Final BPEE Questions and Answers.docx

DOCX document 11 KB Posted

Attached to
Bi-Parting Empennage Enclosure for C-5 MTE-1
Solicitation number
FA6606-11-R-0002
Issued by

About this file

final questions BPEE

View the file

Other files

File Type Posted
Final BPEE Questions and Answers.pdf PDF
Questions and Answers 12 May 2011.pdf PDF
Q A 10 May 2011.docx DOCX document
Q A 10 May 2011.pdf PDF
Participant List for Site Visit.pdf PDF
SOO-29 April 2011.pdf PDF
Site Visit Q A.pdf PDF
BPEE Q A 1 docx.pdf PDF
BPEE Attachments 1 thru 5.pdf PDF
MTE SITE VISIT NOTICE.pdf PDF
BPEE SOW Template 4-19-11.doc DOC document
MTE SITE VISIT NOTICE.docx DOCX document
Drawings.pdf PDF
0 Statement of Objective_14 April 11.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BPEE Questions and Answers

Q. "Subject: Rollup Door. We can provide personnel doors because one can step up and over the bottom beam structure. An overhead door will require that the bottom beam structure be interrupted. This will negatively effect the structural integrity of the steel framing. While I can't say that it is impossible, it is certainly not recommended. Please consider deleting this requirement."

A. We can remove the requirement for the overhead rollup door. The User still requires a personnel door stepping over the beam.

(All interested parties can consider the requirement for the overhead rollup door deleted).

Q. "Subject: Connections. We will try to come up with a design that does not require connecting and disconnecting the fire protection system. But given the size, it is going to be difficult. Section 4.1.1.16 states that the connecting and disconnecting shall be performed without tools. I don't know of a NFPA approved quick-connect. Four bolts are required to be installed and un-installed. This will require a ratchet or box-end wrench."

A. We will accept a four bolt flange connection on the fire protection system.

With the fire connections referenced above we should add in the clarifications that all connections are at ground level.