09_51_00___Acoustical_Ceiling_Tile_Specs.pdf
PDF 42 KB Posted
- Attached to
- Bldg 200 HVAC Renovation Federal contract opportunity
- Solicitation number
- FA4497-15-R-0004
About this file
Ceiling Tile Specs
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_ _Answers__2_HVAC_Renovation _B200.pdf | ||
| SOW_Attachment_2_-_B200_Energy_Upgrades_Specifications.pdf | ||
| UFGS_01_45_00.00_10_Quality_Control.pdf | ||
| Questions_ _Answers_HVAC_Renovation _B200.pdf | ||
| FA4497-15-R-0004-0002_Amendment_to_Extend_RFP_Due_Date.pdf | ||
| SOW_Attachment_2_-_B200_Energy_Upgrades_Specifications.pdf | ||
| 01_11_10_DAFB_General_Requirements_(1_MAY_14).doc | DOC document | |
| B200_Energy_100__Dwg_Set.pdf | ||
| 02_61_10_DAFB_Environmental_Specifications_(1_MAY_14).doc | DOC document | |
| 31_25_10_DAFB_Sediment_and_Erosion_Control_(1_MAY_14).doc | DOC document | |
| Davis-Bacon_WD_DE150004.pdf | ||
| FA4497-15-R-0004-0001___Amendment_to_B200_HVAC_Reno_RFP.pdf | ||
| JAG_Office_200_HVAC_SOW__(05-15-15).pdf | ||
| FA4497-15-R-0004_RFP_Bldg_200_HVAC_Reno.pdf | ||
| 01_14_10_DAFB_Site_Management_(1_MAY_14).doc | DOC document |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DAFB BUILDING 200
Project No. FJXT 111215
SECTION 09 51 00
ACOUSTICAL CEILINGS
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A580/A580M (2012a) Standard Specification for Stainless Steel Wire
ASTM A641/A641M (2009a) Standard Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM C423 (2009a) Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method
ASTM C635/C635M (2007) Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-In Panel Ceilings
ASTM C636/C636M (2008) Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels
ASTM C834 (2010) Latex Sealants
ASTM E1264 (2008e1) Acoustical Ceiling Products
ASTM E1414/E1414M (2011a) Airborne Sound Attenuation Between Rooms Sharing a Common Ceiling Plenum
ASTM E1477 (1998a; R 2008) Luminous Reflectance Factor of Acoustical Materials by Use of Integrating-Sphere Reflectometers
ASTM E580/E580M (2011b) Application of Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels in Areas Requiring Moderate Seismic Restraint
ASTM E795 (2005) Mounting Test Specimens During Sound Absorption Tests
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-310-04 (2007; Change 1) Seismic Design for Buildings
SECTION 09 51 00 Page 1
UNDERWRITERS LABORATORIES (UL)
UL Fire Resistance (2012) Fire Resistance Directory
1.2 SYSTEM DESCRIPTION
Provide sound controlling units mechanically mounted on a ceiling suspension system for acoustical treatment. The unit size, texture, finish, and color must be as specified. The location and extent of acoustical treatment shall be as shown on the approved detail drawings.
Submit drawings showing suspension system, method of anchoring and fastening, details, and reflected ceiling plan. Coordinate with paragraph RECLAMATION PROCEDURES for reclamation of mineral fiber acoustical ceiling panels to be removed from the job site.
1.2.1 Ceiling Attenuation Class and Test
Provide a ceiling system with an attenuation class (CAC) of not less than 35 for when determined in accordance with ASTM E1414/E1414M. Provide fixture attenuators over light fixtures and other ceiling penetrations, and provide acoustical blanket insulation adjacent to partitions, as required to achieve the specified CAC. Provide test ceiling continuous at the partition and assembled in the suspension system in the same manner that the ceiling will be installed on the project.
1.2.2 Ceiling Sound Absorption
Determine the Noise Reduction Coefficient (NRC) in accordance with ASTM C423 Test Method.
1.2.3 Light Reflectance
Determine light reflectance factor in accordance with ASTM E1477 Test Method.
1.2.4 Other Submittals Requirements
The following shall be submitted:
a. Manufacturer's data indicating percentage of recycle material in acoustic ceiling tiles to verify affirmative procurement compliance.
b. Total weight and volume quantities of acoustic ceiling tiles with recycle material.
Reports by an independent testing laboratory attesting that acoustical ceiling systems meet specified fire endurance and sound transmission requirements. Data attesting to conformance of the proposed system to Underwriters Laboratories requirements for the fire endurance rating listed in UL Fire Resistance may be submitted in lieu of test reports.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
SECTION 09 51 00 Page 2
DAFB BUILDING 20
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-03 Product Data
Acoustical Ceiling Systems Certification
SD-07 Certificates
Acoustical Units Acoustic Ceiling Tiles
1.4 DELIVERY, STORAGE. AND HANDLING
Deliver materials to the site in the manufacturer's original unopened containers with brand name and type clearly marked. Carefully handle and store materials in dry, watertight enclosures. Immediately before installation, store acoustical units for not less than 24 hours at the same temperature and relative humidity as the space where they will be installed in order to assure proper temperature and moisture acclimation.
1.5 ENVIRONMENTAL REQUIREMENTS
Maintain a uniform temperature of not less than 60 degrees F nor more than 85 degrees F and a relative humidity of not more than 70 percent for 24 hours before, during, and 24 hours after installation of acoustical units.
1.6 SCHEDULING
Complete and dry interior finish work such as plastering, concrete and terrazzo work before ceiling installation. Complete mechanical, electrical, and other work above the ceiling line; install and start operating heating, ventilating, and air conditioning systems in order to maintain temperature and humidity requirements.
1.7 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a one year period. Include an agreement to repair or replace acoustical panels that fail within the warranty period in the standard performance guarantee or warranty. Failures include, but are not limited to, sagging and warping of panels; rusting and manufacturers defects of grid system.
1.8 EXTRA MATERIALS
Furnish spare tiles, from the same lot as those installed, of each color at the rate of 5 tiles.
PART 2 PRODUCTS
2.1 ACOUSTICAL UNITS
Submit two samples of each type of acoustical unit and each type of suspension grid tee section showing texture, finish, and color. Conform
SECTION 09 51 00 Page 3 acoustical units to ASTM E1264, Class A, and the following requirements:
2.1.1 Units for Exposed-Grid System
a. Type: III (non-asbestos mineral fiber with painted finish) .
b. Flame Spread: Class A, 25 or less
c. Pattern: CD (for non-administrative/office type spaces) and F (for administrative office type spaces).
d. Minimum NRC: 0.75 in open office areas; 0.60 in conference rooms, executive offices, teleconferencing rooms, and other rooms as designated; 0.50 in all other rooms and areas when tested on mounting Type E-400 of ASTM E795.
e. Minimum Light Reflectance Coefficient: LR-1, 0.75 or greater.
f. Nominal size: 24 by 24 inch.
g. Edge detail: Beveled Tegular.
h. Finish: Factory-applied standard finish.
i. Minimum CAC: 40.
2.2 SUSPENSION SYSTEM
Provide standard width flange 15/16 inch suspension system conforming to ASTM C635/C635M . Provide surfaces exposed to view of aluminum with a clear anodized finish . Provide wall molding having a flange of not less than 15/16 inch . Provide inside and outside corner caps . Suspended ceiling framing system must have the capability to support the finished ceiling, light fixtures, air diffusers, and accessories, as shown. Provide a suspension system with a maximum deflection of 1/360 of the span length.
Conform seismic details to the guidance in UFC 3-310-04 and ASTM E580/E580M.
2.3 HANGERS
Provide hangers and attachment capable of supporting a minimum 300 pound ultimate vertical load without failure of supporting material or attachment.
2.3.1 Wires
Conform wires to ASTM A641/A641M, Class 1, 0.11 inch in diameter.
ASTM A580/A580M, composition 302 or 304, condition annealed stainless steel, 0.11 inch in diameter.
2.4 ACCESS PANELS
Provide access panels that match adjacent acoustical units, designed and equipped with suitable framing and fastenings for removal and replacement without damage. Size panel to be not less than 12 by 12 inch or more than 12 by 24 inch.
a. Attach an identification plate of 0.032 inch thick aluminum, 3/4 inch in diameter, stamped with the letters "AP" and finished the same as the unit, near one corner on the face of each access panel.
SECTION 09 51 00 Page 4
b. Identify ceiling access panel by a number utilizing white identification plates or plastic buttons with contrasting numerals.
Provide plates or buttons of minimum 1 inch diameter and securely attached to one corner of each access unit. Provide a typewritten card framed under glass listing the code identification numbers and corresponding system descriptions listed above. Mount the framed card where directed and furnish a duplicate card to the Contracting Officer. Code identification system is as follows:
1 Fire detection/alarm system
2 Air conditioning controls
3 Plumbing system
4 Heating and steam systems
5 Air conditioning duct system
6 Sprinkler system
7 Intercommunication system
11 Program entertainment
12 Telephone junction boxes
2.5 FINISHES
Use manufacturer's standard textures, patterns and finishes as specified for acoustical units and suspension system members. Treat ceiling suspension system components to inhibit corrosion.
2.6 COLORS AND PATTERNS
Use colors and patterns for acoustical units and suspension system components as indicated on drawings..
2.7 ACOUSTICAL SEALANT
Conform acoustical sealant to ASTM C834, nonstaining.
PART 3 EXECUTION
3.1 INSTALLATION
Examine surfaces to receive directly attached acoustical units for unevenness, irregularities, and dampness that would affect quality and execution of the work. Rid areas, where acoustical units will be cemented, of oils, form residue, or other materials that reduce bonding capabilities of the adhesive. Complete and dry interior finish work such as plastering, concrete, and terrazzo work before installation. Complete and approve mechanical, electrical, and other work above the ceiling line prior to the start of acoustical ceiling installation. Provide acoustical work complete with necessary fastenings, clips, and other accessories required for a complete installation. Do not expose mechanical fastenings in the finished work. Lay out hangers for each individual room or space. Provide hangers to support framing around beams, ducts, columns, grilles, and other
SECTION 09 51 00 Page 5 penetrations through ceilings. Keep main runners and carrying channels clear of abutting walls and partitions. Provide at least two main runners for each ceiling span. Wherever required to bypass an object with the hanger wires, install a subsuspension system so that all hanger wires will be plumb.
3.1.1 Suspension System
Install suspension system in accordance with ASTM C636/C636M and as specified herein. Do not suspend hanger wires or other loads from underside of steel decking.
3.1.1.1 Plumb Hangers
Install hangers plumb and not pressing against insulation covering ducts and pipes. Where lighting fixtures are supported from the suspended ceiling system, provide hangers at a minimum of four hangers per fixture and located not more than 6 inch from each corner of each fixture.
3.1.2 Wall Molding
Provide wall molding where ceilings abut vertical surfaces. Miter corners where wall moldings intersect or install corner caps. Secure wall molding not more than 3 inch from ends of each length and not more than 16 inch on centers between end fastenings. Provide wall molding springs at each acoustical unit in semi-exposed or concealed systems.
3.1.3 Caulking
Seal all joints around pipes, ducts or electrical outlets penetrating the ceiling. Apply a continuous ribbon of acoustical sealant on vertical web of wall or edge moldings.
3.2 CLEANING
Following installation, clean dirty or discolored surfaces of acoustical units and leave them free from defects. Remove units that are damaged or improperly installed and provide new units as directed.
-- End of Section --