FA3047-12-T-0010 Bidder Q A
31 KB Posted
- Attached to
- Replace Existing 300 KVA Transformer Bldg 6300
- Solicitation number
- FA3047-12-T-0010
About this file
FA3047-12-T-0010 Answers to Questions 1-7 for Transformer Project.
Text of this file
802 CONS/LGCAB
FA3047-12-T-0010
Lackland AFB, TX
Replace Existing Transformer B6300, WO# 41977
QUESTIONS & ANSWERS (#1)
(21 Aug 12) Question 1: Will the contractor or the local utility company supply the new transformer, high voltage switch, and 45’ Class 2 pole with pole top hardware and terminations?
Government Response: There is no electrical utility company at LAFB, only CES.
Contractor shall furnish all of the materials for this project. They will be removing a high voltage switch/transformer from the BLDG; the new work will require cutouts with fuses on the pole. See Amendment 0001 for FA3047-12-T-0010, Section J – Attachment 6, Typical Pole Installation 23 Aug 12.
Question 2: If the prospective contractor is to supply the new transformer, is there a more detailed specification for the new transformer than was provided in the SOW dated 11 August 2012?
Government Response: See Amendment 0001 for FA3047-12-T-0010, Section J – Attachment 5, Detail Spec Sheet 23 Aug 12.
Question 3: Please provide a site plan of the project parking lot & mechanical yard of Building #6300.
Government Response: See Amendment 0001 for FA3047-12-T-0010, Section J – Attachment 4, Existing and New B6300 Design dated 23 Aug 12.
Question 4: Please provide a detail of an acceptable Transformer Pad construction from the Base Electric company, showing dimensions, thickness, support beams, safety bollards that may be required.
Government Response: See Amendment 0001 for FA3047-12-T-0010, Section J – Attachment 1, Revised Statement of Work dated 24 Aug 12.
Question 5: Does the existing transformer contain PCB that will require hazardous disposal?
Government Response: The existing transformer is NON PCB.
Question 6: Please provide a contact for the LAFB Electric company that we can coordinate the installation of the new power pole & shut down of the existing service.
Government Response: Paragraph # 2.3 of the SOW have the contacts names and phone numbers.
Question 7: Is there a detailed specification, regarding the high voltage switch for the transformer,that can be provided?
Government Response: There is not a high voltage switch in the new installation; Cutouts are standard for this installation. See Amendment 0001 for FA3047-12-T-0010, Section J – Attachment 6, Typical Pole Installation dated 23 Aug 12.