FIELD OFFICE: BUILDING NUMBER: BUILDING ADDRESS:
ANNUAL MAN-HOUR
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
A-1 AIR DRYER, REFRIGERATED OR REFRIGERATIVE DESICCANT TYPE0 1 0.5 2
A-2 UNITARY, HEATING AND COOLING UNIT 0 1 2 3.5
A-3 HUMIDIFICATION SYSTEM 0 2 1 1
A-4 AIR COMPRESSOR 0 1 1.5 2.3
A-5 AIR CONDITIONING MACHINE, SPLIT SYSTEM
COMFORT COOLING
10 TONS AND UNDER 0 1 3 3
OVER 10 TONS 0 1 6 6
SPECIAL PURPOSE
10 TONS AND UNDER 0 12 3 3
OVER 10 TONS 0 12 6 6
A-6 AIR CONDITIONING MACHINE PACKAGE UNIT
COMFORT COOLING
10 TONS AND UNDER 0 1 3 3
OVER 10 TONS 0 1 6 6
A-7 AIR CONDITIONING MACHINE, PACKAGE UNIT
SPECIAL PURPOSE
10 TONS AND UNDER 0 12 3 3
OVER 10 TONS 0 12 6 6
A-8 AIR CONDITIONING, WINDOW UNIT 0 0 0 2
A-9 AIR-COOLED CONDENSER
20 TONS AND UNDER 0 1 4 4
OVER 20 TONS 0 1 5 5
A-10 HEAT PUMPS, OVER 10 TONS
5 TONS AND UNDER 0 1 2 3
6 to 10 TONS 0 1 4 6
OVER 10 TONS 0 1 6 9
A-11 AIR HANDLER UNIT
UNDER 5,000 CFM 0 1 2 2
5,001 TO 15,000 CFM 0 1 4 4.5
15,001 TO 30,000 CFM 0 1 4 8.25
30,001 TO 50,000 CFM 0 1 12 13.25
50,001 TO 75,000 CFM 0 1 16 19.25
OVER 75,000 CFM 0 1 20 21.25
A-12 GLYCOL DRY COOLER
(COMFORT COOLING)
20 TONS OR LESS 0 1 3.5 3.5
OVER 20 TONS TO 40 TONS 0 1 4.5 4.5
OVER 40 TONS 0 1 9 9
(SPECIAL PURPOSE)
20 TONS OR LESS 0 2 7 7
OVER 20 TONS TO 40 TONS 0 2 9 9
OVER 40 TONS 0 2 12 12
A-13 AIR CONDITIONING UNIT, CEILING/WALL MOUNTED
COMFORT COOLING 0 1 3 3
SPECIAL PURPOSE 0 1 3 3
A-14 AIR WASHER OR WET COIL SYSTEM
(AIR WASHER)
20,000 CFM OR LESS 0 1 4 4
20,001 TO 50,000 CFM 0 1 5 5
50,001 TO 75,000 CFM 0 1 6 6
Bidder's Library Solicitation: GS-07-P-16-JU-D-7006-0003
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
OVER 75,000 CFM 0 1 8 8
(WET COIL)
20,000 CFM OR LESS 0 1 1.5 1.5
20,001 TO 40,000 CFM 0 1 2 2
OVER 40,000 CFM 0 1 3 3
A-15 AFTER-COOLER/SEPARATOR 0 2 6 6
A-24 ASH CONVEYOR TUBE (PNEUMATIC AND HYDRAULIC), 0 0.33 4 4
PER TUBE SECTION
B-1 BATTERY CHARGER 0 4 0.25 0.25
B-2 BOILER, (COAL, OIL, AND GAS)
120 MBTU'S OR LESS 0 1 2.5 2.5
120 TO 300 MBTU'S 0 1 5 5
300 TO 500 MBTU'S 0 1 8 8
500 TO 700 MBTU'S 0 1 24 24
700 TO 1,000 MBTU'S 0 1 32 32
OVER 1,000 MBTU'S 0 1 40 40
B-3 BURNER, GAS 0 1 2 2
B-4 BURNER, OIL 0 1 3 3
B-5 ELECTRIC BOILERS 0 1 2 2
B-6 BOILER INSTRUMENTS/CONTROLS 0 1 1 1
C-1 CLOCKS, CENTRAL SYSTEM 0 2 4 7.25
C-2 REMOTE AIR INTAKE DAMPERS 0 2 0.5 0.5
C-3 COILS, PREHEAT, REHEAT, ETC. (REMOTE LOCATIONS) 0 1 0.75 0.75
C-4 CENTRAL MINI-COMPUTER - HVAC SYSTEMS 0 2 0 40
C-5 AUTOMATIC MIXING BOX, PNEUMATIC OR ELECTRIC 0 1 1 1
C-6 CONTROLS, CENTRAL SYSTEM, HVAC 0 1 0.5 0.5
C-7 CONDENSATE OR VACUUM PUMP 0 1 3 3
C-8 CENTRAL CONTROL PANEL 0 1 0 1600
C-9 COOLING TOWER, MAINTENANCE
50 TONS AND UNDER 0 1 6 6
OVER 50 TO 500 TONS 0 1 15 30
OVER 500 TO 1,000 TONS 0 1 25 50
OVER 1,000 TONS 0 1 35 70
C-10 COOLING TOWER, CLEANING
50 TONS AND UNDER 0 4 15 20
OVER 50 TO 500 TONS 0 4 20 30
OVER 500 TO 1,000 TONS 0 4 30 40
OVER 1,000 TONS 0 4 40 60
C-11 EVAPORATIVE CONDENSER
50 TONS AND UNDER 0 1 7.5 15
OVER 50 TONS 0 1 10 20
C-13 CRANE, ELECTRIC 0 4 8 8
C-14 CHAIN HOIST AND TROLLEY 0 2 5 5
C-16 COOLING POND (SUITLAND, MD, HEATING AND 0 1 320 320
COOLING PLANT ONLY)
C-21 CARTS AND SCOOTERS, ENGINE OR BATTERY POWERED 0 52 0.3 0.3
ENGINE POWERED 0 1 3 3
BATTERY POWERED 0 1 1 1
C-24 CONDENSING UNIT, REFRIGERATION
COMFORT
20 TONS AND UNDER 0 1 1 5.5
OVER 20 TONS 0 1 3.5 7
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
CRITICAL
20 TONS AND UNDER 0 12 1 5.5
OVER 20 TONS 0 12 2 7
D-1 DOOR, POWER OPERATED 0 2 1.25 1.25
D-2 DUMBWAITER 0 4 3.75 3.75
D-3 DRAINS, ROOF, GUTTER (PER 100') 0 1 0.5 0.5
D-4 DOOR, HYDRAULIC, ELECTRIC OR PNEUMATIC OPERATED0 4 1.25 1.25
D-5 DOOR, MAIN ENTRANCE 0 2 1 1
D-6 DRAINS, AREAWAY, DRIVEWAY, STORM 0 1 0.5 0.5
D-7 SEDIMENT BASIN 0 2 0.5 0.5
D-9 DISTILLER, WATER, (LABORATORY USE ONLY) 0 1 1 1
D-10 DOOR, MANUAL, OVERHEAD 0 1 1 1
E-17 EXPANSION JOINTS IN PIPING 0 1 1.25 1.25
E-18 EMERGENCY LIGHTS (WET CELL) 0 4 0.4 0.4
E-19 EMERGENCY LIGHTS (CLOSED SYSTEM) 0 4 0.2 0.2
E-20 INDUCTION DISC OVER CURRENT RELAY 0 1 1.5 1.5
E-21 OVER AND/OR UNDER VOLTAGE RELAY 0 1 1.6 1.6
E-22 THERMAL OVER CURRENT RELAY 0 1 0.8 0.8
E-23 INDUCTION DISC-DIRECTIONAL OVER CURRENT RELAY 0 1 0.5 0.5
E-24 POWER FACTOR REVERSE CURRENT OR WATT TYPE RELAY0 1 1.2 1.2
E-25 GROUND FAULT TYPE TRANSFORMER OR DIFFERENTIAL RELAY0 1 1.5 1.5
E-25A BOLTED PRESSURE CONTRACT SWITCH (LOW VOLTAGE) 0 1 1.5 1.5
E-26 LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER 0 0.33 3.9 3.9
E-27 LOW VOLTAGE POWER CIRCUIT BREAKER (OVER 50 AMPS)0 0.33 4.2 4.2
E-28 MOTOR STARTERS 100 HP AND UP 0 0.33 6 6
E-29 HIGH VOLTAGE OIL CIRCUIT BREAKER 0 1 6 6
E-30 SWITCHBOARD (PER CUBICLE), MEDIUM VOLTAGE 0 0.33 2 2
E-30A SWITCHBOARDS (PER CUBICLE), LOW VOLTAGE 0 0.33 2 2
E-31 NETWORK PROTECTORS 0 1 2.5 5.5
E-32 HIGH VOLTAGE NETWORK AND POWER
TYPE TRANSFORMER (OIL FILLED)
POWER TYPE 0 1 3 3
NETWORK TYPE 0 1 0.5 0.5
E-33 HIGH VOLTAGE NETWORK AND POWER DRY TYPE TRANSFORMER
POWER TYPE 1 3.5 6.5
NETWORK TYPE 0 1 4 5
E-34 DISCONNECTS (ISOLATING SWITCH; PER SWITCH) 0 1 2 3
E-34A DISCONNECT OR ISOLATING SWITCH, LOW VOLTAGE
(FUSED/NON-FUSED, 200 AMPS AND UP)
200 TO 500 AMPS 0 1 1 2
OVER 500 AMPS 0 1 3 3
E-35 MOTOR CONTROL CENTER 0 2 3 3
(INCLUDES MOTOR STARTERS UNDER 100 HP)
E-36 AUTOMATIC TRANSFER SWITCH 0 2 1.5 1.5
E-37 ALUMINUM BUS DUCT AND CONNECTORS
PER DISCONNECT OR 0 2 1 1
PER 10 FOOT BUST DUCT SECTION 0 2 0.2 0.2
E-37A ALUMINUM BUS DUCT AND CONNECTORS 0 2 0.08 0.08
E-38 HIGH VOLTAGE AIR CIRCUIT BREAKER 0 1 6.2 6.2
E-39 SUPERVISION SET 0 1 0.15 0.15
E-40 EMERGENCY GENERATOR; ELECTRIC, GASOLINE, OR NATURAL GAS0 1 4 4
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
E-41 EMERGENCY GENERATOR, ELECTRIC DIESEL POWER 0 1 4 4
E-42 EMERGENCY GENERATOR ELECTRIC 0 12 1.25 1.25
E-42A EMERGENCY GENERATOR 0 12 2 2
E-43 LEAD ACID BATTERY (PER CELL) 0 4 0.03 0.03
E-44 EDISON NICKEL-IRON-ALKALINE BATTERY (PER CELL) 0 4 0.02 0.02
E-45 EMERGENCY GENERATOR, STEAM TURBINE DRIVER 0 1 6 6
E-49 EMERGENCY PUMP OR VENTILATOR 0 1 3 3
E-50 EMERGENCY PUMP OR VENTILATOR 0 4 0.5 0.5
E-51 MOTOR STARTER, 0 1 1 1
5 HP TO LESS THAN 100 HP
AND LESS THAN 600 VOLTS (FORMERLY E-35A)
E-52 AUXILIARY PROTECTIVE RELAY 0 1 0.25 0.25
E-56 DIMMER AND CONTROL, STAGE AND GENERAL LIGHTING 0 4 2 4.5
E-57 LOW VOLTAGE DRY TYPE TRANSFORMER 0 0.33 3 3
(30 KVA AND UP, 600 VOLTS OR LESS)
F-1 ALARM CHECK VALVES & ACCESSORIES 0 2 1.25 1.25
F-2 DRY PIPE, DELUGE AND PREACTION VALVES 0 12 0.15 0.15
F-2A DRY PIPE, DELUGE AND PREACTION VALVES 0 4 0.4 0.4
F-2B DRY PIPE, DELUGE AND PREACTION VALVES 0 1 2 2
F-3 FIRE POST INDICATOR VALVE 0 1 0.75 0.75
F-4 FIRE CONTROL VALVES (4 IN. OR OVER) 0 1 0.2 0.2
FOR INTERIOR WATER DISTRIBUTION SYSTEMS
F-5 FIRE PUMP (MOTOR OR ENGINE DRIVEN 0 52 0.6 0.6
F-6 FIRE PUMP (MOTOR OR ENGINE DRIVEN 0 12 0.2 0.2
F-7 FIRE PUMP
MOTOR DRIVEN 0 1 1.6 1.6
ENGINE DRIVEN 0 1 3.4 3.4
F-8 FIRE HOSE (1 IN. RACKED IN BUILDINGS) 0 1 0.2 0.2
F-9 FIRE DEPARTMENT HOSE CONNECTIONS (STANDPIPE OUTLETS)0 1 0.15 0.15
F-10 FIRE DEPARTMENT PUMPER CONNECTIONS 0 1 0.3 0.3
(STANDPIPE OR SPRINKLER)
F-11 FIRE DOORS - STAIRWELLS & EXIT WAYS (SWINGING) 0 4 0.05 0.05
F-12 FIRE DOORS - SLIDING TYPE 0 4 0.2 0.2
F-13 FIRE SUPERVISORY SIGNAL - TESTING 0 4 0.3 0.3
F-14 AUTOMATIC FIRE DETECTION OR ALARM DEVICES 1000 4 0.3 0.3
F-15A FIRE ALARM CONTROL PANEL, SPECIAL SYSTEMS 0 4 0.55 0.55
F-15B CENTRAL STATION, TRANSMITTERS 0 12 0.3 0.3
F-15C CENTRAL STATION, TRANSMITTERS/RETRANSMISSION EQUIPMENT0 251 1 1
F-16 FIRE ALARM SYSTEM - RECORDER 0 52 0.1 0.1
F-17 FIRE ALARM BOX (MANUAL - CODED AND UNCODED) 0 4 0.3 0.3
F-18 FIRE AND SMOKE DAMPERS 0 0.5 0.2 0.2
F-19 FIRE HYDRANT (DRY BARREL OR WET BARREL) 0 1 0.65 0.65
F-20 SPRINKLER HEAD - SPRINKLERED AREAS (PER 1,000 SQ. FT.)0 2 0.1 0.1
F-21 FIRE EXTINGUISHER - SODA ACID OR FOAM 0 1 0.75 0.75
F-22 FIRE EXTINGUISHER - STORED PRESSURE WITH GAUGE 0 1 0.1 0.1
F-22A FIRE EXTINGUISHER, STORED PRESSURE WITH GAUGE AND 0 0.17 0.34 0.34
NON STAINLESS STEEL SHELL
F-23 FIRE EXTINGUISHER - GAS CARTRIDGE OR CYLINDER (NO GAUGE)0 1 0.2 0.2
F-24 FIRE EXTINGUISHER - INSPECTION 0 12 0.02 0.02
F-25 FIRE EXTINGUISHER - HYDROSTATIC TESTING OF CARBON DIOXIDE,0 0.2 1 1
STORED PRESSURE AND CARTRIDGE TYPE
F-26 FIRE EXTINGUISHER SYSTEM - CARBON DIOXIDE (HIGH PRESSURE),0 2 0.75 0.75
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
HALON, DRY CHEMICAL
F-27 FAN, CENTRIFUGAL
UP TO 5,000 CFM 0 1 1 1
OVER 5,000 TO 10,000 CFM 0 1 1.3 1.3
OVER 10,000 TO 15,000 CFM 0 1 1.6 1.6
OVER 15,000 TO 20,000 CFM 0 1 1.95 1.95
OVER 20,000 CFM 0 1 2.25 2.25
F-28 FILTER, MOVEABLE CURTAIN, OIL COATED 0 4 1.75 1.75
F-29 FILTER, ROLL TYPE, DISPOSABLE MEDIA 0 4 1.75 1.75
F-30 FILTERS, VISCOUS TYPE 0 4 0.5 0.5
F-31 FILTER, ROLL TYPE, DISPOSABLE MEDIA, MANUAL OR MOTOR DRIVEN0 2 1.75 1.75
F-32 FILTER, THROW AWAY 0 4 0.08 0.08
F-33 FILTER, ELECTROSTATIC 0 4 2.5 2.5
F-34 FLUORESCENT LIGHTING FIXTURE, WASHING AND RELAMPING
INDUSTRIAL TYPE:
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
(1) LAMP/48" 0 0.4 0.07 0.07
(1) LAMP/96" 0 0.4 0.12 0.12
(2) LAMPS/48" 0 0.4 0.12 0.12
(2) LAMPS/96" 0 0.4 0.2 0.2
(3) LAMPS/48" 0 0.4 0.17 0.17
(4) LAMPS/48" 0 0.4 0.25 0.25
LOUVER TYPE:
(1) LAMP/48" 0 0.4 0.18 0.18
(2) LAMPS/48" 2500 0.4 0.23 0.23
(3) LAMPS/48" 0 0.4 0.29 0.29
(4) LAMPS/48" 0 0.4 0.33 0.33
DIFFUSER TYPE
(1) LAMP/48" 0 0.4 0.13 0.13
(2) LAMPS/48" 0 0.4 0.17 0.17
(3) LAMPS/48" 0 0.4 0.22 0.22
(4) LAMPS/48" 0 0.4 0.25 0.25
F-35 FLUORESCENT LIGHT FIXTURE - RELAMPING ONLY
(1) LAMP 0 0.2 0.05 0.05
(2) LAMPS 0 0.2 0.07 0.07
(3) LAMPS 0 0.2 0.11 0.11
(4) LAMPS 0 0.2 0.13 0.13
F-36 FAN, PROPELLER, 24 IN. DIAMETER OR LARGER 0 1 0.75 0.75
F-37 FLOOR POLISHING MACHINE 0 2 0.35 0.35
F-38 LIGHTNING PROTECTION (PER DOWN CONDUCTOR) 0 1 0.5 0.5
F-39 CAFETERIA EXHAUST HOOD 0 2 16 16
(DUCT SYSTEM PER FEET OF DUCT WORK)
F-40 FILTER, THROW AWAY, BAG TYPE (BY DEPTH)
OVER 4" TO 6" 0 2 0.08 0.08
OVER 6" TO 12" 0 2 0.1 0.1
OVER 12" TO 24" 0 2 0.2 0.2
OVER 24" TO 48" 0 2 0.25 0.25
F-43 FILTER, CHARCOAL 0 4 0.16 0.16
F-44 FOUNTAIN, MEMORIAL OR DECORATIVE 0 2 2 2
F-46 FIREPLACE 0 12 0.5 0.5
F-47 FIREPLACE 0 4 0.5 0.5
F-49 FILTER, CONTROL AIR 0 4 0.5 0.5
G-1 FUEL OIL FILTER/STRAINER 0 2 1 1
G-2 GREASE TRAPS 0 12 0.75 0.75
G-3 GATES AND FENCES, SECURITY AND ACCESS 0 2 2 2
H-1 HOT WATER CONVERTER (STEAM) 0 1 6 6
H-2 HOT WATER HEATER - GAS 0 1 0.6 0.6
H-3 HOT WATER HEATER - ELECTRIC 0 1 0.6 0.6
H-4 SECONDARY WATER CHILL CONVERTER 0 1 54 54
H-5 HOT WATER HEATER, STEAM COIL 0 1 0.6 0.6
H-6 HOT AIR FURNACE
120 MBTU'S OR LESS 0 1 2.5 2.5
120 TO 300 MBTU'S 0 1 5 5
300 TO 500 MBTU'S 0 1 8 8
500 TO 700 MBTU'S 0 1 24 24
700 TO 1,000 MBTU'S 0 1 32 32
OVER 1,000 MBTU'S 0 1 40 40
H-12 HEATER, FUEL OIL, UNIT 0 1 16 16
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
H-14 HOIST, LIGHTING 0 1 1 1
H-15 HOIST, ELECTRIC 0 1 0.75 0.75
I-1 INCINERATOR 0 1 15.25 15.25
I-2 FAN COIL UNIT, UNDER 0 1 0.4 0.4
I-3 INDUCTION UNIT, UNDER WINDOW TYPE 0 1 0.4 0.4
I-4 FAN COIL UNIT, CEILING HUNG 0 1 1 1
I-5 FAN COIL UNIT, CEILING HUNG, VAV BOX WITH ELECTRIC REHEAT0 1 0 2
L-1 LAWN MOWER AND EDGER 0 2 2 2
L-2 LOADING RAMP, ADJUSTABLE 0 4 1.25 1.25
L-3 LIGHTING, SPECIAL FEATURE 0 1 0.5 0.5
L-4 LIGHTING, OUTSIDE
INCANDESCENT 0 2 1 1
FLUORESCENT, MERCURY VAPOR
OR HIGH PRESSURE SODIUM 0 2 1.75 1.75
L-5 LAWN SPRINKLERS (PER NOZZLE) 0 1 0.25 0.25
L-6 LOCOMOTIVE, DIESEL (DFC ONLY) 0 2 14 14
L-7 LOCOMOTIVE, DIESEL (ELECTRICAL CONTROLS)(DFC ONLY)0 2 8 8
L-8 SPOTLIGHTS, FIXED AND 0 12 1.5 1.5
L-10 LIFT, ELECTRIC, STAGE SCREEN PORTABLE 0 2 3 3
M-1 MANHOLE ELECTRICAL 0 1 2 2
M-2 MANHOLE, SEWER 0 4 2 2
M-3 MOTORS
1 TO 7.5 HP 0 1 0 0.3
OVER 7.5 TO 50 HP 0 1 0 0.5
OVER 50 HP 0 1 0 0.6
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
M-4 MANHOLE, WATER/STEAM/FUEL OIL (ALSO INCLUDES HOT WATER,0 2 2 2
CHILLED WATER, AND CONDENSER WATER)
M-6 MATERIAL HANDLING EQUIPMENT, ENGINE DRIVEN 0 2 1 1
M-7 MATERIAL HANDLING EQUIPMENT 0 1 0.5 0.5
M-8 MAGNETIC DRIVE 0 4 0.5 0.5
M-9 MOBILE EQUIPMENT 0 4 1 1
M-10 MOTOR CONTROLLER UNIT (600 VOLTS AND ABOVE) 0 1 3.75 3.75
M-11 MOTORS, 600 VOLT OR 200 HP AND ABOVE 0 1 1 1
P-1 PAPER BALER 0 1 1 1
P-2 PNEUMATIC TUBE SYSTEM 0 1 4 4
P-4 PUMP, CENTRIFUGAL
1 TO 24 HP 0 1 0 1.5
25 TO 100 HP 0 1 0 5.5
OVER 100 HP 0 1 0 6.5
P-6 PUMP, VACUUM 0 2 0 2.3
P-7 PUMP, GEAR AND RECIPROCATING00 HP 0 1 1.5 1.5
R-1 RADIATOR, HEATING 0 2 0 0.15
R-2 ROOF INSPECTION (PER SQUARE, OR 100 SQ. FT.) 0 2 0.03 0.03
R-3 REFRIGERATION MACHINE (ABSORPTION)
UP TO 500 TONS 0 1 20 60
OVER 500 TO 1,000 TONS 0 1 40 100
OVER 1,000 TONS 0 1 60 140
R-4 CENTRAL CHILLED WATER PACKAGE UNIT
COMFORT COOLING OR CENTRAL DRINKING WATER
25 TONS AND UNDER 0 1 8 18
25 TO 50 TONS 0 1 16 26
50 TO 75 TONS 0 1 22 34
75 TO 100 TONS 0 1 28 42
OVER 100 TONS 0 1 35 50
SPECIAL PURPOSE OR COMPUTER COOLING
25 TONS AND UNDER 0 1 8 18
25 TO 50 TONS 0 1 16 26
50 TO 75 TONS 0 1 22 34
75 TO 100 TONS 0 1 28 42
OVER 100 TONS 0 1 35 50
R-5 REFRIGERATION MACHINE, CENTRIFUGAL
50 TONS AND UNDER 0 1 8 20
50 TO 25O TONS 0 1 12 28
251 TONS - 500 TONS 0 1 18 50
501 TONS - 750 TONS 0 1 22 70
751 TO 1,000 TONS 0 1 24 90
ADD 20 MAN-HOURS FOR EACH ADDITIONAL 250 TON 0 1 0 0
INCREMENT OVER 1,000 TONS. 0
R-6 REFRIGERATION MACHINE, RECIPROCATING AND SCROLL
50 TONS AND UNDER 0 1 10 20
50 TO 100 TONS 0 1 12 24
100 TO 250 TONS 0 1 14 28
OVER 250 TONS 0 1 20 40
R-7 REFRIGERATION MACHINE, SCREW
50 TONS AND UNDER 0 1 10 20
50 TO 250 TONS 0 1 12 28
250 TO 500 TONS 0 1 16 50
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
500 TO 750 TONS 0 1 20 70
750 TO 1,000 TONS 0 1 30 90
OVER 1000 TONS 0 1 40 120
R-8 CONTROL PANEL - CENTRAL REFRIGERATION UNIT 0 1 4 4
R-9 RADIATION, BASEBOARD/CONVECTORS 0 0.5 0.5 0.5
(STEAM, HOT WATER, OR ELECTRIC - PER LINEAR FOOT)
R-10 RAILROAD TRACKAGE (PER 1,000 FT.) 0 1 3.5 3.5
R-11 REFRIGERATION CONTROLS, CENTRAL SYSTEM 0 1 1 1
R-12 RAILROAD TURNOUT 0 1 0.55 0.55
R-13 NON-DESTRUCTIVE CHILLER TUBE ANALYSIS 0 0.33 9 9
R-14 HIGH EFFICIENCY PURGE UNITS 0 1 2 2
S-2 SEWAGE EJECTOR (PNEUMATIC TANK TYPE EJECTORS) 0 1 4 4
S-5 SWEEPER 0 2 3 3
S-6 SEWAGE EJECTOR, SUMP TYPE 0 1 4 4
S-7 SUMP PUMP 0 1 3.75 3.75
S-8 STRAINER, Y-TYPE 0 1 0.5 0.5
S-9 STRAINER, BOLTED FLANGE (WATER AND STEAM)
6 TO 14 BOLTS 0 1 2 2
14 TO 34 BOLTS 0 1 6 8
34 TO 58 BOLTS 0 1 10 16
OVER 58 BOLTS 0 1 20 36
S-10 SCRUBBING MACHINE (BATTERY OR PROPANE POWERED)0 4 1 1
S-11 SNOW BLOWER 0 1 0.9 0.9
S-14 DUAL STRAINER 0 1 9 17
S-15 BACKWASH STRAINER 0 1 6 60
T-1 TANK, WATER (ALL TYPES) 0 0.33 6.25 6.25
T-2 TANK, AIR/REFRIGERANT/;P GAS 0 1 6.25 6.25
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
T-3 TANK, FUEL OIL STORAGE 0 0.25 6.25 6.25
T-5 TRASH COMPACTOR 0 1 4 4
T-6 TANK, CHEMICAL 0 1 8 8
T-8 TRAPS, ALL TYPES
LOW PRESSURE 0 0.2 0.5 0.5
HIGH PRESSURE 0 1 0.5 0.5
T-9 TURBINE, STEAM 0 1 11.5 11.5
T-10 TELECOMMUNICATIONS 0 4 0.75 0.75
T-12 FLUID DRIVE TRANSMISSIONS 0 1 5 5
U-1 UNIT HEATER (STEAM AND HOT WATER) 0 1 1 1
U-2 UNIT HEATER (GAS AND OIL FIRED) 0 1 1 1
V-1 VACUUM CLEANER, HEAVY DUTY, TANK TYPE 0 2 0.5 0.5
V-2 VALVE, SAFETY RELIEF 0 12 0.5 0.5
V-3 VALVE REGULATING 0 1 0.6 0.6
V-5 VALVE, MANUALLY OPERATED
MAIN LINE OR CRITICAL 0 1 0.4 0.4
OTHER OVER 2 INCHES 0 0.2 0.4 0.4
V-6 VALVE, MOTOR OPERATED 0 1 0.4 0.4
V-7 VALVE, HYDRAULIC/PNEUMATIC/ELECTRIC 0 1 1.5 1.5
V-8 VALVE 0 1 1.5 1.5
V-9 BACKFLOW PREVENTER
UP TO 1 1/2 INCHES 0 1 0.75 0.75
1 1/2 TO 2 INCHES 0 1 1.5 1.5
2 TO 3 INCHES 0 1 2 2
3 TO 4 INCHES 0 1 3 3
4 TO 6 INCHES 0 1 4 4
6 TO 8 INCHES 0 1 6 6
OVER 8 INCHES 0 1 8 8
V-10 VACUUM SYSTEM, CENTRALIZED 0 1 2.5 2.5
W-1 DRINKING WATER FILTER SYSTEMS 0 4 3 3
W-2 WASH, EMERGENCY 0 52 0.05 0.05
W-3 WATER SOFTENER 0 2 4 4
W-4 FILTER, WATER 0 2 0.5 0.5
W-5 WINDOW WASHING SCAFFOLD, POWER OPERATED 0 1 4 4
W-7 WHEELCHAIR LIFT 0 12 1.75 1.75
W-8 WATER TREATMENT FOR COOLING TOWERS 0 12 2 2
W-9 WATER TREATMENT FOR HEATING SYSTEMS 0 12 2 2
X-21 KEY CARD SYSTEM 0 4 1 1
X-22 FLAG POLE, ELECTRIC 0 4 0.25 0.25
X-23 HEATER UNIT, ELECTRIC 0 2 0.75 0.75
X-26 SOLAR HEATING SYSTEM 0 2 4 4
X-26A SOLAR HEATING SYSTEM (SOLAR COLLECTORS) 0 1 0.03 0.03
X-29 CHEMICAL FEEDER 0 2 1 1
X-32 PARKING ARM GATES 0 1 1 1
X-37 EMERGENCY SHOWER 0 1 0.1 0.1
X-39 SEPTIC TANK AND DRAIN FIELD 0 1 2 2
X-41 TRACTOR, DIESEL 0 12 0.5 0.5
0 2 0.25 0.25 0 1 5 5
X-42 METAL-ENCLOSED BUSS DUCT
(LOW VOLTAGE, 600 VOLTS OR LESS)
OUTDOORS
PREVENTIVE MAINTENANCE
REQUIREMENTS REGION: PREPARED BY: SHOP: DATE:
ALL
SECTION 1 - PM MAN-HOUR REQUIREMENTS
PM MAN-HOURS
GUIDE ITEM QUANTITY FREQUENCY April '15 Legacy (old)
NO. STANDARD STANDARD
PER DISCONNECT OR POWER TAKEOFF 0 1 1 1
PER 10 FOOT BUSS DUCT SECTION 0 1 0.2 0.2
INDOORS
PER DISCONNECT OR POWER TAKEOFF 0 0.33 1 1
PER 10 FOOT BUSS DUCT SECTION 0 0.33 0.2 0.2
Totals 2134.31 4853.71
* ADDITION P.M.'S
GENERAL SERVICES ADMINISTRATION #REF!