This document contains an appendix estimating the heating water system volume for the Pine Ridge Hospital replacement project. It provides pipe sizing, length, area, cubic feet, and gallons for the existing heating water supply and return systems for various buildings on site. It also includes notes on the basis of design for the heating plant and estimated volumes for air handling unit coils, VAV terminal units, unit heaters, and radiant panels. The related federal contract opportunity is a solicitation to replace the existing heating plant at Pine Ridge Hospital in Pine Ridge, South Dakota. The contractor will furnish all labor, equipment, materials, and transportation necessary to perform the project in accordance with the attached scope of work, technical provisions, and drawings. The soliciting agency is the Department of Health and Human Services Indian Health Service.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ESTIMATED HEATING WATER SYSTEM VOLUME
SITE: PINE RIDGE HOSPITAL
SYSTEM: HEATING WATER SUPPLY AND RETURN
REVISED: 4‐21‐2022
BUILDING AREA PIPE SIZE LENGTH (FT) AREA (FT2) CUBIC FEET GALLONS NOTES
A 0.50 235 0.001 0.3 2.4
A 0.75 1720 0.003 5.3 39.5
A 1 190 0.005 1.0 7.8
A 1.25 160 0.009 1.4 10.2
A 1.5 200 0.012 2.5 18.4
A 2 70 0.022 1.5 11.4
A 3 110 0.049 5.4 40.4
B 0.50 310 0.001 0.4 3.2
B 0.75 1340 0.003 4.1 30.8
B 1 490 0.005 2.7 20.0
B 1.25 190 0.009 1.6 12.1
B 1.5 100 0.012 1.2 9.2
B 2 60 0.022 1.3 9.8
B 4 80 0.087 7.0 52.2
C 0.5 465 0.001 0.6 4.7
C 0.75 620 0.003 1.9 14.2
C 1 210 0.005 1.1 8.6
C 1.25 170 0.009 1.4 10.8
C 2 70 0.022 1.5 11.4
C 4 370 0.087 32.3 241.5
D 0.50 740 0.001 1.0 7.5
D 0.75 765 0.003 2.3 17.6
D 1 290 0.005 1.6 11.8
D 1.25 175 0.009 1.5 11.2
D 1.5 110 0.012 1.3 10.1
D 2 150 0.022 3.3 24.5
D 3 50 0.049 2.5 18.4
E 0.50 725 0.001 1.0 7.4
E 0.75 310 0.003 1.0 7.1
E 1 260 0.005 1.4 10.6
E 1.25 60 0.009 0.5 3.8
E 1.5 70 0.012 0.9 6.4
E 2 100 0.022 2.2 16.3
E 2.5 55 0.034 1.9 14.0
E 3 60 0.049 2.9 22.0
F 0.75 350 0.003 1.1 8.0 HEATING PLANT PIPING.
F 1 80 0.005 0.4 3.3 AHU‐1 BRANCH PIPING.
F 1.25 100 0.009 0.9 6.4 AHU‐3 & 8 BRANCH PIPING.
F 1.25 160 0.009 1.4 10.2 HEATING PLANT PIPING.
F 1.5 130 0.012 1.6 11.9 AHU‐6 BRANCH PIPING.
VOLUME
VAV REHEAT AND FIN TUBE PIPING.
VAV REHEAT AND FIN TUBE PIPING.
VAV REHEAT AND FIN TUBE PIPING.
GENERAL NOTE: ALL FINAL PIPE LENGTHS INCLUDE SUPPLY AND RETURN PIPING AND ESTIMATED VERTICAL
RISERS.
VAV REHEAT AND FIN TUBE PIPING.
VAV REHEAT AND FIN TUBE PIPING.
APPENDIX A
BUILDING AREA PIPE SIZE LENGTH (FT) AREA (FT2) CUBIC FEET GALLONS NOTES
F 2.5 140 0.034 4.8 35.7 HEATING PLANT PIPING.
F 3 100 0.049 4.9 36.7 HEATING PLANT PIPING.
F 4 380 0.087 33.2 248.0 HEATING PLANT PIPING.
F 6 250 0.196 49.1 367.2 HEATING PLANT PIPING.
G 0.50 670 0.001 0.9 6.8
G 0.75 1200 0.003 3.7 27.5
G 1 175 0.005 1.0 7.1
G 1.25 260 0.009 2.2 16.6
G 1.5 210 0.012 2.6 19.3
G 2 290 0.022 6.3 47.3
G 2.5 120 0.034 4.1 30.6
G 3 150 0.049 7.4 55.1
H 0.50 420 0.001 0.6 4.3
H 0.75 1075 0.003 3.3 24.7
H 1 400 0.005 2.2 16.3
H 1.25 90 0.009 0.8 5.7
H 1.5 170 0.012 2.1 15.6
H 2 40 0.022 0.9 6.5
J 0.75 800 0.003 2.5 18.4
J 1 1400 0.005 7.6 57.1
J 1.25 170 0.009 1.4 10.8
J 1.5 340 0.012 4.2 31.2
J 2 80 0.022 1.7 13.1
J 2.5 30 0.034 1.0 7.6
J 3 230 0.049 11.3 84.5
J 4 400 0.087 34.9 261.1
K 0.5 125 0.001 0.2 1.3
K 0.75 1470 0.003 4.5 33.7
K 1 280 0.005 1.5 11.4
K 1.25 50 0.009 0.4 3.2
K 1.5 230 0.012 2.8 21.1
K 2 160 0.022 3.5 26.1
K 2.5 0.034 0.0 0.0
K 3 280 0.049 13.7 102.8
365.0
AVERAGE OF ALL VAV, UNIT HEATER,
AND RADIANT PANEL COILS. 365 UNITS
@ 1 GALLON AVG. PER UNIT.
400.0 ALDRICH 125 HP BASIS OF DESIGN.
400.0 ALDRICH 125 HP BASIS OF DESIGN.
400.0 ALDRICH 125 HP BASIS OF DESIGN.
10.0 ESTIMATED
5.0 ESTIMATED
12.0 ESTIMATED
15.0 ESTIMATED
5.0 ESTIMATED
15.0 ESTIMATED
12.0 FROM NEW AH‐7 SUBMITTAL.
8.0 ESTIMATED
BOILER 1
BOILER 1
BOILER 1
AHU‐1 COIL
AHU‐2 COIL
AHU‐3 COIL
AHU‐4 COIL
AHU‐5 COIL
AHU‐6 COIL
VAV REHEAT AND FIN TUBE PIPING.
VAV REHEAT AND FIN TUBE PIPING.
VAV REHEAT AND FIN TUBE PIPING.
VAV REHEAT AND FIN TUBE PIPING.
AHU‐7 COIL
AHU‐8 COIL
VAV, UNIT HEATER, AND RADIANT PANEL COILS
BUILDING AREA PIPE SIZE LENGTH (FT) AREA (FT2) CUBIC FEET GALLONS NOTES
10.0 ESTIMATED
8.0 ESTIMATED
15.0 ESTIMATED
10.0 ESTIMATED
515 FROM ORIGINAL DESIGN SCHEDULE.
464.7
5111.3GRAND TOTAL
EXPANSION TANK
10% MORE FOR MISCELLANEOUS OR ITEMS MISSED
AHU‐9 COIL
RTU‐1
AHU‐10 COIL
AHU‐11 COIL