This document is a Construction Manager at Risk (CMAR) Guaranteed Maximum Price (GMP) Amendment between the State of Arizona, specifically the Department of Administration's General Services Division, and Concord General Contracting, Inc. The amendment is related to the ARPA State Parks Water and Wastewater Upgrades project, specifically focusing on the Buckskin Mountain State Park Valve Replacement. The contract is identified by APP Contract No. CTR0066685, with the amendment dated December 20, 2024, and is associated with Agency Project No. PCS-22-091.
The GMP amendment establishes a guaranteed maximum price of $700,912.00 for the Buckskin Mountain State Park Valve Replacement. This amount includes site utilities for Greensand Plus Filters, performance and payment bond, general liability and builders risk insurance, and the contractor's fee. The total contract value, including the original pre-construction agreement, is now $960,204.00. The project involves installing four 36-inch vertical filter tanks with specific technical requirements, including ASME code construction, inlet and air wash distributors, gravel support beds, GreensandPlus and anthracite media, valve systems, and associated equipment. The work is to be completed with specific technical specifications for tank construction, media installation, and system components.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXHIBIT U
CONSTRUCTION MANAGER AT RISK
GUARANTEED MAXIMUM PRICE
(GMP) AMENDMENT
State of Arizona
General Services Division 1400 W. Washington St., Ste. B200
Phoenix, AZ 85007
APP Contract No. CTR0066685 Agreement No. 1
Date of Agreement:
December 20, 2024
Agency Project No:
PCS-22-091
Statutory Review No: PCS-22-091 Project Name: ARPA State Parks Water and Wastewater Upgrades
Construction Manager at Risk GMP Amendment
REV 02072023
The State of Arizona, (DEPARTMENT OF ADMINISTRATION, GENERAL SERVICES DIVISION), and (CONCORD GENERAL CONTRACTING, INC., hereby amend the Agreement to establish a Guaranteed Maximum Price.
Project Sites Address: Cattail Cove, Alamo Lake, River Island, Buckskin Mountain, Lake Havasu City, and Deadhorse State Parks
Agency: Department of Administration, General Services Division Agency Address: 1400 W. Washington St., Ste. B200
Phoenix, AZ 85007
Agency’s Representative Email:
Telephone Number:
Britt Olachea britt.olachea@azdoa.gov
(602) 552-3355
Agency Procurement Officer:
Dustin Deason
Dustin.deason@azdoa.gov
(480) 772-3446
Design Professional Firm: Kimley-Horn Design Professional of Record
Ray Montoya ray.montoya@kimley-horn.com
(520) 730-4558
Design Professional Firm:
Design Professional of Record Email:
Telephone Number:
Design Professional Firm:
Design Professional of Record:
EPS Group Mike LoTempio mike.lotempio@epsgroupinc.com
(602) 828-9662
Entellus, Inc.
Will Janiga
Contractor Name:
Contractor Address:
Contractor Project Manager:
wjaniga@entellus.com
(480) 298-5266
Concord General Contracting 2240 W. Broadway Rd., Suite 105 Mesa, AZ 85202
Jason Beaver jbeaver@concondinc.com
(480) 258-1361 c or (480) 962-8080 o
Docusign Envelope ID: B91422D9-7AB2-4844-9F6E-D98F7F31F0E6 mailto:ray.montoya@kimley-horn.com
(GMP) AMENDMENT
State of Arizona
General Services Division 1400 W. Washington St., Ste. B200
Phoenix, AZ 85007
APP Contract No. CTR0066685 Agreement No. 1
Date of Agreement:
December 20, 2024
Agency Project No:
1.0 CONSTRUCTION SERVICES GUARANTEED MAXIMUM PRICE
1. This Amendment # 1 establishes a Guaranteed Maximum Price (“GMP”) and Construction Phase Fee for Construction Services and incorporates such terms into the Agreement, making the Agreement effective for Construction Phase Services:
a. The Guaranteed Maximum Price (“GMP”) for Construction Services, as defined under the Agreement for Buckskin Mountain State Park Valve Replacement, shall be Seven Hundred Thousand Nine Hundred Twelve Dollars and no cents ($700,912.00).
2. Attached to this Amendment and incorporated herein is an itemized statement of the GMP organized by line items, allowances, contingencies, alternates, the Construction Manager’s Fee, and any other items that comprise the GMP.
3. Summary of Agreement Total:
Original Exhibit A Agreement PreConstruction $ 259,292.00
Previous Amendments: $
This GMP 1 Amendment Alamo SP Valve Replacement $ 700,912.00
Total (Including this Amendment) $ 960,204.00
(GMP) AMENDMENT
State of Arizona
General Services Division 1400 W. Washington St., Ste. B200
Phoenix, AZ 85007
APP Contract No. CTR0066685 Agreement No. 1
Date of Agreement:
December 20, 2024
Agency Project No:
IN WITNESS WHEREOF, STATE OF ARIZONA, DEPARTMENT OF ADMINISTRATION, acting by and through the Agency procurement authority, and CONTRACTOR in connection with the Project, have executed this Agreement as of the date set forth in the date of Agreement signed by the authorized Agency Procurement Officer.
CONTRACTOR: CONCORD GENERAL CONTRACTING, INC.
(Typed Name)
(Signature)
(Title)
(Date)
STATE OF ARIZONA, DEPARTMENT OF ADMINISTRATION:
(Typed Name)
(Signature)
(Title)
(Date)
END OF CONSTRUCTION MANAGER AT RISK GUARANTEED MAXIMUM PRICE AMENDMENT
21-Dec-24 | 8:54 AM EST
Vice President/COO
JASON BEAVER
Dustin Deason
Procurement Manager
21-Dec-24 | 7:27 AM MST
ENGAGE.
BUILD.
DELIVER.
BUSKSKIN MOUNTAIN STATE PARK
Water Treatment and Restroom Upgrades
PCS-22-091 GMP #1 Estimate
November 26, 2024
TABLE OF CONTENTS
TAB 1
TAB 2
TAB 3
� TAB 4SUBCONTRACTOR BID
CLARIFICATIONS
SCHEDULE OF VALUES
ESTIMATE LETTER
Estimate Letter
TAB 1
November 26, 2024
Arizona Department of Administration PCS-22-091 Buckskin State Park Attn: Britt Olachea 5476 N Highway 95 Parker, AZ 85344
RE: GMP #1 Estimate
Dear Britt:
Attached is our package for the GMP #1 estimate of the Buckskin Mountain State Park and associated site work.
This estimate represents the drawings and specification and is to be used as a project budget for the specified items. We have utilized our knowledge from similar projects, the current construction market and subcontractor input to put together the schematic estimate. The estimate presented in this package represents a budget for the project based off the current information.
We have included a schedule of values, written narrative, as well as various On-Screen takeoffs.
We look forward to continuing working with the project team on this exciting project. If you have any questions or need further information, please feel free to contact me at any time.
Sincerely, Concord General Contracting, Inc.
Jason Beaver Derick Aidoo Vice President/COO Director of Estimating
Attachments
Schedule of Values
TAB 2
11/26/2024
GMP #1 - Greensand Plus Filters
PCS-22-091 Bucksin Mountain State Park 5476 N Highway 95 Parker, AZ 85344
Item
DIVISION 33 - SITE UTILITIES
1 Site Utilities - Greensand Plus Filters $618,000
2 Subtotal $618,000
3 Performance & Payment Bond $7,469
4 General Liability Insurance 1.25% $8,761
5 Builders Risk Insurance 0.4% $2,804
6 Contractors Fee 5.0% $35,046
7 Subtotal $672,080
8 Sales Tax - (Parker, AZ) 4.29% $28,832
9 TOTAL $700,912
$700,912UPDATED TOTALS WITH ALTERNATES
Description Of Work Bid
Clarifications
TAB 3
Buckskin Mountain State Park
Parker, Arizona
11/26/2024
CLARIFICATIONS
1. This “GMP#1 Estimate” is based on the quote from Hungerford & Terry, Inc and Sample
Specification by EPS.
2. Includes General Contractor General Liability.
3. Includes Builders Risk Insurance for the value of new work.
4. Includes a performance and payment bond.
5. Excludes handling and removal of any contaminated, hazardous, or unsuitable materials.
6. Excludes inspection fees, tap fees, agency fees, bonds, and special inspection charges.
7. Excludes water and sewer development fees.
8. Excludes building permit and plan check fees.
9. Excludes any variance application fees, and architectural / engineering filling fees.
10. Excludes cad as-built drawings.
11. Excludes all furniture, fixtures & equipment (FFE) not listed.
12. Excludes SRP/APS development fees.
13. Excludes special system monitoring.
14. Excludes phone line.
15. Includes all low voltage work.
16. Pricing assumes work will take place during normal business hours.
NARRATIVE SCOPE OF WORK
Architecture and Engineering
• Does not include SRP/APS, architectural, structural engineering, landscape, civil engineering, mechanical, electrical design, and fees.
Regulatory Requirements
• Project design and construction shall conform to all state and local regulations. General Liability Insurance, Workmen’s Compensation will be maintained for the duration of the project.
Construction Closeout
• The project site will be left free from debris and materials related to the work performed on this project.
• Any training will be provided to the owner as specified.
• A complete set of project record documents to include Owner’s manuals, warranties, and as built drawings per ADOA closeout requirements.
DIVISION 33 – SITE UTILITIES
Site Utilities – Greensand Plus Filters
• Four (4) 36” OD x 63” straight shell vertical filter tanks.
120 PSI design pressure
ASME code section VIII construction with stamp.
One (1) 14 inch x 18 inch elliptical manway with spare gasket.
Necessary flanged nozzle type connections.
Four (4) lifting lugs.
Four (4) structural steel I-beam type supports.
Tank interiors will be white metal sandblasted (SSPC-SP10) and lined with a
Tnemec Series 21 NSF61-600 certified coating system.
Tank exteriors will be commercial sandblasted (SSPC-SP6) and painted with one
(1) shop coat (1.5–3 mils DFT) of Tnemec Series N69 primer and two (2) coats (2.5 mils DFT/coat) of Sherwin-Williams Pro Industrial Enamel 100 series B54Z.
Finish painting of the filter tank exteriors and all provided piping is to be field applied by the contractor in accordance with the painting section of the specifications.
Per ASME Sect. VIII UG-125 a) and g) the customer shall furnish and install pressure relief devices on all pressure sources to our system.
Four (4) H-Type inlet distributor/waste collectors with schedule 80 PVC pipe and fittings.
Four (4) Gravel retaining screens with 304 stainless steel support angles and flats, 8-mesh 304 stainless steel screen, and stainless-steel nelson studs as required to fasten the screen to the tank and supports.
Four (4) Header-lateral air wash distributors of schedule 40, 304 stainless steel construction complete with manifolds and slotted laterals.
Four (4) Hub (polypropylene) curved radial lateral (schedule 80 PVC) underdrain distributor. Laterals are curved to follow the contour of the tank bottom heads.
The tank inlet and underdrain distributor will be shop installed by H&T prior to shipment.
Four (4) 12-inch graded gravel support beds.
Four (4) 18-inch beds of GreensandPlus.
Four (4) 18-inch beds of Anthracite.
H&T will provide approximately 136 one half cubic foot bags of graded gravel plus 5% extra, 200 one half cubic foot bags of GreensandPlus and 100 one cubic foot bags of Anthracite.
Four (4) Valve nest exteriors consisting of:
• Bray model 3W or model 20 butterfly control valves with wafer style cast iron bodies, nylon 11 coated ductile iron discs, metal reinforced EPDM seats, and Bray Series 70 (120VAC) electric motor operators with NEMA 4 enclosures, manual handwheel declutchable overrides, visual open/close indication, and integral heaters for: Inlet, outlet, backwash inlet/ slow refill-modulating, backwash outlet, rinse outlet, air pressurizing and air inlet.
• Bray model 3W butterfly valves with wafer style cast iron bodies, nylon 11 coated ductile iron discs and manual lever operators for: Inlet isolating, and outlet isolating.
• Apco model 200A or equal automatic single body air release valve with threaded ductile iron bodies and stainless-steel floats for: Tank air release
• Flow-Tek S80 or equal ball valves stainless steel and manual lever for:
Venting isolating, backwash tell-tale, and tank drain.
All piping will be Schedule 10 #304 stainless steel with schedule 10 butt weld #304 fittings and 150# #304 weld neck flanges.
• Air line from blower to the filter units
• Filter face piping.
• Filter interconnecting inlet header.
• Filter interconnecting waste header.
• Filter interconnecting outlet header.
All pipe supports for the interconnecting piping not located on a factory skidmounted unit will be included in GMP#2.
Start-Up Chemicals: For every 100 cubic feet of GreensandPlus, 20 gallons of 15% bleach, or 50 gallons of 6% bleach is required for conditioning of the media and disinfecting of the tanks.
Filter Pressure Equipment
• One (1) Ashcroft model D-400 snap acting differential pressure switch for the system common inlet and outlet with a NEMA 4 enclosure and stainless steel 3-valve manifold.
• Eight (8) Ashcroft model 1279AS pressure gauges for the tank inlet and outlets with 4.5-inch diameter dials and stainless-steel bourdon tubes.
• Nine (9) Sets of stainless-steel supply tubing. Nine (9) Sets of isolating valves.
• Nine (9) Sets of sampling valves.
Flow Equipment
• Four (4) Rosemount model 8750WA magnetic bi-directional flow meter, complete with 150 lb. flanged carbon steel process connections, with local display and 4-20 mA output and grounding rings. Filter inlets
Filter Air Blower
• One (1) Roots model RAI air blower rated 6 cfm complete with flexible connections, v-belt drive with guard, inlet filter/silencer, weight type pressure relief valve, motor slide rails, common steel baseplate, and a 3-phase, 60 hertz, TEFC motor.
• One (1) Check-Rite or equal check valve of steel construction for:
o The blower discharge
• One (1) Bray model 3W butterfly valves with wafer style cast iron bodies, nylon 11 coated ductile iron discs and manual lever operators for:
o The blower discharge
• One (1) Asco solenoid valve for:
o Blower condensation removal.
Air Blower Motor Starters
• One (1) Allen Bradley series 512 A-C-L combination motor starter with a NEMA 4 painted steel enclosure, fusible power disconnects, 480V/120V CPT, H-O-A switch, electronic overload relay, nameplates & etc.
Filter Control Panel
• One (1) NEMA 4X, electrical control panel of ANSI 61 stainless steel construction with an Allen Bradley PLC and OIT.
• Two (2) NEMA4X Junction boxes.
Programming integral to the operation of the equipment supplied by Hungerford & Terry, Inc. will be performed by Hungerford & Terry, Inc.
Skid numbers 1 and two will include two (2) greensand filtration system complete with internal distributors, exterior face piping and valves, and a NEMA 4X junction box or control panel on the skid with wiring and conduit to each electrical item.
Skid number 3 will include one (1) air scour blower mounted to the skid mounted NEMA 4 junction box, including NEMA 4 A-C-L motor starters with wiring and R.G.S. / flexible liquid-tite conduit to each electrical item.
Skid number 3 will include one (1) air scour blower mounted to the skid mounted NEMA 4 junction box, including NEMA 4 A-C-L motor starters with wiring and R.G.S. / flexible liquid-tite conduit to each electrical item.
The interiors of all lined tanks will be sandblasted to near white metal in accordance with SSPC-SP10. Lining will be as specified in the general description of the tanks.
The exteriors of all steel tanks will be commercial sandblasted in accordance with SSPC-SP6. Painting will be as specified in the general description of the tanks. Stainless steel and PVC piping will not be painted.
The exterior surface of all misc. valves, pumps, etc. will be furnished with the manufacturer’s standard prime coat painting or standard prime and finish painting.
Finish painting of all equipment furnished by Hungerford & Terry, Inc. is to be field applied by Concord’s contractor and will be included in GMP#2.
H&T will provide a service technician for 9 days over a period of 3 trips. These trips will include assistance for media installation and internal installation, startup, and training services.
If additional service is needed, H&T, Inc., will furnish a Field Supervisor at USD $1,200.00 per weekday of 8 consecutive hours or USD-$150.00 per hour.
Refer to Sample Specification by H&T, Inc.
Furnish and install pressure relief devices on all pressure sources to system will be included in GMP#2.
Any additional material or equipment required will be included in GMP#2.
Skid numbers one and two will include two (2) greensand filtration system complete with internal distributors, exterior face piping and valves, and a NEMA 4X junction box or control panel on the skid with wiring and conduit to each electrical item.
Skid number three will include one (1) air scour blower mounted to the skid mounted NEMA 4 junction box, including NEMA 4 A-C-L motor starters with wiring and R.G.S / flexible liquid-tite conduit to each electrical item.
See attached H&T Inc. proposal clarification.
Subcontractor Bid
TAB 4
Four (4) 3’ Diameter Greensand Plus filters with airwash and Assembled –
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 3
Pressure relief valves are to be provided by contractor. This is outside of H&T’s scope of supply
The general contractor will install the filter media on site. The life of the media is anticipated to be 7-10 years before needing replacement. This is dependent upon care and influent water quality.
Ductile iron piping is too large for the filter systems used. We could use welded steel as an option, but after labor and painting it is the same price to use sch.10 stainless steel.
Stainless steel is more durable so that is our recommendation.
Start up media seasoning is to be performed the contractor. Time is included in the proposal to oversee some of the media loading process, instructional time and assisting with putting the system into operation. An estimated three trips over a period of 9 days are anticipated.
Finish coating will be included, but touch up paint will need to be applied in the field.
The warrantee will cover 2 years per owner’s request.
H&T will guarantee treatment to the appropriate iron and manganese MCLs or 0.3 mg/L and 0.05 mg/L respectively.
Estimated Schedule:
Engineering time: 12 weeks
Tank assembly: 16 weeks
Control panel assembly: 35 weeks
System assembly and testing: 8 weeks
Anticipated Date of completion mid Nov 2025.
Invoicing will be as follows:
20% of the total contract price will be invoiced upon approval of submittals
35% of the total contract price will be invoiced upon start of assembly
40% of the total contract price will be invoiced upon delivery of equipment to job site
5% of the total contract price will be withheld for retainage.
Net Terms 30 days
COMMENTS
mailto:sales@hungerfordterry.com
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 4
NSF INTERNATIONAL:
The specifications on this project reference NSF 61 for drinking water components.
Our proposal includes as many NSF certified products as possible and commercially available, however there are structural items in our tank interiors that are not available with the NSF certification.
If the proposed materials for a component that will be in contact with the treated water does not have NSF/ANSI 61 certification, the component shall be constructed of material designated as an “acceptable material” in Annex C of the NSF/ANSI/CAN 61 Standard.
Examples of the above are items such as nuts/bolts/washers, screen, angles/flats, studs, etc. These items have been provided for many years in water treatment plants, are normally of #304 and #316 stainless steel, and do not carry the NSF certification.
Tanks that are specified to have an internal lining will be lined with an NSF-61-600 certified painting system.
1. SCOPE OF SUPPLY
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 5
VERTICAL GREENSANDPLUS FILTRATION SYSTEM:
FILTER TANKS:
Four (4) 36 inch OD x 63 inch straight shell vertical filter tanks designed in accordance with the following:
120 PSI design pressure.
ASME code section VIII construction with stamp.
One (1) 14 inch x 18 inch elliptical manway with spare gasket.
Necessary flanged nozzle type connections.
Four (4) lifting lugs.
Four (4) structural steel I-beam type supports.
Tank interiors will be white metal sandblasted (SSPC-SP10) and lined with a Tnemec Series 21 NSF61-600 certified coating system.
Tank exteriors will be commercial sandblasted (SSPC-SP6) and painted with one (1) shop coat (1.5–3 mils DFT) of Tnemec Series N69 primer and two (2) coats (2.5 mils DFT/coat) of Sherwin-Williams Pro Industrial Enamel 100 series B54Z.(by contractor)
NOTES:
1. Finish painting of the filter tank exteriors and all provided piping is to be field applied by the contractor in accordance with the painting section of the specifications.
2. All anchor bolts are part of the foundation equipment and shall be furnished and installed by the equipment installer or contractor.
3. Per ASME Sect. VIII UG-125 a) and g) the customer shall furnish and install pressure relief devices on all pressure sources to our system. Pressure relief valves are not included on each tank.
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 6
TANK INTERNAL DISTRIBUTORS:
Four (4) H-Type inlet distributor/waste collectors with schedule 80 PVC pipe and fittings.
Four (4) Gravel retaining screens with 304 stainless steel support angles and flats, 8-mesh 304 stainless steel screen, and stainless steel nelson studs as required to fasten the screen to the tank and supports.
Four (4) Header-lateral air wash distributors of schedule 40, 304 stainless steel construction complete with manifolds and slotted laterals.
Four (4) Hub (polypropylene), curved radial lateral (schedule 80 PVC) underdrain distributor. Laterals are curved to follow the contour of the tank bottom heads.
NOTES:
1. The tank inlet and underdrain distributors will be shop installed by H&T prior to shipment.
FILTER MEDIA:
Four (4) 12 inch graded gravel support beds
Four (4) 18 inch beds of GreensandPlus.
Four (4) 18 inch beds of Anthracite.
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 7
NOTES:
1. The GreensandPlus will meet the following criteria:
a) Specific gravity: ………..approx. 2.4
b) Effective size: ……….….0.30 – 0.35 mm
c) Uniformity coefficient: …less than 1.6
d) Screen grading: ….……. 18 x 60 mesh
The Anthracite will meet the following criteria:
a) Specific gravity: …….….approx. 1.6
b) Effective size: …………..0.6 – 0.8 mm
c) Uniformity coefficient: …less than 1.6
2. All filter media is to be field installed by the contractor.
3. H&T will provide approximately 136 one half cubic foot bags of graded gravel plus 5% extra, 200 one half cubic foot bags of GreensandPlus and 100 one cubic foot bags of Anthracite.
4. GreensandPlus and anthracite are available in bulk sacks if desired. Bulk sacks are a special order and if desired we would require notice upon receipt of an order.
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 8
FILTER EXTERIORS:
Four (4) Valve nest exteriors consisting of:
Bray model 3W or model 20 butterfly control valves with wafer style cast iron bodies, nylon 11 coated ductile iron discs, metal reinforced EPDM seats, and Bray Series 70 (120VAC) electric motor operators with NEMA 4 enclosures, manual handwheel declutchable overrides, visual open/close indication, and integral heaters for:
Inlet Outlet Backwash inlet/ slow refill- modulating Backwash outlet Rinse outlet Air pressurizing Air inlet
Bray model 3W butterfly valves with wafer style cast iron bodies, nylon 11 coated ductile iron discs and manual lever operators for:
Inlet isolating Outlet isolating
Apco model 200A or equal automatic single body air release valve with threaded ductile iron bodies and stainless steel floats for:
Tank air release
Flow-Tek S80 or equal ball valves stainless steel and manual lever for:
Vent isolating Backwash tell-tale Tank drain
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 9
SYSTEM FACE AND INTERCONNECTING PIPING:
Piping:
All piping will be Schedule 10 #304 stainless steel with schedule 10 butt weld #304 fittings and 150# #304 weld neck flanges.
Air line from blower to the filter units Filter face piping.
Filter interconnecting inlet header.
Filter interconnecting waste header.
Filter interconnecting outlet header.
Notes:
1. Pricing is based on the most compact arrangement of the units as practical.
2. All pipe supports for the interconnecting piping not located on a factory skid-mounted unit are to be furnished by the purchaser.
3. The extent of piping included by H&T, Inc. will be limited to the filter connecting headers. Piping to and from the headers is to be furnished by the contractor.
4. All system face and interconnecting piping will be furnished with the required bolts, studs, nuts, and gaskets as follows:
Bolts: ASTM A193 stainless steel.
Studs: ASTM A193 stainless steel.
Nuts: ASTM A194 stainless steel hex.
Gaskets: EPDM Shore 70 or equal, 1/8 inch thick.
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 10
AUXILIARY EQUIPMENT:
START-UP CHEMICALS:
For every 100 cubic feet of GreensandPlus, 20 gallons of 15% bleach, or 50 gallons of 6% bleach is required for conditioning of the media and disinfecting of the tanks.
NOTE:
All start-up chemicals are to be supplied by the purchaser or contractor.
FILTER PRESSURE EQUIPMENT:
One (1) Ashcroft model D-400 snap acting differential pressure switch for the system common inlet and outlet with a NEMA 4 enclosure and stainless steel 3-valve manifold.
Eight (8) Ashcroft model 1279AS pressure gauges for the tank inlet and outlets with 4.5 inch diameter dials and stainless steel bourdon tubes.
Nine (9) Sets of stainless steel supply tubing.
Nine (9) Sets of isolating valves.
Nine (9) Sets of sampling valves.
FLOW EQUIPMENT:
Four (4) Rosemount model 8750WA magnetic bi-directional flow meter, complete with 150 lb. flanged carbon steel process connections, with local display and 4-20 mA output and grounding rings.
Filter inlets
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 11
FILTER AIR BLOWER:
One (1) Roots model RAI air blower rated 6 cfm complete with flexible connections, v-belt drive with guard, inlet filter/silencer, weight type pressure relief valve, motor slide rails, common steel baseplate, and a 3-phase, 60 hertz, TEFC motor.
One (1) Check-Rite or equal check valve of steel construction for:
The blower discharge
One (1) Bray model 3W butterfly valves with wafer style cast iron bodies, nylon 11 coated ductile iron discs and manual lever operators for:
The blower discharge
One (1) Asco solenoid valve for:
Blower condensation removal.
Air Blower Motor Starters:
One (1) Allen Bradley series 512 A-C-L combination motor starter with a NEMA 4 painted steel enclosure, fusible power disconnect, 480V/120V CPT, H-O-A switch, electronic overload relay, nameplates & etc.
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 12
Filter Control Panel:
One (1) NEMA 4X, electrical control panel of ANSI 61 stainless steel construction with an Allen Bradley PLC and OIT
Two (2) NEMA4X Junction boxes
System Software/Programming equipment:
Programming integral to the operation of the equipment supplied by Hungerford & Terry, Inc. will be performed by Hungerford & Terry, Inc. Should the customer choose to modify the original factory program, a laptop computer and a registered copy of Allen Bradley RSLOGIXS 5000 PLC & Allen Bradley OIT software will be required.
SKID MOUNTING AND SHOP ASSEMBLY
Skid Numbers 1&2:
Skid numbers 1 and two will include two (2) greensand filtration system complete with internal distributors, exterior face piping and valves, and a NEMA 4X junction box or control panel on the skid with wiring and conduit to each electrical item.
Skid Number 3:
Skid number 3 will include one (1) air scour blower mounted to the skid mounted NEMA 4 junction box, including NEMA 4 A-C-L motor starters with wiring and R.G.S. / flexible liquid-tite conduit to each electrical item.
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 13
HUNGERFORFORD AND TERRY, INC. STANDARD SURFACE PREPARATION AND
SYSTEM PAINTING:
LINED TANKS:
The interiors of all lined tanks will be sandblasted to near white metal in accordance with SSPC-SP10. Lining will be as specified in the general description of the tanks.
TANK EXTERIORS AND PIPING:
The exteriors of all steel tanks will be commercial sandblasted in accordance with SSPC-SP6.
Painting will be as specified in the general description of the tanks. Stainless steel and PVC piping will not be painted.
MISC. EQUIPMENT:
The exterior surface of all misc. valves, pumps, etc. will be furnished with the manufacturer’s standard prime coat painting or standard prime and finish painting.
FINISH PAINTING:
Unless specifically mentioned above, finish painting of all equipment furnished by Hungerford & Terry, Inc. is to be field applied by the installation contractor
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 14
Price: 618,000 Six Hundred and Eighteen Thousand Dollars
F.O.B. Shipping Points: With full motor freight allowed to the jobsite:
Payable in US currency, plus any applicable Municipal, State or Federal Taxes.
Payment Terms:
TBD
Net thirty (30) days. All invoices are due within 30 days. A service or interest charge of 1 ½% per month (18% per annum) will be assessed on all amounts which become past due.
A copy of the payment bond (if applicable) will be required as part of the credit approval process. Purchaser agrees to make pro rata payments for partial shipments and further agrees that if shipment of material is delayed by any act or omission on part of purchaser, payment shall become due within thirty (30) days after the material is ready for shipment
Shipment:
Applicable freight to location is included in the price of the contract. Logistics of shipment will be advised as project proceeds.
Acceptance by Purchaser HUNGERFORD & TERRY, INC.
This proposal is hereby accepted by:
Christopher Ralph
- Inside Sales Manager
Date By___________________________
2. PRICE SUMMARY
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 15
Prices are based on present day labor and material costs and subject to revision after thirty days from date of quotation. They do not include any Federal, State, Municipal or other tax or Government charge applicable to the sale, shipment or use of equipment quoted on.
Deliveries are contingent upon strikes, accidents, delays in manufacture and other causes beyond our control.
Any typographical or clerical errors in the prices or specifications are subject to correction.
Order shall be made out to Hungerford & Terry, Inc., Clayton, NJ, and shall be subject to acceptance by us at Clayton, NJ. After acceptance, orders may be cancelled only with our written consent and on terms that will indemnify us against loss. Equipment on material cannot be returned except by special permission and when so returned will be subject to discount.
The Company will, free of charge, replace or repair, after receipt f.o.b. its factory promptly and within one year from shipment by it, any part of equipment which, under normal or proper use proves to be defective in workmanship or material. In no event shall the Company be liable for consequential damages.
The Company shall not be liable for failure to perform or delay in performing any obligation if such failure or delay shall be caused directly or indirectly by invasion, insurrection, riot, war, military authority, or by fire, flood, strike, or labor difficulty or by any other cause, whether of the same or different nature from those enumerated, beyond our reasonable control.
From the time said machinery of apparatus or any part thereof arrives on the premises, and until Hungerford & Terry, Inc., for an amount equal to the unpaid portion of the purchase price of the same; such loss or damage to be payable to Hungerford & Terry, Inc., as its interests may appear. All losses by fire or other casualties for which Hungerford & Terry, Inc., is not indemnified and paid under such policies of insurance, shall be borne by the Purchaser on and after the arrival of said machinery or apparatus, or any part thereof on Purchaser's premises.
The title and right of possession of above described articles shall remain vested in Hungerford & Terry, Inc. until Purchaser shall have made full payment thereof in cash and this right shall not be waived by attachment of said articles to the real estate. Upon Purchaser's failure to make above agreed payments or any part thereof, Hungerford & Terry, Inc. is to retain any and all partial payments which may have been made as liquidated damages, and shall be entitled to take immediate possession of said materials.
This proposal, of which the Conditions of Sale are an integral part, shall not become a contract or become binding until it has been approved and signed by a representative of Hungerford & Terry, Inc. at its home office, Clayton, NJ. Persons signing on behalf of purchaser hereby represent that they are legally authorized to enter into this contract.
3. CONDITIONS
Buckskin WTP H&T Budgetary Proposal - BDJ72889- PCS-22-091
HUNGERFORD & TERRY, INC.
226 N. ATLANTIC AVE
CLAYTON, NEW JERSEY 08312-0650
PHONE: 856-881-3200 FAX 856-881-6859
EMAIL: sales@hungerfordterry.com
PG. 16
H&T will provide a service technician for 9 days over a period of 3 trips. These trips will include assistance for media installation and internal installation, startup, and training services.
If additional service is needed, Hungerford & Terry, Inc., will furnish a Field Supervisor at USD- $1,200.00 per weekday of 8 consecutive hours or USD-$150.00 per hour, coinciding with the Purchaser's regular business hours during the normal work week of Monday through Friday including traveling time, plus living and traveling expenses from date of departure from Clayton, NJ, to destination and return. All time in excess of 8 hours shall be charged at 1-1/2 times the daily rate and all traveling and living expenses will be charged at cost. Meal charge is USD-$50.00 per day.
All overtime will be charged at 1-1/2 times the daily rate.
PLEASE NOTE: The Purchaser will be charged for the services of the Field Supervisor at the jobsite when service cannot be rendered because of delay or conditions beyond Hungerford &
Terry's control. In cases of undue delay, Hungerford & Terry reserves the right to recall the supervisor.
HUNGERFORD & TERRY, INC.
PER:
Christopher Ralph- Inside Sales Manager
DATE:
ACCEPTED:
PER:
TITLE:
DATE:
4. FIELD SERVICE CHARGES
SAMPLE SPECIFICATIONS
FOR:
BUCKSKIN MOUNTAIN STATE PARK
GREENSAND-PLUS PRESSURE FILTER SYSTEM:
I. DESCRIPTION:
A. This section of the specifications provides for an automatic pressure type filtration system complete and operable as indicated on the drawings and as specified herein.
B. The following items shall be included in this section and are to be furnished by the water treatment equipment manufacturer:
1. Treatment Vessels
2. Inlet Distributor/Waste Collectors
3. Airwash Distributors
4. Underdrain Distributors
5. Support Gravel
6. Filtration Media
7. Control and Isolating Valves
8. Filter Face Piping
9. System Interconnecting Piping 10.Air Blower 11.Reclaim system 12.Control Panel 13.Equipment Assembly
C. All interconnecting wiring and conduit, motor starters, and appurtenant electrical work running up to the filtration system shall be furnished and installed by the general contractor in accordance with specification section
( ), "ELECTRICAL WORK".
II. REQUIREMENTS:
A. The treatment system shall be furnished by a single manufacturer who is an established manufacturer of water treatment systems and who shall:
1. The filter supplier must be an American owned and operated company and furnish proof of successful operating experience during the last ten (10) years on ten (10) municipal installations comparable in size and flow rate to that specified herein.
2. Accept responsibility for the satisfactory operation of the entire filtration system and equipment.
3. Guarantee for a period of two (2) year from the date of acceptance that all equipment is free from defects in design, materials, and workmanship. Furnish replacement parts for any defective component at no cost to the owner.
B. Alternates will need to provide the following information in order to be considered.
1. Custom, CAD generated shop drawings pertinent to this specific application showing interconnections of the components in the system, including scaled double line piping drawings (schematics will not be acceptable), control logic schematic/wiring diagrams, control panel drawings to include front panel view, internal wiring detail, and panel internal arrangements, control panel equipment charts, equipment arrangements, installation and erection details, anchor bolts, equipment pads, etc.
2. Proposed V&E list
3. Pilot lab report proving comparable treatment capability. The pilot lab shall be run for a minimum of 10 business days. The final report must be presented at least 14 business days prior to the closing of the bid.
C. The base bid shall be for a filter system as manufactured by Hungerford & Terry, Inc., Clayton, New Jersey, (856-881-3200) all in accordance with the following detailed specification and as shown on the drawings.
Should the bidding contractor wish to submit substitute equipment and/or materials, he must do so by listing the substitute equipment and/or materials in the bid. The contractor shall also list adjacent to the substitute equipment and/or material, the amount of monies that the Owner may deduct from the contractor's bid for accepting the substitute equipment and/or material. Only deducts will be acceptable to the Owner.
This proposed substitution shall not constitute an alternate bid.
D. All of the bidding contractors are required to submit their bids, based on the specified equipment. A contract will be awarded based on the lowest responsible bidder (not including substitutions), and only to a bidder who has based his bid on all specified equipment and/or material.
E. Only after the award of the contract to the lowest responsible bidder will the owner examine "substitutions" listed by the bidding contractor. Should the owner feel that the substitute equipment and/or material submitted is not of his selection, standards, liking, or the amount of monies offered as a deduct for the use of the substitute equipment and/or materials is of an insufficient amount, then the bidding contractor will be expected to furnish and install the specified equipment and/or material.
F. The contractor shall also submit with his bid sufficient detailed information pertaining to each substitute piece of equipment and/or material that the contractor has listed as a "substitute" in the proposal.
G. Failure to submit information on substitute equipment and/or materials at the time that the proposal is received by the owner, is cause for rejection of the proposed substitute, and only the specified equipment and/or materials will be permitted to be incorporated in the finished project.
H. It is the intention of these specifications that the pressure filter specified in this section shall be furnished as part of a coordinated system supplied by a single manufacturer so that undivided responsibility for a complete and operable system is assured. The pressure filter manufacturer shall be the coordinating supplier of the pressure filter system. The pressure filter system shall include the pressure filters and all other equipment and accessories specified herein.
III. SUBMITTALS:
A. The filtration equipment supplier shall submit to the Engineer a pdf.
document with complete sets of shop drawings, details, data sheets, and other descriptive drawings and material as may be required to fully describe the equipment proposed and to verify compliance with the contract documents.
B. All submittals shall be complete, neat, and orderly. The submittals shall include the following, as applicable:
1. Custom, CAD generated shop drawings pertinent to this specific application showing interconnections of the components in the system, including scaled double line piping drawings (schematics will not be acceptable), control logic schematic/wiring diagrams, control panel drawings to include front panel view, internal wiring detail, and panel internal arrangements, control panel equipment charts, equipment arrangements, installation and erection details, anchor bolts, equipment pads, etc.
2. Detailed descriptions of each piece of equipment specified.
3. Description of the operation and control of the equipment along with an annotated copy of the control logic program.
4. Four (4) copies of operation and maintenance requirements for the system.
IV. PERFORMANCE AND DESIGN REQUIREMENTS:
A. The pressure filter system shall be specifically designed to provide filtration and treatment for iron and manganese removal from groundwater. The filter media shall consist of GreensandPlus and anthracite. A sodium hypochlorite chemical feed system shall serve to catalytically regenerate the Greensand Plus. The chemical feed system is to be supplied by installing contractor
B. Design requirements are as follows:
1. The pressure filter equipment shall be designed based on the following requirements:
a. System design flow rate 91 GPM
b. Unit design flow rate 23 GPM
c. Filter loading rate at design flow 4.3 GPM/FT2
d. Normal maximum operating pressure 100 PSI
e. Influent water quality:
Iron 0.215 mg/L, avg Manganese 1.62 mg/L, avg
2. The pressure filter backwash water source is to be a separate filtered water source. Temperature of the backwash water estimated to be 70 degrees F.
a. Normal filter backwash rate...... 17 GPM/FT2 @ 76 deg. F.
3. The system is guaranteed to produce an effluent quality for iron and manganese below that of the MCL. The MCL for iron is 0.3 mg/L and 0.05 mg/L for manganese.
V. EQUIPMENT DESIGN:
A. FILTER TANKS:
1. System will consist of four (4) vertical pressure filters, 36 inch O.D.
by 63 inch straight shell.
2. The filter tanks shall be of welded steel construction using SA-516 Grade 70 steel, and shall be tested to withstand a hydrostatic pressure 30% in excess of the designed working pressure of 120 psi. The tanks shall be designed in accordance with the requirements of the latest ASME code section VIII construction and include the code stamp.
3. Tanks are to include the following features:
a. One (1) 14 inch x 18 inch elliptical manhole with a spare gasket.
b. Flange nozzle or pad type connections as shown on the drawings.
c. Four (4) lifting lugs.
d. Four (4) structural steel I-beam type support legs.
f. Necessary # 304 stainless steel clips and studs to for gravel retaining screen
b. Tank interiors are to be cleaned and free of any debris or contaminates
c. Tank exteriors will be commercial sandblasted (SSPC-SP6) and painted with one (1) primer coat (3.0 – 5.0 mils DFT) of Tnemec 90-97, one (1) intermediate coat (3.0-5.0 mils DFT) of Tnemec 161-EN15, and one (1) finish coat (2.5-5.0 mils DFT) of Tnemec 73-112GN.
d. Finish painting of the tank exteriors shall be furnished and field applied by others in accordance with the painting section of the specification
B. Filter Inlet Distributors:
1. Each filter shall be furnished with an inlet distributor/backwash collector system designed with schedule 80 PVC pipe and fittings.
The hub will extend down from the tank top head and include two
(2) lateral arms, each ending with one (1) upturned elbows. A trough or splash plate type distributor will not be accepted.
2. The inlet distributors are to be installed by the filter manufacturer prior to shipment.
C. Supplemental Air Wash Distributor:
1. Each filter tank shall be furnished with a separate header-lateral air wash distributor located near the top of the gravel support bed. The distributor shall be constructed of Schedule 40 304 stainless steel pipe and fittings. The design of the air wash system will include a 2 inch central manifold with 3/8 inch laterals on 7.5 inch maximum centers. Each lateral shall be supported from the gravel retaining screen with 1 inch 304 stainless steel pipe and all necessary stainless steel fasteners. The air discharging orifices shall be formed by slotting holes every 3 inches, approximately. Air nozzles will not be accepted.
2. Air and water must have separate distributors. Air distribution through the same inlet as the underdrain will not be accepted.
3. The air wash distributors shall be field installed by the general contractor.
D. Gravel Retaining Screen
1. Each filter tank shall be furnished with a gravel retaining screen assembly consisting of all necessary #304 stainless steel angles, #304 stainless steel flats, tank clips, #304 stainless steel screen, and #304 stainless steel welding studs and fasteners. Tank clips shall be 1/4 inch thick plate 1.5 inches wide x 3.5 inches long.
These clips will act as connecting points for the steel support angles and flats of various lengths. Angle clips for support of the air wash distributor shall be welded to the cross angles. The cross angles will support an 8 mesh type 304 stainless steel screen with a wire diameter of 0.028 inches with an approximate overlap of three (3) inches. The stainless steel cross flats will hold and secure the screen to the cross angle supports. The filter tank is to include a row of #316 stainless steel Nelson pointed end welding studs every 8 inches around the circumference of the tank wall for screen attachment, and the steel cross angles shall include the welding studs every 12 inches.
E. Underdrain System:
1. Each filter shall be furnished with a non-ferrous underdrain system designed to uniformly distribute backwash water and for collection of filtered water. The distributor shall be of the hub-curved radial lateral type design. The hub shall be of polypropylene construction.
The laterals shall be constructed of schedule 80 PVC, and are to be curved to follow the contour of the tank bottom head. The filter tank bottom head is to include #304 stainless steel threaded studs and clips to securely clamp the laterals in place.
2. The underdrain systems are to be installed by the filter manufacturer prior to shipment.
F. Gravel Supporting Bed:
1. A gravel support bed shall be incorporated in the bottom of each vessel, consisting of five (5) layers of graded gravel, with the largest size gravel loaded into the filter first and the succeeding smaller sizes placed on top. The gravel graduations shall be as follows:
1/8" x 1/16" 3.0 inches 1/4" x 1/8" 3.0 inches 1/2" x 1/4" 1.5 inches 3/4" x 1/2" 1.5 inches 1.5" x 3/4" 3.0 inches 1.5” x ¾” bottom head fill
2. The gravel shall be washed and shipped in clearly marked fifty(50#) pound bags. The gravel must meet the requirements of the American Water Works Association (AWWA) Specification number B-100-89.
3. All gravel is to be field installed by the general contractor.
G. Filtration media:
1. Each filter is to be provided with an 18 inch deep bed of GreensandPlus. The GreensandPlus is to meet the following criteria:
a. Specific gravity: approx. 2.4
b. Effective size: 0.30 - 0.35 mm
c. Uniformity coefficient: less than 1.6
d. Screen grading: 18 x 60 mesh
2. In addition to the GreensandPlus filter media, the equipment supplier shall provide an 18” depth of specially graded anthracite cap. The anthracite is to meet the following criteria:
a. Specific gravity: approx. 1.6
b. Effective size: 0.6 - 0.8 mm
c. Uniformity coefficient: less than 1.6
3. The total GreensandPlus and anthracite bed depth shall total 36 inches.
4. The anthracite shall be shipped in one (1) cu.ft. bags. Gravel shall be shipped in one half ½ cubic foot bags on pallets, and the GreensandPlus shall be shipped in ½ cubic foot bags on pallets.
5. All media shall be accepted under ANSI/NSF Standard 61.
6. GreensandPlus shall be loaded into the filters and conditioned in accordance with the manufacturer’s recommendations.
7. All filter media is to be field installed by others.
8. The general contractor shall furnish 40 pounds of HTH (65 % available chlorine by weight) or equivalent for every 100 cubic feet of GreensandPlus filter media as required for the initial conditioning of the media.
H. Filter exterior valving:
1. Each filter shall be furnished with an automatic and manual valve nest exterior consisting of the following:
a. Automatic valving:
Bray Series 20 butterfly control valves with wafer style cast iron bodies, nylon coated discs, metal reinforced EPDM seats, with Bray Series 70 electric motor operators with auxiliary limit switches, and anti-condensation heaters.
Valves are to be furnished for the following filter sequences:
1. Inlet (1.5 inch)
2. Outlet (1.5 inch)
3. Backwash inlet/Slow refill (1.5 inch)- modulating
4. Backwash outlet (1.5 inch)
5. Rinse outlet (1 inch)
6. Tank Draindown (1 inch)
7. Air wash inlet (1 inch)
8. Air pressurizing (1 inch)
b. Manual isolating valves:
Bray Series 20 butterfly valves with wafer style cast iron bodies, nylon coated discs, field replaceable EPDM seats, and manual gear operators.
Valves are to be furnished for the following:
1. Inlet isolating (1.5 inch)
2. Outlet isolating (1.5 inch)
3. Air vent isolating (1/2 inch)
c. Manual ball valves:
Flow Tek S80 or equal stainless steel ball valves with manual lever operators.
Valves are to be furnished for the following:
1. Drain (1 inch)
2. Backwash tell-tale (1/2 inch)
3. Air vent (1/2 inch)
d. Apco model 200A automatic air/vacuum release valves with threaded cast iron bodies and stainless steel floats
1. Filter top head
I. Filter System Piping:
1. Water/Air service piping:
a. All air piping shall be Schedule 10 304 stainless steel pipe with 304 stainless steel socket weld fittings and flanges
2. General notes:
a. All pipe supports for face and interconnecting piping not located on the skid mounted unit are to be furnished by others. The filter manufacturer shall support all skid mounted piping and valves from the tank and/or skid as required.
a. All piping shall be furnished with the required bolts, studs, nuts and gaskets as follows:
Bolts: ASTM A193 stainless steel.
Studs: ASTM A193 stainless steel.
Nuts: ASTM A194 stainless steel hex.
G…