FA4809-10-R-0004
Questions & Answers 23 Jul 2010
1. QUESTION: Are any As-Built Drawings available in CADD Format?
RESPONSE: See upload of previous drawings dtd 16 Jul 10.
2. QUESTION: Will the Government issue standard Title Block in CADD Format for use in the proposal?
RESPONSE: Standard SJAFB cover sheet is not required for the sample project. However, the successful MACC contractors will be issued it and expect to use it for future projects.
3. QUESTION: Do the 35% fire protection drawings need to be signed by a PE?
RESPONSE: PE seal not required for 35%.
4. . QUESTION: Is a sprinkler line flow test available. Pipe sizing cannot be performed without a test.
RESPONSE: Hydrant flow data is attached and current.
5. QUESTION: The past performance questionnaire (PPQ)references R-0001. If the PPQ has been forwarded already, is it necessary to submit a revised PPQ?
RESPONSE: No, unless the offeror desires to submit a revised PPQ. However, ensure l PPQs are forwarded by the date and time for receipt of offers, or along with your proposal. s