Attch 11_Tech Specs DIV26 Electrical.pdf
PDF 182 KB Posted
- Attached to
- B7 Electrical Svc Upgrade & 2nd Floor Structural Spt Federal contract opportunity
- Solicitation number
- N40085-20-B-2531
About this file
This solicitation is for electrical service upgrades and second floor structural support repairs at Portsmouth Naval Shipyard in Kittery, Maine. The project includes providing all labor, equipment, materials, transportation, and supervision to complete electrical service upgrades and repairs. The solicitation was issued by the Department of the Navy Naval Facilities Engineering Command. Responses are due by the date listed on the solicitation. The awarded contractor will be responsible for all aspects of the project, including structural repairs, electrical upgrades, and associated work.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 1419 B7 Electric Svc and 2nd Flr.pdf | ||
| RFI 2 - B7 Elect Svc Upgrade 20B2531.pdf | ||
| N4008520B2531 0003.pdf | ||
| RFIS - B7 Elect Svc Upgrade 20B2531.pdf | ||
| N4008520B2531 0002.pdf | ||
| SV B7 Sign-In.pdf | ||
| N4008520B2531 0001.pdf | ||
| Attch 10_Permanent Structural Shoring.pdf | ||
| Attch 4_PNSY Div 1 Submittal Reg 1650933.pdf | ||
| Attch 3_Tech Specs - Permanent Shoring and Heater.pdf | ||
| Attch 6_eOMSI WKBK 1650933 B7 ELECTRICAL SVC UPGRADE.pdf | ||
| Attch 9_Temp Shoring Specs.pdf | ||
| Attch 2_PNSYDIV1 Specs 152020.pdf | ||
| N4008520B2531.pdf | ||
| Attch 1_Bid Form.pdf | ||
| Attch 5_Drawings B7 Electrical Svc - Signed.pdf | ||
| Attch 8_Electrical Systems and Const. Stds PNSY.pdf | ||
| SOW B7 Elec Svc Upgrade and 2nd Flr Spt_02-25-20.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
02/14
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B1 (2013) Standard Specification for Hard‐Drawn Copper Wire
ASTM B8 (2011) Standard Specification for Concentric‐Lay‐Stranded Copper Conductors, Hard, Medium‐Hard, or Soft
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2017) National Electrical Safety Code
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C80.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)
ANSI C80.3 (2005) American National Standard for Electrical Metallic Tubing (EMT)
ANSI C80.5 (2005) American National Standard for Electrical Rigid Aluminum Conduit
NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 6 (1993; R 2011) Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2016) Motors and Generators
NEMA MG 11 (1977; R 2012) Energy Management Guide for Selection and Use of Single Phase Motors
NEMA RN 1 (2005; R 2013) Polyvinyl‐Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (1992; R 1997) Standard for Dry‐Type Transformers for General Applications
NEMA TC 2 (2013) Standard for Electrical Polyvinyl Chloride (PVC) Conduit
NEMA TC 3 (2015) Standard for Polyvinyl Chloride (PVC) Fittings for Use With Rigid PVC Conduit and Tubing
NEMA Z535.4 (2011) American National Standard for Product Safety Signs and Labels
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017) National Electrical Code
NFPA 70E (2015; Errata 1 2015) Standard for Electrical Safety in the Workplace U.S. NATIONAL ARCHIVES
AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.147 Control of Hazardous Energy (Lock Out/Tag Out)
UNDERWRITERS LABORATORIES (UL)
UL 1 (2005; Reprint Jul 2012) Standard for Flexible Metal Conduit
UL 1063 (2006; Reprint Jul 2012) Machine‐Tool Wires and Cables
UL 1242 (2006; Reprint Mar 2014) Standard for Electrical Intermediate Metal Conduit
UL 1449 (2014; Reprint Mar 2015) Surge Protective Devices
UL 360 (2013; Reprint Jan 2015) Liquid‐Tight Flexible Steel Conduit
UL 4248‐1 (2007; Reprint Oct 2013) UL Standard for Safety Fuseholders ‐ Part 1: General Requirements
UL 4248‐12 (2007; Reprint Dec 2012) UL Standard for Safety Fuseholders ‐ Part 12: Class R
UL 489 (2016) Molded‐Case Circuit Breakers, Molded‐Case Switches, and Circuit‐Breaker Enclosures
UL 498 (2012; Reprint Jan 2016) Attachment Plugs and Receptacles
UL 50 (2007; Reprint Apr 2012) Enclosures for Electrical Equipment, Non‐environmental Considerations
UL 506 (2008; Reprint Oct 2013) Specialty Transformers
UL 508 (1999; Reprint Oct 2013) Industrial Control Equipment
UL 514C (2014; Reprint Dec 2014) Nonmetallic Outlet Boxes, Flush‐Device Boxes, and Covers
UL 5A (2015) Nonmetallic Surface Raceways and Fittings
UL 6 (2007; Reprint Nov 2014) Electrical Rigid Metal Conduit‐Steel
UL 651 (2011; Reprint May 2014) Standard for Schedule 40 and 80 Rigid PVC Conduit and Fittings
UL 67 (2009; Reprint Apr 2015) Standard for Panelboards
UL 6A (2008; Reprint Nov 2014) Electrical Rigid Metal Conduit ‐ Aluminum, Red Brass, and Stainless Steel
UL 797 (2007; Reprint Dec 2012) Electrical Metallic Tubing – Steel
UL 870 (2008; Reprint Feb 2013) Standard for Wireways, Auxiliary Gutters, and Associated Fittings
UL 943 (2006; Reprint Jun 2012) Ground‐Fault Circuit‐Interrupters
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in IEEE 100.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00.
SD‐02 Shop Drawings Panelboards; G Transformers; G Cable trays; G Marking strips Labels; G
SD‐03 Product Data
Circuit breakers; G Switches; G Wire, 500MCM RHW‐2 EPR; G Splices, heat shrink, 600VAC; G Transformers; G Panelboards; G Enclosed circuit breakers; G Surge protective devices (Include performance and characteristic curves); G
SD‐06 Test Reports
600‐volt wiring test; G Grounding system test; G Transformer tests; G
SD‐07 Certificates
Fuses; G
SD‐09 Manufacturer's Field Reports Transformer factory tests; G
Submit operation and maintenance data in accordance with Section 01 78 23, OPERATION AND MAINTENANCE DATA and as specified herein.
SD‐11 Closeout Submittals As Built drawings; G
1.4 QUALITY ASSURANCE
1.4.1 Interior Distribution System
a. Not used.
b. The General Contractor and Subcontractors shall work together to resolve conflicts between trades. Work shall not be fabricated until the General Contractor has coordinated all trades and resolved conflicts.
1.4.2 As Builts
Submit As Built drawings per requirements in Section 01 78 00.00 22.
1.4.3 Fuses
Submit coordination data as specified in paragraph, FUSES of this section.
1.4.4 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" or "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.4.5 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2‐year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.5.1 Alternative Qualifications
Products having less than a 2‐year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.4.5.2 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site are not acceptable.
1.5 WARRANTY
Provide equipment items supported by service organizations that are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
As a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70 for all materials, equipment, and devices.
2.2 CONDUIT AND FITTINGS
Conform to the following:
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc‐Coated Steel Conduit
ANSI C80.1, UL 6.
2.2.2 Rigid Nonmetallic Conduit
PVC Type EPC‐40, and EPC‐8 in accordance with NEMA TC 2,UL 651, or fiberglass conduit, in accordance with NEMA TC 14.
2.2.3 Not Used.
2.2.4 Electrical, Zinc‐Coated Steel Metallic Tubing (EMT) UL 797, ANSI C80.3.
2.2.5 Plastic‐Coated Rigid Steel Type 40( 40 mils thick).
2.2.6 Flexible Metal Conduit UL 1.
2.2.6.1 Liquid‐Tight Flexible Metal Conduit, Steel UL 360.
2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit UL 514B. Ferrous fittings: cadmium‐ or zinc‐coated in accordance with UL 514B.
2.2.7.1 Fittings for Rigid Metal Conduit Threaded‐type. Split couplings unacceptable.
2.2.7.2 Fittings for EMT
Die Cast compression type.
2.2.8 Fittings for Rigid Nonmetallic Conduit
NEMA TC 3 for PVC and NEMA TC 14 for fiberglass, and UL 514B.
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
UL 5, two‐piece painted steel, totally enclosed, snap‐cover type.
2.3.2 Surface Nonmetallic Raceway
UL 5A, nonmetallic totally enclosed, snap‐cover type.
2.4 CABLE TRAYS
Provide the following:
a. Cable trays: form a wireway system, with a nominal depth as indicated.
b. Cable trays: constructed of yellow composite fiberglass.
c. Cable trays: include splice and end plates, dropouts, and miscellaneous hardware.
d. Edges, fittings, and hardware: finished free from burrs and sharp edges.
e. Fittings: ensure not less than load‐carrying ability of straight tray sections and have manufacturer's minimum standard radius.
2.4.1 Ladder‐Type Cable Trays
Provide size as indicated with maximum rung spacing of 12 inches.
2.5 OUTLET BOXES AND COVERS
UL 514A, cadmium‐ or zinc‐coated, if ferrous metal. UL 514C, if nonmetallic.
2.5.1 Outlet Boxes
a. Depth of boxes: large enough to allow manufacturers' recommended conductor bend radii.
2.6 CABINETS, JUNCTION BOXES, AND PULL BOXES
Volume greater than 100 cubic inches, UL 50, hot‐dip, zinc‐coated, if sheet steel.
2.7 WIRES AND CABLES
Provide wires and cables in accordance applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Do not use wires and cables manufactured more than 12 months prior to date of delivery to site.
2.7.1 Conductors
a. Conductor sizes and capacities shown are based on copper, unless indicated otherwise.
b. Conductors No. 8 AWG and larger diameter: stranded.
c. Conductors No. 10 AWG and smaller diameter: solid.
d. Conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3: stranded unless specifically indicated otherwise.
e. All conductors: copper.
2.7.1.1 Minimum Conductor Sizes
Provide minimum conductor size in accordance with the following:
a. Branch circuits: No. 12 AWG.
b. Class 1 remote‐control and signal circuits: No. 14 AWG.
c. Class 2 low‐energy, remote‐control and signal circuits: No. 16 AWG.
d. Class 3 low‐energy, remote‐control, alarm and signal circuits: No. 22 AWG.
2.7.2 Color Coding
Provide color coding for service, feeder, branch, control, and signaling circuit conductors.
2.7.2.1 Ground and Neutral Conductors
Provide color coding of ground and neutral conductors as follows:
a. Grounding conductors: Green.
b. Neutral conductors: White.
c. Exception, where neutrals of more than one system are installed in same raceway or box, other neutrals color coding: white with a different colored (not green) stripe for each.
2.7.2.2 Ungrounded Conductors
Provide color coding of ungrounded conductors in different voltage systems as follows:
a. 208/120 volt, three‐phase
(1) Phase A ‐ black
(2) Phase B ‐ red
(3) Phase C ‐ blue
b. 480/277 volt, three‐phase
(1) Phase A ‐ brown
(2) Phase B ‐ orange
(3) Phase C ‐ yellow
c. 120/240 volt, single phase: Black and red
2.7.3 Insulation
Unless specified or indicated otherwise or required by NFPA 70, provide power and lighting wires rated for 600‐volts, RHW conforming to UL 44, except that grounding wire may be type TW conforming to UL 83; remote‐control and signal circuits: Type TW or TF, conforming to UL 83. Where lighting fixtures require 90‐degree Centigrade (C) conductors, provide only conductors with 90‐degree C insulation or better.
2.7.4 Bonding Conductors
ASTM B1, solid bare copper wire for sizes No. 8 AWG and smaller diameter;
ASTM B8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger diameter.
2.8 SPLICES AND TERMINATION COMPONENTS
UL 486A‐486B for wire connectors and UL 510 for insulating tapes. Connectors for No. 10 AWG and smaller diameter wires: insulated, pressure‐type in accordance with UL 486A‐486B or UL 486C (twist‐on splicing connector). Provide solderless terminal lugs on stranded conductors.
2.9 DEVICE PLATES
Provide the following:
a. UL listed, one‐piece device plates for outlets to suit the devices installed.
b. For metal outlet boxes, plates on unfinished walls: zinc‐coated sheet steel or cast metal having round or beveled edges.
c. For nonmetallic boxes and fittings, other suitable plates may be provided.
d. Screws: machine‐type with countersunk heads in color to match finish of plate.
e. Sectional type device plates are not be permitted.
f. Plates installed in wet locations: gasketed and UL listed for "wet locations."
2.10 SWITCHES
2.10.1 Disconnect Switches
NEMA KS 1. Provide heavy duty‐type switches where indicated, where switches are rated higher than 240 volts, and for double‐throw switches. Utilize Class R fuseholders and fuses for fused switches, unless indicated otherwise. Provide horsepower rated for switches serving as the motor‐disconnect means.
Provide switches in NEMA1 painted steel, enclosure per NEMA ICS 6 or as indicated.
2.11 FUSES
NEMA FU 1. Provide complete set of fuses for each fusible switch.
Coordinate time‐current characteristics curves of fuses serving motors or connected in series with circuit breakers or other circuit protective devices for proper operation. Submit coordination data for approval.
Provide fuses with a voltage rating not less than circuit voltage.
2.11.1 Fuseholders
Provide in accordance with UL 4248‐1.
2.11.2 Cartridge Fuses, Current Limiting Type (Class R) UL 198M, Class RK‐5 time‐delay type. Provide only Class R associated fuseholders in accordance with UL 4248‐12.
2.12 RECEPTACLES
Not used
2.13 PANELBOARDS
Provide panelboards in accordance with the following:
a. UL 67 and UL 50 having a short‐circuit current rating as indicated.
b. Panelboards for use as service disconnecting means: additionally conform to UL 869A.
c. Panelboards: circuit breaker‐equipped, bolt on style.
d. Designed such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining clearances as required by UL.
e. "Specific breaker placement" is required in panelboards to match the breaker placement indicated in the panelboard schedule on the drawings.
f. Use of "Subfeed Breakers" is not acceptable unless specifically indicated otherwise.
g. Main breaker: "separately" mounted "above"branch breakers.
h. Where "space only" is indicated, make provisions for future installation of breakers.
i. Directories: indicate load served by each circuit in panelboard.
j. Directories: indicate source of service to panelboard (e.g., Panel PA served from Panel MDP).
k. Provide new directories for existing panels modified by this project as indicated.
l. Type directories and mount in holder behind transparent protective covering.
m. Panelboards: listed and labeled for their intended use.
n. Panelboard nameplates: provided in accordance with paragraph FIELD FABRICATED
NAMEPLATES.
2.13.1 Enclosure
Provide panelboard enclosure in accordance with the following:
a. UL 50.
b. Cabinets Type NEMA 1 Steel.
c. Cabinets: painted in accordance with paragraph PAINTING.
d. Front edges of cabinets: form‐flanged or fitted with structural shapes welded or riveted to the sheet steel, for supporting the panelboard front.
e. All cabinets: fabricated such that no part of any surface on the finished cabinet deviates from a true plane by more than 1/8 inch.
f. Each door: fitted with a combined catch and lock, except that doors over 24 inches long provided with a three‐point latch having a knob with a T‐handle, and a cylinder lock.
g. Keys: two provided with each lock, with all locks keyed alike.
h. Finished‐head cap screws: provided for mounting the panelboard fronts on the cabinets.
2.13.2 Panelboard Buses
Support bus bars on bases independent of circuit breakers. Design main buses and back pans so that breakers may be changed without machining, drilling, or tapping. Provide isolated neutral bus in each panel for connection of circuit neutral conductors. Provide separate ground bus identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet.
2.13.3 Circuit Breakers
UL 489, thermal magnetic‐type having a minimum short‐circuit current rating equal to the short‐circuit current rating of the panelboard in which the circuit breaker will be mounted. Bolt on style. Breaker terminals: UL listed as suitable for type of conductor provided. Series rated circuit breakers and plug‐in circuit breakers are unacceptable.
2.13.3.1 Multipole Breakers
Provide common trip‐type with single operating handle. Design breaker such that overload in one pole automatically causes all poles to open. Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively.
2.13.3.2 Circuit Breaker With Ground‐Fault Circuit Interrupter UL 943 and NFPA 70.
Provide with "push‐to‐test" button, visible indication of tripped condition, and ability to detect and trip on current imbalance of 6 milliamperes or greater per requirements of UL 943 for Class A ground‐fault circuit interrupter.
2.13.3.3 Circuit Breakers for HVAC Equipment
Provide circuit breakers for HVAC equipment having motors (group or individual) marked for use with HACR type and UL listed as HACR type.
2.14 ENCLOSED CIRCUIT BREAKERS
UL 489. Individual molded case circuit breakers with voltage and continuous current ratings, number of poles, overload trip setting, and short circuit current interrupting rating as indicated. Enclosure type as indicated.
2.15 MOTOR SHORT‐CIRCUIT PROTECTOR (MSCP)
Not Used.
2.16 TRANSFORMERS
Provide transformers in accordance with the following:
a. NEMA ST 20, general purpose, dry‐type, self‐cooled, ventilated.
b. Provide transformers in NEMA4X type 316 Stainless Steel enclosure.
c. Transformer insulation system:
(1) 220 degrees C insulation system for transformers 15 kVA and greater, with temperature rise not exceeding 80 degrees C under full‐rated load in maximum ambient of 40 degrees C.
(2) 180 degrees C insulation for transformers rated 10 kVA and less, with temperature rise not exceeding 80 degrees C under full‐rated load in maximum ambient of 40 degrees C.
d. Transformer of 80 degrees C temperature rise: capable of carrying continuously 130 percent of nameplate kVA without exceeding insulation rating.
e. Transformers: quiet type with maximum sound level at least 3 decibels less than NEMA standard level for transformer ratings indicated.
2.16.1 Specified Transformer Efficiency
Transformers, indicated and specified with: 480V primary, 80 degrees C or 115 degrees C temperature rise, kVA ratings of 37.5 to 100 for single phase or 30 to 500 for three phase, energy efficient type.
Minimum efficiency, based on factory test results: not be less than NEMA Class 1 efficiency as defined by NEMA TP 1.
2.17 MOTORS
Not Used.
2.18 MOTOR CONTROLLERS
Not Used.
2.19 LOCKOUT REQUIREMENTS
Provide disconnecting means capable of being locked out for machines and other equipment to prevent unexpected startup or release of stored energy in accordance with 29 CFR 1910.147. Comply with requirements of Division 23, "Mechanical" for mechanical isolation of machines and other equipment.
2.20 GROUNDING AND BONDING EQUIPMENT
2.20.1 Ground Rods
UL 467. Ground rods: copper‐clad steel solid copper, with minimum diameter of 3/4 inch and minimum length 10 feet. Sectional ground rods are permitted.
2.21 MANUFACTURER'S NAMEPLATE
Provide on each item of equipment a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.22 FIELD FABRICATED NAMEPLATES
Provide field fabricated nameplates in accordance with the following:
a. ASTM D709.
b. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings.
c. Each nameplate inscription: identify the function and, when applicable, the position.
d. Nameplates: melamine plastic, 0.125 inch thick, black with white center core.
e. Surface: matte finish. Corners: square. Accurately align lettering and engrave into the core.
f. Minimum size of nameplates: one by 2.5 inches.
g. Lettering size and style: a minimum of 0.25 inch high normal block style.
2.23 WARNING SIGNS
Provide warning signs for flash protection in accordance with NFPA 70E and NEMA Z535.4 for switchboards, panelboards, industrial control panels, and motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing, or maintenance while energized. Provide field installed signs to warn qualified persons of potential electric arc flash hazards when warning signs are not provided by the manufacturer. Provide marking that is clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.
2.24 FIRESTOPPING MATERIALS
Provide firestopping around electrical penetrations as indicated.
2.25 WIREWAYS
UL 870. Material: steel galvanized 16 gauge for heights and depths up to 6 by 6 inches, and 14 gauge for heights and depths up to 12 by 12 inches. Provide in length required for the application with hinged‐ cover NEMA4X enclosure per NEMA ICS 6.
2.26 SURGE PROTECTIVE DEVICES
Provide parallel type surge protective devices (SPD) which comply with UL 1449 at the service entrance.
Provide surge protectors in a NEMA 1 enclosure per NEMA ICS 6. Use Type 1 or Type 2 SPD and connect on the load side of a dedicated circuit breaker.
Provide the following modes of protection:
FOR SINGLE PHASE AND THREE PHASE WYE CONNECTED SYSTEMS
Phase to phase ( L‐L ) Each phase to neutral ( L‐N ) Neutral to ground ( N‐G ) Phase to ground ( L‐G )
SPDs at the service entrance: provide with a minimum surge current rating of 80,000 amperes for L‐L mode minimum and 40,000 amperes for other modes (L‐N, L‐G, and N‐G).
Provide SPDs. Maximum L‐N, L‐G, and N‐G Voltage Protection Rating:
1,200V for 480Y/277V, three phase system Maximum L‐L Voltage Protection Rating:
2,000V for 480Y/277V, three phase system The minimum MCOV (Maximum Continuous Operating Voltage) rating for L‐N and L‐G modes of operation:
120% of nominal voltage for 240 volts and below;
115% of nominal voltage above 240 volts to 480 volts.
2.27 FACTORY APPLIED FINISH
Provide factory‐applied finish on electrical equipment in accordance with the following:
a. NEMA 250 corrosion‐resistance test and the additional requirements as specified herein.
b. Interior and exterior steel surfaces of equipment enclosures: thoroughly cleaned followed by a rust‐inhibitive phosphatizing or equivalent treatment prior to painting.
c. Exterior surfaces: free from holes, seams, dents, weld marks, loose scale or other imperfections.
d. Interior surfaces: receive not less than one coat of corrosion‐resisting paint in accordance with the manufacturer's standard practice.
e. Exterior surfaces: primed, filled where necessary, and given not less than two coats baked enamel with semigloss finish.
f. Equipment located indoors: ANSI Light Gray, and equipment located outdoors: ANSI Light Gray.
g. Provide manufacturer's coatings for touch‐up work and as specified in paragraph FIELD
APPLIED PAINTING.
2.28 SOURCE QUALITY CONTROL
2.28.1 Transformer Factory Tests
Submittal: include routine NEMA ST 20 transformer test results on each transformer and also provide the results of NEMA "design" and "prototype" tests that were made on transformers electrically and mechanically equal to those specified.
PART 3 EXECUTION
3.1 INSTALLATION
Electrical installations, including weatherproof and hazardous locations and ducts, plenums and other air‐handling spaces: conform to requirements of NFPA 70 and IEEE C2 and to requirements specified herein.
3.1.1 Underground Service
Underground service conductors and associated conduit: continuous from service entrance equipment to outdoor power system connection.
3.1.2 Service Entrance Identification
Service entrance disconnect devices, switches, and enclosures: labeled and identified as such.
3.1.2.1 Labels
Wherever work results in service entrance disconnect devices in more than one enclosure, as permitted by NFPA 70, label each enclosure, new and existing, as one of several enclosures containing service entrance disconnect devices. Label, at minimum: indicate number of service disconnect devices housed by enclosure and indicate total number of enclosures that contain service disconnect devices. Provide laminated plastic labels conforming to paragraph FIELD FABRICATED NAMEPLATES. Use lettering of at least 0.25 inch in height, and engrave on black‐on‐white matte finish. Service entrance disconnect devices in more than one enclosure: provided only as permitted by NFPA 70.
3.1.3 Wiring Methods
Provide insulated conductors installed in rigid steel conduit, IMC, rigid nonmetallic conduit, or EMT, except where specifically indicated or specified otherwise or required by NFPA 70 to be installed otherwise. Grounding conductor: separate from electrical system neutral conductor. Provide insulated green equipment grounding conductor for circuit(s) installed in conduit and raceways. Minimum conduit size: 1/2 inch in diameter for low voltage lighting and power circuits. Vertical distribution in multiple story buildings: made with metal conduit in fire‐rated shafts, with metal conduit extending through shafts for minimum distance of 6 inches.
3.1.3.1 Pull Wire
Install pull wires in empty conduits. Pull wire: plastic having minimum 200‐pound force tensile strength. Leave minimum 36 inches of slack at each end of pull wire.
3.1.4 Conduit Installation
Unless indicated otherwise, conceal conduit under floor slabs and within finished walls, ceilings, and floors. Keep conduit minimum 6 inches away from parallel runs of flues and steam or hot water pipes.
Install conduit parallel with or at right angles to ceilings, walls, and structural members where located above accessible ceilings and where conduit will be visible after completion of project.
3.1.4.1 Restrictions Applicable to EMT
a. Do not install underground.
b. Do not encase in concrete, mortar, grout, or other cementitious materials.
c. Do not use in areas subject to severe physical damage including but not limited to equipment rooms where moving or replacing equipment could physically damage the
EMT.
d. Do not use in hazardous areas.
e. Do not use outdoors.
f. Do not use in fire pump rooms.
g. Do not use when the enclosed conductors must be shielded from the effects of High‐ altitude Electromagnetic Pulse (HEMP).
3.1.4.2 Restrictions Applicable to Nonmetallic Conduit
a. PVC Schedule 40 and PVC Schedule 80
(1) Do not use in areas where subject to severe physical damage, including but not limited to, mechanical equipment rooms, electrical equipment rooms, hospitals, power plants, missile magazines, and other such areas.
(2) Do not use in hazardous (classified) areas.
(3) Do not use in fire pump rooms.
(4) Do not use in penetrating fire‐rated walls or partitions, or fire‐rated floors.
(5) Do not use above grade, except where allowed in this section for rising through floor slab or indicated otherwise.
(6) Do not use when the enclosed conductors must be shielded from the effects of High‐altitude Electromagnetic Pulse (HEMP).
3.1.4.3 Restrictions Applicable to Flexible Conduit
Use only as specified in paragraph FLEXIBLE CONNECTIONS. Do not use when the enclosed conductors must be shielded from the effects of High‐altitude Electromagnetic Pulse (HEMP).
3.1.4.4 Underground Conduit
Plastic‐coated rigid steel; plastic‐coated steel IMC; PVC, Type EPC‐40 Plastic coating: extend minimum 6 inches above floor.
3.1.4.5 Conduit for Circuits Rated Greater Than 600 Volts
Rigid metal conduit or IMC only.
3.1.4.6 Conduit Installed Under Floor Slabs
Conduit run under floor slab: located a minimum of 12 inches below the vapor barrier. Seal around conduits at penetrations thru vapor barrier.
3.1.4.7 Conduit Through Floor Slabs
Where conduits rise through floor slabs, do not allow curved portion of bends to be visible above finished slab.
3.1.4.8 Conduit Installed in Concrete Floor Slabs
PVC, Type EPC‐40, unless indicated otherwise. Locate so as not to adversely affect structural strength of slabs. Install conduit within middle one‐third of concrete slab. Do not stack conduits.
Space conduits horizontally not closer than three diameters, except at cabinet locations. Curved portions of bends must not be visible above finish slab. Increase slab thickness as necessary to provide minimum one inch cover over conduit. Where embedded conduits cross building and/or expansion joints, provide suitable watertight expansion/deflection fittings and bonding jumpers.
Expansion/deflection fittings must allow horizontal and vertical movement of raceway. Conduit larger than one inch trade size: installed parallel with or at right angles to main reinforcement;
when at right angles to reinforcement, install conduit close to one of supports of slab. Where nonmetallic conduit is used, convert raceway to plastic coated rigid steel or plastic coated steel IMC before rising above floor, unless specifically indicated.
3.1.4.9 Stub‐Ups
Provide conduits stubbed up through concrete floor for connection to free‐standing equipment with adjustable top or coupling threaded inside for plugs, set flush with finished floor. Extend conductors to equipment in rigid steel conduit, except that flexible metal conduit may be used 6 inches above floor. Where no equipment connections are made, install screwdriver‐operated threaded flush plugs in conduit end.
3.1.4.10 Conduit Support
Support conduit by pipe straps, wall brackets, threaded rod conduit hangers, or ceiling trapeze.
Fasten by wood screws to wood; by toggle bolts on hollow masonry units; by concrete inserts or expansion bolts on concrete or brick; and by machine screws, welded threaded studs, or spring‐ tension clamps on steel work. Threaded C‐clamps may be used on rigid steel conduit only. Do not weld conduits or pipe straps to steel structures. Do not exceed one‐fourth proof test load for load applied to fasteners. Provide vibration resistant and shock‐resistant fasteners attached to concrete ceiling. Do not cut main reinforcing bars for any holes cut to depth of more than 1 1/2 inches in reinforced concrete beams or to depth of more than 3/4 inch in concrete joints. Fill unused holes. In partitions of light steel construction, use sheet metal screws. In suspended‐ ceiling construction, run conduit above ceiling. Do not support conduit by ceiling support system. Conduit and box systems: supported independently of both (a) tie wires supporting ceiling grid system, and (b) ceiling grid system into which ceiling panels are placed. Do not share supporting means between electrical raceways and mechanical piping or ducts. Coordinate installation with above‐ceiling mechanical systems to assure maximum accessibility to all systems. Spring‐steel fasteners may be used for lighting branch circuit conduit supports in suspended ceilings in dry locations. Where conduit crosses building expansion joints, provide suitable watertight expansion fitting that maintains conduit electrical continuity by bonding jumpers or other means. For conduits greater than 2 1/2 inches inside diameter, provide supports to resist forces of 0.5 times the equipment weight in any direction and 1.5 times the equipment weight in the downward direction.
3.1.4.11 Directional Changes in Conduit Runs
Make changes in direction of runs with symmetrical bends or cast‐metal fittings. Make field‐ made bends and offsets with hickey or conduit‐bending machine. Do not install crushed or deformed conduits. Avoid trapped conduits. Prevent plaster, dirt, or trash from lodging in conduits, boxes, fittings, and equipment during construction. Free clogged conduits of obstructions.
3.1.4.12 Locknuts and Bushings
Fasten conduits to sheet metal boxes and cabinets with two locknuts where required by NFPA 70, where insulated bushings are used, and where bushings cannot be brought into firm contact with the box; otherwise, use at least minimum single locknut and bushing. Provide locknuts with sharp edges for digging into wall of metal enclosures. Install bushings on ends of conduits, and provide insulating type where required by NFPA 70.
3.1.4.13 Flexible Connections
Provide liquidtightflexible steel conduit between 3 and 6 feet in length for recessed and semirecessed lighting fixtures; for equipment subject to vibration, noise transmission, or movement; and for motors. Install flexible conduit to allow 20 percent slack. Minimum flexible steel conduit size: 1/2 inch diameter. Provide separate ground conductor across flexible connections.
3.1.5 Cable Tray Installation
Install cable trays parallel with or at right angles to ceilings, walls, and structural members. Support as indicated. Provide supports to resist forces of 0.5 times the equipment weight in any direction and 1.5 times the equipment weight in the downward direction.
3.1.6 Boxes, Outlets, and Supports
Provide boxes in wiring and raceway systems wherever required for pulling of wires, making connections, and mounting of devices or fixtures. Boxes for metallic raceways: cast‐metal, hub‐type when located in wet locations, when surface mounted on outside of exterior surfaces, when surface mounted on interior walls exposed up to 7 feet above floors and walkways, and when specifically indicated. Boxes in other locations: sheet steel, except that aluminum boxes may be used with aluminum conduit, and nonmetallic boxes may be used with nonmetallic conduit system. Provide each box with volume required by NFPA 70 for number of conductors enclosed in box. Boxes for mounting lighting fixtures: minimum 4 inches square, or octagonal, except that smaller boxes may be installed as required by fixture configurations, as approved. Boxes for use in masonry‐block or tile walls: square‐cornered, tile‐type, or standard boxes having square‐cornered, tile‐type covers. Provide gaskets for cast‐metal boxes installed in wet locations and boxes installed flush with outside of exterior surfaces. Provide separate boxes for flush or recessed fixtures when required by fixture terminal operating temperature; provide readily removable fixturesfor access to boxes unless ceiling access panels are provided. Support boxes and pendants for surface‐mounted fixtures on suspended ceilings independently of ceiling supports. Fasten boxes and supports with wood screws on wood, with bolts and expansion shields on concrete or brick, with toggle bolts on hollow masonry units, and with machine screws or welded studs on steel. Threaded studs driven in by powder charge and provided with lockwashers and nuts may be used in lieu of wood screws, expansion shields, or machine screws. In open overhead spaces, cast boxes threaded to raceways need not be separately supported except where used for fixture support; support sheet metal boxes directly from building structure or by bar hangers. Where bar hangers are used, attach bar to raceways on opposite sides of box, and support raceway with approved‐type fastener maximum 24 inches from box. When penetrating reinforced concrete members, avoid cutting reinforcing steel.
3.1.6.1 Boxes
Boxes for use with raceway systems: minimum 1 1/2 inches deep, except where shallower boxes required by structural conditions are approved. Boxes for other than lighting fixture outlets:
minimum 4 inches square, except that 4 by 2 inch boxes may be used where only one raceway enters outlet. Telecommunications outlets: a minimum of 4 11/16 inches square by 2 1/8 inches deep. Mount outlet boxes flush in finished walls.
3.1.6.2 Pull Boxes
Construct of at least minimum size required by NFPA 70 of code‐gauge aluminum or galvanized sheet steel, except where cast‐metal boxes are required in locations specified herein. Provide boxes with screw‐fastened covers. Where several feeders pass through common pull box, tag feeders to indicate clearly electrical characteristics, circuit number, and panel designation.
3.1.7 Mounting Heights
Mount panelboards, enclosed circuit breakers, motor controller and disconnecting switches so height of operating handle at its highest position is maximum 78 inches above floor. Mount lighting switches 48 inches above finished floor. Mount receptacles 18 inches above finished floor, unless otherwise indicated. Mount other devices as indicated. Measure mounting heights of wiring devices and outlets.
3.1.8 Conductor Identification
Provide conductor identification within each enclosure where tap, splice, or termination is made. For conductors No. 6 AWG and smaller diameter, provide color coding by factory‐applied, color‐ impregnated insulation. For conductors No. 4 AWG and larger diameter, provide color coding by plastic‐coated, self‐sticking markers; colored nylon cable ties and plates; or heat shrink‐type sleeves.
Identify control circuit terminations in accordance with manufacturer's recommendations.
3.1.8.1 Marking Strips
Provide marking strips in accordance with the following:
a. Provide white or other light‐colored plastic marking strips, fastened by screws to each terminal block, for wire designations.
b. Use permanent ink for the wire numbers
c. Provide reversible marking strips to permit marking both sides, or provide two marking strips with each block.
d. Size marking strips to accommodate the two sets of wire numbers.
e. Assign a device designation in accordance with NEMA ICS 1 to each device to which a connection is made. Mark each device terminal to which a connection is made with a distinct terminal marking corresponding to the wire designation used on the Contractor's schematic and connection diagrams.
f. The wire (terminal point) designations used on the Contractor's wiring diagrams and printed on terminal block marking strips may be according to the Contractor's standard practice;
however, provide additional wire and cable designations for identification of remote (external) circuits for the Government's wire designations.
g. Prints of the marking strips drawings submitted for approval will be so marked and returned to the Contractor for addition of the designations to the terminal strips and tracings, along with any rearrangement of points required.
3.1.9 Splices
Make splices in accessible locations. Make splices in conductors No. 10 AWG and smaller diameter with insulated, pressure‐type connector. Make splices in conductors No. 8 AWG and larger diameter with solderless connector, and cover with insulation material equivalent to conductor insulation.
3.1.10 Covers and Device Plates
Install with edges in continuous contact with finished wall surfaces without use of mats or similar devices. Plaster fillings are not permitted. Install plates with alignment tolerance of 1/16 inch. Use of sectional‐type device plates are not permitted. Provide gasket for plates installed in wet locations.
3.1.11 Grounding and Bonding
Provide in accordance with NFPA 70. Ground exposed, non‐current‐carrying metallic parts of electrical equipment, metallic raceway systems, grounding conductor in metallic and nonmetallic raceways, telecommunications system grounds, and neutral conductor of wiring systems. Make ground connection at main service equipment, and extend grounding conductor to point of entrance of metallic water service. Make connection to water pipe by suitable ground clamp or lug connection to plugged tee. If flanged pipes are encountered, make connection with lug bolted to street side of flanged connection.
Supplement metallic water service grounding system with additional made electrode in compliance with NFPA 70. Make ground connection to driven ground rods on exterior of building. Interconnect all grounding media in or on the structure to provide a common ground potential. This includes l electrical service, as well as underground metallic piping systems.
3.1.11.1 Ground Rods
Provide cone pointed ground rods. Measure the resistance to ground using the fall‐of‐ potential method described in IEEE 81. Do not exceed 25 ohms under normally dry conditions for the maximum resistance of a driven ground. If this resistance cannot be obtained with a single rod,one additional rods, spaced on center, not less than twice the distance of the length of the rod, or if sectional type rods are used,one additional sections may be coupled and driven with the first rod. If the resultant resistance exceeds 25 ohms measured not less than 48 hours after rainfall, notify the Contracting Officer who will decide on the number of ground rods to add.
3.1.11.2 Grounding Connections
Make grounding connections which are buried or otherwise normally inaccessible, excepting specifically those connections for which access for periodic testing is required, by exothermic weld or compression connector.
a. Make exothermic welds strictly in accordance with the weld manufacturer's written recommendations. Welds which are "puffed up" or which show convex surfaces indicating improper cleaning are not acceptable. Mechanical connectors are not required at exothermic welds.
b. Make compression connections using a hydraulic compression tool to provide the correct circumferential pressure. Provide tools and dies as recommended by the manufacturer. Use an embossing die code or other standard method to provide visible indication that a connector has been adequately compressed on the ground wire.
3.1.11.3 Ground Bus
Provide a copper ground bus in the electrical equipment rooms as indicated. Noncurrent‐ carrying metal parts of transformer neutrals and other electrical equipment: effectively grounded by bonding to the ground bus. Bond the ground bus to both the entrance ground, and to a ground rod or rods as specified above having the upper ends terminating approximately 4 inches above the floor.
Make connections and splices of the brazed, welded, bolted, or pressure‐connector type, except use pressure connectors or bolted connections for connections to removable equipment.
3.1.11.4 Resistance
Maximum resistance‐to‐ground of grounding system: do not exceed 5 ohms under dry conditions. Where resistance obtained exceeds 5 ohms, contact Contracting Officer for further instructions.
3.1.12 Equipment Connections
Provide power wiring for the connection of motors and control equipment under this section of the specification. Except as otherwise specifically noted or specified, automatic control wiring, control devices, and protective devices within the control circuitry are not included in this section of the specifications and are provided under the section specifying the associated equipment.
3.1.13 Government‐Furnished Equipment
Contractor make connections to Government‐furnished equipment to make equipment operate as intended, including providing miscellaneous items such as plugs, receptacles, wire, cable, conduit, flexible conduit, and outlet boxes or fittings.
3.1.14 Repair of Existing Work
Perform repair of existing work, demolition, and modification of existing electrical distribution systems as follows:
3.1.14.1 Workmanship
Lay out work in advance. Exercise care where cutting, channeling, chasing, or drilling of floors, walls, partitions, ceilings, or other surfaces is necessary for proper installation, support, or anchorage of conduit, raceways, or other electrical work. Repair damage to buildings, piping, and equipment using skilled craftsmen of trades involved.
3.1.14.2 Existing Concealed Wiring to be Removed
Disconnect existing concealed wiring to be removed from its source. Remove conductors; cut conduit flush with floor, underside of floor, and through walls; and seal openings.
3.1.14.3 Removal of Existing Electrical Distribution System
Removal of existing electrical distribution system equipment includes equipment's associated wiring, including conductors, cables, exposed conduit, surface metal raceways, boxes, and fittings, as indicated.
3.1.14.4 Continuation of Service
Maintain continuity of existing circuits of equipment to remain. Maintain existing circuits of equipment energized. Restore circuits wiring and power which are to remain but were disturbed during demolition back to original condition.
3.1.15 Surge Protective Devices
Connect the surge protective devices in parallel to the power source, keeping the conductors as short and straight as practically possible. Maximum allowed lead length is 3 feet.
3.2 FIELD FABRICATED NAMEPLATE MOUNTING
Provide number, location, and letter designation of nameplates as indicated. Fasten nameplates to the device with a minimum of two sheet‐metal screws or two rivets.
3.3 WARNING SIGN MOUNTING
Provide the number of signs required to be readable from each accessible side. Space the signs in accordance with NFPA 70E.
3.4 FIELD APPLIED PAINTING
Paint electrical equipment as required to match finish of adjacent surfaces or to meet the indicated or specified safety criteria. Painting: as specified in Section 09 90 00 PAINTS AND COATINGS.
3.5 FIELD QUALITY CONTROL
Furnish test equipment and personnel and submit written copies of test results. Give Contracting Officer 5 working days notice prior to each tests.
3.5.1 Devices Subject to Manual Operation
Operate each device subject to manual operation at least five times, demonstrating satisfactory operation each time.
3.5.2 600‐Volt Wiring Test
Test wiring rated 600 volt and less to verify that no short circuits or accidental grounds exist. Perform insulation resistance tests on wiring No. 6 AWG and larger diameter using instrument which applies voltage of approximately 500 volts to provide direct reading of resistance. Minimum resistance:
1,000,000 ohms.
3.5.3 Transformer Tests
Perform the standard, not optional, tests in accordance with the Inspection and Test Procedures for transformers, dry type, air‐cooled, 600 volt and below; as specified in NETA ATS. Measure primary and secondary voltages for proper tap settings. Tests need not be performed by a recognized independent testing firm or independent electrical consulting firm.
3.5.4 Ground‐Fault Receptacle Test
Test ground‐fault receptacles with a "load" (such as a plug in light) to verify that the "line" and "load" leads are not reversed.
3.5.5 Grounding System Test
Test grounding system to ensure continuity, and that resistance to ground is not excessive. Test each ground rod for resistance to ground before making connections to rod; tie grounding system together and test for resistance to ground. Make resistance measurements in dry weather, not earlier than 48 hours after rainfall. Submit written results of each test to Contracting Officer, and indicate location of rods as well as resistance and soil conditions at time measurements were made.
‐‐ End of Section ‐‐
SECTION 26 24 13
SWITCHBOARDS
05/15
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI C12.1 (2008) Electric Meters Code for Electricity Metering
ASTM INTERNATIONAL (ASTM)
ASTM A780/A780M (2009; R 2015) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM D149 (2009; R 2013) Dielectric Breakdown Voltage and Dielectric Strength of Solid Electrical Insulating Materials at Commercial Power Frequencies
ASTM D1535 (2014) Specifying Color by the Munsell System
ASTM D709 (2016) Standard Specification for Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2017) National Electrical Safety Code
IEEE C37.13 (2015) Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures
IEEE C37.90.1 (2013) Standard for Surge Withstand Capability (SWC) Tests for Relays and Relay Systems Associated with Electric Power Apparatus
IEEE C57.12.29 (2014) Standard for Pad-Mounted Equipment - Enclosure Integrity for Coastal Environments
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI/NEMA PB 2.1 (2013) General Instructions for Proper Handling, Installation, Operation and Maintenance of Deadfront Distribution Switchboards Rated 600 V or Less
NEMA ICS 6 (1993; R 2011) Enclosures
NEMA PB 2 (2011) Deadfront Distribution Switchboards
NEMA ST 20 (1992; R 1997) Standard for Dry-Type Transformers for General Applications
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017) National Electrical Code
UNDERWRITERS LABORATORIES (UL)
UL 467 (2013) Grounding and Bonding Equipment
UL 489 (2016) Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures
UL 891 (2005; Reprint Oct 2012) Switchboards
1.2 RELATED REQUIREMENTS
Section 26 08 00 APPARATUS INSPECTION AND TESTING applies to this section, with the additions and modifications specified herein.
1.3 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in IEEE 100.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor QC approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Switchboard…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .