d._HVAC-05-08-24-Walton_County_RR_-_SnS-DS.pdf
PDF 808 KB Posted
- Attached to
- Driftwood Road Municipal Parking Facility
- Solicitation number
- ITB 24-34
- Issued by
- Walton County, Florida
About this file
This is a mechanical HVAC design document prepared by Stokes Architectural, Inc. and Anton Lee Engineering, LLC for the Driftwood Transit Stop & Restroom facility located at 79 Driftwood Road in Walton County, Florida. The project specifications detail the heating, ventilation, and air conditioning systems required for the municipal parking facility project (ITB 24-34), including comprehensive mechanical plans, equipment schedules, ductwork details, and control sequences. The HVAC system consists of one split-system DX heat pump unit (AHU-1/HPU-1) with a cooling capacity of 25.3 MBH and heating capacity of 31.9 MBH, rated at 16 SEER and 3.9 COP, featuring a variable-speed indoor air handler with a 2-inch MERV 8 filter and 980 CFM airflow capacity. Additional components include three exhaust fans (EF-1, EF-2, and EF-3) with capacities ranging from 80 to 150 CFM, externally insulated ductwork meeting SMACNA standards at 2 inches water column static pressure class, and condensate drain systems with minimum 1-inch flexible elastomeric cellular insulation. The mechanical design document is dated May 8, 2024, and has been digitally signed and sealed by Anton Lee, P.E. (Florida PE# 82369), with the project number identified as 21-147.
The specifications require compliance with the 2023 Florida Building Code, Florida Mechanical Code, Florida Energy Conservation Code, ASHRAE standards, and NFPA codes. All ductwork must be fabricated per SMACNA HVAC Duct Construction Standards with proper reinforcement, hangers, and supports positioned within 24 inches of elbows and 48 inches of branches. The refrigerant piping utilizes R-410A with hard-drawn copper lines insulated with minimum 3/4-inch thick unicellular insulation on suction lines, mounted on concrete housekeeping pads with corrosion protection rated for minimum 10,000 hours salt spray exposure. Control systems include a manufacturer-programmable thermostat with scheduled start-stop capability, fire alarm relay integration, and occupancy-based operation modes for heating, cooling, and defrost cycles. The mechanical contractor is responsible for Test and Balance services per specification 23 05 93, coordinating all ductwork and piping routing to avoid structural members, coordinate with other trades for proper clearances and penetrations, and provide complete system commissioning and operator training. Double-wall ductwork is required for all exposed ductwork in the restroom areas, fabricated from 24-gauge galvanized steel with 1-inch internal insulation and perforated metal liners.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
S
ABBREVIATIONS
@ AT
A/C ABOVE CEILING
A/E ARCHITECTS AND ENGINEERS
A/G ABOVE GRADE
ACC AIR COOLED CHILLER
ACD AUTOMATIC CONTROL DAMPER
AD ACCESS DOOR
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFMS AIRFLOW MEASURING STATION
AHRI AIR-CONDITIONING, HEATING AND
REFRIGERATION INSTITUTE
AHU AIR HANDLING UNIT
ALT ALTERNATE
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATING AND AIR
CONDITIONING ENGINEERS
AS AIR SEPARATOR
ATU AIR TERMINAL UNIT
AI ANALOG INPUT
AO ANALOG OUTPUT
B BOILER
BAS BUILDING AUTOMATION SYSTEM
BD BELT DRIVE
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BP BOILER PUMP -PRIMARY LOOP
BTUH BRITISH THERMAL UNIT PER HOUR
CEF CEILING EXHAUST FAN
CFM CUBIC FEET PER MINUTE
CF CHEMICAL FEEDER
CFH CUBIC FEET PER HOUR
CHWS/R CHILLED WATER PIPING SUPPLY
AND RETURN
CHWS CHILLED WATER PIPING SUPPLY
CHWR CHILLED WATER PIPING RETURN
CHWP CHILLED WATER PUMP
CO CARBON MONOXIDE / CLEANOUT
CONT CONTINUOUS
COP COEFFICIENT OF PERFORMANCE
COMP COMPRESSOR
CT COOLING TOWER
CWV CHILLED WATER VALVE
Cv FLOW COEFFICIENT
DB DRY BULB TEMPERATURE
DBA DECIBEL A RATING
DCW DOMESTIC COLD POTABLE WATER
DD DIRECT DRIVE
DDC DIRECT DIGITAL CONTROL
DEG. F DEGREES IN FAHRENHEIT
DN DOWN
DP DEW POINT TEMPERATURE
DPS DIFFERENTIAL PRESSURE SENSOR
DWGS DRAWINGS
DX DIRECT EXPANSION
DI DIGITAL INPUT
DO DIGITAL OUTPUT
(E) EXISTING
EA EXHAUST AIR OR EACH
EAG EXHAUST AIR GRILLE
EAL EXHAUST AIR LOUVER
EAR EXHAUST AIR REGISTER
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EMCS ENERGY MANAGEMENT AND
CONTROL SYSTEM
ENT ENTERING
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
FD FLOOR DRAIN
FLA FULL LOAD AMPS
FLP FLOOR PLAN
FPM FEET PER MINUTE
FT FEET
FT W.C. FEET OF WATER COLUMN
GI GRAVITY INTAKE
GR GRAVITY RELIEF
GPM GALLONS PER MINUTE
HDPE HIGH-DENSITY POLYETHYLENE
HDT HORIZONTAL DRAW THROUGH
HBT HORIZONTAL BLOW THROUGH
HOA HAND-OFF-AUTO
HP HORSEPOWER
HPU HEAT PUMP UNIT
HVAC HEATING VENTILATING AND
AIR CONDITIONING
HWS/R HOT WATER PIPING SUPPLY
AND RETURN
HWS HOT WATER SUPPLY
HWR HOT WATER RETURN
HWP HOT WATER PUMP
HWV HOT WATER VALVE
HZ HERTZ
IL INLINE
IPLV INTEGRATED PART LOAD VALUE
IN W.C. INCH OF WATER COLUMN
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BTUHS
MCA MINIMUM CIRCUIT AMPS
MERV MINIMUM EFFICIENCY REPORTING
VALUE (FILTER)
MFG MANUFACTURING
MFR MANUFACTURER
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT
PROTECTION DEVICE
MVD MANUAL VOLUME DAMPER
NEC NATIONAL ELECTRICAL CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NO NORMALLY OPEN
NC NORMALLY CLOSED OR NOISE
CRITERIA
NPLV NON-STANDARD PART LOAD VALUE
NTS NOT TO SCALE
OA OUTSIDE AIR
OAL OUTSIDE AIR LOUVER
OAU OUTSIDE AIR UNIT
O.C. ON CENTER
PD PRESSURE DROP
PEX CROSS-LINKED POLYETHYLENE
PH PHASE
PPM PARTS PER MILLION
PRV PRESSURE REDUCING VALVE
P/T PRESSURE/TEMPERATURE PORTS
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH (GAGE
PRESSURE)
QTY QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RAR RETURN AIR REGISTER
RH RELATIVE HUMIDITY
RPBFP REDUCED PRESSURE BACKFLOW
PREVENTER
RPM REVOLUTION PER MINUTE
RLA RATED LOAD AMPS
SA SUPPLY AIR
SAR SUPPLY AIR REGISTER
SD SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY
RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR
CONDITIONING CONTRACTORS'
NATIONAL ASSOCIATION
SPT STATIC PRESSURE TRANSMITTER
TA TRANSFER AIR
TAG TRANSFER AIR GRILLE
T'STAT THERMOSTAT
TT TEMPERATURE TRANSMITTER
TSP TOTAL STATIC PRESSURE
TYP. TYPICAL
UNO UNLESS NOTED OTHERWISE
UV ULTRAVIOLET
UV-C ULTRAVIOLET TYPE C
U/G UNDERGROUND
V VOLTS
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
WB WET BULB TEMPERATURE
WCC WATER COOLED CHILLER
WHP WATER SOURCE HEAT PUMP
WOG WATER, OIL, GAS
W.G. WATER GAUGE
NOTE:
NOT ALL ABBREVIATIONS ARE USED ON THIS
DRAWINGS
SHEET NOTE
DETAIL NOTE
REVISION # AND CLOUD
THERMOSTAT MOUNT TO
MATCH LIGHT SWITCH ('1'
INDICATES EQUIPMENT
CONTROLLED).
DUCT MOUNT OR WALL
MOUNT CARBON DIOXIDE
SENSOR
DUCT MOUNT SMOKE
DETECTOR
(PROVIDED BY DIVISION 26,
INSTALLED BY DIVISION 23
AND WIRED BY DIVISION 26).
UNDER CUT DOOR 3/4"
CO2
LEGEND
24"x12"
DUCTWORK
RECTANGULAR DUCT SIZE. FIRST SIZE
LISTED IS SIDE SHOWN IN PLANS
ROUND DUCT SIZE
EXTERNALLY INSULATED DUCTWORK
EXTERNALLY INSULATED ROUND
FLEXIBLE DUCTWORK (MIN R-6)
DUCT 90° ELBOW WITH TURNING
VANES
DUCT 45° TRANSITION WITH
TURNING VANES
RADIUSED DUCT ELBOW. TURNING
RADIUS SHALL BE 1.5 TIMES THE
TURNING DIMENSION
FLEXIBLE DUCT CONNECTION
TRANSITION
SUPPLY OR OUTSIDE AIR DUCT
TURNING UP (POSITIVE PRESSURE)
RETURN OR EXHAUST AIR DUCT
TURNING UP (NEGATIVE PRESSURE)
SUPPLY OR OUTSIDE AIR DUCT
TURNING DOWN (POSITIVE
PRESSURE)
RETURN OR EXHAUST AIR DUCT
TURNING DOWN (NEGATIVE
PRESSURE)
MANUAL VOLUME DAMPER
DO
ANALOG INPUT
ANALOG OUTPUT
DIGITAL INPUT
DIGITAL OUTPUT
SPACE TEMPERATURE
SENSOR OR THERMOSTAT
SPACE HUMIDITY SENSOR
DUCT MOUNT
TEMPERATURE SENSOR
DUCT MOUNT HUMIDITY
SENSOR
DUCT MOUNT
MOTORIZED DAMPER
AND ACTUATOR
DUCT MOUNTED AIR
FLOW MEASURING
STATION
FREEZESTAT
LINEAR AVERAGING
TEMPERATURE SENSOR
DIFFERENTIAL PRESSURE
TRANSMITTER
MANUAL VOLUME
DAMPER
VARIABLE FREQUENCY
DRIVE
DDC PANEL
AIRFLOW
FAN
FILTER
T
H
M
FM
DI
AO
AI
T
H
DP
MVD
VFD
M
OR
1 SCALE
TITLE DESCRIPTION
DWG SCALE,
SCHEMATIC,
OR
NOT TO SCALE (NTS)
AHU
(E)AHU-1
DDC
CONTROLS LEGEND
FZ
12"Ø
EQUIPMENT WITH CLEARANCE
SHOWN IN DASHED LINE
NEW EQUIPMENT TAG
EXISTING EQUIPMENT TAG
CONNECT TO EXISTING
EQUIPMENT TO BE DEMOLISHED
T
PROJECT BUILDING CODE REQUIREMENTS
WORK SHALL COMPLY WITH THE FOLLOWING AGENCIES:
· 2023 FLORIDA BUILDING CODE
· 2023 FLORIDA MECHANICAL CODE
· 2023 FLORIDA ENERGY CONSERVATION CODE
· 2023 FLORIDA PLUMBING CODE
· 2023 FLORIDA FUEL GAS CODE
· 2023 FLORIDA FIRE PREVENTION CODE
· AMERICAN SOCIETY OF HEATING AND REFRIGERATION ENGINEERS (ASHRAE)
· AMERICAN SOCIETY OF PLUMBING ENGINEERS (ASPE)
· NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
· 2020 NFPA 70 NATIONAL ELECTRICAL CODE
· NFPA 101 LIFE SAFETY CODE
M301
M301
BUILDING SECTION
BUILDING ELEVATION
D
SINGLE LINE PIPING
ELBOW TURN UP
ELBOW TURN DOWN
CONNECTION, BOTTOM
CONNECTION, TOP
CONDENSATE DRAIN PIPING
REFRIGERANT PIPING
GENERAL MECHANICAL NOTES
1. CONTRACTOR SHALL COORDINATE WITH OTHER TRADES REQUIRED OPENINGS IN WALLS,
FOUNDATIONS, FLOORS, AND ROOFS.
2. FIELD VERIFY ALL DIMENSIONS, SIZES, AND CONNECTION LOCATIONS BEFORE ANY
DUCTWORK FABRICATION OR PIPE CUTTING IS COMMENCED. PROVIDE ANY OFFSETS,
TRANSITIONS, AND OTHER MINOR ADJUSTMENTS AS REQUIRED FOR A COMPLETE AND
WORKING SYSTEM INSTALLATION.
3. COORDINATE FLOOR DRAIN LOCATIONS IN MECHANICAL ROOMS WITH ANY EQUIPMENT
LOCATED IN THE MECHANICAL ROOM. ROUTE CONDENSATE DRAIN PIPING OUT OF
WALKWAY PATHS. CONDENSATE DRAIN PIPING SHALL BE COPPER TYPE L WITH A MIN. OF 1"
FLEXIBLE ELASTOMERIC CELLULAR INSULATION AND VAPOR BARRIER.
4. VERIFY MECHANICAL EQUIPMENT LOCATIONS AND PROVIDE ADEQUATE MAINTENANCE
CLEARANCE AROUND EACH PIECE OF EQUIPMENT PER THE MANUFACTURER'S
RECOMMENDATIONS. PROVIDE CLEARANCE IN FRONT OF ELECTRICAL PANELS AND OTHER
ELECTRICAL EQUIPMENT PER THE NATIONAL ELECTRICAL CODE REQUIREMENTS. COORDINATE
WITH OTHER TRADES.
5. HVAC EQUIPMENT, PIPING, AND ETC. ARE SHOWN IN APPROXIMATE LOCATIONS. ACTUAL
LOCATIONS SHALL BE DETERMINED IN THE FIELD, FULLY COORDINATED AND IN COMPLIANCE
WITH CONTRACT DOCUMENTS. IN NO INSTANCE SHALL THE LOCATION VIOLATE STANDARDS,
CODES, GOOD HVAC PRINCIPLES, AND THE INTENT OF THE HVAC DESIGN. CONSULT
ENGINEER PRIOR TO RELOCATION. MECHANICAL DRAWINGS, IN SOME RESPECTS, ARE
DIAGRAMMATIC. COORDINATION, LAYOUT OF SECTIONS, OR FIELD MEASUREMENTS MAY BE
REQUIRED PRIOR TO FABRICATION OF DUCTWORK OR PIPING. MODIFY SIZES, AS DIRECTED BY
ENGINEER, FOR FIT. ARRANGE ALL DUCTWORK AND PIPING IN A NEAT AND ORDERLY
MANNER. COORDINATE WITH OTHER TRADES.
6. CONTRACTOR SHALL NOT CUT ANY STRUCTURAL MEMBERS OF BUILDING.
7. PROVIDE WATER PROOF SEALING OF PIPE AND DUCT PENETRATIONS OF EXTERIOR WALLS,
FLOORS, AND/OR ROOF.
8. DO NOT MOUNT DISCONNECT SWITCHES ON HVAC EQUIPMENT EXCEPT AS RECOMMENDED
BY MANUFACTURER. EQUIPMENT OF DIFFERING ELECTRICAL CHARACTERISTICS, PHYSICAL
DIMENSIONS, CAPACITIES, AND RATINGS MAY BE FURNISHED, PROVIDED SUCH PROPOSED
EQUIPMENT IS APPROVED BY THE ENGINEER IN WRITING AND CONNECTING MECHANICAL
SERVICES, CIRCUIT BREAKERS, CONDUIT, MOTORS, BASES, AND EQUIPMENT SPACES ARE
INCREASED. ADDITIONAL COSTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
PROVIDING DIFFERING EQUIPMENT.
9. THERMOSTATS SHALL BE GENERALLY LOCATED AS SHOWN. COORDINATE WITH FURNITURE,
CASEWORK AND OWNER PROVIDED ITEMS.
10. REFER TO DIVISION 23 SPECIFICATIONS FOR FURTHER REQUIREMENTS.
11. TEST AND BALANCE (TAB) SHALL BE PROVIDED FOR THIS PROJECT. CONTRACTOR SHALL
COORDINATE ALL TAB REQUIREMENTS WITH THE TAB CONTRACTOR DURING THE
CONSTRUCTION. REFER TO SPECIFICATION 23 05 93 FOR FURTHER INFORMATION.
DIFFUSER/GRILLE LEGEND AND SPECIFICATION
AIRFLOW
OR
AIRFLOW
CD: ALUMINUM CEILING DIFFUSER SUITABLE FOR INSTALLATION IN LAY-IN
CEILING OR GYPSUM BOARD CEILINGS. INLET SIZE AND AIRFLOW AS
INDICATED. PROVIDE WITH SQUARE-TO-ROUND NECK TRANSITION AS
REQUIRED. PRICE ASPD, TITUS OMNI-AA, OR EQUIVALENT.
SAG: ALUMINUM SUPPLY GRILLE WITH 0° DEFLECTION AND 3/4" SPACING
SUITABLE FOR SURFACE MOUNTING TO SIDEWALL GYPSUM BOARD CEILINGS
OR LAY-IN INSTALLATION IN TILE CEILING. REGISTER DESIGNATION INDICATES
GRILLE TO BE PROVIDED WITH OPPOSED BLADE DAMPER. SIZE AS INDICATED.
FOR LAY-IN INSTALLATION, PROVIDE LAY-IN BORDER FRAME AND PROVIDE
FILLER PANEL FOR CEILING TILE LOCATION. PRICE 620D, TITUS 300FS, OR
EQUIVALENT.
NOTES:
· COORDINATE COLORS WITH ARCHITECTURAL RCP. PROVIDE COLOR
SELECTION FOR A/E REVIEW.
· COORDINATE ALL LOCATION WITH ARCHITECTURAL RCP AND LIGHTING.
· MAXIMUM NC VALUE FOR ALL AIR DISTRIBUTION SYSTEM SHALL BE 20.
EAG OR RAG OR TAG:
ALUMINUM GRILLE WITH 0° DEFLECTION AND 3/4" SPACING SUITABLE FOR
SURFACE MOUNTING TO SIDEWALL GYPSUM BOARD CEILINGS OR LAY-IN
INSTALLATION IN TILE CEILING. REGISTER DESIGNATION INDICATES GRILLE
TO BE PROVIDED WITH OPPOSED BLADE DAMPER. SIZE AS INDICATED. FOR
LAY-IN INSTALLATION, PROVIDE LAY-IN BORDER FRAME AND PROVIDE
FILLER PANEL FOR CEILING TILE LOCATION. PRICE 610 , TITUS 350 ZF OR
EQUIVALENT.
GENERAL DUCTWORK NOTES
1. UNLESS NOTED OTHERWISE, ALL NEW SUPPLY, RETURN, OUTSIDE AND EXHAUST AIR DUCTWORK
SHALL BE LOW PRESSURE SINGLE WALL METAL RECTANGULAR, SMACNA STATIC PRESSURE CLASS
2" W.G., SEAL CLASS A. INSULATION PER SPECIFICATIONS.
2. ALL DUCTWORK CONSTRUCTION, DUCT HANGERS, AND SUPPORTS SHALL COMPLY WITH
SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE" FOR METAL
THICKNESS', REINFORCING TYPES AND INTERVALS, TIE-ROD APPLICATIONS, AND JOINT TYPES AND INTERVALS. SUPPORT HORIZONTAL DUCTS WITHIN 24" OF EACH ELBOW AND WITHIN 48" OF
EACH BRANCH. SEE DUCT HANGER DETAILS.
3. VERIFY COLLAR SIZES ON ALL EQUIPMENT INLETS AND OUTLETS. TRANSITION DUCTWORK AS
NECESSARY. EXTERNALLY INSULATE ALL TRANSITIONS AT EQUIPMENT CONNECTIONS.
4. PROVIDE FLEXIBLE CONNECTIONS, AND VIBRATION ISOLATORS FOR INTERNALLY ISOLATED UNITS.
PROVIDE FLEXIBLE DUCT CONNECTORS AT ALL HVAC EQUIPMENT CONNECTIONS COMPLYING
WITH UL-181, NFPA 90A, AND NFPA 90B.
5/8/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21014
St o ke s
A rc hi te c tu ra l, In c
St o ke s
A rc hi te c tu ra l, in c
. h e re b y e xp re ss ly re se rv e s its c o m m o n-la w c o p yr ig ht a nd o th e r p ro p e rty ri g ht s to th e se p la ns
D ra w in g s a re n o t t o b e re p ro d uc e d , c ha ng e d
, o r c o p ie d in a ny fo rm w ha ts o e ve r, no r a re th e y to b e a ss ig ne d to a ny th ird p a rty w ith o ut fi rs t o b ta in in g th e e xp re ss w rit te n p e rm is si o n a nd c o ns e nt o f S to ke s A rc hi te c tu ra l, in c
DRAWN BY:
AL
CHECKED BY:
AL
A rc hi te c tu re
M a st e r P la nn in g
In te rio r D e si g n
C lo ve rd a le
B o ul e va rd
Fo rt
W a lto n
Be a c h, F lo rid a
Ph o ne
0)
-2
F x:
(8
) 6
-6
FL
L ic en se
: A R
L
C or p Li ce ns e
A
AC
Architectural Inc.
Stokes
M ir a m a r
B ea ch
Fl o ri d a
Drift woo d Tr ansi t Sto p &
Rest room
- W alto n Co unty
D ri ft w o o d R o a d
PROFESSIONAL SEAL:
ANTON LEE ENGINEERING, LLC
1765 E. NINE MILE RD., STE. 1 #220
PENSACOLA, FL 32514
CERTIFICATE OF AUTHORIZATION:
FL 32794 | AL 5685-E
ANTON LEE, P.E.
FL PE# 82369 | AL PE# 37427-E
PROJECT NUMBER 21-147
AL
ILF
O AD
No 82369
STATE OF
ESNECIL
PROFES SIONAL E NGR IN
E
RE
A
TN NO EEL
Th is it em h as b ee n di gi ta lly s ig ne d an d se al ed b y
An to n Le e, P
E, o n
/0 8/
. P rin te d co pi es o f t hi s do cu m en t a re n ot c on si de re d si gn ed a nd s ea le d an d th e si gn at ur e m us t b e ve rif ie d on a ny e le ct ro ni c co pi es
M-001
MECHANICAL
LEGEND AND NOTES
DETAIL 3 NOTES:
· DELETE INSULATION STAND-OFF ON DUCTWORK
WITHOUT EXTERIOR INSULATION.
· DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER
INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE
DAMPERS & ROUND DAMPERS.
MVD SIDE ELEVATION MVD SECTION
VANE
VANE
R SHALL
EQUAL
OR BE
GREATER
THAN
W.
R SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
W
R
R
2/3W 1/ 3W
R SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
STANDARD RADIUS
ELBOW
SHORT RADIUS
ELBOW WITH ONE
VANE
SHORT RADIUS
ELBOW WITH TWO
VANES
W W
1/2W 1/ 3W
1/6W
R
1/4"W" (4" MIN.)
NEGATIVE - PRESSURE AIR STREAM
POSITIVE - PRESSURE AIR STREAM
"W"
2 DUCT BRANCH CONNECTION AND MVD DETAIL
NOT TO SCALE
MAIN DUCT
BRANCH DUCT
MANUAL VOLUME DAMPER (MVD).
PROVIDE NUTS ON BOTH SIDES.
45° CLINCH
COLLAR
2" WRAP INSULATION
(IF REQUIRED)
1/2" ROUND ROD PIN
OUTSIDE END BEARING
STIFFEN BLADE AS REQUIRED DUCT
INSULATION
INSULATION STAND OFF
DAMPER BLADE
DAMPER BLADE
1/8" CLEARANCE
ALL AROUND
INSIDE END BEARINGHANDLE WITH LOCKING QUADRANT
6 DUCTWORK RADIUS ELBOW DETAIL
NOT TO SCALE
DETAIL 6 NOTES:
· THE INTERIOR SURFACE OF ALL RADIUS
ELBOWS SHALL BE MADE ROUND.
· ALL STANDARD RADIUS ELBOWS SHOWN
ON FLOOR PLANS MAY BE MADE SHORT
RADIUS ELBOWS. ALL SHORT RADIUS
ELBOWS SHALL HAVE VANES. VANES
SHALL BE CONSTRUCTED, SUPPORTED
AND FASTENED AS RECOMMENDED BY
SMACNA.
4 CONDENSATE DRAIN TRAP DETAIL
NOT TO SCALE
3/4" 1/2"
1-1/2"
2-1/2"
UNIT PRIMARY CONDENSATE
DRAIN CONNECTION
UNION
NOTES:
1. PROVIDE CLEARANCE
BELOW AIR HANDLER
UNIT TO ALLOW
PROPER P-TRAP AND
SLOPE REQUIREMENTS.
TOTAL CLEARANCE
MIN. 6".
2. ROUTE PVC
CONDENSATE PIPE
AND SLOPE TO FLOOR
DRAIN. PROVIDE WITH
1-1/2" AIR GAP.
PROVIDE 1/2" ELASTOMERIC
INSULATION THROUGHOUT
CONDENSATE DRAIN PIPE.
HAND TIGHT PLUG
DUCTWORK WALL
PENETRATION DETAIL
NOT TO SCALE
SEALANT ALL AROUND
INSULATION
FIBERGLASS BATTS
INSULATION (1.5 PCF)
PROVIDE 1/2" MINIMUM
CLEARANCE BETWEEN
WALL OPENING AND
DUCTWORK.
PROVIDE SHEET METAL SCREWS AT 8" O.C.
CONTINUOUS GALV. STEEL ANGLE WITH
WELDED CORNERS AND JOINTS. MIN.
2"x2"x14 GA.
DETAIL 3 NOTE:
PROVIDE PLASTIC PHENOLIC ENGRAVED
NAMEPLATE/TAG WITH BLACK BACKGROUND AND
WHITE TEXT. MECHANICALLY AFFIXED.
AHU-#
MIN. 3"
M
IN
. 1 .5
3 EQUIPMENT TAG DETAIL
NOT TO SCALE
1 INCH FONT SIZE
DESIGN CONDITIONS
OUTSIDE INSIDE - OCCUPIED MODE
DB (DEG. F) WB (DEG. F) DB (DEG. F) RH
SUMMER 94 78 72 50%
WINTER 29 - 70
NOTES:
1. INSIDE SUMMER DESIGN TEMPERATURE IS +0/-2 DEG. F.
2. INSIDE SUMMER DESIGN RELATIVE HUMIDITY IS + 10%.
3. INSIDE WINTER DESIGN TEMPERATURE IS +2/-0 DEG. F.
SPLIT SYSTEM DX HEAT PUMP UNIT EQUIPMENT SCHEDULE - WALTON COUNTY TRANSIT AND RR
INDOOR UNIT OUTDOOR UNIT
FAN DATA COOLING COIL DATA HEATING COIL DATA ELECTRIC HEAT
ELECTRICAL DATA ELECTRICAL DATASA OA TOTAL SENSIBLE LATENT ARI TOTAL REQ. PROVIDED
AIRFLOW AIRFLOW EXT. S. P. POWER CAP. CAP. CAP. EAT (DB) EAT (WB) LAT (DB) LAT (WB) SEER/ CAP. EAT (DB) LAT (DB) ARI HEAT HEAT # OF COMP FAN MARK (CFM) (CFM) (IN. W.C.) (HP) (MBH) (MBH) (MBH) (DEG. F) (DEG. F) (DEG. F) (DEG. F) EER (MBH) (DEG. F) (DEG. F) HSPF (KW) (KW) STAGE MCA MOP VOLTS PHASE Hz MARK QTY QTY MCA MOP VOLTS PHASE Hz AHU-1 980 100 0.50 1/3 HP 25.3 21.3 4.0 73.5 60.7 54.0 51.5 16 SEER 31.9 65 95 3.9 COP 9.3 9.6 1 54 60 240 1 60 HPU-1 1 1 15 25 240 1 60
NOTES:
1. UNIT EFFICIENCY IS RATED AT ARI STANDARD CONDITIONS.
2. PROVIDE INDOOR AIR HANDLER UNIT WITH VARIABLE SPEED MOTOR AND 2" MERV 8 FILTER.
3. PROVIDE FIELD FABRICATED INSULATED METAL PLENUM BOX AND NEOPRENE ISOLATOR.
4. PROVIDE OUTDOOR UNIT WITH LOUVERED PANELS OR COIL GUARD AND DIGITAL SCROLL COMPRESSOR
5. REFRIGERANT R-410A PIPING SIZE, ROUTING, AND CONFIGURATION SHALL BE AS RECOMMENDED BY MANUFACTURER.
6. INSULATE ENTIRE LENGTH OF REFRIGERANT SUCTION LINES WITH MINIMUM 3/4" THICK UNICELLULAR INSULATION.
7. MOUNT AND SECURE ALL OUTDOOR UNIT ON 4 INCH THICK CONCRETE PAD.
8. PROVIDE OUTDOOR UNIT WITH CORROSION PROTECTION FOR COILS AND CASINGS. MIN. 10,000 HOURS SALT SPRAY.
9. PROVIDE SINGLE POWER POINT CONNECTION. COORDINATE FINAL POWER REQUIREMENTS WITH ELECTRICAL.
10. BASIS OF DESIGN IS TRANE.
FAN SCHEDULE
MARK TYPE DRIVE CONTROLS INTERLOCK
PERFORMANCE DATA ELECTRICAL DATA
CFM
E.S.P.
(IN.
W.C.)
MAX.
RPM
MAX.
SONES
FAN
POWER
(HP) VOLTS PHASE Hz
EF-1 IL DD LIGHT SWITCH 150 0.40 1,000 1.0 124W 115 1 60
EF-2 IL DD LIGHT SWITCH 150 0.40 1,000 1.0 124W 115 1 60
EF-3 CEF DD LIGHT SWITCH 80 0.40 1,000 2.0 80W 115 1 60
NOTES:
1. IL - INLINE CABINET; CEF - CEILING MOUNT; DD - DIRECT DRIVE
2. PROVIDE WITH GALVANIZED HOUSING AND SOLID STATE SPEED CONTROLLER FOR AIR FLOW BALANCING, NEMA-1 SWITCH, TOGGLE ALONG WITH JUNCTION BOX MOUNTED AND WIRED. PROVIDE WITH BACKDRAFT DAMPER.
3. BASIS OF DESIGN:
EF-1 AND 2: GREENHECK CSP-A200.
EF-3: GREENHECK SP-B110.
1 CEILING EXHAUST FAN DETAIL
NOT TO SCALE
DETAIL 1 KEY NOTES:
CORROSION RESISTANT GALVANIZED
STEEL SCROLL AND HOUSING WITH
SOUND ABSORBING INSULATION
ARCHITECTURAL CEILING GRILLE
RECTANGULAR OUTLET DUCT COLLAR
AND TRANSITION TO ROUND
OUTLET WITH INTEGRAL SPRING LOADED
BACK DRAFT DAMPER
ACCESS PANEL (BOTTOM)
FLEXIBLE DUCT CONNECTOR
MOUNTING ANGLE BRACKET
VIBRATION ISOLATOR - TOP & BOTTOM
1/4" S.S. THREADED HANGER ROD
(TOTAL OF FOUR). SUPPORT FROM
BUILDING PER FAN MANUFACTURER'S
RECOMMENDATIONS.
S.S. NUT AND WASHER
AIRFLOW
5/8/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21014
St o ke s
A rc hi te c tu ra l, In c
St o ke s
A rc hi te c tu ra l, in c
. h e re b y e xp re ss ly re se rv e s its c o m m o n-la w c o p yr ig ht a nd o th e r p ro p e rty ri g ht s to th e se p la ns
D ra w in g s a re n o t t o b e re p ro d uc e d , c ha ng e d
, o r c o p ie d in a ny fo rm w ha ts o e ve r, no r a re th e y to b e a ss ig ne d to a ny th ird p a rty w ith o ut fi rs t o b ta in in g th e e xp re ss w rit te n p e rm is si o n a nd c o ns e nt o f S to ke s A rc hi te c tu ra l, in c
DRAWN BY:
AL
CHECKED BY:
AL
A rc hi te c st e r P la nn rio r D e si g n
C lo ve rd a le
B o ul e va rd
Fo rt
W a lto n
Be a c h, F lo rid a
Ph o ne
0)
-2 x:
(8
) 6
-6
FL
L ic en se
: A R
C or p Li ce ns e
A
AC
Architectural Inc.
Stokes
M ir a m a r
B ea ch
Fl o ri d a
Drift woo d Tr ansi t Sto p &
Rest room
- W alto n Co unty
D ri ft w o o d R o a d
PROFESSIONAL SEAL:
ANTON LEE ENGINEERING, LLC
1765 E. NINE MILE RD., STE. 1 #220
PENSACOLA, FL 32514
CERTIFICATE OF AUTHORIZATION:
FL 32794 | AL 5685-E
ANTON LEE, P.E.
FL PE# 82369 | AL PE# 37427-E
PROJECT NUMBER 21-147
AL
ILF
O AD
No 82369
STATE OF
ESNECIL
PROFES SIONAL E NGR IN
E
RE
A
TN NO EEL
Th is it em h as b ee n di gi ta lly s ig ne d an d se al ed b y
An to n Le e, P
E, o n
/0 8/
. P rin te d co pi es o f t hi s do cu m en t a re n ot c on si de re d si gn ed a nd s ea le d an d th e si gn at ur e m us t b e ve rif ie d on a ny e le ct ro ni c co pi es
M-002
SCHEDULES AND DETAILS
GENERAL:
• APPLICABLE FOR AHU/HPU-1
• PROVIDE ALL REQUIRED CONTROLS TO OPERATE THE UNITS AS NOTED
BELOW.
• PROVIDE CONDUIT FOR ALL CONTROLS WIRING EXPOSED IN THE
MECHANICAL ROOM.
• CONDUIT SHALL COMPLY WITH ELECTRICAL REQUIREMENTS.
START/STOP CONTROL:
• PROVIDE MANUFACTURER PROGRAMMABLE T'STAT SYSTEM FOR
SCHEDULED START/STOP AND LOCAL OVERRIDE.
• PROVIDE ALL REQUIRED THE FIRE ALARM RELAY AND ALL SAFETIES
FEATURES FROM MFR.
OCCUPIED COOLING MODE:
· THE AHU FAN SHALL START AND ONLY MODULATE AS NEEDED.
· THE STAGES OF DX COOLING SHALL BE CYCLED AS REQUIRED TO
MAINTAIN SPACE TEMPERATURE WHEN THE SPACE TEMPERATURE RISES
ABOVE THE COOLING SETPOINT.
OCCUPIED HEATING MODE:
· THE AHU FAN SHALL START AND ONLY MODULATE AS NEEDED.
· THE STAGES OF DX HEATING SHALL BE CYCLED AS REQUIRED TO MAINTAIN
SPACE TEMPERATURE WHEN THE SPACE TEMPERATURE DROPS BELOW THE
HEATING SETPOINT.
· WHEN THE DX HEATING CYCLE IS INCAPABLE TO MAINTAIN SPACE
TEMPERATURE, THE ELECTRICAL STRIP HEAT SHALL BE MODULATED AS
REQUIRED TO MAINTAIN HEATING SETPOINT.
OCCUPIED DEFROST MODE:
· THE AHU FAN SHALL START.
· DURING HEATING MODE, IF THE UNIT DEFROST CYCLE ACTIVATES, THE UNIT
SHALL RUN THE INDOOR FAN AND MODULATE THE ELECTRIC STRIP HEATER
TO SATISFY THE SPACE HEATING REQUIREMENTS.
UNOCCUPIED MODE:
· THE AHU ONLY RUN AS NEEDED TO SATISFY UNOCCUPIED SPACE
TEMPERATURE.
OVERRIDE MODE:
· THE OVERRIDE TIMERS SHALL PLACE THE SYSTEM IN OCCUPIED MODE FOR
2 HOURS (ADJ.)
SEQUENCE OF OPERATION
NOTES:
1. PREP AND PAINT CHANNEL AFTER CUTTING
AND BEFORE INSTALLATION
2. SUPPORT CHANNEL FROM STRUCTURE
ABOVE
3. PROVIDE SUPPORT PER PROJECT
SPECIFICATIONS AND WITHIN 6" OF ANY
ELBOW
OVERHEAD INTERIOR REFRIGERANT
PIPE SUPPORT DETAIL
3/8" THREADED ROD SHALL BE SECURED TO
STRUCTURE. TYP.
INSULATE AROUND ALL SUCTION LINES
BENEATH CLAMP. TYP.
LOCKNUT AND WASHER. TYP.
SECURE REFRIGERANT PIPING TO CHANNEL WITH
"UNISTRUT" PIPE CLAMP OR EQUAL. TYP.
1-5/8" P-1000 "UNISTRUT"
CHANNEL OR EQUAL
(TYPICAL)
WEATHER EXPOSED OUTDOOR
REFRIGERANT PIPE SUPPORT DETAIL
RUN INSULATION AND ALUMINUM JACKET
OF SUCTION LINE THRU CLAMP ASSEMBLY
"UNISTRUT" CHANNEL OR
EQUAL. TYP.
SECURE REFRIGERANT PIPING TO CHANNEL
WITH "UNISTRUT" PIPE CLAMP OR EQUAL. TYP.
2-3/8" EXPANSION BOLTS 3" LONG
NOT TO SCALE
NOT TO SCALE
SPLIT SYSTEM DX AHU AND HPU DETAIL2 NOT TO SCALE
DETAIL 4 KEY NOTES:
INDOOR AIR HANDLER UNIT. ROUTE CONTROL WIRING IN
CONDUIT TO AHU. ABOVEGROUND HVAC CONTROL
CONDUIT WITH PULL-WIRE INSTALLED BY MECHANICAL
CONTRACTOR. CONTROL WIRING IN FLEX CONDUIT TO
OUTDOOR CONDENSING UNIT.
OUTDOOR HEAT PUMP UNIT. ANCHOR CONDENSING UNIT
TO THE HOUSEKEEPING PAD WITH AT WITH GASKETED
WASHERS THROUGH MFR PROVIDED HOLES IN THE BASE
OF THE UNIT.
FLEXIBLE DUCT CONNECTION. TYP.
NEOPRENE ISOLATORS.
ROUTE OA TO EXTERIOR WALL CAP OR SOFFIT GRILLE.
HARD DRAWN COPPER REFRIGERANT LINES. INSTALL
AWAY FROM EQUIPMENT MAINTENANCE CLEARANCE.
SECURE TO WALL AND CEILING.
CONDENSATE DRAIN. SIZE COPPER CONDENSATE LINE AT
FULL SIZE OF UNIT CONNECTION. MIN 3/4" DIA. INSULATE
CONDENSATE WITH 1/2" FLEXIBLE UNICELLULAR
INSULATION AND SECURE PIPING TO STRUCTURE. ROUTE
DRAIN TO EXTERIOR SPLASH BLOCK.
PROVIDE SLEEVE ON ALL PIPE PENETRATION. SEAL
WEATHER TIGHT.
2" PLEATED FILTER.
FIELD FABRICATED SIDE RETURN FILTER BASE. PROVIDE WITH
HINGED FILTER ACCESS DOOR.
EX
TE
RI
O
R W
A
LL
STRUCTURAL
FOUNDATION
9 10
OA DUCT
FINISH FLOOR
TYPICAL FOR AHU/HPU #1
PROVIDE UNIT WITH
COIL GUARD
RA DUCT
SA DUCT
EXPOSED DOUBLE WALL DUCT NOTES
· PROVIDE DOUBLE WALL RECTANGULAR AND ROUND DUCT FOR ALL
EXPOSED DUCTWORK LOCATED INSIDE RESTROOM AS NOTED.
· SURFACE PREPARATION - EXPOSED TO BE PAINTED. COLOR PER
ARCHITECTURAL.
· DUCTWORK SHALL BE FABRICATED PER SMACNA HVAC DUCT
CONSTRUCTION STANDARDS 3RD ED. 2005. PRESSURE RATING SHALL BE
2" W.G.
· COORDINATE WITH A/E FOR FINAL COLOR SELECTION. DUCTWORK
SHALL BE FIELD PAINTED. HANDLE WITH CARE. ALL DENTS AND
IRREPARABLE DAMAGE AS DETERMINED BY THE A/E SHALL BE REPLACED
BY THE CONTRACTOR WITH NO ADDITIONAL COST TO THE OWNER.
· BASIS OF DESIGN IS CROWN PRODUCTS AND EQUAL BY SPIRAL PIPE OF
TEXAS.
· PROVIDE CABLE WIRE SUPPORT TO STRUCTURE.
RECTANGULAR DOUBLE WALL DUCTWORK:
· OUTER WALL SHELL MATERIAL: 24 GAUGE G-60 GALVANIZED STEEL.
· INNER WALL: PERFORATED METAL LINER FABRICATED OF G-60
GALVANIZED STEEL, 22 GAUGE GALVANIZED PERFORATED STEEL, 3/32"
DIAMETER HOLES ON 3/16" STAGGERED CENTERS 2" W.G. PROVIDE WITH
1" THICK INTERNAL INSULATION CONSISTS OF HIGH DENSITY GLASS FIBER
BOARD (4 PCF).
· DUCT CONSTRUCTION: PROVIDE GASKET FOR TRANSVERSE
CONNECTORS WITH TDF FITTINGS.
ROUND SPIRAL DOUBLE WALL DUCTWORK
· OUTER WALL SHELL:. MATERIAL: 24 GAUGE GALVANIZED STEEL PER ASTM
A653, CS TYPE B. GALVANNEALED STEEL (PAINTABLE) PER ASTM A65. 24
GAUGE
· INNER WALL: 24 GAUGE PERFORATED STEEL 3/32" DIA. HOLE, 3/16" CENTER
STAGGER. 1" THICK INTERNAL INSULATION.
· PIPE CONSTRUCTION: SPIRAL LOCK SEAM SMACNA RL-1.
· TRANSVERSE CONNECTIONS: FACTORY INSTALLED 18 GAUGE OUTBOARD
FLANGE WITH FIELD INSTALLED FACTORY PROVIDED BUTYL GASKET;
SCREWED TOGETHER WITH #10 TEK SCREWS.
AHU
HPU
EF 1
EF
EF
24"x8" SAR
400 CFM
(TYP. OF 2)
12"x6" SAR
100 CFM
24"x14" RAR
SIDEWALL
RETURN
8"x8" SAR
80 CFM
DOUBLE WALL
ROUND DUCT
DOUBLE WALL
ROUND DUCT
"Ø
14"Ø"
12"x6" SAR
100 CFM
T 1
KEY NOTES
1 ROUTE 6" EXH TO ALUMINUM WALL VENT CAP EQUAL TO
SEIHO CFXC-6
8"x8" TAG. TYP. OF 2.
INLINE CABINET EXHAUST FAN. INTERLOCK WITH LIGHTING
OCCUPANCY SENSOR. SEE ELECTRICAL. TYP.
ROUTE 8" OA TO ALUMINUM WALL CAP EQUAL TO SEIHO
SFXN-8.
PROVIDE ALUMINUM JACKET ON ALL WEATHER EXPOSED
INSULATED REFRIGERANT PIPE.
MOUNT CONDENSING UNIT ON CONCRETE
HOUSEKEEPING PAD. PROVIDE WITH NEOPRENE PAD.
12"x6" EAR
150 CFM
12"x6" EAR
150 CFM
5/8/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21014
St o ke s
A rc hi te c tu ra l, In c
St o ke s
A rc hi te c tu ra l, in c
. h e re b y e xp re ss ly re se rv e s its c o m m o n-la w c o p yr ig ht a nd o th e r p ro p e rty ri g ht s to th e se p la ns
D ra w in g s a re n o t t o b e re p ro d uc e d , c ha ng e d
, o r c o p ie d in a ny fo rm w ha ts o e ve r, no r a re th e y to b e a ss ig ne d to a ny th ird p a rty w ith o ut fi rs t o b ta in in g th e e xp re ss w rit te n p e rm is si o n a nd c o ns e nt o f S to ke s A rc hi te c tu ra l, in c
DRAWN BY:
AL
CHECKED BY:
AL
A rc hi te c st e r P la nn rio r D e si g n
C lo ve rd a le
B o ul e va rd
Fo rt
W a lto n
Be a c h, F lo rid a
Ph o ne
0)
-2 x:
(8
) 6
-6
FL
L ic en se
: A R
C or p Li ce ns e
A
AC
Architectural Inc.
Stokes
M ir a m a r
B ea ch
Fl o ri d a
Drift woo d Tr ansi t Sto p &
Rest room
- W alto n Co unty
D ri ft w o o d R o a d
PROFESSIONAL SEAL:
ANTON LEE ENGINEERING, LLC
1765 E. NINE MILE RD., STE. 1 #220
PENSACOLA, FL 32514
CERTIFICATE OF AUTHORIZATION:
FL 32794 | AL 5685-E
ANTON LEE, P.E.
FL PE# 82369 | AL PE# 37427-E
PROJECT NUMBER 21-147
AL
ILF
O AD
No 82369
STATE OF
ESNECIL
PROFES SIONAL E NGR IN
E
RE
A
TN NO EEL
Th is it em h as b ee n di gi ta lly s ig ne d an d se al ed b y
An to n Le e, P
E, o n
/0 8/
. P rin te d co pi es o f t hi s do cu m en t a re n ot c on si de re d si gn ed a nd s ea le d an d th e si gn at ur e m us t b e ve rif ie d on a ny e le ct ro ni c co pi es
MECHANICAL PLAN1
4' 8'
SCALE: 1/4"=1'-0"
4' 0'
M-101
PLAN AND DETAILS
| Sheets and Views |
| M001 |
| M002 |
| M101 |