Drawing qya26443m03.pdf

PDF 124 KB Posted

Attached to
QYA ARSR HVAC Replacement Federal contract opportunity
Solicitation number
697DCK-24-R-00106
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This solicitation requests proposals for an HVAC replacement project at the QYA ARSR facility in Bucks Harbor, Maine. The Federal Aviation Administration seeks to award a firm fixed price contract to remove and dispose of two existing HVAC units and associated components, and install two new 25-ton packaged HVAC units with ductwork and controls. The project is set aside for small businesses and has an estimated cost between $250,000 to $500,000. Interested parties must submit technical and cost proposals by February 7, 2024. An optional site visit will be held on January 24, 2024. The awarded contractor must be registered in the System for Award Management.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STANDBY

ACU

D-4

SET AT 78 FTS

VD

VD

500 CFM

16x8

14" DIA NECK CD

500 CFM

TELCO ROOM

ACU

MAIN

D-2 (ON-OFF) OUTSIDE AIR

MOTORIZED DAMPER IN

PARALLEL WITH FAN

STARTER

EF-1

FAN STARTER

WITH HOA SWITCH

D-1

GENERATOR

ROOM

SET AT 90 F

TO RMMS

(FUTURE)

M

TS

2 M

DO DO AI DO DI X

DIRECT DIGITAL CONTROL PANEL NO.1

INTRUSION ALARM

MICROSWITCH

EQUIPMENT ROOM

ACU-FAN (STARTER)

COMPRESSORS

ACU

DIRECT DIGITAL CONTROL PANEL NO.1

D-3

M

PS

F I L

T E

R

TS

S

DI AO AO DI DO AI DI DO DI

SET THERMOSTAT

AT 65 F

EUH

500 CFM MIN.

D-3

MNC

SET THERMOSTAT

AT 40 F

8x12 TRANSFER

GRILLE (TYP FOR 2)

VD

VD VD

20" DIA NECK CD

1600 CFM (TYP FOR 5)

EUH

T

EQUIPMENT ROOM

T

9500 CFM

NC

M

D-1

EUH

M

SET THERMOSTAT

AT 40 F

SET AT 90 F TS

ENGINE/GENERATOR ROOM

FILTER

9500 CFM

EF

SET THERMOSTAT

AT 65 F

EUH

T

SCHEMATIC FLOW DIAGRAM

CONTROL FLOW DIAGRAM FOR ENGINE/GENERATOR ROOM

FLOW AND CONTROL FLOW DIAGRAM

NOT TO SCALE (SIMILAR FOR ACU-1 AND ACU-2)

NOT TO SCALE

NOT TO SCALE

T

B

M03

C

M03

A

M03

ARE COUNTERWEIGHT

BACKDRAFT DAMPERS

DDCP

DI

LEAK DETECTION

MONITOR

FUEL LEVEL

SENSING MONITOR

LEAK DETECTION

MONITOR

FUEL LEVEL

SENSING MONITOR

DO

PS

F I L

T E

R

AO

NOTE: D-4 AND D-5

SET THERMOSTAT

AT 65 F

VD

VD

1200 CFM

400 CFM

VD

AUX. CONTACT

ALARMS

COMPRESSOR

CONDENSER

SEQUENCE OF OPERATION:

M

CONTACTOR

INTAKE

LOUVER

EXHAUST FAN

W/ GRAVITY DAMPER

T-STAT

208V

SELECTOR

SWITCH

AUTO

OFF

HAND120V

RELAY

TERMINALS IN E/G CONTROL CABINET

ENERGIZED WHEN E/G RUNS

L

N

FAN AND DAMPER CONTROL DIAGRAML

N

20A

POWER PANEL

IN E/G ROOM

D-5

VD

VD

200 CFM

200 CFM

T

SET THERMOSTAT

AT 65 F

EUH

T

EUH

M N

C

D-2

A. EQUIPMENT ROOM :

AIR CONDITIONING UNIT ACU-1 OR ACU-2 OPERATE ON DEMAND FROM DDC CONTROL

PANEL AFTER RECEIVING TEMPERATURE SIGNAL FROM ROOM TEMPERATURE SENSOR TS-1.

THE DDC CONTROLLER PROVIDES THE FOLLOWING: INDOOR FAN ON ACU-1 OPERATE

CONTINUOUSLY. ACU-1 PROVIDES AUTOMATIC SEQUENCE OF TWO COMPRESSORS, TO

MAINTAIN INDOOR TEMPERATURE OF 78 F. WHENEVER INDOOR ROOM TEMPERATURE RISES

TO 85 F, ACU-2 ENERGIZES AND ACU-1 DE-ENERGIZES.

WHENEVER SPACE TEMPERATURE DROPS BELOW 65 F, UNIT HEATERS (EUH-2 AND 3) ENERGIZES

TO MAINTAIN 65 F IN THE SPACE. ACU-1 OR ACU-2 DE-ENERGIZES AND CORRESPONDING

DAMPER IN SUPPLY, RETURN, OUTDOOR AIR DUCT AND RELIEF HOOD CLOSED. REVERSE OCCURS

WHEN TEMPERATURE RISES ABOVE 65 F.

UNIT HEATER (EUH-4) ENERGIZES WHENEVER SPACE TEMPERATURE IN TELCO ROOM DROPS

BELOW 40 F. THE REVERSE OCCURS WHEN TEMPERATURE RISES ABOVE 40 F. SMOKE DETECTOR

IN RETURN AIR DUCT OF ACU-1 OR ACU-2 DE-ENERGIZES RESPECTIVE ACU'S AND ALARM

SIGNAL SENTS TO DDC IF SMOKE OR FIRE IS DETECTED.

A PROGRAM IS PROVIDED TO ALTERNATE AUTOMATICALLY THE ACU-1 TO ACU-2 UNIT FOR

EVERY 500 HOURS OF DISTRIBUTED USAGE OF UNIT.

ACU INTERLOCKS:

A PROGRAM IS PROVIDED TO INTERLOCK ACU-1 AND ACU-2 SO THAT ONLY ONE OF THE UNITS

CAN OPERATE AT A TIME.

A MINIMUM OF FOLLOWING POINTS ARE PROVIDED IN DDCP PANEL:

a) START/STOP STATUS AND ALARM OF EACH ACU'S SYSTEM.

b) SPACE TEMPERATURE INDICATION WITH HIGH ALARM OF 85 F AND LOW ALARM OF 60 F.

c) TOTAL RUN TIME OF EACH UNIT

d) ALARMS (AUX CONTACTS)

1. DIRTY FILTER

2. COMPRESSOR FAILURE

3. FAN FAILURE

B. ENGINE/GENERATOR ROOM:

WHEN ENGINE IS IN OFF POSITION AND INDOOR TEMPERATURE RISES TO AND ABOVE

90 F(TS-2), DAMPER D-1 AND D-2 OPENS.

UPON FURTHER RISE IN TEMPERATURE TO 95 F EXHAUST FAN (EF-1) OPERATES.

WHEN INDOOR TEMPERATURE FALLS TO BELOW 90 F EXHAUST FAN(EF-1) DE-ENERGIZES.

DAMPER D-1 AND D-2 CLOSES.

INTAKE DAMPER D-2 AND EXHAUST DAMPER D-1 INTERLOCKS WITH EXHAUST FAN

EF-1 TO OPEN FULLY WHENEVER THE EXHAUST FAN IS IN OPERATION.

PROVIDE 10 SECOND TIME DELAY FOR FAN OPERATION.

ELECTRIC UNIT HEATER: UNIT HEATER EUH-1 ACTIVATES BY BUILT-IN

THERMOSTAT TO MAINTAIN INDOOR TEMPERATURE OF 40 F.

PROVIDE A MINIMUM OF FOLLOWING POINTS:

a) STATUS OF DAMPER POSITION

b) START/STOP STATUS OF EXHAUST FAN-1

c) ALARMS

1. FUEL LEVEL AND LEAK DETECTION

C. GENERAL:

ALL TEMPERATURE SENSORS LOCATED AT HEIGHT OF 5 FEET ABOVE FLOOR LEVEL.

D. INTRUSION ALARM:

A MICROSWITCH ON DDCP PANEL TO MONITOR UNAUTHORIZED OPENING OF PANEL.

MICROSWITCH SENDS ALARM TO THE DDCP.

WHEN GENERATOR IS STARTED, DAMPER D-1 AND D-2 OPEN, AND EXHAUST FAN EF-1 STARTS

AND OPERATES.

CONTROL SCHEMATIC

MECHANICAL

SITE PREPARATION

ARSR-4

BUCKS HARBOR, ME

ANI-140

26443-M03 QYA 1

1 JBB

11-05-99

NE-D-26443-M03/C

0 05/01/94 4418

QYA26443M03.DGN

SC

AS BUILT /C REMOVED UPDATED DRAWING

SET AT 78°F (ROOM)

B. ANDREWS

B. NG

File details come from the government source that posted it. Updated .