Attachment VI - 2025-10-17 MICU Bid Drawings3 10-17-2025.pdf
PDF 13 MB Posted
- Attached to
- Z2DA--Renovate MICU/SICU 539-20-104
- Solicitation number
- 36C25026B0001_1
About this file
These documents are 100% Construction Documents for a VA Medical Center Renovation project located in Cincinnati, Ohio, focusing specifically on technology and electrical systems for a Medical Intensive Care Unit (MICU) renovation. The project number is 2019-05193, with design documents prepared by Heapy Engineering and JPA Architecture, dated 10/17/2025.
The technical drawings include detailed plans for electrical systems, technology infrastructure, security systems, and communication networks. Key components include new patient room technology installations, redesigned communication closets, electrical panel configurations, pathway routing, and security door control details. The drawings specify precise technical requirements for various systems such as nurse call systems, paging systems, CCTV cameras, electronic door controls, and technology outlets with specific mounting heights and connection specifications. The renovation appears comprehensive, addressing multiple technical and infrastructural elements to modernize the MICU space while maintaining VA construction standards.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
J
EP4A
Mech Room
A456E
E4A
MCCG
MCCF
MCCE
MCCD
R4A
15 KVA
EP4B 4P1
CU-2
EP4A
EF-3 (REDUN.) VFD
EF-3 VFD
EF-3 (REDUN.)
EF-3
WP
EP4A - 19,21,23
4P1 - 1,3,5
E4A
MCCG
MCCF
MCCE
MCCD
R4A
15 KVA
EP4B 4P1
TYP.
TYP.
TYP.
TYP.
HEPA-3
ESWB-408
C2F1 - 39
APPROXIMATE LOCATION OF C2F1 ON LEVEL 2 BELOW
P: 937-224-0861 www.heapy.com
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO. STATE COA FIRM NO.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290
/1 /2
:0
:4
P
M
Renovate MICU/SICU
10/17/2025
PARTIAL ROOF PLAN - POWER
EP104
DJWMSG
19018.00
539-20-104
Cincinnati, Ohio
100% CONSTRUCTION
DOCUMENTS
2019-05193 01528
N Scale:Scale: 1/8" = 1'-0"1/8" = 1'-0"
PARTIAL ROOF PLAN - ELECTRICAL
PLAN NOTES
1. REFER TO PANEL SCHEDULE ON THIS SHEET AND MOTOR SCHEDULE ON SHEET E601
FOR MORE INFORMATION.
2. EXTEND EXISTING LIGHTNING PROTECTION SYSTEM TO NEW EQUIPMENT AS
REQUIRED PER NFPA 780, UL96A AND SPECIFICATION 264100. ENSURE UL MASTER
LABEL IS MAINTAINED.
3. EXISTING UNISTRUT TO REMAIN. MODIFY RACK AS REQUIRED TO ACCOMMODATE
MOUNTING OF NEW MOTOR CONTROLLERS. LOCATE NEW VFD'S WITHIN MECHANICAL
PENTHOUSE AS REQUIRED TO ACCOMMODATE PHASING. MAINTAIN CLEARANCES OF
EQUIPMENT PER NEC 110.26. COORDINATE WITH DIVISION 23.
4. REFER TO SHEET EP102 AND MOTOR SCHEDULE ON SHEET E601 FOR MORE
INFORMATION.
5. PROVIDE 120V CONNECTION TO BIPOLAR IONIZATION AIR PURIFICATION SYSTEM.
COORDINATE WITH DIVISION 23.
6. LIGHTNING PROTECTION STRIKE TERMINATION DEVICE.
7. LIGHTNING PROTECTION ROOF CONDUCTOR.
8. REFER TO SHEET EP102 FOR LOCATION OF PANELBOARD.
9. RELOCATED EXHAUST FAN. EXTEND/REWORK CIRCUIT, ASSOCIATED DISCONNECT
AND ELECTRICAL EQUIPMENT TO NEW LOCATION. EXTEND/REWORK LIGHTNING
PROTECTION BOND TO NEW LOCATION. ENSURE UL MASTER LABEL IS MAINTAINED.
10. PROVIDE SHIELDED VFD CABLES FROM VFD TO MOTOR. VFD CABLE SHALL BE 3
CONDUCTOR XHHW LOW CAPACITANCE COPPER, FULL SIZE INSULATED COPPER
GROUND, 1.5 MIL AL FOIL AND 85% TINNED COPPER WOVEN BRAID SHIELD WITH PVC
OIL AND SUNLIGHT RESISTANT JACKET. UL TC-ER, 90 DEGREES C.
GENERAL NOTES
A. REFER TO MECHANICAL DRAWINGS (DIVISION 23) FOR PHASING AND MORE
INFORMATION. COORDINATE WITH DIVISION 23 FOR ALL MECHANICAL EQUIPMENT
CONNECTIONS.
B. REFER TO PARTIAL SINGLE-LINE DIAGRAM FOR MORE INFORMATION.
C. REFER TO THE ARCHITECTURAL DOCUMENTS FOR A SEQUENCE OF
CONSTRUCTION PLAN, WHICH INCLUDES DETAILED NOTES REGARDING PROJECT
PHASING. ALL WORK SHALL BE COORDINATED AND SCHEDULED WITH THIS
CONSTRUCTION SEQUENCE. ALL REQUIRED SHUTDOWNS SHALL BE IDENTIFIED AT
THE START OF CONSTRUCTION AND SHALL BE COORDINATED AND SCHEDULED
WITH THE VA.
D. ALL METALLIC ROOF-MOUNTED EQUIPMENT SHALL BE BONDED AND CONNECTED
TO EXISTING LIGHTNING PROTECTION SYSTEM FOR A COMPLETE AND FUNCTIONAL
SYSTEM AS REQUIRED PER NFPA 780, UL96A AND SPECIFICATION SECTION 264100.
REFER TO MECHANICAL DRAWINGS FOR MORE INFORMATION.
N Scale:Scale: 1" = 20'-0"1" = 20'-0"
PARTIAL THIRD FLOOR PLAN - NEW WORK - POWER
177.35 kVA
TOTAL CONNECTED ESTIMATED DEMAND
Notes: REFER TO MOTOR SCHEDULE AND PARTIAL SINGLE LINE DIAGRAM FOR MORE INFORMATION.
Total Load: 59.12 kVA 59.12 kVA 59.12 kVA
41 -- -- -- 633 VA 633 VA -- -- -- 42
39 -- -- -- 633 VA 633 VA -- -- -- 40
37 EF-12 20 A 3 633 VA 633 VA 3 20 A EF-13 38
35 -- -- -- 5066... 5066... -- -- -- 36
33 -- -- -- 5066... 5066... -- -- -- 34
31 P1 VFD 40 A 3 5066... 5066... 3 40 A P2 VFD 32
29 -- -- -- 8133... 8133... -- -- -- 30
27 -- -- -- 8133... 8133... -- -- -- 28
25 OR VAC PUMP 60 A 3 8133... 8133... 3 60 A CU 26
23 -- -- -- 9422... 0 VA 1 20 A Spare 24
21 -- -- -- 9422... 0 VA 1 20 A Spare 22
19 EF-3 60 A 3 9422... 0 VA 1 20 A Spare 20
17 -- -- -- 7482... 7482... -- -- -- 18
15 -- -- -- 7482... 7482... -- -- -- 16
13 EF-1 50 A 3 7482... 7482... 3 50 A EF-2 14
11 Spare 20 A 1 0 VA 3533... -- -- -- 12
9 Spare 20 A 1 0 VA 3533... -- -- -- 10
7 Spare 20 A 1 0 VA 3533... 3 30 A 1-DPF2 8
5 Spare 20 A 1 0 VA 3533... -- -- -- 6
3 Spare 20 A 1 0 VA 3533... -- -- -- 4
1 Spare 20 A 1 0 VA 3533... 3 30 A 1-DPF2 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 225 A
Supply From: Enclosure: Type 1 Mains Type: 225A MB
Location: Mech Room A456E Mounting: Surface A.I.C. Rating:
Panel: EP4A
MCC-E
SEE NOTE 6 ON E401
(EXISTING)
Revisions Date
EN
EN
EN
EN
G G
EN EN EN
E N
EN
ENEN
EN EN EN
EN EN
EXIST. DISTRIBUTION PANEL "ESB"
EXIST. DIST. SWBD "IE3"
EXIST. DISTR. PANEL "CDP"EXIST. DIST. PANEL "LSDP"
EX. DIST. SWBD "IE7"
GENERATOR PARALLELING SWITCHGEAR
EXIST. DIST. SWBD "GDE"
EXIST. DIST. SWBD "ESWB"
EXIST. DIST. SWBD
"ESWB-40"
EX. DIST. SWBD "ESWB-20" EX. DIST. SWBD "ESWB-10"
2000A, 208Y/120V-3PH-4W
NORMAL POWER BRANCH
800A
ATS
"1E7" 800A
EQUIPMENT
BRANCH
300A
200A
200A 200A 400A
PCSB-E
PNL
E4A
PNL
MCP-E
PNL
P1
PNL
P2
4TH FLR
UPS
600A
ATS
"1E6" 600A
EQUIPMENT
BRANCH
ATS
"1E4" 400A
EQUIPMENT
BRANCH
PPNL
EL2
ELEVATORS
1 # 2
ATS
"1E3" 600A
CRITICAL
BRANCH
600A
600A, 208Y/120V-3PH-4W, 65 KAIC
C3E
C4E
C2E
C1E
C3B
C4B
C2B
C1B
200A 200A 200A 200A
C6B2 C6B1
C7B
150A 200A
CBB
C5B
MEDICAL
AIR
CBE EG
C3K1
C6B
C8B
C9B
C1E
ED
TRAILER
C3K2
ATS
"1E8" 200A
400A
ATS
"1E15" 200A
200A
BLDG.
800A
FIRE PUMP
JOCKEY
PUMP
2000A
600A, 208Y/120V-3PH-4W (RM. A23)
CRITICAL POWER BRANCH
/3
/3
CBC
S P
A R
E
S P
A R
E
/3
S P
A R
E
/3
/3
/3
/3
C4C
C1C
C2C
C3C
C8C
C7C
C6C
C5C
C9C
CBD
/3
C4D
C1D
C2D
C3D
C8D
C7D
C6D
C5D
C9D
PBX
E4A1
/3
400A, 208Y/120V-3PH-4W (RM. A23)
LIFE SAFETY BRANCH
LSAB
/3
LSA4
LSA1
LSA2
LSA3
LSA8
LSA7
LSA6
LSA5
LSA10
/3
LSA2A
LSA9
800A, 208Y/120V-3PH-4W, 65 KAIC
5000A, 208Y/120V-3PH-4W
/3
/3
CONNECTION
TO LOAD
BANK / TRAILER
GENSET
SPARE
TGEN #1
750 KVA
480/208Y/120V, 3P,4W
/3
/3
/3
/3
/3
1500KW
GENSET
480Y/277V
3PH, 4W
RM. B13
ATS-14
"1E1"
400A LIFE
SAFETY
BRANCH
RM. A23
600A 200A
300KVA
480V/ 208Y/120V
3PH, 4W
ATS-16
"1E2" 600A
CRITICAL
BRANCH
ATS-17
"1E9" 225A
EQUIPMENT
BRANCH
RM. A23
"EM"
UPS
SYSTEM
250A
1500KW
GENSET
480Y/277V
3PH, 4W
RM. B13
NONCNCNONCNCNO
BASEMENT
1000A, 208Y/120V-3PH-4W, RM A23
1600A, 480Y/277V-3PH-4W
ATS-12
"ESWB-50"
250A
ATS-11
600A
EQUIP.
BRANCH
600A
600A, 480Y/277V-3PH-4W, 35 KAIC
200A 400A 200A 150A125A 200A
X1A
X2A
X3A
OR
C1F
ER ELEV
C1F1
ATS-10
400A
CRITICAL
BRANCH
400A
400A, 480Y/277V-3PH-4W, 35 KAIC
200A 200A 250A 100A 60A
200A
C1A
CR2A CR2A1C2B
C3B
C2B
C3B
C2A
C3A
SPARE
ATS-9
200A
LIFE SAFETY
BRANCH
200A
200A, 480Y/277V-3PH-4W, 35 KAIC
50A 100A 100A20A 100A
LS2A
LS3A
LS2B
LS3B
S3B
SICU
XFMR
LS2C
LS3C
T7
300A
ATS-SURG SUITE
200A
LIFE SAFETY
BRANCH
200A250A
ATS-13
SURGERY
SUITE
SEVENTH FLOOR
EIGTH FLOOR
NINTH FLOOR
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FIFTH FLOOR
SIXTH FLOOR
FOURTH FLOOR
TENTH FLOOR
400A
ELEVENTH FLOOR
PPNL
EL3
ELEVATORS
5 & 6
400A
PPNL
EL1
ELEVATORS
3 & 4
ATS
"1E5" 400A
EQUIPMENT
BRANCH
400A
SUB BASEMENT
45 KVA
CR2C1
C5C2
15 KVA
E4A
EP4B
T8
9KVA
CR3A
CR2B
T2 T1
MECH
RM
LTS
40A
CR3F C3E
TA
75KVA
CR3G
50A
BC
30KVA
BCEC1
ELEV.
ELEV
"E-16"
ELEV.
ELEV
"E-15"
LSA10A
75 KVA
C2F C2F1
150A
150A
AHU-40
EXIST. DISTRIBUTION PANEL "DPD"
EXIST. DISTRIBUTION PANEL "DS-1B"
/3
/3
/3
/3
/3
800A, 208Y/120V-3PH-4W
NORMAL POWER BRANCH
1000A, 208Y/120V-3PH-4W
NORMAL POWER BRANCH
/3
/3
/3
/3
800A
1D3 1D2 1D1
5D2 5D1
2D12D2
3D13D2
4D2 4D1
BD1BD2
6D2 6D1
8D2 8D1
1 2 3 4 5 6 7 8 9
7D27D1
9D1
2DX
S P
A R
E
L5D
3DP
2DP
3A1
1C4P1C3P1C2P1C2PA1C2PB1C1P1C1PA
BC1P
1B1P1A1P
/3
/3
/3
/3
/3
/3
/3
/3
/3
/3
/3
/3
/3
BC2P
/3
BC3P
3C5P 3C6P R3D R3E
/3
DPF
2F12F2 1F21F1
225A 150A
150A
MCCE
MCCD
TO DS-1P (NORMAL POWER)
ATS-1
EQUIPMENT
BRANCH
EP4A
CU-2
MCCF
200A
4P1
FED FROM US-1X
100A
P-17
200A
CU-1
SCOPE OF WORK
VFD
EF-3 (REDUN.)
VFD
EF-3
LOAD SUMMARY
ESWB-20
(ESWB-20 CALCULATION BASED ON METERED DATA
RECEIVED ON NOVEMBER 2ND, 2020)
EXISTING LOAD: 105A X 1.25 = 131A
ESTIMATED ADDED LOAD: 59 kVAD (71A)
ESTIMATED FINAL LOAD: 202A
EQUIPMENT RATING: 400A
CDP
(CDP CALCULATION BASED ON METERED DATA
RECEIVED ON NOVEMBER 2ND, 2020)
EXISTING LOAD: 90A X 1.25 = 112.5A
ESTIMATED ADDED LOAD: 59 kVAD (71A)
ESTIMATED FINAL LOAD: 184A
EQUIPMENT RATING: 600A
ESWB-40
(ESWB-40 CALCULATION BASED ON METERED DATA
RECEIVED ON MAY 12TH, 2022)
EXISTING LOAD: 100A X 1.25 = 125A
ESTIMATED ADDED LOAD: 250 kVAD (300A)
ESTIMATED FINAL LOAD: 425A
EQUIPMENT RATING: 600A
P: 937-224-0861 www.heapy.com
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO. STATE COA FIRM NO.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290
/1 /2
:0
:2
P
M
Renovate MICU/SICU
10/17/2025
PARTIAL SINGLE LINE DIAGRAM
E401
DJWMSG
19018.00
539-20-104
Cincinnati, Ohio
100% CONSTRUCTION
DOCUMENTS
2019-05193 01528
N.T.S.Scale:
PARTIAL-SINGLE-LINE DIAGRAM
SINGLE LINE NOTES:
1. PROVIDE NEW SPLICE BOX. BACK-FEED EXISTING FEEDER CURRENTLY SERVING
EXISTING 75 KVA TRANSFORMER (C1F). COORDINATE DOWNTIME AND OUTAGE OF
AFFECTED LOADS WITH COR. CUTOVER SHALL BE COMPLETED IN LESS THAN 4 HOUR
TOTAL OUTAGE.
2. 4-#/1/0, 1-#6 GRD., IN 1.5" CONDUIT.
3. PROVIDE NEW 150A/3P BREAKER IN EXISTING DISTRIBUTION PANEL. NEW BREAKER
SHALL MATCH TYPE AND CHARACTERISTICS OF EXISTING BREAKERS.
4. UTILIZE EXISTING 200A/3P BREAKER IN EXISTING PANEL.
5. REFER TO MOTOR SCHEDULE FOR FEEDER SIZING.
6. THE FEEDER SERVING PANELBOARD EP4A AND THE FEEDER SERVING MCCE SHALL
EACH BE METERED FOR A MINIMUM OF (30) DAYS AT BEGINNING OF PROJECT. BOTH
REPORTS SHALL BE SUBMITTED TO ENGINEER OF RECORD, TO ENSURE CAPACITY IS
AVAILABLE TO ACCOMMODATE NEW LOADS.
7. PROVIDE NEW 60A/3P BREAKER FOR POWER TO EF-3. NEW BREAKER SHALL MATCH
TYPE AND CHARACTERISTICS OF EXISTING BREAKERS.
8. REFER TO NOTE 10 ON SHEET EP104 FOR ADDITIONAL REQUIREMENTS.
GENERAL NOTES:
A. LIGHT LINE WEIGHT REPRESENTS EXISTING WORK THAT SHALL REMAIN.
B. HEAVY, DASHED LINE WEIGHT REPRESENTS EXISTING WORK TO BE REMOVED.
C. HEAVY, CONTINUOUS LINE WEIGHT REPRESENTS NEW WORK.
E9
E9
E9
E9
E9
E9
E9
E9
3'-0" MAX
LENGTH AS REQUIRED
3/8" MAX
FLOOR SLAB PENETRATION DETAIL
NTS
NTS NTS
NTS NTS NTS
NTS
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
NTS
STEEL EXPANSION
ANCHOR, TYP
FLOOR SLAB,
TYP.
INTEGRAL GALVANIZED
LIPPED STEAL MOUNTING
CHANNEL, TYP.
SPRING
NUT, TYP
CONDUIT COMPRESSION
FITTING, TYP.
JUNCTION BOX
(SIZE AS REQUIRED)
[10mm]
FIRESTOP SEALANT
PER SECTION 07 84 00,
FIRESTOPPING
MINERAL WOOL
(FIRMLY PACKED)
CONDUIT, TYP
EXIT SIGN MOUNTING - LAY-IN CEILING
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
ARCHITECTURAL
CEILING GRID
ACOUSTICAL
CEILING
TILE (TYP)
#12 GA. HANGER WIRE THROUGH INTEGRAL
GALVANIZED LIPPED STEEL MOUNTING
CHANNEL & ATTACHED TO STRUCTURE
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
JUNCTION BOX
LOCKING SQUARE
WASHER & NUT
1/4" SCREW
ARCHITECTURAL
CEILING GRID
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
DOWNLIGHT MOUNTING - LAY-IN CEILING
CEILING HANGER
WIRE, TYP.
RECESSED CAN
LUMINAIRE
ARCHITECTURAL
CEILING GRID
WIRE TIE OR SCREW
BAR HANGER TO
ARCHITECTURAL
CEILING GRID TYP.
LUMINAIRE
BAR HANGERS
12GA. HANGER WIRE AT DIAGONAL
CORNER ATTACHED TO STRUCTURE
ACOUSTICAL
CEILING TILE (TYP)
RECESSED CAN
LUMINAIRE
ARCHITECUTRAL
CEILING GRID
DOWNLIGHT MOUNTING - GYPBOARD CEILING
CEILING HANGER
WIRE, TYP.
RECESSED CAN
LUMINAIRE
CEILING MAIN
BEAM
GYPSUM
BOARD (TYP)
WIRE TIE OR SCREW
BAR HANGER TO
CROSS BEAM TYP.
LUMINAIRE
BAR HANGERS
12GA. HANGER WIRE AT DIAGONAL
CORNER ATTACHED TO STRUCTURE
CEILING
CROSS BEAM
RECESSED CAN
LUMINAIRE
CEILING BEAM
LUMINAIRE MOUNTING - LAY-IN CEILING
LUMINAIRE
SUSPENSION WIRES
(#10 MIN) ATTACHED
TO STRUCTURE
(TYP EA. CORNER)
3 TWIST MINIMUM
(TYP)
FIXTURE WHIP FROM
JUNCTION BOX
(6FT. LONG MAX.)
LUMINAIRE.
REFER TO
SCHEDULE
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
ACOUSTICAL CEILING
TILE (TYP)
ARCHITECTURAL
CEILING GRID
LUMINAIRE.
REFER TO
SCHEDULE
LUMINAIRE MOUNTING - GYPBOARD CEILING
LUMINAIRE
SUSPENSION WIRES
(#10 MIN) ATTACHED
TO STRUCTURE
(TYP EA. CORNER)
3 TWIST MINIMUM
(TYP)
FIXTURE WHIP FROM
JUNCTION BOX
(6FT. LONG MAX.)
CEILING MAIN BEAM
GYPSUM BOARD (TYP)
LUMINAIRE.
REFER TO
SCHEDULE
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
CEILING CROSS BEAM
GYPSUM BOARD
CEILING CROSS BEAM
LUMINAIRE.
REFER TO
SCHEDULE
DRYWALL BORDER
CONDUIT TRAPEZE MOUNTING DETAIL
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
NOTES
1. METAL CHANNEL STRUT SUPPORT LONGER THAN THAN
36" SHALL BE INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 0533, RACEWAYS AND
BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT
CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO
SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
LOCKING SQUARE
WASHER & LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
CONDUIT JOINT CROSSING DETAIL
SEISMIC OR EXPANSION
JOINT. FIELD VERIFY
ACTUAL CONDITIONS &
LOCATIONS.FLOOR OR ROOF
STRUCTURE. FIELD VERIFY
ACTUAL CONDITIONS, TYP.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
CONDUIT
TRAPEZE PER
SD260533-02,
TYP.
[914mm]
BEAM
CLAMP,
TYP.
CONDUIT,
TYP.
15" FLEXIBLE GALVANIZED STEEL
CONDUIT WITH CONDUCTORS &
GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
STEEL EXPANSION
ANCHOR
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT COMPRESSION
FITTING
SPRING NUT
120V N
HCONTROL
UNIT
LUMINAIRE(S)
OCCUPANCY
SENSOR
SWITCH &
DIMMER WALL
CONTROL
GENERAL NOTES
A OCCUPANCY SENSOR SHALL TURN OFF LIGHTS AFTER 15 MINUTES UPON VACANCY OF THE ROOM.
B CONTRACTOR SHALL COORDINATE WITH MANUFACTURER FOR EXACT QUANTITY OF OCCUPANCY SENSORS (FOR COMPLETE ROOM COVERAGE) AND PROVIDE ANY ADDITIONAL COMPONENTS FOR A COMPLETE AND OPERABLE SYSTEM. COORDINATE COMPONENT MOUNTING LOCATIONS FOR PROPER CLEARANCE OF ACCESSIBILITY PRIOR TO ROUGH-IN. COORDINATE PROGRAMMING OF ZONES AND WALL STATION CONFIGURATIONS, AS SHOWN ON
DRAWINGS, WITH MANUFACTURER.
C DETAIL IS SCHEMATIC IN NATURE. REFER TO MANUFACTURER'S WIRING DIAGRAM FOR EXACT WIRING INFORMATION.
D WALL CONTROL SHALL MANUALLY TURN-ON-OFF AND DIM LIGHT FIXTURES USING A 0-10V CONTROL SIGNAL COMPATIBLE
WITH ATTACHED LIGHT FIXTURE DRIVERS.
NADDITIONAL WALL
CONTROLS
CAT5
CAT5
0-10V
DMDM
120V
N
HCONTROL
UNIT
EMERGENCY
LUMINAIRE(S)
OCCUPANCY
SENSOR
SWITCH &
DIMMER WALL
CONTROL
GENERAL NOTES
A UL924 POWER/RELAY PACK. SWITCHES TO EMEGENCY POWER UPON LOSS OF NORMAL POWER.
B N.C. MOMENTARY TEST SWITCH. MOUNT ON ROOM WALL. LABEL PLATE "EMR. LIGHT TEST"
N
ADDITIONAL WALL
CONTROLS
CAT5
CAT5
0-10V
120V N
NORMAL FEED
EMERGENCY FEED
TEST
120V
HCONTROL
UNIT
LUMINAIRE(S)
N NORMAL FEED
0-10V
DM
DM
N
120V N
HCONTROL
UNIT
LUMINAIRE(S)
OCCUPANCY
SENSOR
GENERAL NOTES
A OCCUPANCY SENSOR SHALL TURN OFF LIGHTS AFTER 15 MINUTES UPON VACANCY OF THE ROOM.
B CONTRACTOR SHALL COORDINATE WITH MANUFACTURER FOR EXACT QUANTITY OF OCCUPANCY SENSORS (FOR COMPLETE ROOM COVERAGE) AND PROVIDE ANY ADDITIONAL COMPONENTS FOR A COMPLETE AND OPERABLE SYSTEM. COORDINATE COMPONENT MOUNTING LOCATIONS FOR PROPER CLEARANCE OF ACCESSIBILITY PRIOR TO ROUGH-IN. COORDINATE PROGRAMMING OF ZONES AND WALL STATION CONFIGURATIONS, AS SHOWN ON
DRAWINGS, WITH MANUFACTURER.
C DETAIL IS SCHEMATIC IN NATURE. REFER TO MANUFACTURER'S WIRING DIAGRAM FOR EXACT WIRING INFORMATION.
D WALL CONTROL SHALL MANUALLY TURN-ON-OFF AND DIM LIGHT FIXTURES USING A 0-10V CONTROL SIGNAL COMPATIBLE
WITH ATTACHED LIGHT FIXTURE DRIVERS.
N
CAT5
ADDITIONAL
OCCUPANCY
SENSOR
0-10V
N1 C1
N1 N1 N1 N1
C1 C1 C1 C1
N2 N2 N2 N2
C2 C2 C2 C2
N2 C2
J J J J J J J J
N1 C1 N1 C1 N2 C2 N2 C2
P: 937-224-0861 www.heapy.com
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO. STATE COA FIRM NO.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290
/1 /2
:0
:5
P
M
Renovate MICU/SICU
10/17/2025
DETAILS
E501
DJWMSG
19018.00
539-20-104
Cincinnati, Ohio
100% CONSTRUCTION
DOCUMENTS
2019-05193 01528
N.T.S.Scale:
LIGHTING CONTROL DIAGRAM - MANUAL DIMMING &
OVERRIDE
N.T.S.Scale:
EMERGENCY LIGHTING CONTROL DIAGRAM - MANUAL
DIMMING & OVERRIDE
N.T.S.Scale:
LIGHTING CONTROL DIAGRAM - OCCUPANCY SENSOR
ONLY
Scale:Scale: 3/4" = 1'-0"3/4" = 1'-0"
PATIENT HEADWALL - POWER
PATIENT HEADWALL -
POWER NOTES:
A. REFER TO EP102 FOR ADDITIONAL INFORMATION. "N1"
SHALL BE NORMAL POWER CIRCUIT 1. "N2" SHALL BE
NORMAL POWER CIRCUIT 2. "C1" SHALL BE CRITICAL
POWER CIRCUIT 1. "C2" SHALL BE CRITICAL POWER
CIRCUIT 2.
B. MAKE CONNECTIONS TO EACH VERTICAL HEADWALL
SECTION (NORMAL AND CRITICAL POWER). EACH SET
OF BOXES REPRESENTS (1) SECTION (TOTAL OF (4)
SECTIONS).
Type B2
RECESSED LED LENSED LAY-IN FIXTURE
HOUSING: DIE-FORMED COLD-ROLLED STEEL. HINGED OPTIC
SYSTEM. SPRING LOADED LATCHES.
FINISH: HIGH-REFLECTANCE WHITE BAKED ENAMEL FINISH.
OPTICS: HIGH TRANSMISSION EXTURDED ACRYLIC LENSES. A12
PATTERN.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: UL1598, UL2108, CSA LABEL. EMERGENCY FIXTURES-
UL924. DESIGNLIGHTS CONSORTIUM (DLC) QUALIFIED.
DAMP LOCATION LABELED.
IC RATING - STANDARD
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “B2a” 2’ X 2’ 1400 LM, 13 W, NOMINAL “B2a - WL” 2’ X 2’ 1400 LM, 13 W, NOMINAL, WET
LOCATION LISTED.
“B2b” 2’ X 2’ 2500 LM, 24 W, NOMINAL “B2c” 2’ X 2’ 3500 LM, 31 W, NOMINAL “B2d” 2’ X 2’ 4300 LM, 42 W, NOMINAL
B2
Type U2
LED UNDERCABINET FIXTURE
HOUSING: 20 GA STEEL HOUSING.
FINISH: POLYESTER POWDER COAT ANTI-MICROBIAL FINISH.
WHITE.
OPTICS: HIGH IMPACT ACRYLIC LENS.
LAMPS: LED LIGHT SOURCE, 4000K
CERTIFICATION: DAMP LOCATION LISTED.
LINKS: OPTIONAL LINKING CONNECTOR CORDS.
VOLTAGE: MVOLT 120V - 277V.
VARIATIONS: “U2a” 1’ 290 LM, 8 W, NOMINAL “U2b” 2’ 990 LM, 14 W, NOMINAL “U2c” 3’ 1540 LM, 28 W, NOMINAL
U2
Type X1, X2
LED EXIT SIGN
HOUSING: DIE-CAST ALUMINUM BODY. BLACK TEXTURED FINISH.
MOUNTING: UNIVERSAL WALL, CEILING, END MOUNTING.
LAMPS: LED LIGHT SOURCE, RED STENCIL LETTERS. BREAK OUT
CHEVRONS.
CERTIFICATION: DAMP LOCATION LISTED. EMERGENCY FIXTURES-UL924
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “X1” SINGLE FACE EXIT.
“X2” DOUBLE FACE EXIT.
X1 X2
Type F1
RECESSED LED 6” DIAMETER LENSED DOWNLIGHT FIXTURE
HOUSING: 22 GA. NON-CORROSIVE STEEL PLATFORM. J-BOX WITH
SNAPON COVER. ACCESSABLE FROM ABOVE AND BELOW
CEILING.
REFLECTOR: ALUMINUM, ALZAK SEMI-DIFFUSE REFLECTOR. SELF-
TRIMED.
45DEG BEAM SPREAD.
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L70, 80 CRI.
4000K
CERTIFICATION: CSA LABEL. WET LOCATION LISTED. NON-IC RATING.
DIMMING: 0-10VDC 10% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “F1a” 6” 45DEG 1100 LM, 13 W, NOMINAL “F1a - WL” 6” 45DEG 1100 LM, 13 W, NOMINAL, WHITE
NON-CONDUCTIVE TRIM.
“F1b” 6” 45DEG 1500 LM, 16 W, NOMINAL “F1c” 6” 45DEG 2000 LM, 22 W, NOMINAL
F1
Type NL
LED PATIENT NIGHT LIGHT FIXTURE
HOUSING: 0.050 ALUMINUM BACKPLATE.
FINISH: MOLDED POLYCARBONATE OPTICAL LENS.
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L80, 80 CRI.
AMBER LIGHT.
VOLTAGE: MVOLT 120V-277V.
VARIATIONS: “NL” 18 LM, 2 W, NOMINAL
NL
Type D6
LED PATIENT VANITY FIXTURE
HOUSING: EXTRUDED ALUMINUM HOUSING, WELDED ALUMINUM END
CAPS.
FINISH: BRUSHED NICKEL FINISH.
OPTICS: EXTRUDED ACRYLIC DIFFUSER.
LAMPS: LED LIGHT SOURCE. 4000K
VOLTAGE: 120V - 277V.
VARIATIONS: “D6” 2’ 1550 LM, 18 W, NOMINAL
D6
Type B3
PATIENT BED - AMBIENT / EXAM / READING
HOUSING: 20 GAUGE STEEL. GASKET SEALS DOORFRAME TO
HOUSING.
FINISH: MATTE SATIN WHITE ANTIMICROBIAL POLYESTER
POWDER COAT.
OPTICS: IMPACT-RESISTANT ACRYLIC LENS. READING LIGHT WITH
FIELD AIMING CAPABILITY.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: UL CERTIFIED IP65. NSF2.
WET LOCATION LABELED.
SWITCHING: LOW-VOLTAGE CONTROLLER - SEQUENTIAL SWITCHING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “B3” 8" X 4'. 600 LUMENS READING. 3,200 LUMENS
AMBIENT. 6,800 LUMENS AMBIENT + EXAM, 87W.
B3
Type B4
4" ASYMMETRIC LINEAR FIXTURE
HOUSING: 20 GAUGE STEEL.
FINISH: POLYESTER POWDER COAT.
OPTICS: ACRYLIC LENS .098" THICK SATIN FINISH.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: UL AND cUL CERTIFIED.
DAMP LOCATION LISTED.
DIMMING: 0-10V DIMMING. 1%.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “B4a” 2' 375 LUMENS PER FOOT. 10 W.
“B4b” 4' 375 LUMENS PER FOOT. 20 W.
"B4c" 8' 375 LUMENS PER FOOT. 40 W.
NOTE:
LENGTHS AND CONTINUOUS RUNS OF LUMINAIRE(S) SHALL BE
COORDINATED WITH ARCHITECTURAL PLANS PRIOR TO INSTALLATION.
ENSURE LUMINAIRE IS INSTALLED STRAIGHT WITH NO VISIBLE LIGHT
LEAKS AND CLEANLY MITERED CORNERS/TRANSITIONS. WORK VERY
CLOSELY WITH DRYWALL/FRAMING INSTALLER.
LUMINAIRES SHALL BE ORIENTED AND INSTALLED SUCH THAT LIGHT RAYS
ILLUMINATE TOWARD CENTER OF CORRIDOR.
B4
Type F2
RECESSED LED 4.5” SQUARE DOWNLIGHT
HOUSING: 22 GA. NON-CORROSIVE STEEL PLATFORM. J-BOX WITH
SNAPON COVER. ACCESSABLE FROM ABOVE AND BELOW
CEILING.
REFLECTOR: 50 DEGREE CUT-OFF.
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L70, 80 CRI.
4000K
CERTIFICATION: UL AND cUL CERTIFIED.
DAMP LOCATION LISTED.
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “F2a” 4.5” 1000 LM, 11 W, NOMINAL
“F2b” 4.5” 1500 LM, 19 W, NOMINAL
F2
Type P1
SURFACE MOUNT ROUND LED LUMINAIRE
HOUSING: TWO-PIECE 20 GA. STEEL REFLECTOR AND HOUSING.
FINISH: POLYESTER POWDER COAT.
OPTICS: FROSTED ACRYLIC LENS.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: UL1598, UL2108, CSA LABEL. DESIGNLIGHTS CONSORTIUM
(DLC) QUALIFIED.
DAMP LOCATION LABELED.
IC RATING - STANDARD
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “P1” 3’ 4000 LM, 49 W, NOMINAL
P1
P: 937-224-0861 www.heapy.com
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO. STATE COA FIRM NO.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290
/1 /2
:0
:5
P
M
Renovate MICU/SICU
10/17/2025
LUMINAIRES SCHEDULE
E600
DJWMSG
19018.00
539-20-104
Cincinnati, Ohio
100% CONSTRUCTION
DOCUMENTS
2019-05193 01528
Type B5
LED STATIC WHITE TAPELIGHT
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L80, 90+ CRI.
4000K
CERTIFICATION: IP20. IP65. IP68. CE. ETL. RoHS.
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: 24V.
VARIATIONS: "B5" 3.0 WATTS PER FOOT. 402 LUMENS PER FOOT.
NOTE:
PROVIDE ALL REQUIRED ACCESSORIES FOR A COMPLETE, OPERATIONAL
SYSTEM. THIS INCLUDES, BUT NOT LIMITED TO, DRIVERS, CONTROLLERS,
WIRING, CONDUIT, DAISY CHAIN CONNECTORS, END/BACK/SIDE FEED
HARD WIRE THROUGH CHANNELS.
PROVIDE CHANNEL FIXTURE WITH FROSTED LENS (85% LIGHT
TRANSMISSION) AND 118-DEGREE WIDE BEAM ANGLE.
REFER TO ARCHITECTURAL DETAILS FOR LENGTHS OF RUNS AND
MOUNTING INFORMATION. TAPELIGHT SHALL HAVE 1.97 INCH FIELD
CUTTABLE LENGTHS.
B5
Type B6
2X2 LED PATIENT BED FIXTURE – AMBIENT / EXAM
HOUSING: 20 GA SEAM-WELDED CONSTRUCTION. 18 GA. HOUSING
FLANGE WITH MILTERED AND WELDED CORNERS.
FINISH: POLYESTER POWDER COAT . WHITE.
OPTICS: IMPACT-RESISTANT ACRYLIC LENS.
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: UL1598. WET LOCATION LISTED. IP64. NSF2.
DIMMING: 0-10VDC 1% DIMMING.
SWITCHING: LOW VOLTAGE CONTROLLER – SEQUENTIAL
SWITCHING.
VOLTAGE: 120V OR 277V.
VARIATIONS: “B6” 2’ X 2’ 2100 LM, 21 W AMBIENT. 5250 LM, 56 W
EXAM
B6
Type C1
LED LENSED STRIPLIGHT FIXTURE
SURFACE MOUNTED OR CHAIN HUNG
HOUSING: DIE-FORMED COLD-ROLLED STEEL.
FINISH: NON-GLARE HIGH-REFLECTANCE BAKED ENAMEL FINISH,
PAINTED AFTER FABRICATION.
OPTICS: ACRYLIC LENS.
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: UL1598, UL2108, CSA LABEL.
DESIGNLIGHTS CONSORTIUM (DLC) QUALIFIED. DAMP
LOCATION LABELED.
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “C1” 4’ 5000 LM, 25 W, NOMINAL
C1
Type B7
6" LINEAR SLOT POP-DOWN LENS
HOUSING: 20 GAUGE STEEL.
FINISH: POLYESTER POWDER COAT.
OPTICS: EXTRUDED ACRYLIC LENS .06" THICK FROSTED FINISH.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: UL AND cUL CERTIFIED.
DAMP LOCATION LISTED.
DIMMING: 0-10V DIMMING. 1%.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “B7a” 4' 625 LUMENS PER FOOT. 32 W.
"B7b" 8' 750 LUMENS PER FOOT. 72 W.
NOTES:
COORDINATE WITH ARCHITECTURAL PLANS AND CEILING VENDOR PRIOR
TO INSTALLATION AND ORDERING PRODUCT.
ENSURE LUMINAIRE IS INSTALLED STRAIGHT WITH NO VISIBLE LIGHT
LEAKS.
LUMINAIRES SHALL BE SUPPORTED FROM GRID OR DECK ABOVE.
LUMINAIRES SHALL NOT BE SUPPORTED BY CEILING PLANKS.
B7
Type F3
6" PATIENT ROOM DOWNLIGHT
HOUSING: 22 GA. NON-CORROSIVE STEEL PLATFORM. J-BOX WITH
SNAPON COVER. ACCESSABLE FROM ABOVE AND BELOW
CEILING.
REFLECTOR: POLYCARBONATE LENS INTEGRAL TO LIGHT ENGINE.
FINISH: TEXTURED LENS.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L70, 80 CRI.
4000K
CERTIFICATION: CSA LABEL. IP66. NSF2 SPLASH/NON-FOOD ZONE WET
LOCATION LISTED.
DIMMING: 0-10VDC 10% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “F3” 6” 1500 LM, 19 W, NOMINAL
F3
Type B8
3.5" RECESSED PERIMETER RGBW
HOUSING: EXTRUDED ALUMINUM HOUSING WITH NARROW 3.5"
APERTURE.
FINISH: WHITE POWDER COATED FINISH.
OPTICS: EXTRUDED, SATIN ACRYLIC LENS.
LAMPS: LED LIGHT SOURCE, 72,000 HOUR RATED AT L80, 83
+ CRI.
RED (335-805 mcd) GREEN (710-1400 mcd) BLUE (140-355 mcd)
CERTIFICATION: ETL AND cUL CERTIFIED.
DAMP LOCATION LISTED.
DIMMING/DRIVER: DMX. 100-0%.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “B8” X' 500 LUMENS PER FOOT. 3.8 WATTS PER
FOOT.
NOTES:
PROVIDE COMPATIBLE DMX CONTROLLER. DMX CONTROLLER SHALL BE
MOUNTED, RECESSED, IN WALL.
REFER TO ARCHITECTURAL DETAILS FOR LUMINAIRE MOUNTING AND
MORE INFORMATION.
REFER TO ARCHITECTURAL PLANS FOR LENGTHS OF LUMINAIRE. PROVIDE
CONTINUOUS RUN OF LUMINAIRE, WITHOUT BREAKS. PROVIDE END
FILLERS AS REQUIRED. PROVIDE ALL REQUIRED ACCESSORIES FOR A
COMPLETE, OPERATIONAL SYSTEM.
B8
B1
Type B1
RECESSED LED VOLUMETRIC FIXTURE
HOUSING: RUGGED, ONE-PIECE COLD-ROLLED STEEL COATED
POLYESTER.
FINISH: NON-GLARE HIGH-REFLECTANCE WHITE POWER COAT
FINISH, PAINTED AFTER FABRICATION.
OPTICS: IMPACT-MODIFIED, SINGLE CLEAR ACRYLIC DIFFUSER.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: CSA LABEL. DESIGNLIGHTS CONSORTIUM (DLC)
QUALIFIED.
DAMP LOCATION LABELED.
IC RATING - STANDARD
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “B1a” 2’ X 2’ 2200 LM, 16 W, NOMINAL “B1b” 2’ X 2’ 3300 LM, 26 W, NOMINAL “B1c” 2’ X 2’ 4800 LM, 38 W, NOMINAL
P: 937-224-0861 www.heapy.com
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO. STATE COA FIRM NO.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290
/1 /2
:0
:3
P
M
Renovate MICU/SICU
10/17/2025
SCHEDULES
E601
DJWMSG
19018.00
539-20-104
Cincinnati, Ohio
100% CONSTRUCTION
DOCUMENTS
2019-05193 01528
33.66 kVA 24.43 kVA (68 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. EXISTING NORMAL POWER PANELBOARD.
2. REFER TO SINGLE-LINE DIAGRAM FOR MORE INFORMATION.
Total Load: 9.59 kVA 13.59 kVA 10.48 kVA
41 REC A283 20 A 1 900 VA 1220... 1 20 A REC A284 42
39 REC A283 20 A 1 1220... 900 VA 1 20 A REC A284 40
37 REC A283 20 A 1 900 VA 900 VA 1 20 A REC A284 38
35 REC A280 20 A 1 900 VA 900 VA 1 20 A REC A282 36
33 REC A280 20 A 1 1220... 1220... 1 20 A REC A282 34
31 REC A280 20 A 1 900 VA 900 VA 1 20 A REC A282 32
29 REC A288 20 A 1 1220... 900 VA 1 20 A REC A286 30
27 REC A288 20 A 1 900 VA 1220... 1 20 A REC A286 28
25 REC A288 20 A 1 900 VA 900 VA 1 20 A REC A286 26
23 REC A285 20 A 1 1220... 900 VA 1 20 A REC A287 24
21 REC A285 20 A 1 900 VA 1220... 1 20 A REC A287 22
19 REC A285 20 A 1 900 VA 900 VA 1 20 A REC A287 20
17 REC A278 20 A 1 900 VA 900 VA 1 20 A REC A279 18
15 REC A278 20 A 1 1220... 1220... 1 20 A REC A279 16
13 REC A278 20 A 1 900 VA 900 VA 1 20 A REC A279 14
11 EXISTING 20 A 1 0 VA 518 VA 1 20 A LTG 12
9 LTG CORR. 20 A 1 438 VA 172 VA 1 20 A TAPELIGHT 10
7 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 8
5 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 6
3 EXISTING 20 A 1 0 VA 1742... 1 20 A LTG 4
1 LTG 20 A 1 593 VA 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 225 A
Supply From: Enclosure: Type 1 Mains Type: MLO
Location: Electrical A275 Mounting: Surface A.I.C. Rating: EXIST
Panel: 2F1(EXISTING)
DPF
18.62 kVA 14.31 kVA (40 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. EXISTING NORMAL POWER PANELBOARD.
2. * REPRESENTS TO PROVIDE GFCI TYPE BREAKER. REFER TO FLOOR PLANS FOR MORE INFORMATION.
3. REFER TO SINGLE-LINE DIAGRAM FOR MORE INFORMATION.
Total Load: 7.04 kVA 5.84 kVA 5.74 kVA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 Receptacle 20 A 1 180 VA 0 VA 1 20 A SPARE 38
35 360 VA 1 20 A REC A292A 36
33 REC A281 20 A 1 720 VA 900 VA 1 20 A REC A292 34
31 OMNICELL A294A 20 A 1 1500... 720 VA 1 20 A REC 32
29 REC 20 A 1 1500... 1180... 1 20 A REC WOW 30
27 *MW 20 A 1 1500... 360 VA 1 20 A REC C226D 28
25 Receptacle 20 A 1 900 VA 0 VA 1 20 A EXISTING 26
23 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 24
21 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 22
19 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 20
17 EXISTING 20 A 1 0 VA 720 VA 1 20 A REC A294A 18
15 REC C226D 20 A 1 180 VA 1180... 1 20 A REC WOW 16
13 REC C226D 20 A 1 180 VA 680 VA 1 20 A REC WOW 14
11 REC A294A 20 A 1 540 VA 1440... 1 20 A REC A294A 12
9 COPIER A290 20 A 1 1000... 0 VA 1 20 A SPARE 10
7 REC A290 & A293 20 A 1 1440... 1440... 1 20 A REC A294A 8
5 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 6
3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4
1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 225 A
Supply From: Enclosure: Type 1 Mains Type: MLO
Location: Electrical A275 Mounting: Surface A.I.C. Rating: EXIST
Panel: 2F2 (EXISTING)
2F1 (SUB-FEED LUGS)
35.65 kVA 25.08 kVA (70 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. EXISTING CRITICAL POWER PANELBOARD.
2. REFER TO SINGLE-LINE DIAGRAM FOR MORE INFORMATION.
Total Load: 11.43 kVA 12.55 kVA 11.68 kVA
41 REC A294A 20 A 1 360 VA 1000... 1 20 A REC WOW 42
39 LTG 20 A 1 1328... 900 VA 1 20 A REC A282 40
37 REC/SENSORS 20 A 1 630 VA 1200... 1 20 A REC A282 38
35 REC A280 20 A 1 1200... 900 VA 1 20 A REC A282 36
33 REC A280 20 A 1 900 VA 900 VA 1 20 A REC A286 34
31 REC A280 20 A 1 900 VA 1200... 1 20 A REC A286 32
29 REC A279 20 A 1 900 VA 900 VA 1 20 A REC A286 30
27 REC A279 20 A 1 1200... 720 VA 1 20 A REC A293 28
25 REC A279 20 A 1 900 VA 720 VA 1 20 A REC A290 26
23 REC A288 20 A 1 900 VA 720 VA 1 20 A REC/SENSORS 24
21 REC A288 20 A 1 1200... 900 VA 1 20 A REC/SENSORS 22
19 REC A288 20 A 1 900 VA 1200... 1 20 A REC A287 20
17 REC A278 20 A 1 1200... 900 VA 1 20 A REC A287 18
15 REC A278 20 A 1 900 VA 900 VA 1 20 A REC A287 16
13 REC A278 20 A 1 900 VA 1200... 1 20 A REC A285 14
11 EXISTING 20 A 1 0 VA 900 VA 1 20 A REC A285 12
9 EXISTING 20 A 1 0 VA 900 VA 1 20 A REC A285 10
7 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 8
5 EXISTING 20 A 1 0 VA 1800... 1 20 A ELEC. GLASS 6
3 EXISTING 20 A 1 0 VA 1800... 1 20 A ELEC. GLASS 4
1 LTG 20 A 1 1676... 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 225 A
Supply From: Enclosure: Type 1 Mains Type: MLO
Location: Electrical A275 Mounting: Surface A.I.C. Rating: EXIST
Panel: C2F (EXISTING)
C1F1 (SUB-FEED LUGS)
31.38 kVA 20.69 kVA (57 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. EXISTING CRITICAL POWER PANELBOARD
2. * REPRESENTS TO PROVIDE GFCI TYPE BREAKER. REFER TO FLOOR PLANS FOR MORE INFORMATION.
3. REFER TO SINGLE-LINE DIAGRAM FOR MORE INFORMATION.
Total Load: 10.26 kVA 10.80 kVA 10.32 kVA
41 REC A292 20 A 1 1080... 900 VA 1 20 A REC A281 42
39 BIPOLAR IONIZATION 20 A 1 180 VA 720 VA 1 20 A REC A281 40
37 REC A292A 20 A 1 360 VA 1200... 1 20 A REC A284 38
35 COPIER A290 20 A 1 1000... 900 VA 1 20 A REC A284 36
33 REC A292A 20 A 1 720 VA 900 VA 1 20 A REC A284 34
31 REC/SENSORS 20 A 1 720 VA 1200... 1 20 A REC A283 32
29 REC 20 A 1 540 VA 900 VA 1 20 A REC A283 30
27 REC A294A 20 A 1 1000... 900 VA 1 20 A REC A283 28
25 REC A294A 20 A 1 1500... 720 VA 1 20 A REC CORR. 26
23 EXISTING 20 A 1 0 VA 1500... 1 20 A *UC/RF A291 24
21 REC A294A 20 A 1 1080... 1540... 1 20 A Receptacle 22
19 REC A294A 20 A 1 1080... 1500... 1 20 A BW A294A 20
17 UC RF A294A 20 A 1 1500... 0 VA 1 20 A EXISTING 18
15 OMNICELL A294A 20 A 1 1500... 0 VA 1 20 A EXISTING 16
13 REC A294A 20 A 1 1080... 0 VA 1 20 A EXISTING 14
11 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 12
9 REC A294A 20 A 1 1080... 0 VA 1 20 A EXISTING 10
7 Receptacle 20 A 1 180 VA 180 VA 1 20 A PTS 8
5 REC WOW 20 A 1 1000... 1000... 1 20 A REC WOW 6
3 REC C226D 20 A 1 180 VA 1000... 1 20 A REC WOW 4
1 REC C226D 20 A 1 360 VA 180 VA 1 20 A REC C226D 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 225 A
Supply From: Enclosure: Type 1 Mains Type: MLO
Location: Electrical A275 Mounting: Surface A.I.C. Rating: EXIST
Panel: C2F1 (EXISTING)
C2F (SUB-FEED LUGS)
NOTES:
1. EF-3 CONSISTS OF (2) MOTORS, (1) OPERATING AND (1) REDUNDANT. EACH MOTOR SHALL HAVE A VFD PROVIDED WITH LOCAL DISCONNECTING MEANS. PROVIDE ALL INTERCONNECTING WIRING AS REQUIRED. PROVIDE INTERLOCK BETWEEN VFD AND OUTDOOR
DISCONNECT.
2. EQUIPMENT PROVIDED WITH INTEGRAL DISCONNECT.
MOTORS, STARTERS, DISCONNECTS & CONTROLS
MARK
MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER
S E
E N
O T
E
NAMEPLATE
CHARACTERISTICS LOCATION
N E
M A
S
IZ
E
TYPE LOCATION
F U
R N
IS
H
E D
B Y
TYPE LOCATION
F U
R N
IS
H
E D
B Y
I N
T E
R L O
C K
W
IT
H M
O T
O R
N O
B
Y E
.C
M A
N U
A L A
T S
T A
R T
E R
I N
T E
G R
A L
W
IT
H E
Q U
IP
M
E N
T
F U
R N
IS
H
E D
B Y
S E
E N
O T
E
N U
M B
E R
O F
C O
N D
U C
T O
R S
W
IR
E S
IZ
E
G R
O U
N D
S
IZ
E
C O
N D
U
IT
S
IZ
E
H O
R S
E P
O W
E R
H
P
L O
A D k V
A
V
-1 P
H
V
-1 P
H
V
-3 P
H
V
-1 P
H
V
-3 P
H
V
-1 P
H
V
-1 P
H
V
-3 P
H
R O
O M
N U
M B
E R
ROOM NAME M
A
N U
A L
M A
G N
E T
IC
B U
IL
T
-I N
M O
T O
R O
/L
-S
P E
E D
V F
D
S E
E N
O T
E
N E
A R
M O
T O
R
M O
T O
R C
O N
T C
E N
T E
R
E Q
U
IP
C O
N T
P A
N E
L
R O
O M
N U
M B
E R
S E
E N
O T
E
D
IS
C S
W
IT
C H
M A
N U
A L S
T A
R T
E R
R E
C E
P T
A C
L E
F E
E D
E R
S W
O R
B R
E A
K E
R
N E
M A
T Y
P E
D
IS
C S
IZ
E
F U
S E
S
IZ
E
N E
A R
M O
T O
R
M O
T O
R C
O N
T C
E N
T E
R
E Q
U
IP
C O
N T
P A
N E
L
P A
N E
L B
O A
R D
S E
E N
O T
E
CU-2 CONDENSING UNIT 2 80 TON 145 ● ROOF ● DIV. 23 ● 3R 200 NF ● DIV. 26 DIV. 23 4 3/0 6 2"
EF-3 EXHAUST FAN 3 (2) 25 HP 28.27 ● <varies
ROOF ● B456E DIV. 26 2 DIV. 23 DIV. 23 3 4 10 1.25" 1, 2
AV SYMBOLS WITH ELECTRICAL REQUIREMENTS
W
CS
CLASSROOM SOUNDFIELD SYSTEM RECEIVER/AMPLIFIER/MIXER AND WALL OUTLET (44" MH UNLESS NOTED OTHERWISE).
PROVIDE GROMMETED FACEPLATES, CABLING, TWO 1-GANG BOXES WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
SUBSCRIPT "W" INDICATES WALL MOUNTED ON SHELF. SOUNDFIELD SYSTEM,
S H
SURFACE MOUNTED PAGING/INTERCOM SPEAKER (90" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "H" INDICATES HANGING CEILING SPEAKER. PROVIDE SPEAKER, CABLING, AND 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE
CEILING.
CEILING MOUNTED MUSIC PLAY BACK SPEAKER. PROVIDE 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE GROMMETED FACEPLATE, SPEAKER, INSTALLATION ADJACENT TO BOX AND WIRING.S
M
S HORN TYPE PAGING/INTERCOM SYSTEM SPEAKER (90" MH UNLESS NOTED OTHERWISE). PROVIDE GROMMETED FACEPLATE, SPEAKER, INSTALLATION, WIRING, AND 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
V SOUND SYSTEM WALL MOUNTED SPEAKER VOLUME CONTROLLER (46" MH UNLESS NOTED OTHERWISE). PROVIDE 1- GANG BOX AND 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE VOLUME CONTROLLER WITH FACEPLATE, INSTALLATION AND WIRING.
M# X
MICROPHONE JACKPLATE (18" MH UNLESS NOTED OTHERWISE). "#"=NUMBER OF GANG, "X"=NUMBER OF JACKS IF OTHER THAN TWO (2). PROVIDE 0.75" CONDUIT FOR 1-GANG BOX OR 1" CONDUIT FOR 2-GANG AND LARGER BOX TO ABOVE
ACCESSIBLE CEILING. PROVIDE JACKS, FACEPLATE AND CABLING.
WC X
WALL MOUNTED AV SYSTEM CONTROL INTERFACE. SUBSCRIPT "X" INDICATES TYPE. REFER TO SYSTEM DIAGRAMS.
PROVIDE CONTROLLER, CABLING, AND BACKBOX (46" MH UNLESS NOTED OTHERWISE) WITH 1" CONDUIT TO ABOVE
ACCESSIBLE CEILING.
SR X
Z
LOCAL SOUND REINFORCEMENT SYSTEM SPEAKER. SUBSCRIPT "X" INDICATES TYPE. REFER TO SYSTEM DIAGRAMS.
SJ
SPEAKER JACKPLATE (18" MH UNLESS NOTED OTHERWISE). PROVIDE 3-GANG BOX WITH 0.75" CONDUIT TO ABOVE
ACCESSIBLE CEILING.
WSF
WALL MOUNTED SOUNDFIELD SYSTEM SPEAKER. PROVIDE SPEAKER, CABLING, AND 1-GANG BOX WITH 1" CONDUIT TO
ABOVE CEILING.
PR
X
WALL MOUNTED PROJECTOR. PROVIDE BACKBOX WITH 1-1.25" CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE PROJECTOR, MOUNT AND CABLING. SUBSCRIPT "X" INDICATES CONFIGURATION TYPE, REFER TO FACEPLATE DETAILS.
WALL MOUNT ELECTRIC PROJECTION SCREEN. PROVIDE SCREEN, LOW VOLTAGE CONTROL, AND 1-GANG BOX WITH 1"
CONDUIT TO ABOVE ACCESSIBLE CEILING.
PS
E
CEILING MOUNT ELECTRIC PROJECTION SCREEN. PROVIDE SCREEN, LOW VOLTAGE CONTROL, AND 1-GANG BOX WITH 1"
CONDUIT TO ABOVE ACCESSIBLE CEILING.
PS
E
LOCAL SOUND SYSTEM SENSING MICROPHONE. PROVIDE 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE
CEILING. PROVIDE MICROPHONE WITH GROMMETED FACEPLATE, INSTALLATION AND WIRING.SM
HM (x) HANGING MICROPHONE OUTLET. PROVIDE 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING. SUBSCRIPT "X" INDICATES QUANTITY OF MICROPHONES IF MORE THAN ONE (1). PROVIDE MICROPHONE, JACK, FACEPLATE AND WIRING.
MA
MIC/AUX WALL MOUNTED INPUT (18" MH UNLESS NOTED OTHERWISE). PROVIDE 2-GANG BOX WITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING. PROVIDE JACKS, FACEPLATE AND CABLING.
MS
MICROPHONE/SPEAKER WALL MOUNTED JACKPLATE (18" MH UNLESS NOTED OTHERWISE). PROVIDE 1-GANG BOX WITH
0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE JACKS, FACEPLATE AND CABLING.
ME
MONITOR/EFFECTS WALL OUTLET (18" MH UNLESS NOTED OTHERWISE). PROVIDE 1-GANG BOX WITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING. PROVIDE JACKS, FACEPLATE, AND WIRING.
WALL MOUNTED BLUETOOTH INPUT MODULE (46" MH UNLESS NOTED OTHERWISE). PROVIDE 1-GANG BOX WITH 0.75"
CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE JACKS, FACEPLATE AND WIRING.
MP
REMOTE POWER SWITCH OUTLET (46" MH UNLESS NOTED OTHERWISE). PROVIDE 1-GANG BOX WITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING. PROVIDE SWITCH, FACEPLATE AND WIRING.
R
P PROGRAM SOURCE CABINET FOR PAGING/INTERCOM SYSTEM. PROVIDE TWO 1-GANG BOXES WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE GROMMETED FACEPLATES, CABINET, INSTALLATION AND WIRING.
CA
WALL MOUNTED CALL ANNUNCIATOR FOR PAGING/INTERCOM SYSTEM (90" MH UNLESS NOTED OTHERWISE). PROVIDE ANNUNCIATOR, WIRING, AND CUSTOM BACKBOX INSTALLED WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
CO WALL MOUNTED CALL ORIGINATION SWITCH FOR PAGING/INTERCOM SYSTEM (46" MH UNLESS NOTED OTHERWISE). PROVIDE CALL SWITCH, FACEPLATE, WIRING, AND 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
W
SINGLE FACED WALL MOUNTED CLOCK (102” MH UNLESS NOTED OTHERWISE). 12” DIAMETER FACE ANALOG CLOCK UNLESS SUBSCRIPT “15” FOR 15” DIAMETER FACE ANALOG CLOCK OR “LED” FOR LED DIGITAL CLOCK. SUBSCRIPT “W”
INDICATES WIREGUARD. 1-GANG BOX WITH 0.75” CONDUIT TO ABOVE ACCESSIBLE CEILING.
15 DOUBLE FACED WALL MOUNTED CLOCK (102” MH UNLESS NOTED OTHERWISE). 12” DIAMETER FACE ANALOG CLOCK UNLESS SUBSCRIPT “15” FOR 15” DIAMETER FACE ANALOG CLOCK OR “LED” FOR LED DIGITAL CLOCK. 1-GANG BOX WITH
0.75” CONDUIT TO ABOVE ACCESSIBLE CEILING.
ROOF MOUNTED ANTENNA. REFER TO ANTENNA MOUNTING DETAIL FOR MORE INFORMATION. SUBSCRIPT INDICATES
TYPE.
A X
SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS
CC
CCTV SYSTEM CEILING MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. PROVIDE CAMERA, CABLING, AND 1-GANG BOX WITH 0.75" CONDUIT ABOVE
ACCESSIBLE CEILING.
PS
LOCAL LOW VOLTAGE POWER SUPPLY FOR EXTERIOR CAMERA. SUBSCRIPT "X" INDICATES ASSOCIATED CAMERA.
PROVIDE 120V POWER INTO LOCAL JUNCTION BOX ABOVE CEILING AND CONNECTION TO POWER SUPPLY. PROVIDE
POWER SUPPLY MOUNTED ABOVE CEILING AND LOW VOLTAGE WIRING TO LOCAL CAMERA.
IC
WALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERWISE). PROVIDE INTERCOM, CABLING, AND 1-
GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
DM
DOOR POSITION SWITCH WITH WIRING. PROVIDE CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR OPENINGS. REFER TO
SECURITY ROUGH-IN DETAILS.
EL
ELECTRONIC DOOR LOCK. PROVIDE LOW VOLTAGE WIRING AND CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON
SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN DETAILS.
EM
ELECTRONIC MAG LOCK AND INSTALLATION BY OTHERS. PROVIDE LOW VOLTAGE WIRING AND CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN
DETAILS.
ES
ELECTRONIC STRIKE. PROVIDE LOW VOLTAGE WIRING AND CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS
JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN DETAILS.
LB
RX
REQUEST TO EXIT SWITCH IN DOOR HARDWARE. PROVIDE LOW VOLTAGE WIRING AND CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN DETAILS.
HD
HANDICAP DOOR OPERATOR MOTOR ASSEMBLY. PROVIDE 120V POWER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. PROVIDE LOW VOLTAGE WIRING AND INTERFACE WITH
SMS AND DOOR ACTUATOR BUTTONS. REFER TO SECURITY ROUGH-IN DETAILS.
HA
WALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON. PROVIDE BOX AS REQUIRED BY SYSTEM MANUFACTURER WITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. PROVIDE ALL LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR MOTOR. REFER TO SECURITY ROUGH-IN DETAILS.
HO
FA
WALL/FLOOR MOUNTED ELECTROMAGNETIC DOOR HOLD OPEN WITH POWER SUPPLY. PROVIDE 120V POWER AND CONNECTION, BOX AS REQUIRED BY MANUFACTURER AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. PROVIDE LOW VOLTAGE WIRING FROM POWER SUPPLY TO HOLD OPEN AND INTERFACE WITH SMS. SUBSCRIPT "FA" INDICATES DEVICES POWERED FROM FIRE ALARM SYSTEM AND INTERFACE FROM SMS TO FIRE ALARM SYSTEM
REQUIRED FOR DOOR RELEASE. REFER TO SECURITY ROUGH-IN DETAILS.
CR
WALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERWISE). PROVIDE READER, WIRING, AND 1-GANG BOX WITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN
DETAILS.
CR EL
ELEVATOR CAB MOUNTED CARD READER. READER TO BE INSTALLED IN ELEVATOR CAB AS COORDINATED WITH ELEVATOR CONTRACTOR. PROVIDE WIRING FROM CAB THRU TRAVELING CABLE TO ELEVATOR CONTROLLER IN ELEVATOR MACHINE ROOM AND INTERFACE WITH ELEVATOR CONTROLLER AND SMS. COORDINATE WITH ELEVATOR
CONTRACTOR. REFER TO SECURITY ROUGH-IN DETAILS.
KC
WALL MOUNTED COMBINATION KEYPAD/CARD READER (46" MH UNLESS NOTED OTHERWISE). PROVIDE DEVICE, CABLING, AND 2-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING.
K WALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERWISE). PROVIDE KEYPAD, CABLING, AND 1-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING.
MD
WALL MOUNTED MOTION DETECTOR (90" MH UNLESS NOTED OTHERWISE). PROVIDE MOTION DETECTOR, WALL MOUNT HARDWARE, CABLING, AND 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
PP W
WALL MOUNTED PANIC/DURESS BUTTON (46" MH UNLESS NOTED OTHERWISE). PROVIDE BUTTON, CABLING, AND 1-GANG
BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
X WALL MOUNTED SECURITY SYSTEM WIRING OUTLET MOUNTED BELOW COUNTER TOP. PROVIDE 2-GANG BOX WITH 2-1" CONDUITS TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. PROVIDE GROMMETED FACEPLATE AND
SECURITY SYSTEM CABLING PER DIV 28.
CM
WALL MOUNTED MONITOR OUTLET FOR CCTV SYSTEM (84" MH UNLESS NOTED OTHERWISE). PROVIDE 1-GANG BOX WITH
1" CONDUIT TO ABOVE CORRIDOR CEILING. PROVIDE JACK, FACEPLATE AND CABLING.
MIC
CEILING MOUNTED SECURITY/CCTV SYSTEM AUDIO MICROPHONE. PROVIDE MICROPHONE, CABLING, AND 1-GANG BOX
MOUNTED IN CEILING.
BR
WALL MOUNTED BIOMETRIC READER (46" MH UNLESS NOTED OTHERWISE). PROVIDE READER, CABLING, AND 2-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN
DETAILS.
X
X
MD
PB W
WALL MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE (46" MH UNLESS NOTED OTHERWISE). PROVIDE
BUTTON, CABLING, AND 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
ELECTRONIC LATCH BOLT MONITORING. PROVIDE HARDWARE, LOW VOLTAGE WIRING, AND CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SECURITY JUNCTION BOX ABOVE CEILING. REFER TO SECURITY ROUGH-IN DETAILS.
CEILING MOUNTED MOTION DETECTOR. PROVIDE DETECTOR, CABLING, AND 1-GANG BOX MOUNTED IN CEILING.
DC
LOCAL IP BASED 2-DOOR ACCESS CONTROL PANEL SERVING LOCAL CARD READER/SECURITY CONTROLLED DOORS.
LOCATE ABOVE ADJACENT ACCESSIBLE CEILING. PROVIDE DATA DROP IN 0.75" CONDUIT TO LOCAL DATA CLOSET.
EXTEND 1" CONDUIT WITH DOOR SECURITY WIRING TO LOCAL SECURITY SYSTEM JUNCTION BOX. REFER TO SECURITY
ROUGH-IN DETAILS.
JB M
SECURITY SYSTEM JUNCTION BOX TO BE LOCATED ABOVE ACCESSIBLE CEILING (MIN 6"X6"X4"). ROUTE LOCAL DOOR SECURITY WIRING CONDUITS/RACEWAYS TO JUNCTION BOX. EXTEND 1" CONDUIT WITH DOOR SECURITY WIRING TO LOCAL 2-DOOR CONTROL PANEL/REMOTE DOOR CONTROL PANEL AS INDICATED ON DRAWINGS. REFER TO SECURITY
ROUGH-IN DETAILS.
PL
SITE POLE FOR MOUNTING SECURITY CAMERAS (REFER TO SPECIFICATIONS FOR SIZE/TYPE). PROVIDE POLE WITH CONCRETE BASE AS INDICATED ON PLANS. EXTEND AND CONNECT TO SITE CONDUIT SYSTEM AS INDICATED ON PLANS.
PROVIDE NEMA 3R JUNCTION BOX AT BASE OF POLE FOR CAMERA EQUIPMENT (120V POWER SUPPLY, FIBER
CONVERTERS, ETC.). REFER TO SECURITY ROUGH-IN DETAILS.
TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS
P WALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERWISE). PROVIDE BOX WITH CONDUIT TO CABLE TRAY PER ABOVE ACCESSIBLE CEILING. PROVIDE JACKS, FACEPLATE AND CABLE. REFER TO FACEPLATE DETAILS.
X R
WALL MOUNTED AV OUTLET (84" MH UNLESS NOTED OTHERWISE). PROVIDE BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING. REFER TO FACEPLATE DETAILS. PROVIDE JACKS, FACEPLATE AND CABLING. SUBSCRIPT "X" INDICATES ALTERNATE
CONFIGURATION.
X V
WALL MOUNTED AV OUTLET (44" MH UNLESS NOTED OTHERWISE). PROVIDE BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING. REFER TO FACEPLATE DETAILS. PROVIDE JACKS, FACEPLATE AND CABLING. SUBSCRIPT "X" INDICATES
ALTERNATE CONFIGURATION.
CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU WALL (1-2" SLEEVE UNLESS NOTED OTHERWISE).
J TELECOM JUNCTION BOX AND CONDUIT, REFER TO PLANS.
D WALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). PROVIDE BOX WITH CONDUIT(S) TO CABLE TRAY ABOVE ACCESSIBLE CEILING. PROVIDE JACKS, FACEPLATE AND CABLE. REFER TO FACEPLATE DETAILS.
X I
WALL MOUNTED AV OUTLET (18" MH UNLESS NOTED OTHERWISE). PROVIDE BOX WITH CONDUITS TO CABLE TRAY ABOVE ACCESSIBLE CEILING. REFER TO FACEPLATE DETAILS. PROVIDE JACKS, FACEPLATE AND CABLING. SUBSCRIPT "X"
INDICATES ALTERNATE CONFIGURATION.
AP
EXISTING CEILING MOUNTED WIRELESS ACCESS POINT, RELOCATED AS NOTED ON DRAWINGS. PROVIDE WAP, CABLE, AND BOX WITH CONDUIT TO CABLE TRAY.
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL CONTRACTOR
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY CONTRACTOR
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
CUSTOM FURNITURE OUTLET IN SURFACE RACEWAY. PROVIDE SURFACE RACEWAY, OUTLET JACKS, FACEPLATE, AND
CABLING.
N
N
N B
N Z
NC
NS
ND
N
W
NM
N T
N E
N B
NCCP
C
NS
P
NS
NURSE CALL SYMBOLS
NURSE CALL DESK MOUNTED MASTER CONTROL STATION (OUTLET AT 18" MH UNLESS NOTED OTHERWISE). SUBSCRIPT
"W" INDICATES WALL MOUNT (46" MH UNLESS NOTED OTHERWISE).
NURSE CALL CONTROL PANEL.
NURSE CALL STAFF STATION (46" MH UNLESS NOTED OTHERWISE).
NURSE CALL DUTY STATION (46" MH UNLESS NOTED OTHERWISE).
EMERGENCY NURSE CALL STATION WITH PULL CORD FOR PATIENT USE (46” MH AND TO SIDE AND WITHIN 12” FROM FRONT OF TOILET BOWL IN TOILET ROOMS, 66” MH IN SHOWERS AND WET AREAS, 46” MH UNLESS NOTED OTHERWISE IN
ALL OTHER AREAS).
PATIENT NURSE CALL UTILITY CONSOLE (46" MH UNLESS NOTED OTHERWISE).
PATIENT NURSE CALL STATION (ONE OR TWO CORDS AS INDICATED, 46" MH UNLESS…
This is the start of the file's text. The full file is on GovTribe.