Drawing qya26443m01.pdf
PDF 115 KB Posted
- Attached to
- QYA ARSR HVAC Replacement Federal contract opportunity
- Solicitation number
- 697DCK-24-R-00106
About this file
This document summarizes a federal solicitation for replacement of HVAC systems at an Air Route Surveillance Radar facility in Bucks Harbor, Maine. The Federal Aviation Administration is seeking proposals to demolish and dispose of two existing HVAC units and associated components, and install two new 25-ton packaged HVAC units with ductwork and controls. Offerors must be registered in SAM and submit technical and cost proposals by February 7, 2024. The project value is between $250,000 and $500,000 and work must be completed within 45 days. The solicitation is set aside for small businesses under NAICS code 238220 with a $19 million size standard. An optional site visit will be held on January 24, 2024.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 697DCK-24-R-00106 0002.pdf | ||
| Drawing qya26443a09 - Copy.pdf | ||
| Drawing qya-d-arsr-e001-bl.pdf | ||
| QYA ARSR HVAC Replacement Site Pictures - for Contractors.pdf | ||
| Requests For Information - QYA HVAC Replacement.pdf | ||
| SUMMARY OF WORK_QYA ARSR HVAC Replacement Project_Rev B.pdf | ||
| OAS 2.5 User Manual (Final).pdf | ||
| 697DCK-24-R-00106 Amendment 0001.pdf | ||
| SUMMARY OF WORK_QYA ARSR HVAC Replacement Project_Rev A.pdf | ||
| M001(I)_QYA ARSR_Rev A.pdf | ||
| 697DCK-24-R-00106.pdf | ||
| Wage Determination ME20230013 092923.pdf | ||
| SUMMARY OF WORK_QYA ARSR HVAC Replacement Project.pdf | ||
| Drawing M001(I)_QYA ARSR.pdf | ||
| Drawing qya26443m04.pdf | ||
| Drawing qya26443m02.pdf | ||
| Drawing qya26443m03.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C
M
C
M
B
M
A
M02
B
M
D
M
EUH
EUH
EUH
EF
42x24 32x24 24x20 18x12
14" FLEXIBLE
TUBING TO
DIFFUSER
24x42 S.A.
27x42 R.A.
400 CFM
1200 CFM
500 CFM
(SEE NOTE 9)
C F
M
C F
M
SEE ARCH. DWGS
FOR DUCT WALL
PENETRATIONS
x
18x12
(TYP FOR XX)
RUSKIN MODEL MDR-525
MANUAL AIR VOLUME
DAMPER OR APPROVED
EQUAL (TYP FOR 7) TITUS MODEL AG-45
ADJUSTABLE AIR VOLUME
EXTRACTOR OR APPROVED
EQUAL (TYP FOR 6)
50 CFM
EXHAUST FAN
RESTROOM
(SEE NOTE 7)
BACKDRAFT
DAMPERS
F
M
D-2
NC
(4) 24x24x1
DISPOSABLE
AIR FILTERS
RAINHOOD W/
INSECT SCREEN
9500 CFM
FUEL LEVEL
SENSING MONITOR
LEAK DETECTION
MONITOR
SECURITY SCREEN
(SEE NOTE 10)
SECURITY SCREEN
(SEE NOTE 10)
M
D-1
NC
TS-1 SET @ 78'F
VD
VD
VD
VD
VD
VD
VD
VD
M
D-3
NC
RELIEF DAMPER
(SEE NOTE 6)
SEE UNIT HEATER
DETAIL (TYP FOR 4)
D
M05
NOTES:
04 4 8
SCALE IN FEET
A
M01
HVAC FLOOR PLAN
ACU
EUH
EUH
x
R
A
42x24 S.A.
x S
.A
D4
D5
EF-2
DDCP
B
E01
VD
VD
200 CFM
200 CFM
SECURITY SCREEN
(SEE NOTE 10)
x x
EUH
M
A
M05
ACU
24x24 ACCESS
PANEL (TYP BOTH
S.A. DUCTS)
4' CONC. WALKWAY
1. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR
DIMENSIONS AFTER LINING.
2. ALL SUPPLY AIR DUCTS INSIDE BUILDING ARE
PROVIDED WITH 1" INTERIOR THERMAL DUCT LINER.
3. ALL DUCT FROM ACU-1 AND 2 OUTSIDE THE BUILDING
ARE PROVIDED WITH 1" INTERIOR THERMAL DUCT
LINER AND 2" EXTERIOR THERMAL DUCTBOARD. ATTACH
TO DUCT WITH APPROVED ADHESIVE AND MECH.
FASTENERS. SEAL ALL JOINTS WITH A VAPOR BARRIER
TAPE AND COMPLETELY COVER WITH A WEATHERPROOF
MASTIC IN ACCORDANCE WITH INSULATION MANUFACTURERS
INSTRUCTIONS. SLOPE TOP OF DUCT INSULATION TO
ELIMINATE STANDING WATER ON TOP OF DUCTWORK.
INSTALL 0.040 ALUMINUM SHEETING OVER MASTIC
COATING. SEAL WEATHERPROOF.
4. ALL DUCTS ARE SUPPORTED AS SHOWN AND IN ACCORDANCE
WITH LATEST SMACNA LOW PRESSURE DUCT STANDARDS.
5. ACU-1 AND ACU-2 HAVE HAIL SCREENS OVER FAN BLADES
AND CONDENSER COILS.
6. ALL MOTORIZED DAMPERS OPERATE ON ESTABLISHED CONTROL
SYSTEM VOLTAGE (I.E. 24 VAC, 110 VAC, ETC).
7. REFERENCE DRAWING A10 AND P01 FOR RESTROOM DETAILS.
8. RETURN AIR GRILLS ARE 1" X 1" X 1" ALUMINUM GRID
WITH STANDARD WHITE FINISH, TITUS MODEL # 50F OR
APPROVED EQUAL.
9. NOT USED.
10. MAXIMUM UNSECURED OPENING ALLOWED THROUGH THE
EXTERIOR WALL IS 96 SQ. IN. REFERENCE SHT. M06
FOR SECURITY SCREEN DETAILS.
11. ALL CONTROL DAMPERS ARE SPRING RETURN OPEN, MOTORIZED
CLOSED. (FAILS OPEN ON LOSS OF POWER).
12. FLEXIBLE CONNECTIONS INSTALLED BETWEEN THE AHU AND
DUCT WORK. USE FLUOROELAS TOMER (FRM) SYNTHETIC
RUBBER MATERIAL DESIGNED FOR EXTERIOR USE.
13. AIR BAFFLES FOR AIR COOLED CONDENSERS INSTALLED TO PREVENT
SUBCOOLING OF REFRIGIRENT IN WINTER AND ALSO FROM SAND STORMS.
DISCONNECT
MECHANICAL FLOOR PLAN
MECHANICAL
SITE PREPARATION
ARSR-4
BUCKS HARBOR, ME
ANI-140
26443-M01 QYA 1
1 JBB
11-05-99
NE-D-26443-M01/C
0 05/01/94 4418
QYA26443M01.DGN
SC
B. ANDREWS
AS BUILT /C REMOVED UPDATED DRAWING
REG/SGS
B. NG
File details come from the government source that posted it. Updated .