Responses to Questions - 27 Mar 09.doc
DOC document 23 KB Posted
- Attached to
- Repair/Renovate Dorm 748 (USMC)
- Solicitation number
- FA4460-09-B-0001
About this file
Response to unanswered RFI #21 from yesterday's posting.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Responses to Questions - 2 April 09-2.doc | DOC document | |
| Responses to Questions - 2 April 09.doc | DOC document | |
| Responses to Questions - 1 April 09.doc | DOC document | |
| Responses to Questions - 31 March 09.doc | DOC document | |
| 11 A-8 Layout1 | — | |
| RFI 39 Supporting Photo.JPG | JPG image | |
| Site Visit Attendees.doc | DOC document | |
| 08 87 16 FRAGMENT RETENTION FILM FOR GLASS.doc | DOC document | |
| 28 31 00 FIRE DETECTION AND ALARM SYSTEMS.doc | DOC document | |
| Responses to Questions - 26 Mar 09.doc | DOC document | |
| Responses to Questions - 13 Mar.doc | DOC document | |
| Amendment 1.pdf | ||
| drawings.pdf | ||
| Attachment 2 EMIS Instruction Guide.doc | DOC document | |
| 97 - 2003 Schedule of Material Submittals.xls | XLS spreadsheet | |
| Solicitation FA4460-09-B-0001.doc | DOC document | |
| Attachment 1 - WAGE DETERMINATION 080175 23 JAN 09.docx | DOCX document | |
| Attachment 3 Addendum to MOA.doc | DOC document | |
| Attachment 4 C&D Report.doc | DOC document | |
| SPEC NKAK 09-1025 REPAIR RENOVATE DORM 748 | — |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA4460-09-B-0001
NKAK 09-1025
Repair/Renovate Dorm 748 (USMC)
Little Rock AFB, AR
Responses to Questions
27 March 2009
RFI #21: Fire suppression lines that are shown on detail 2/A-3 shows a new fur down to be built on the inside of the occupant walls at the ceiling. There are a couple of problems with this: (a) in some of the rooms the 7” dimension shown from the ceiling to the bottom of the fur down will cover a portion of the air grill in those rooms and (b) where the new ductwork from the new air handling unit runs through the chase, the new line shows going through it. Where should the line be ran instead of what is shown?
Response # 21 Depth of the fur-down may be extended downward to approximately 12” (=/-) to allow for the sprinkler pipe run. Existing grilles will have to be ducted out the 8" in galvanized exterior insulated metal duct work with new grilles.