Drawing qya26443m04.pdf
PDF 104 KB Posted
- Attached to
- QYA ARSR HVAC Replacement Federal contract opportunity
- Solicitation number
- 697DCK-24-R-00106
About this file
This solicitation and drawing package outline requirements for an HVAC replacement project at an FAA site. The Federal Aviation Administration is seeking proposals to demolish and remove two existing HVAC units and associated components, and install two new 25-ton packaged HVAC units, ductwork, controls, and all other associated components. Offerors must be registered in SAM and able to complete the project within approximately 45 calendar days. Proposals are due by February 7, 2024 and the contract will be a firm fixed price awarded to a small business. The site visit is optional on January 24 and the estimated cost is between $250,000 to $500,000.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 697DCK-24-R-00106 0002.pdf | ||
| Drawing qya26443a09 - Copy.pdf | ||
| SUMMARY OF WORK_QYA ARSR HVAC Replacement Project_Rev B.pdf | ||
| Drawing qya-d-arsr-e001-bl.pdf | ||
| QYA ARSR HVAC Replacement Site Pictures - for Contractors.pdf | ||
| Requests For Information - QYA HVAC Replacement.pdf | ||
| OAS 2.5 User Manual (Final).pdf | ||
| 697DCK-24-R-00106 Amendment 0001.pdf | ||
| SUMMARY OF WORK_QYA ARSR HVAC Replacement Project_Rev A.pdf | ||
| M001(I)_QYA ARSR_Rev A.pdf | ||
| 697DCK-24-R-00106.pdf | ||
| Wage Determination ME20230013 092923.pdf | ||
| SUMMARY OF WORK_QYA ARSR HVAC Replacement Project.pdf | ||
| Drawing qya26443m02.pdf | ||
| Drawing qya26443m03.pdf | ||
| Drawing M001(I)_QYA ARSR.pdf | ||
| Drawing qya26443m01.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EQUIPMENT SCHEDULES
MECHANICAL
SITE PREPARATION
ARSR-4
BUCKS HARBOR, ME
ANI-140
26443-M04 QYA 1
1 JBB
11-05-99
NE-D-26443-M04/C
0 05/01/94 4418
QYA26443M04.DGN
SC
REG
AS BUILT /C REMOVED UPDATED DRAWING
B. ANDREWS
B. NG
EQUIPMENT
NUMBER
MANUFACTURER
MODEL
AND TYPE LOCATION
TCH300B4
OR EQUAL
SINGLE PKG.
ROOFTOP TYPE
3470 7.5 34701.2
EXT. S.P.
(IN H O)2
RPM BHP RPMCFM
10,000
TYPE
290,000272,000
DISCHARGE
HORIZ.
(SIDE BY
SIDE
SUPPLY
RETURN)
TOTALSENSIBLE
OUTDOOR
SLAB
MOUNTED
CAPACITY (BTUH)
TRANE
ACU-1
(MAIN)
ACU-2
(STANDBY)
COOLING
ONLY
INDOOR FAN DATA MOTOR DATA
ELECT.
460V
60Hz
TYPE
DISPOSABLE
PLEATED
MEDIA
TYPE
FILTER DATA
NUMBER
SIZE (IN.)
20 x 25 x 2
NOMINAL INPUT
460V, 30, 60Hz
ELECTRICAL DATA
COMPRESSORS
QTY.
RLA
17.7
LRA
104 2
QTY. FLA
3.0
OUTDOOR FAN INDOOR FAN
HP
7.5
FLA
11.0
HEATERS
NONE
CONTROLS
PROVIDE
CONTACTS
FOR
MOUNTING
OF ALARMS
BY DDCP
OUTDOOR
AMBIENT
CONDITION
94 F DB/
77 F WB
INDOOR
SPACE
TEMP ( F)
78 F DB/
65 F WB
REMARKS
AIR CONDITIONING UNIT SCHEDULE
OPTIONAL (REGION BY REGION ADAPTATION)
ACU-1 AND 2 SHALL BE SELECTED TO OPERATE AT OUTDOOR AMBIENT TEMPERATURE FOR EACH REGION
MANUFACTURERS INDICATED ARE FOR REFERANCE ONLY IN ORDER TO ESTABLISH REQUIRED PERFORMANCE VALUES. OTHER ACCEPTABLE MANUFACTURERS MAY BE SUBSTITUTED AS INDICATED IN SPECIFICATIONS.
PROVIDE STATIC PRESSURE DAMPERS CONTROLS.
EXHAUST FAN SCHEDULE
ELECTRIC UNIT HEATER SCHEDULE
EF-1
BAYLEY/
PROPELLER
MODEL NUMBER
CDP-36 OR
APPROVED
EQUAL
LOCATION
ENGINE
GEN
ROOM
DISCHARGE
HORIZONTAL
TYPE
PROPELLER
CFM
9,500
FAN DATA
EXT. S.P.
(IN H O)2
1/2
DRIVE
DIRECT
MIN.H.P.
1 1/2 1140
RPM
MOTOR DATA
ELECT.
208V
60Hz
REMARKS
WITH MOTOR GUARD
AND MOUNTING PANEL
MANUFACTURERS INDICATED ARE FOR REFERANCE ONLY IN ORDER TO ESTABLISH REQUIRED PERFORMANCE VALUES. OTHER ACCEPTABLE MANUFACTURERS MAY BE
SUBSTITUTED AS INDICATED IN SPECIFICATIONS.
EQUIPMENT
NUMBER
MANUFACTURER LOCATION
EUH-1 ELECTROMODE
GENERATOR
ROOM
EUH-2 ELECTROMODE
EQUIPMENT
ROOM
EUH-3 ELECTROMODE
EQUIPMENT
ROOM
EUH-4 ELECTROMODE
TELCO
ROOM
CAPACITY
HEATER DATA
ELECT. INPUT
3.0 KW
10,245
7.5 KW
25,600
7.5 KW
25,600
3.0 KW
10,245
208V, 30/, 60Hz
208V, 30/, 60Hz
208V, 30/, 60Hz
208V, 30/, 60Hz
AMPS
8.3
20.8
20.8
8.3
CFM
FAN DATA
ELECT. INPUT
208V, 30/, 60Hz
208V, 30/, 60Hz
208V, 30/, 60Hz
208V, 30/, 60Hz
THROW
(FT.)
AIR TEMP.
RISE ( F)
MAX. MTG.
HEIGHT (FT.)
OUTDOOR WINTER
DESIGN TEMP ( F)
BELOW 40
0 TO 20
-20 TO 20
40 AND ABOVE
REMARKS
WALL MOUNTING BRACKETS
AND BUILT-IN THERMOSTATS
WALL MOUNTING
BRACKETS AND
BUILT-IN THERMOSTATS
WALL MOUNTING
BRACKETS AND
BUILT-IN THERMOSTATS
WALL MOUNTING BRACKETS
AND BUILT-IN THERMOSTATS
MANUFACTURERS INDICATED ARE FOR REFERANCE ONLY IN ORDER TO ESTABLISH REQUIRED PERFORMANCE VALUES. OTHER ACCEPTABLE MANUFACTURERS MAY BE
SUBSTITUTED AS INDICATED IN SPECIFICATIONS.
PROVIDE UNIT HEATER CAPABLE TO MEET HEATING CAPACITY FOR OUTDOOR WINTER DESIGN TEMPERATURE AS SPECIFIED.
DAMPER SCHEDULE
EQUIPMENT
NUMBER
WALL OPENING (IN)
WIDTH HGT.
SERVES REMARKS
D-1
D-2
D-3
D-4
D-5
EF-1
EG ROOM
AIR INTAKE
RELIEF AIR
ACU-2
SUPPLY
ACU-1
SUPPLY
27 42
MOTORIZED
SPRING RETURN OPEN
EQUIP RM
MOTORIZED
SPRING RETURN OPEN
MOTORIZED
SPRING RETURN OPEN
COUNTER-WEIGHT
BACK DRAFT
COUNTER-WEIGHT
BACK DRAFT
1 INCLUDES DAMPER ASSEMBLY
CENTRI-
FUGAL
CLASS 1
2 RUSKIN WITH HONEYWELL MOTOR OPERATOR, OR APPROVED EQUAL
3 RUSKIN CBD6, OR APPROVED EQUAL
% EFF
89.5
EUH-5 ELECTROMODE
U P S
ROOM
5.0 KW
17,075 208V, 30/, 60Hz 13.9 350 208V, 30/, 60Hz 15 50 9 20 TO 40
1 WALL MOUNTING BRACKETS
AND BUILT-IN THERMOSTATS
EF-2
DAYTON/
CENTRIFUGAL
4C819 OR
APPROVED
EQUAL
REST
ROOM
VERTICAL
CENTRI-
FUGAL
WATTS
DIRECT
120V
60HZ
WITH WALL CAP
4C388
5 FURNISH WITH HAIL GUARD COMPRESSOR UNLOADERS, HEAD PRESSURE CONTROL PACKAGE DOWN TO -20 F ANTI SHORT CYCLE TIMER AND TIME DELAY RELAY
EUH-6 ELECTROMODE
OFFICE
ROOM
5.0 KW
17,075 208V, 30/, 60Hz 13.9 350 208V, 30/, 60Hz 15 50 9 20 TO 40
1 WALL MOUNTING BRACKETS
AND BUILT-IN THERMOSTATS
MANUFACTURER
EQUIPMENT
NUMBER
File details come from the government source that posted it. Updated .