
B B
R E
V
IA
T
IO
N S
A N
D G
E N
E R
A L
N O
T E
S
R E
P L
A C
E H
E A
T
IN
G P
L A
N T
02/22/2022
A. SHRESTHA
S. PARK
FIRETUBE BOILER SCHEDULE
TAG SERVICE MODEL
BOILER
TYPE
INPUT
BOILER
CAPACITY
MBH MBH
BOILER
HP
TYPE FUEL
FUEL OIL
(GPH)
BOILER BOILER
MIN.
FLOW
MAX.
FLOW
(GPM)
BLOWER
MOTOR
(HP)
OIL PUMP
MOTOR HP
(NO.2 OIL)
HEATING
SURFACE
(SQ. FT.)
B-1
HEATING HW,
DOMESTIC HW ALDRICH
CLASSIC
SERIES A3W4 5,040 4,184 125
FUEL OIL
#2 36 180 200 200 502 5 3/4 508
B-2
FIRE TUBE
WATER
BOILER
FUEL OIL
#2 180 200 200 502 5 3/4
VENT
STACK DIA.
(FLANGED)
(IN.)
PRV
(IN.)
DRAIN
(IN.)
WATER
RETURN
150#
ANSI FLANGE
WATER
OUTLET
150#
ANSI FLANGE
NORMAL
WATER WT
(LBs)
WINTER
AMBIENT
AIR ◦F
SUMMER
AMBIENT
AIR ◦F
ALTITUDE
(FT.)
LENGTH
(IN.)
WIDTH
(IN.)
HEIGHT
(IN.)
FRONT
TUBE
REMOVAL
12 2 1-1/2 4 4 5850 -7 92 3,240 164 34 80 103
12 2 1-1/2 4 4 5850 -7 92 3,240
(IN.)
EWT (◦F) LWT (◦F)
(GPM)
FIRETUBE BOILER SCHEDULE (CONTD.)
PRIMARY PUMP SCHEDULE
TAG LOCATION
PUMP
SERIES
PUMP
SIZE
PUMP
TYPE
COUPLING
TYPE
IMPELLER
SIZE
GPM
PUMP
EFFICIENCY
PUMP
RPM
ELECTRICAL
PUMP
WEIGHT
LBS
NOTES
VOLTS PH HZ
PUMP
BHP
PUMP
HP
PUMP
FLA
PUMP
MCA
BWCP-1
BOILER
ROOM
B & G SERIES 80 4x4x9-1/2 INLINE
CLOSE
COUPLED
9-1/2 275 73 1150 460 3 60 2.8 3 4.5 5.6
BWCP-2
BOILER
ROOM
B & G SERIES 80 4x4x9-1/2 INLINE
CLOSE
COUPLED
9-1/2 275 73 1150 460 3 60 2.8 3 4.5 5.6
BWCP-3
BOILER
ROOM
B & G SERIES 80 4x4x9-1/2 INLINE
CLOSE
COUPLED
9-1/2 275 73 1150 460 3 60 2.8 3 4.5 5.6
PRIMARY PUMP SCHEDULE NOTES:
WPD
FT
MFR OR
APPROVED
EQUAL
SECONDARY PUMP SCHEDULE
TAG LOCATION MODEL
PUMP
SIZE
IMPELLER
SIZE
HIGH
SPEED
(GPM)
HIGH
SPEED
WPD
(FT)
HIGH
SPEED
(RPM)
HIGH
SPEED
HP
HIGH
SPEED
FLA
HIGH
SPEED
MCA
HIGH
SPEED
MOCP
BWSP - 1A & 1B
HIGH SPEED
BOILER
ROOM ARMSTRONG
DUAL ARM 4302
0408-020 4x4x6.66 6.66 400 140 3337 25 31.00 38.80 46.5 627
TAG LOCATION
IMPELLER
SIZE
LOW
SPEED
(GPM)
LOW
SPEED
WPD
(FT)
LOW
SPEED
RPM
LOW
SPEED
BHP
LOW
SPEED
FLA
LOW
SPEED
MCA
LOW
SPEED
MOCP
300 75.00 2476 17.2 25 31 37
SECONDARY PUMP SCHEDULE NOTES:
NOTES
MFR OR
APPROVED
EQUAL
MFR OR
APPROVED
EQUAL
PUMP
WEIGHT
LBS
MFR OR
APPROVED
EQUAL
FIRE TUBE
WATER
BOILER
ALDRICH
CLASSIC
SERIES A3W4 508365,040 4,184 125
OUTPUT
BOILER
CAPACITY
B-3
FIRE TUBE
WATER
BOILER
FUEL OIL
#2
180 200 200 502 5 3/4ALDRICH
CLASSIC
SERIES A3W4 508365,040 4,184 125
12 2 1-1/2 4 4 5850 -7 92 3,240
164 34 80 103
164 34 80 103
BOILER TAG PUMP TAG
BWCP-1
BWCP-2
BWCP-3
BWSP-1A & 1B
BWSP-2A & 2B
B-1
B-2
B-3
V / P/ Hz
460 V / 3P / 60 HZ
FLA
MCA
MOCP
BURNER
POWER FLAME
MFR OR
APPROVED
EQUAL
C4 OB
MODEL
BLOWER
FAN
FLA
8.9
8.9
8.9
460 V / 3P / 60 HZ 16 20 30
460 V / 3P / 60 HZ 16 20 30
1 2 3 4 5
6 7 8
1 MOUNT ON HOUSEKEEPING PAD PER DETAIL 6/M-12
2 PROVIDE DIFFERENTIAL PRESURE TRANSDUCER ACROSS EACH PUMP
3 PUMP VFD, DISCONNECTS TO BE PROVIDED BY HVAC
4 PROVIDE LOW AND HIGH PUMP SPEED SIGNALS FOR PUMP VFDs
5 HAND-OFF-AUTO CONTROL PANEL W/RUN STATUS LIGHTS AND MANUAL POTENTIOMETER SPEED CONTROL
6 PROVIDE VFD " ENABLING" AND "DISABLING"
7 PROVIDE VFD FEEDBACK STATUS AND VFD ALARMING TO BAS
8 EACH PUMP HAS DOUBLE VOLUTE CONFIGURATION W/ TWO PUMP MOTORS AND TWO VFDS PER PUMP
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 PROVIDE COMBINATION DISCONNECT AND STARTER IN NEMA 12 ENCLOSURE
2 PROVIDE CHECK VALVE, INSTALL PER DERAIL 5/M-11.
3 PROVIDE SUCTION DIFFUSER WITH START UP SOCKS
4 PROVIDE FLOW SWITCH FOR PROOF OF FLOW
5 SYSTEM IS BEING DESIGNED FOR POSSIBLE FUTURE USE WITH GLYCOL
6 INTERLOCK PUMP START AND STOP WITH BOILER CONTROLLER. INTERFACE CONTROL POINTS WITH EXISTING BMS FOR VISIBILITY
(FUTURE)
% GLYCOL
(SEE NOTE 5)
TAG
B-1
B-2
B-3
(FUTURE)
% GLYCOL
SECONDARY PUMP GENERAL NOTE:
• THERE ARE 4 PUMPS IN TOTAL, EACH SET CONSISTS OF DOUBLE VOLUTE PUMPS, W/ 2 MOTORS & 2 VFDS EACH.
HIGH SPEED & LOW SPEED DATA SHOWN FOR INFORMATION PURPOSES ONLY.
9 SYSTEM IS BEING DESIGNED FOR POSSIBLE FUTURE USE WITH GLYCOL
460 V / 3P / 60 HZ
V / P / HZMODEL
PUMP
SIZE
1 PROVIDE BACNET MS/TP SERIAL COMMUNICATION CARDS FOR EACH BOILER BURNER MANAGMENT CONTROLS SYSTEMS
7 PROVIDE BACNET MS/TP SERIAL COMMUNICATION CARDS FOR EACH PRIMARY PUMP
BWSP - 2A & 2B
HIGH SPEED
BOILER
ROOM ARMSTRONG
DUAL ARM 4302
0408-020 4x4x6.66 6.66 400 140 3337 25 31.00 38.80 46.5 627 25
BWSP - 1A & 1B
LOW SPEED
BOILER
ROOM ARMSTRONG
DUAL ARM 4302
0408-020 4x4x6.66 6.66
BWSP - 2A & 2B
LOW SPEED
BOILER
ROOM ARMSTRONG
DUAL ARM 4302
0408-020 4x4x6.66 6.66 300 75.00 2476 17.2 25 31 37 460 V / 3P / 60 HZ
10 PROVIDE BACNET MS/TP SERIAL COMMUNICATION CARDS FOR EACH SECONDARY PUMP
NOTES
HEATING HW,
DOMESTIC HW
HEATING HW,
DOMESTIC HW
8 CONTRACTOR SHALL UTILIZE BALANCING VALVE OR TRIPLE DUTY VALVE TO SET FLOW RATES PER PUMP
11 CONTRACTOR SHALL UTILIZE BALANCING VALVE OR TRIPLE DUTY VALVE TO SET FLOW RATES PER PUMP
2 INSTALL ON HOUSEKEEPING PAD PER DETAIL 8/M-12.
GENERAL NOTES
1. FOR ALL COMMUNICATING EQUIPMENT, PROVIDE
BACNET/MSTP COMPATIBLE CARDS NEXT TO EQUIPMENT
CONTROLLER IN CONTROL PANEL IN ORDER TO FULLY
INTEGRATE/COMMUNICATE WITH THIRD PARTY DEVICES
WITH (E) JCI METASYS CONTROL SYSTEM.
S T
A
T E
O F CA L I FOR N
I A
EXP.________
M 34008 3-31-2022
R
EG
IS
TE
RED
PROFESS IONAL
ENG
IN
E
ER
S
H A N E P A R
K
M E C H A N I C A
L www.ihs.gov
Scale
Project number
Date
Drawn by
Checked by
GREAT PLAINS
AREA INDIAN
HEALTH SERVICE
OFFICE OF
ENVIRONMENTAL
HEALTH &
ENGINEERING
115 4TH AVENUE SE, ROOM 309
ABERDEEN, SD 57401
(605) 226-7451 FAX (605) 226-7689
K. F. DAVIS ENGINEERING, INC.
530 LA GONDA WAY,
SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
N.T.S
PE STAMP:
/2
/2
:2
:3
P
M
M-2
M E
C H
A N
IC
A
L S
C H
E D
U L
E S
R E
P L
A C
E H
E A
T
IN
G P
L A
N T
02/22/2022
A. SHRESTHA
S. PARK
DOMESTIC HOT WATER STORAGE TANK SCHEDULE
TAG
MODEL
NUMBER
STANDARD
RECOVERY…