Attachment V -2025-10-17 MICU Bid Drawings2 10-17-2025.pdf

PDF 23 MB Posted

Attached to
Z2DA--Renovate MICU/SICU 539-20-104
Solicitation number
36C25026B0001_1
Issued by

About this file

This document is a set of mechanical, electrical, and construction design drawings for a renovation project at a U.S. Department of Veterans Affairs (VA) facility located in Cincinnati, Ohio. The project involves a comprehensive upgrade of the medical gas systems, HVAC infrastructure, ductwork, piping, electrical systems, and lighting across multiple floors (first, second, third, and roof) of a healthcare facility.

The design documents, prepared by Heapy Engineering and JPA Architecture, include detailed plans for medical gas distribution, sanitary waste and vent systems, emergency exhaust systems, air terminal units, and various mechanical equipment. The project focuses on modernizing the facility's infrastructure, with specific attention to negative pressure patient rooms, medical gas zone valve cabinets, and critical room control sequences. The drawings are dated 10/17/2025 and are marked as "100% Construction Documents" for a fully sprinklered facility, with the project number 2019-05193 and state COA firm number 01528.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Accessory Not Included. Sold SeparatelyAccessory Not Included. Sold Separately

E ABCD

X

W

T.4

T.2

V.6

T.1

Q.2

12.1 17.3

EXISTING MEDICAL GAS

UP TO THIRD FLOOR

2 2

0.75" 0.5"

0.5"

0.75" 0.5"

0.5"

0.75"

0.5" 0.5"

0.5" 1.5" 0.5"

0.5"

1"

0.5" 0.5"

0.75"

0.75"

0.5" 0.5"

0.5" 0.75"

0.5"

MV

O2

MA

M V O

M

A

O

M V

M A

O2 MV

MA

MV

O2

M A

MV

O2 MA

O

M V

M A

0.75" 0.75"

1.5"

A271

Female

Locker Room

AAP

1" 2" 1"

1" 2" 1"

1" 1" 2"

M V

O

M A

O

M V

M A

M A

M V

O

ZVC

O

M A

M V

0.75" 0.75" 1.5"

A292B

Soiled

Utility

C226B Passageway

A270A Staff Toilet

A269

Staff

Lounge

A271A

Staff

Bathroom

A272

Conference

Room

A273 Office

A275 Electrical

A274

HAC

A276 On-Call

A276A Bathroom

A268 Office

A267

RN

Manager

A293

Pharmacy

Office

A286A Toilet

A287A Toilet

A283

Negative

Pressure

Bariatric Patient

Room

A288A Toilet

A289 Grief/Consult

A285

Patient

Room

A278

Patient

Room

A279

Patient

Room

A280

Negative

Pressure

Patient Room

A281

Equipment

Storage

A282

Negative

Pressure

Bariatric Patient

Room

A283A Toilet

A284

Negative

Pressure

Patient Room

A277 Clean Linen

A290

HUC

Station

C226I

Patient

Circulation

A284B Ante Room

Elevator

A270

Male

Locker Room

A271

Female

Locker Room

AREA OF WORK

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:4

:4

A

M

Renovate MICU/SICU

10/17/2025

PARTIAL SECOND FLOOR PLAN -

MEDICAL GAS

PG102

SVHKMB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

N Scale:Scale: 1/8" = 1'-0"1/8" = 1'-0"

PARTIAL SECOND FLOOR PLAN - MEDICAL GAS

1. EXISTING TO REMAIN.

2. EXTEND MEDICAL GAS PIPING DOWN IN WALL AND CONNECT TO PATIENT

HEADWALL.

3. NEGATIVELY PRESSURIZED SPACE. SEAL ALL PENETRATIONS IN WALL AND/OR

CEILING AIRTIGHT.

A. REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS.

B. MAINTAIN AND RESTORE, IF INTERRUPTED, DOMESTIC WATER SUPPLY, MEDICAL

GAS & VACUUM SYSTEMS AND SANITARY & VENT SYSTEMS TO EXISTING

FIXTURES LOCATED IN AN UNDISTURBED AREA.

C. IN THE RENOVATION AREA, CORRECT ANY DOMESTIC WATER, MEDICAL GAS,

SANITARY & VENT PIPE LABELING ON EXISTING PIPING THAT IS MISLABELED/

MISSING LABELS AND/ OR FLOW ARROWS.

D. REFER TO SPECIFICATIONS 22 05 11 SECTION 1.3.B. ASME A13.1 SCHEME

FOR THE IDENTIFICATION OF PIPING SYSTEMS.

E. ALL SANITARY DRAIN, STORM AND DISTRIBUTION PIPING RUN OVER HVAC, BSE,

OR MEDICAL EQUIPMENT SHALL HAVE SPILL/ LEAK PROTECTION AND LEAK

DETECTING SENSORS.

F COORDINATE ALL EXISTING PIPING AND NEW PIPING WITH NEW MEPT SYSTEMS

AND EQUIPMENT AND PATIENT LIFT SUPPORTS, RAILS, AND EQUIPMENT.

GENERAL NOTES

PLAN NOTES

KEYPLAN

A. REFER TO THE ARCHITECTURAL DOCUMENTS FOR A SEQUENCE OF

CONSTRUCTION PLAN, WHICH INCLUDES DETAILED NOTES REGARDING PROJECT

PHASING. ALL WORK SHALL BE COORDINATED AND SCHEDULED WITH THIS

CONSTRUCTION SEQUENCE. ALL REQUIRED SHUTDOWNS SHALL BE IDENTIFIED

AT THE START OF CONSTRUCTION AND SHALL BE COORDINATED AND

SCHEDULED WITH THE VA.

PHASING NOTE

Revisions Date

MEDICAL GAS OR VACUUM

PIPING TO/FROM STATION

INLETS AND OUTLETS

SYSTEM AND SERVICE

AREA LABEL, TYPICAL

MEDICAL GAS OR VACUUM

PIPING TO/FROM

DISTRIBUTION SYSTEM

PRESSURE GAUGE/

VACUUM GAUGE, TYPICAL

NOTE:

1 REFER TO FLOOR PLANS FOR REQUIRED NUMBER OF

VALVES, VALVE SERVICES AND SIZES AT EACH

INDIVIDUAL LOCATION.

MIN. 45 DEGREES

BRANCH OR RUNOUT

TO STATION OUTLET,

INLET OR SPECIAL STATION

MAIN OR BRANCH PIPING

TRAP PRIMER, WITH DISTRIBUTION

UNIT WHEN SERVING MULTIPLE

DRAINS. LOCATE ABOVE CEILING

IN FINISHED AREAS.

0.5''SUPPLY SHALL BE

OFF TOP OF MAIN

COLD WATER MAIN

T P

T P

WALL

FINISHED CEILING

WHERE APPLICABLE

FLOOR DRAINS

FLOOR

TP

PIPING TO FLOOR DRAINS

SHALL BE RUN BELOW FLOOR,

UNLESS NOTED OTHERWISE.

INSTALL PIPING CONCEALED

IN WALL IN FINISHED AREAS.

INSTALL PIPING TIGHT TO WALL

SURFACE IN UNFINISHED AREAS.

UNION

BALL VALVE (SEE SPECS)

CHECK VALVE (SEE SPECS)FLOW CONTROLLER (SEE SPECS)

UNION

BALL VALVE (SEE SPECS)

FINISHED FLOOR8x8 STAINLESS STEEL

ACCESS PANEL

2"

WATER DAM

/2

/4

1' -4

4"

14 1/2"

MALE HOSE THREAD FOR

DIALYSIS CONNECTION

1/2" COPPER PIPE FOR DCW

TRAP PRIMER

2" DRAIN CONNECTION

REDUCED PRESSURE

BACKFLOW PREVENTER

STAINLESS STEEL BOX

WITH SIDE HINGED

COVER AND LATCH.

16 1/2"

/2

FLUSH VALVE

CL

STOP2.

5"

.5

T O

R

IM

FINISHED FLOOR

4" ELECTRICAL BOX -

REFER TO DIVISION 26

DRAWINGS.

PROVIDE COVERPLATE.

GRAB BAR. REFER TO

ARCHITECTURAL DETAILS

FOR ADDITIONAL

INFORMATION.

PROVIDE HARDWIRED WALL

MOUNTED OPERATOR

WITH MANUAL OVERRIDE

FLUSH BUTTON.

0.75" CONDUIT - REFER TO

DIVISION 26 DRAWINGS.

PROVIDE LOW VOLTAGE

WIRING.

FAUCET, REFER

TO SPECIFICATIONS

NON-AERATED FLOW

CONTROL DEVICE

8"

ASSE 1070

THERMOSTATIC

MIXING VALVE

OFFSET WASTE

8"

TRAP PARALLEL

TO WALL

PROVIDE LAV SHIELD

ENCLOSURE.

LOOSE KEY / STOP

ESCUTCHEON

FINISHED FLOOR6"

FAUCET, REFER

TO SPECIFICATIONS

NON-AERATED FLOW

CONTROL DEVICE

COUNTERTOP

OFFSET WASTE

TRAP PARALLEL

TO WALL

FINISHED FLOOR

ENCLOSURE -

REFER TO

GENERAL

TRADES

DRAWINGS.

ESCUTCHEON

LOOSE KEY

/STOP

8"

/4

ASSE 1070

THERMOSTATIC

MIXING VALVE

CONCRETE FILL

TILE FLOOR

CEMENT BED

LOOSE GRAVEL AT

WEEP HOLES 3mm TO 6mm SIZE

NICKEL BRONZE

ADJUSTABLE STRAINER

(FLUSH WITH FINISHED

FLOOR)

CLAMP WATERPROOF

MEMBRANE INSIDE OF

DRAIN BODY

WATERPROOF

MEMBRANE

STRUCTURAL SLAB

FLASHING CLAMP WITH

WEEP HOLES

THREADED, CAULKED

OR NO-HUB

CONNECTION

PROVIDE A METAL SUPPORT

PLATE WHEN DRAIN IS

INSTALLED IN AN EXISTING

FLOOR - CAULK AROUND DRAIN

PRIOR TO RE-GROUTING

NOTE:

SLOPE MEMBRANE LINER 2% TO DRAIN.

DETAIL NOTES

1. CONTROL VALVE. T/P TYPE.

2. BACKING REQUIRED FOR SUPPORT OF ALL SHOWER ACCESSORIES.

3. GRAB BARS. REFER TO ARCHITECTURAL DRAWINGS FOR

ADDITIONAL INFORMATION.

4. HAND SHOWER IN MOUNTED POSITION.

5. HAND SHOWER IN HANGING (DRAINING) POSITION.

6. 60" RUBBER LINED CRS, CHROME PLATED METAL FLEXIBLE

OR WHITE VINYL REINFORCED HOSE.

7. 24" SLIDE BAR & SWIVEL HANGER.

8. VACUUM BREAKER

72"

44"

2" MIN.

75" MIN.

7 1/2"

12"

C L C L

C L

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:4

:2

A

M

Renovate MICU/SICU

10/17/2025

SCHEDULES & DETAILS

P601

SVHKMB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

FIXTURE SCHEDULE

SYMBOL

MOUNTING

HEIGHT DESCRIPTION

FLOW FIXTURE UNITS SUPPLY WASTE & VENT

REMARKSGPM GPF DRAINS

WATER

COLD HOT TEPID OUTLET VENT DIRECT INDIRECTCOLD HOT

P101 17" TO RIM WATER CLOSET/ FLOOR SET/ WALL OUTLET/ ELONGATED

BOWL/ ADA

- 1.6 4 10 0 1" 4" 2" ● HARD-WIRED/ SENSOR OPERATED FLUSH VALVE/ MANUAL

OVERRIDE

P418 34" TO RIM LAVATORY/ WALL HUNG/ 20" x 18"/ ADA 0.5 - 1 0.7 0.7 0.5" 0.5" 1.25" 1.5" ● HARD-WIRED/ SENSOR OPERATED/ GOOSENECK SPOUT/

LAV SHIELD/ T'STATIC MIXING VALVE

P419 C'TOP SOLID

SURFACE

LAVATORY/ C'TOP/ PATIENT ROOM 0.5 - 2 1 1 0.5" 0.5" 1.25" 1.5" ● HARD-WIRED/ SENSOR OPERATED/ GOOSENECK SPOUT/

T'STATIC MIXING VALVE

P502 FLOOR SET MOP BASIN/ 28" x 28" x 12"/ 6" DROP FRONT/ TERRAZO - - 3 2.25 2.25 0.5" 0.5" 1.5" 1.5" ● PAIL HOOK FAUCET/ VACUUM BREAKERS/ CROSS

HANDLES/ INTEGRAL CHECKSTOPS

P505 30" TO RIM CLINIC SERVICE SINK/ WALL HUNG/ FLUSH VALVE/ BED PAN

WASHER

- - 6 10 4 1.5" 1.5" 3" 1.5" ● ELBOW BLADE HANDLES/ BEDPAN WASHER/ RIM GUARD

P528 C'TOP SINK/ SST/ SINGLE COMP'T/ 21" x 22" 1.5 - 2 3 3 0.5" 0.5" 1.5" 1.5" ● WRISTBLADE HANDLES/ GOOSENECK SPOUT/ T'STATIC

MIXING VALVE

P701 SHOWER HEAD & VALVE 2.0 - 0 0 0 0.5" 0.5" PRESSURE AND THERMOSTATIC BALANCING VALVE/

VACUUM BREAKER/ HAND HELD HOSE WITH 3-PORT VALVE

P809 - DIALYSIS SUPPLY AND DRAIN BOX - - 2 1 1 0.5" 0" 2" 1.5" -

FIXTURE SCHEDULE NOTES:

1 SUPPLY SIZES IN THIS SCHEDULE ARE FIXTURE CONNECTION SIZES. DOMESTIC COLD WATER SUPPLY SIZES SERVING FLUSH VALVES SHALL BE MINIMUM ONE PIPE SIZE LARGER THAN THE INDICATED CONNECTION SIZE, OR SIZED AS

SHOWN ON THE FLOOR PLANS. PIPING AT FLUSH VALVE CONNECTION OF A SIZE EQUAL TO THE CONNECTION SIZE, SHALL BE LIMITED TO A MAXIMUM OF 2 FEET IN DEVELOPED LENGTH AND INCLUDE A MAXIMUM OF ONE 90 DEGREE ELBOW FITTING. FULL SIZE MANIFOLDS, WHERE INDICATED ON THE FLOOR PLANS, SHALL BE PROVIDED FULL SIZE THE LENGTH OF THE PIPING CHASE AND TERMINATED WITH A FULL SIZE CAP.

2 PROVIDE NON-AERATED FLOW CONTROL DEVICE ON LAVATORY AND SINK FAUCETS. DO NOT USE AERATORS.

3 PROVIDE CHECK VALVE ON SUPPLIES SERVING LAVATORIES AND SINKS.

SCALE: NONE

MEDICAL GAS ZONE VALVE CABINET

A

SCALE: NONE

BRANCH TAKE-OFF PIPING - MEDICAL GAS

B

DRAIN SCHEDULE

SYMBOL DESCRIPTION

BODY STRAINER / GRATE TOP FINISH

C.I. S.S. C.R. BRASS RD. SQ. ADJUST. FLAT RECESS DOME

NICKLE

BRONZE C.I. C.R. S.S.

FD1 3" LIGHT DUTY/ DOUBLE DRAINAGE/ VANDAL RESISTANT/ TYPE C/ TRAP PRIMER CONNECTION ● ● ● ●

SCALE: NONE

TRAP PRIMER

C

SCALE: NONE

FLOW CONTROLLER ASSEMBLY

D

SCALE: NONE

P-809 DIALYSIS BOX DETAIL

H

SCALE: NONE

P-101 WATER CLOSET

E

SCALE: NONE

P-418 LAVATORY

F

SCALE: NONE

P-419 LAVATORY

G

DRAIN SCHEDULE NOTES:

1 PROVIDE THREADED PLUG FOR ALL TRAP PRIMER CONNECTIONS NOT USED.

SCALE: NONE

FD1 - TYPE "C" FLOOR DRAIN

I

SCALE: NONE

P-701 SHOWER

J

3" - SAN

4" -

SAN4" -

SAN

4" -

SAN

4" -

SAN

4" -

SAN

1.

5"

S

A N

2"

SAN

4" - SAN

1.5"

4" - SAN

1.5" - S A

N

1.5" -

SAN

4" - SAN

1.5"

1.5" - SAN

4" -

SAN

1.5" - SAN

4" -

SAN

4" -

SAN

4" -

SAN

4"

2" -

SAN

2" - SAN

2" - SAN

4"

2" -

SAN

4"

1.5" - SAN

2" - SAN

4" -

SAN

3"

2"

4"

2"

1.5"

4"

2"

4"

2" 2"

4"

2"

2"

1.

5"

1.5"

3"

1.5"

2"

3"

1.5"

1.5"

3"

3"

1.5"

1.5"

1.5"

2"

2"

2"

1.5"

2"

1.5"

1.5"

1.5"

2"

2"

1.5"

1.5"

1.5"

P101

P101

P101

P101

P101

P101

P101

P418

P418

P419

P419

P419

P419

P419

P419

P419

P419P419

P419

P528

P101

P419

P419

P419

P419

P419

P419

P419

P419

P419

P419

P505

P418

P809

P809

P809

P809 P809

P101

P809P809

P418

P809

P809

P809

2"

SAN

2"

4"

4"

2" 2"

1.

5"

2"

2"

1.

5"

1.5"

1.

5"

2"

2"

1.

5"

1.

5"

1.

5"

1.

5"

1.

5"

2"

2"

2"

2"

1.

5"

4" -

SAN

1.

5"

2"

2"

2"

A278A

A278

A279A

A279

A280A

A280

A280B

A282A

A282B

A282

A283B

A283

A283A

A284A

A284

A284B

A285

A285A

A286

A286A

A287A

A288

A291

A292B

SAN

CRV

CO

4"

3" -

SAN

4" - SAN

1.5" - SAN

2" - V

4" - SAN

2" -

SAN

4"

S A

N

4" -

SAN

3" - V

2"

3"

1.

5"

3"

1.

5"

2" 4"

3"

1.

5"

2"

3" 3"

2"

2"

2"

2"

1.

5"

1.

5"

2" 4"

1.5"

2"

4"

2"

1.5"

1.

5"

2"

2"

2"

4"

4"

4"

2"

2"

1.5"

4"

4"

1.

5"

3"

1.5"

2"

2"

2" 2"

CO

CO

2" 2"

1.5"

1.5"

2"

2ND FLR

2"

2"

2"

2"

1.5"

2"

2ND FLR

2"

2"

2"

2"

2"

2"

2"

2"

1.5"

2"

1.5"

1.5"

1.5"

1.5"

CRP

CRP

C R

P

CRP

CRP

CRP

CRP

3RD FLR

1.5"

CRV

3RD FLR

2ND FLR

2ND FLR

1ST FLR

2ND FLR

3RD FLR

3RD FLR

3RD FLR

3RD FLR

3RD FLR

3RD FLR

2ND FLR

3RD FLR

3RD FLR

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:4

:2

A

M

Renovate MICU/SICU

10/17/2025

SANITARY WASTE AND VENT

DIAGRAM

P901

SVHKMB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

SANITARY WASTE AND VENT DIAGRAM

NOTE: ALL SYMBOLS AND ABBREVIATIONS

ARE SUBJECT TO MODIFICATIONS

ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS

MIGHT NOT NECESSARILY BE USED ON

THIS PROJECT.

ABBREVIATIONS

AC - AIR COMPRESSOR OR AIR CONDITIONER

ACCU - AIR COOLED CONDENSING UNIT

AD - ACCESS DOOR OR AREA DRAIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AFMS - AIR FLOW MEASURING STATION

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATC - AUTOMATIC TEMPERATURE CONTROL

(SYNONYMOUS WITH BAS)

BAS - BUILDING AUTOMATION SYSTEM

BDD - BACK DRAFT DAMPER

BFP - BACKFLOW PREVENTER

BLDG - BUILDING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BR - BOTTOM REGISTER

BTU - BRITISH THERMAL UNIT

BTUH - BRITISH THERMAL UNIT PER HOUR

CBD - COUNTER BALANCED BACKDRAFT DAMPER

CD - CEILING DIFFUSER

CFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CFM - CUBIC FEET PER MINUTE

CG - CEILING GRILLE

CHS - CHILLED WATER SUPPLY

CHR - CHILLED WATER RETURN

CHGR - CHILLED WATER GLYCOL SOLUTION RETURN

CHGS - CHILLED WATER GLYCOL SOLUTION SUPPLY

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CO - CLEAN OUT

CO2 - CARBON DIOXIDE

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CR - CEILING REGISTER

CTR - CENTER

CU - COPPER

CW - COLD WATER

CWR - CONDENSER WATER RETURN

CWS - CONDENSER WATER SUPPLY

D - DRAIN LINE

DB - DRY BULB

DDC - DIRECT DIGITAL CONTROLS

DI - DEIONIZED WATER

DIA - DIAMETER

DIM - DIMENSION

DN - DOWN

DWG - DRAWING

EA - EACH OR EXHAUST AIR

EAT - ENTERING AIR TEMPERATURE

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATOR

EQUIP - EQUIPMENT

ET - EXPANSION TANK

ETR - EXISTING TO REMAIN

EQS - EQUIPMENT SUPPLIER

EWT - ENTERING WATER TEMPERATURE

EXH - EXHAUST

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

FD - FLOOR DRAIN

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FOB - FLAT ON BOTTOM

FOF - FUEL OIL FLOW

FOG - FUEL OIL GAUGE

FOR - FUEL OIL RETURN

FOS - FUEL OIL SUPPLY

FOT - FLAT ON TOP

FPM - FEET PER MINUTE

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

G - GAS OR NATURAL GAS

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GC - GENERAL TRADES CONTRACTOR

GPM - GALLONS PER MINUTE

HB - HOSE BIBB

HC - HVAC (DIVISION 23)

HD - HUB DRAIN

HG - REFRIGERANT HOT GAS

HP - HORSEPOWER

HPC - HIGH PRESSURE CONDENSATE RETURN

HPS - HIGH PRESSURE STEAM SUPPLY

HR - HOUR

HT - HEAT TRACE

HTR - HEATER

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

HW - HOT WATER

HWR - HEATING HOT WATER RETURN

HWS - HEATING HOT WATER SUPPLY

ID - INSIDE DIAMETER

INV - INVERT ELEVATION

IN - INCHES

KEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTH

LAT - LEAVING AIR TEMPERATURE

LAV - LAVATORY

LBS - POUNDS

LPC - LOW PRESSURE CONDENSATE RETURN

LPS - LOW PRESSURE STEAM SUPPLY

LWT - LEAVING WATER TEMPERATURE

MAX - MAXIMUM

MDD - MOTORIZED DAMPER

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

MPC - MEDIUM PRESSURE CONDENSATE

RETURN

MPS - MEDIUM PRESSURE STEAM SUPPLY

MU - WATER MAKE-UP

N/C - NORMALLY CLOSED

NIC - NOT IN CONTRACT

N/O - NORMALLY OPEN

NOM - NOMINAL

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

OA - OUTDOOR AIR

OBD - OPPOSED BLADE DAMPER

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR

INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

P - PROPANE GAS

PC - PLUMBING (DIVISION 22)

OR PUMPED CONDENSATE RETURN

PLBG - PLUMBING

PRESS - PRESSURE

PRV - PRESSURE REGULATING VALVE

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSIG - POUNDS PER SQUARE INCH GAUGE

RA - RETURN AIR

RAD - RADIUS

RCP - REFLECTED CEILING PLAN

RD - ROOF DRAIN

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RL - REFRIGERANT LIQUID

ROS - REVERSE OSMOSIS WATER SUPPLY

ROR - REVERSE OSMOSIS WATER RETURN

RPM - REVOLUTIONS PER MINUTE

RS - REFRIGERANT SUCTION

S - SPRINKLER (WET)

SA - SUPPLY AIR

SAN - SANITARY OR SANITARY DRAIN

SCH - SCHEDULE

SCW - SOFT COLD WATER

SHT - SHEET

SPEC - SPECIFICATIONS

SQ - SQUARE

SR - SUPPLY RISER

SRV - SAFETY RELIEF VALVE

SS - STAINLESS STEEL

STD - STANDARD

STM - STORM OR STORM DRAINAGE

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQUIPMENT

TOF - TOP OF FOOTING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TR - TOP REGISTER

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

V - VENT

VAC - VACUUM

VEL - VELOCITY

VIB - VALVE IN BOX

VOL - VOLUME

VTR - VENT THROUGH ROOF

VR - VENT RISER

W/ - WITH

W/O - WITHOUT

WB - WET BULB

WCO - WALL CLEANOUT

GENERAL FLOOR PLAN NOTES

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN UNLESS

NOTED OTHERWISE.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

A1

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS

REFER TO SCHEDULES.

H1 H1OR EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO

SCHEDULES.

H2

B

H2

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION

H2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

H2 = SHEET WHERE DETAIL IS LOCATED

A1 "UP TO" SYMBOL (ITEM ON FLOOR ABOVE)

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF

EQUIPMENT, UNLESS NOTED OTHERWISE

10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOD: 8' - 10"

BOD: 7' - 2"

20x20

20x20

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF

DUCTWORK, UNLESS NOTED OTHERWISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE,

UNLESS NOTED OTHERWISE

DL-1

UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH

UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE WITH GC.

DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.

CONNECT TO EXISTING

HVAC PIPING DESIGNATIONS

CHILLED WATER SUPPLY PIPECHS

CONDENSER WATER SUPPLY PIPECWS

CONDENSER WATER RETURN PIPECWR

DRAIN LINE. PITCH IN DIRECTION INDICATEDD

HEATING HOT WATER SUPPLY PIPEHWS

HEATING HOT WATER RETURN PIPEHWR

WATER MAKE-UP PIPEMU

VENT PIPEV

REFRIGERANT LIQUID LINERL

REFRIGERANT SUCTION LINERS

EXPANSION TANK PIPEET

REFRIGERANT HOT GAS LINEHG

LOW PRESSURE CONDENSATE RETURN PIPELPC

LOW PRESSURE STEAM SUPPLY PIPELPS

MEDIUM PRESSURE CONDENSATE RETURN PIPEMPC

MEDIUM PRESSURE STEAM SUPPLY PIPEMPS

PUMPED CONDENSATE RETURN PIPEPC

HIGH PRESSURE CONDENSATE RETURN PIPEHPC

HIGH PRESSURE STEAM SUPPLY PIPEHPS

STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.10

MISC SYMBOLS

DUCTWORK SYMBOLS

ROUND BRANCH DUCTWORKCONICAL

FITTING

ACOUSTIC

FITTING

ACOUSTIC

FITTING

ADAD

D

R R

D

RECTANGULAR BRANCH DUCTWORK

SQUARE TEE WITH TURNING VANES

NOTE: ALL SQUARE ELBOWS IN

RECTANGULAR AND ROUND / OVAL

DUCTWORK SHALL BE PROVIDED WITH

TURNING VANES. REFER TO

SPECIFICATIONS FOR ADDITIONAL DETAILS.

EXISTING DUCTWORK TO REMOVED

RETURN AIR, RELIEF AIR, OR TRANSFER AIR

DUCTWORK. (UP AND DOWN) RADIUSED

OR SQUARE WITH TURNING VANES.

SUPPLY AIR OR OUTDOOR AIR DUCTWORK.

(UP AND DOWN) RADIUSED OR SQUARE

WITH TURNING VANES.

EXHAUST AIR DUCTWORK. (UP AND DOWN)

RADIUSED OR SQUARE WITH TURNING

VANES.

RECTANGULAR AND ROUND / OVAL

DUCTWORK RISE / DROP WITH 90° RADIUSED

OR SQUARE ELBOWS AND TURNING VANES.

RADIUS ELBOW

90° SQUARE ELBOW (WITH TURNING VANES)

NOTE: ALL SQUARE ELBOWS IN

RECTANGULAR AND ROUND DUCTWORK

SHALL BE PROVIDED WITH TURNING VANES.

ACCESS DOOR OR PANEL

DUCTWORK RISE IN DIRECTION OF AIR

FLOW

DUCTWORK DROP IN DIRECTION OF AIR

FLOW

DUCTWORK WITH ACOUSTICAL LINER.

LISTED DUCT SIZES ARE INSIDE CLEAR

DIMENSIONS.

RECTANGULAR ROUND / OVAL

FLEXIBLE DUCTWORK

FLEXIBLE CONNECTION

DUCTWORK CONSTRUCTED OF SPECIAL

MATERIAL AS NOTED

DIRECTION OF PITCH

RECTANGULAR DUCTWORK DIMENSIONS

(W x H)26x20

ROUND DUCTWORK DIMENSIONS (DIA)26ø

OVAL DUCTWORK DIMENSIONS (W x H)26x20 OV

DUCTWORK DEVICE SYMBOLS

WALL OR DUCTWORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER

TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION SIZE (IN INCHES).

300 = REQUIRED CFM. 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM

OF GRILLE.

A3 10ø

MANUAL BALANCING DAMPER WITH LOCKING DEVICE

BDD = BACK DRAFT DAMPER

CBD = COUNTER-BALANCED BACK DRAFT DAMPER

SD = SMOKE DAMPER

FS = COMBINATION FIRE - SMOKE DAMPER

MDD = MOTORIZED DAMPER

AFMS = AIR FLOW MEASURING STATION

DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.

HUMIDITY SENSOR - DUCT MOUNTED

SG1

20x12

BOG: 9'-0"

XXX

A-D

XX

H

SD

SP

AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE

SCHEDULE FOR VARIOUS DESIGNATIONS).

10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR DEVICE

DISCHARGE 4-WAY UNLESS NOTED WITH FLOW ARROWS. AIR DEVICE

SHOWN IS 2-WAY SIDE THROW. METHOD OF IDENTIFICATION ALSO APPLIES

TO OTHER CEILING MOUNTED AIR DEVICES.

FIRE DAMPER

A = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)

D OR S = DYNAMIC OR STATIC

STATIC PRESSURE SENSOR - DUCT MOUNTED

C

CARBON DIOXIDE SENSOR - DUCT MOUNTED

S

TEMPERATURE SENSOR - DUCT MOUNTED

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUGE OR THERMOMETER

COMBINATION SHUTOFF AND BALANCING VALVE

(REFER TO SPECIFICATIONS FOR REQUIRED

TYPE BASED ON APPLICATIONS)

BALL VALVE

BUTTERFLY VALVE

GATE VALVE

VALVES AND FITTINGS

DOUBLE LINE SINGLE LINE

10"

TOE: 3' - 0"

BOE: 0' - 6"

CHILLED WATER GLYCOL SOLUTION RETURN PIPECHGR

CHILLED WATER GLYCOL SOLUTION SUPPLY PIPECHGS

CHILLED WATER RETURN PIPECHR

SQUARE THROAT / RADIUS HEEL

FITTINGS NOT ACCEPTABLE

PIPING SYMBOLS

DOUBLE LINE SINGLE LINE

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE:

BULLHEAD TEE'S ARE NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOWN

ELBOW UP

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

DD

RR

PIPE RISER

RADIUS'D BRANCH

RADIUS'D TEE

EXISTING DUCTWORK TO REMAIN

UNLESS NOTED OTHERWISE ON DRAWINGS,

15° MAX FOR DIVERGING, 30° MAX FOR

CONVERGING TRANSITION

EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERWISE.

SPACE TEMPERATURE SENSOR / THERMOSTAT. WHEN WALL MOUNTED, MOUNTING

HEIGHT 46" TO MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH

COORDINATE WITH ARCHITECT.

T

DP

DIFFERENTIAL PRESSURE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO

MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH

ARCHITECT.

H

HUMIDITY SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.

CARBON DIOXIDE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.

C

CO

CARBON MONOXIDE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET

ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH

ARCHITECT.

TEMPERATURE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH

ARCHITECT.

S

S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.

STATIC PRESSURE SENSOR.SP

STRAINER WITH A BLOW DOWN VALVE AND HOSE

CONNECTION

DRAIN VALVE WITH HOSE END CONNECTION

AUTOMATIC FLOW CONTROLLER WITH P/T PLUG IN

AND OUT

EXPANSION JOINT

MANUAL AIR VENT

AUTOMATIC AIR VENT

PRESSURE REDUCING VALVE

2 PORT AUTOMATIC CONTROL VALVE

3 PORT AUTOMATIC CONTROL VALVE

QUICK OPENING MANUAL VALVE

VACUUM BREAKER

NEEDLE VALVE

PRESSURE AND TEMPERATURE TEST PLUG

VACUUM GAUGE WITH STOP

END CAP

GLOBE VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE ON RISER

A

M

M

N

V

VB

SOLENOID VALVE

S

SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS

PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN

UNLESS NOTED OTHERWISE. FOR STEAM

SYSTEMS PIPE DISCHARGE TO OUTDOORS.

WATER METERM

PRESSURE GAUGE WITH COCK AND SIPHON LOOP

BI-METALIC STEAM TRAP AND DRIP ASSEMBLY

THERMODYNAMIC STEAM TRAP AND DRIP

ASSEMBLY

INVERTED BUCKET STEAM TRAP AND DRIP

ASSEMBLY

FLOAT AND THERMOSTATIC STEAM TRAP AND

DRIP ASSEMBLY

THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY

BM

TD

IB

FT

TS

FLOW METER

F

UNION

CLEANOUT

STRAINER

AUTOMATIC PRESSURE INDEPENDENT CONTROL

VALVE

M

32. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL

OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN

ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY ANY DIFFICULTIES WHICH

CAN BE ANTICIPATED.

33. FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND EQUIPMENT SIZES,

SERVICES AND LOCATIONS PRIOR TO PERFORMING WORK.

34. HEPA FILTERED EXHAUST IS REQUIRED TO MAINTAIN A MINIMUM OF 0.01" W.G. NEGATIVE

PRESSURE IN CONSTRUCTION AREAS. COORDINATE WITH THE COR.

35. ALL ABANDONED EXTRANEOUS PIPING, DUCTWORK, SUPPORTS, CONTROLS, ETC. SHALL

BE REMOVED.

36. TERMINATE PIPING AND DUCTWORK BELOW FLOORS, ABOVE CEILINGS, ETC., IN CONCEALED

SPACES. ALL CUTTING AND PATCHING SHALL MATCH EXISTING FINISHES.

37. WHERE CONTROL DEVICES ARE REMOVED, PNEUMATIC LINES SHALL BE REMOVED BACK TO

MAIN AND CAPPED; AND CONTROL WIRING AND CONDUIT SHALL BE REMOVED BACK TO

SOURCE.

38. ALL EXISTING DUCTWORK, PIPING, EQUIPMENT, CONTROLS, ETC. SHOWN ON REMOVAL

PLAN(S) SHALL BE REMOVED. THE MAJORITY OF WORK TO BE REMOVED IS SHOWN. REMOVE

ALL INCIDENTAL AND/ OR ABANDONED DUCTWORK, PIPING, ETC. THAT MAY NOT BE SHOWN

BUT IS ASSOCIATED WITH THE REMOVAL WORK.

39. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING, SERVICING,

MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.. EXAMPLES OF

THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF VALVES, FILTERS AND

STRAINER, TRANSMITTERS, CONTROL DEVICES, ETC.

40. WHERE EXISTING HVAC UTILITIES IN SERVICE WILL BE DISRUPTED DURING THE

CONSTRUCTION OF THIS PROJECT, THIS WORK SHALL BE PERFORMED ON WEEKENDS

OR WEEK NIGHTS. DOWNTIME SHALL BE KEPT TO A MINIMUM, AND SHALL BE COORDINATED

AND SCHEDULED WELL IN ADVANCE WITH THE COR.

41. WHEN NEW SUPPLY AND RETURN AIR DUCTS ARE CONNECTED TO EXISTING DUCTWORK,

CLEAN BOTH NEW AND EXISTING DUCTWORK BY MOPPING AND VACUUM CLEANING INSIDE

AND OUTSIDE BEFORE OPERATION. CLEANING OF EXISTING DUCTWORK SHALL BE LIMITED

TO THE IMMEDIATE AREA WITHIN REACH OF THE OPEN END OF THE DUCT.

42. RUNOUT PIPING TO TERMINAL UNITS SHALL BE 0.75” SIZE UNLESS OTHERWISE NOTED. REFER

TO AIR TERMINAL UNIT SCHEDULE(S).

43. APPROXIMATE ELEVATIONS NOTED ON FLOOR PLANS ARE TO THE BOTTOM OF DUCTS AND

EQUIPMENT, AND TO THE CENTER OF PIPES.

44. REFER TO ELECTRICAL DRAWINGS FOR VARIABLE SPEED MOTOR CONTROLLERS ASSOCIATED

WITH MECHANICAL EQUIPMENT.

45. ALL INSULATED DUCTWORK AND PIPING SHALL HAVE DAMPER/ VALVE HANDLE EXTENSIONS.

46. CONTROL CONTRACTORS RESPONSIBILITIES ARE LISTED IN SPECIFICATION SECTION

23 09 23.

1. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.

2. THE DRAWINGS AND SPECIFICATIONS SHALL BE CAREFULLY STUDIED DURING THE COURSE

OF BIDDING AND CONSTRUCTION. ANY ERRORS, OMISSIONS OR DISCREPANCIES ENCOUNTERED

SHALL BE REFERRED IMMEDIATELY TO THE ARCHITECT/ ENGINEER FOR INTERPRETATION OR

CORRECTION.

3. SITE VISIT(S) SHALL BE AS OUTLINED IN PROJECT SPECIFICATIONS.

4. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL

DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

5. INSULATE DUCTWORK AND PIPING WHERE EXISTING INSULATION HAS BEEN DAMAGED

AND/ OR REMOVED IN THE PERFORMANCE OF WORK IN THIS PROJECT.

6. PROVIDE ALL ROOFING PENETRATION, REPAIR & REINFORCEMENT IN THE EXISTING BUILDING

FOR WORK INDICATED. ENGAGE A ROOFING SUBCONTRACTOR TO PERFORM THE ROOFING

WORK. WHERE ROOFING WORK IS REQUIRED, THE EXISTING ROOFING MEMBRANE AND

INSULATION SHALL BE CUT, REMOVED AND RESTORED AS REQUIRED TO ATTAIN A WATERTIGHT

CONDITION. THE ROOFING SUB-CONTRACTOR SHALL BE A CERTIFIED INSTALLER FOR SUCH

INSTALLATION TO MAINTAIN THE EXISTING WARRANTY ON THE ROOF.

7. REFER TO ALL SPECIFICATION SECTIONS AND THESE DRAWINGS FOR DETAILS OF BUILDING

CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY ARRANGEMENT FOR WORK. THE

VARIOUS DRAWINGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED

JOINTLY AT ALL TIMES. REFER TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE

NOTES AND SYMBOLS INDICATED ON THE DRAWINGS ARE FOR THE GUIDANCE OF ALL

TRADES INVOLVED IN THE PROJECT AND MUST BE FOLLOWED TO EXECUTE THE WORK AS

INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE CONTRACTING OFFICER'S

REPRESENTATIVE (COR) THRU THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE

PROCEEDING.

8. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE

CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR THE CONDITIONS ON

THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE

OF THE WORK. THIS WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING

HOURS. REFER TO SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON RESPONSIBILITIES.

9. ALL WORK MUST BE COORDINATED WITH THE COR TO MAINTAIN OPERATION OF THE

EXISTING FACILITY.

10. COORDINATE ALL WORK WITH THE WORK OF OTHERS. KEEP INFORMED OF THE PROGRESS

AND DETAIL DEVELOPMENT OF THE WORK OF OTHERS. COORDINATE AND EXPEDITE WORK

WITH OTHERS SO THAT THE PROGRESS OF THE TOTAL WORK SHALL BE KEPT ON SCHEDULE.

11. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL GOVERNING CODES

AND STANDARDS.

12. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON VISUAL OBSERVATION AND/ OR

AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN

PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD

VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY DISCREPANCIES

BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DOCUMENTS

WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION

OF THE CONTRACTING OFFICER IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH

THE WORK.

13. FITTING OR PLACING WORK INTO OR ON THE WORK OF OTHERS CONSTITUTES ACCEPTANCE

OF THE SUITABILITY OF THE WORK IN PLACE. IF THE WORK OF OTHERS IS NOT ACCEPTABLE, NOTIFY THE CONTRACTING OFFICERS REPRESENTATIVE (COR) FOR THE WORK TO BE

CORRECTED. ANY NEW WORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS SHALL BE

THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE INSTALLING THE NEW WORK. NO

CLAIMS FOR ADDITIONAL COMPENSATION FOR CORRECTING WORK INSTALLED IN

UNSUITABLE EXISTING CONDITIONS WILL BE CONSIDERED.

14. IF, IN THE PERFORMANCE OF THIS WORK, MATERIALS ARE OBSERVED WHICH ARE

SUSPECTED TO CONTAIN ASBESTOS, THE CONTRACTOR SHALL IMMEDIATELY INFORM THE

COR. WORK THAT WOULD EXPOSE WORKERS TO THE INHALATION

OF ASBESTOS PARTICLES SHALL BE TERMINATED. WORK MAY BE RESUMED ONLY AFTER

A DETERMINATION HAS BEEN MADE AND UNSAFE MATERIALS HAVE BEEN REMOVED OR

ENCAPSULATED AND THE AREA DECLARED SAFE.

15. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND

FIRE-RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS THROUGH

FIRE-RATED ASSEMBLIES SHALL BE PROTECTED AND/ OR FIRE-STOPPED AS REQUIRED TO

MAINTAIN FIRE-RATINGS INDICATED. COORDINATE WITH ALL TRADES TO ENSURE FIRE-RATED

PENETRATION REQUIREMENTS AND DETAILS ARE MET.

16. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT & OTHER SIMILAR PENETRATIONS OF FIRE

RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS THROUGH

0-HOUR RATED WALLS & FLOORS SHALL BE SEALED TO RETARD PASSAGE OF SMOKE.

17. ALL PIPING, DUCTS, CONDUITS, ETC. IN FINISHED ROOMS, CORRIDORS, ETC. SHALL BE

CONCEALED IN A FURRED CHASE OR ABOVE THE SUSPENDED CEILING.

18. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.

DUCT SIZES ARE NET INSIDE DIMENSIONS.

19. PROVIDE DUCT ACCESS PANELS AS REQUIRED BY 23 31 00 FOR ACCESS TO FIRE DAMPERS, SMOKE DAMPERS, SMOKE DETECTORS, AND AUTOMATIC CONTROL DAMPERS. COORDINATE

SIZES AND LOCATIONS WITH ACCESSORIES PROVIDED BY OTHER TRADES.

20. ACCESS PANELS IN NON ACCESSIBLE SUSPENDED CEILINGS SHALL BE PROVIDED FOR ALL

VALVES, TRAPS, DAMPERS, CLEANOUTS, FLOW METERS, CONTROLS, ETC. COORDINATE

SIZES AND LOCATIONS WITH OTHER TRADES.

21. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL

UNITS, FILTERS, COILS, ETC.

22. FOR TYPICAL STEAM, WATER AND REFRIGERANT PIPING CONNECTIONS TO EQUIPMENT,

REFER TO STANDARD DETAILS AND PIPING SCHEMATICS.

23. DIFFUSER SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES. REGISTER AND GRILLE SIZES

SHOWN ARE FACE SIZES.

24. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING

DIFFUSERS, REGISTERS, AND GRILLES.

25. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO

PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

26. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE INSTALLED

WITH BOTTOM OF REGISTERS SEVEN INCHES ABOVE FINISHED FLOOR.

27. WHERE DUCTS OR PIPES ARE REMOVED THRU WALL/ FLOOR/ ROOF THAT IS TO REMAIN,

PATCH WALL/ FLOOR/ ROOF OPENING TO MATCH EXISTING WHERE OPENING IS NOT RE-USED.

28. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERWISE NOTED.

29. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE

CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS WORK TO MATCH EXISTING.

30. IN GENERAL, KEEP DUCT AND PIPING MAINS NEXT TO UNDERSIDE OF STRUCTURE.

31. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED BY THE

VA SHALL BE REMOVED FROM THE PREMISES AND DISPOSED OF PROPERLY BY THE

CONTRACTOR.

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:5

:1

A

M

Renovate MICU/SICU

10/17/2025

ABBREVIATION, LEGEND,

GENERAL NOTES, AND INDEX

M001

AJGBRB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

INDEX OF DRAWINGS - MECHANICAL

SHEET NUMBER SHEET NAME

M001 ABBREVIATION, LEGEND, GENERAL NOTES, AND INDEX

MD101 PARTIAL FIRST FLOOR PLAN - MECHANICAL - REMOVALS

MD102 PARTIAL SECOND FLOOR PLAN - MECHANICAL - REMOVALS

MD103 PARTIAL THIRD FLOOR PLAN - MECHANICAL - REMOVALS

MD104 PARTIAL ROOF PLAN - MECHANICAL - REMOVALS

MH101 PARTIAL FIRST FLOOR PLAN - DUCTWORK - NEW WORK

MH102 PARTIAL SECOND FLOOR PLAN - DUCTWORK - NEW WORK

MH103 PARTIAL THIRD FLOOR PLAN - DUCTWORK - NEW WORK

MH104 PARTIAL ROOF PLAN - DUCTWORK - NEW WORK

MP102 PARTIAL SECOND FLOOR PLAN - PIPING - NEW WORK

M501 DETAILS

M502 DETAILS

M503 DETAILS

M601 SCHEDULES

M602 SCHEDULES

M901 CONTROLS

M902 CONTROLS

HVAC GENERAL NOTES

TT

T

T T

T

T

T

T

T

T

T

T

C116 Waiting

C106

PEA

C116A

PEC

C116B

PEC

C107 Exam

C108 Exam

C116G

PIV

Register

C*1*11 Corridor

C119 Police

C119I Holding

C116C

PEC

36x14

UP36x14UP8x14

UP?

x8

10x8 8x6

8x4

14x8

AREA OF WORK

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:5

:3

A

M

Renovate MICU/SICU

10/17/2025

PARTIAL FIRST FLOOR PLAN -

MECHANICAL - REMOVALS

MD101

AJGBRB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

PLAN NOTES

1. REMOVE DUCT BACK TO THIS POINT FOR RECONNECTION IN NEW WORK.

2. REMOVE EXISTING EXHAUST RISER. PATCH AND REPAIR FLOOR TO MATCH EXISTING.

3. EXHAUST AIR VALVE AND ASSOCIATED CONTROLS INSTALLED UNDER PROJECT

539-20-102.

N Scale:Scale: 1/8" = 1'-0"1/8" = 1'-0"

PARTIAL FIRST FLOOR PLAN - MECHANICAL - REMOVALS

KEYPLAN

GENERAL NOTES

A. WHERE SHOWN AS HEAVY, BOLD DASHED LINES, REMOVE DUCT SYSTEM

COMPLETELY, INCLUDING HANGERS, ATTACHMENTS, AND ASSOCIATED CONTROLS.

B. PHASE ALL DEMOLITION AND NEW WORK FOR THE ISOLATION EXHAUST SYSTEM IN

ORDER TO MINIMIZE THE DOWNTIME OF EXISTING EXHAUST FUNCTIONALITY. NEW

SYSTEM SHALL BE INSTALLED AND OPERATIONAL PRIOR TO REMOVING ANY EXISTING

ISOLATION EXHAUST SYSTEMS.

C. ALL EQUIPMENT IS TO BE TURNED OVER TO VA FOR PROPER REMOVAL FROM

INVENTORY LIST.

PHASING NOTE:

A. REFER TO THE ARCHITECTURAL DOCUMENTS FOR A SEQUENCE OF

CONSTRUCTION PLAN, WHICH INCLUDES DETAILED NOTES REGARDING THE

REQUIRED PROJECT PHASING. ALL WORK SHALL BE COORDINATED AND

SCHEDULED WITH THIS CONSTRUCTION SEQUENCE. ALL REQUIRED SHUTDOWNS

SHALL BE IDENTIFIED AT THE START OF CONSTRUCTION AND SHALL BE

COORDINATED AND SCHEDULED WITH THE VA.

ROOF

UP

42x24 DOWN

FROM AH-5

TO AH-5

72x26

TO AH-4

FD

FD FD FD

12x6

12x6 x8

18x8 18x10 26x8 x1 x612 x1 x8 x1

8x

12x6 x1 x1

24x12

22x10 x1

10x8

10x8 x8

18x1030x7 x1 x1

8x

14x8

8ø

14x8

12x8

12x8

16x812x8

42x12

56x12

36x14

42x14

16x10

12x8

8x6

12x6 x8

10x4

10x6 x8

8x6 x8 ø x8 x6

6x

12x10

8ø

36x18 x8 x8

10x6 x4

6ø x4

7ø x6

12x10 x8

6ø

56x14 x2

6ø

12x12

8ø

8ø

8ø

8x ø

12x6

12x6

8ø x1

0 12x6

12x10

8ø x8

20x8

8x x4 x6

8x20 x2

12x6

12ø

8x4 x1

8x

14x10 x8 x812x6 x8

10ø

16x15

12x10

6ø

6ø

6ø

6ø 8ø

6x

10x6

10x6

6ø

6ø

6ø

6ø

8ø

8x

6x8

8ø

8ø

6ø

6ø

10x6 8ø

6ø

6ø

6ø

8x4

10ø

6ø

12x6

12x6 6ø

8ø

8ø 8ø

8ø

8ø

6ø

6ø

12ø4ø

8ø

8ø 8ø 8ø

8ø 8ø x8

6ø

8x8

12ø x1

10x4

8ø

8ø

6ø

12ø

9ø

8ø

8ø

8ø

8ø

8ø

8ø

6ø

TYP.

TYP.

TYP.

TYP.

UP10x10

1.5" -

1.5" -

1.25" - 1.25" -

1" -

1" -

0.75" -

0.75" -

3" - HWR

3" - HWS

6"

C H

S 6"

C

H R

6" - CHR

6" - CHS

3" - HWR

3" - HWS

4" -

4" -

0.75" - HWS

0.75" - HWR

1" - 1" -

3" - HWS

3" - HWR

4" - CHS

4" - CHR

3" - LPS

3" - LPC

UP20x8

UP8x14

UP36x14

UP36x14

VAV-

5-11VAV-

5-8

VAV-

5-12

VAV-5-7

VAV-

5-13

VAV-

5-15

VAV-

5-17

UP16x8

UP16x8

VAV-5-18

VAV-5-20

VAV-5-19

VAV-5-21

VAV-

5-22

VAV-

5-23

VAV-

5-25

VAV-

5-24

UP16x8

UP26x8

VAV-5-26

VAV

5-26

VAV-

5-16

VAV-5-1

HWS

HWR

UP14x8

UP14x8

ACU-250

RS/RL

UP

0.

5"

R

L

0.75" HWS

0.75" HWR

0.5" - RL

0.5" - RS

60x16

72x22 UP TO AH-4 60x16 UP TO AH-4

10BID ITEM #2

DN6x18

UP18x6

13 13

13 13

13 13

13 13

VAV

5-2

VAV

5-6

VAV

5-5

VAV-5-10

VAV-5-9

VAV-5-4

VAV

5-3

VAV

5-14

1 1

1 1

AREA OF WORK

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:5

:3

A

M

Renovate MICU/SICU

10/17/2025

PARTIAL SECOND FLOOR PLAN -

MECHANICAL - REMOVALS

MD102

AJGBRB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

N Scale:Scale: 1/8" = 1'-0"1/8" = 1'-0"

PARTIAL SECOND FLOOR PLAN - MECHANICAL - REMOVALS

PLAN NOTES

1. REMOVE DUCTWORK AS INDICATED. PATCH AND SEAL EXISTING TO REMAIN

AIRTIGHT. PATCH INSULATION TO MATCH EXISTNIG.

2. REMOVE DUCT BACK TO THIS POINT FOR RECONNECTION IN NEW WORK.

3. REMOVE EXISTING EXHAUST RISER FOR REPLACEMENT IN NEW WORK.

4. REMOVE EXISTING DUCT RISERS THEN PATCH FLOOR TO MATCH EXISTING.

5. REMOVE VAV BOX AND ALL ASSOCIATED THERMOSTAT AND CONTROLS. REMOVE

ATTACHED HWS/R PIPING BACK TO MAIN AND CAP AND INSULATE.

6. REMOVE HWS/R BACK TO THIS POINT. CAP AND INSULATE WATERTIGHT.

7. REMOVE DUCT BACK TO THIS POINT. CAP AND SEAL AIRTIGHT.

8. REMOVE GRILLE AND DUCT AS INDICATED. MAINTAIN EXISTING FOR RECONNECTION

IN NEW WORK.

9. REMOVE SECTION OF VRF PIPING. MAINTAIN EXISTING FOR RECONNECTION IN NEW

WORK. PROVIDE BALL VALVES AND BRING REMAINDER OF VRF SYSTEM BACK

ONLINE. VRF SYSTEM (MINUS CASSETTE IN THIS PROJECT SCOPE) SHALL REMAIN IN

OPERATION DURING CONSTRUCTION. VERIFY EXTENT OF DEMOLITION AND

COORDINATE REQUIREMENTS WITH TRANE (VRF SYSTEM MANUFACTURER) PRIOR TO

PERFORMING ANY WORK.

10. BID ITEM #2 - SCOPE OF WORK IN THIS AREA INVOLVES DEMOLITION AND NEW WORK

FOR ALL BRANCH DUCTWORK, AIR CONTROL TERMINALS, HYDRONIC PIPING, AIR

DISTRIBUTION DEVICES, AND CONTROLS. DELETE ALL LABOR AND MATERIALS

ASSOCIATED WITH THE CONSTRUCTION, ALTERATION, PLUMBING, MECHANICAL AND

ELECTRICAL MODIFICATIONS TO THE OFFICE/CONFERENCE/BREAK ROOM WITHIN

THE DASHED LINE. AIR DUCT AND PIPING MAINS REVISIONS ARE PART OF BASE BID.

11. REMOVE EXISITNG AIR CONTROL VALVE AND ALL ASSOCIATED DUCTWORK,

CONTROLS, SUPPORTS, AND ROOM PRESSURE MONITORS THAT ARE INSTALLED

UNDER PROJECT 539-20-102.

12. DUCT INSTALLED UNDER PROJECT 539-20-102.

13. REMOVE EXISTING AIR DEVICE AND ALL ASSOCIATED ACCESSORIES, SUPPORTS, AND

DUCT CONNECTIONS AS INDICATED.

KEYPLAN

GENERAL NOTES

A. WHERE SHOWN AS HEAVY, BOLD DASHED LINES, REMOVE DUCT SYSTEM

COMPLETELY, INCLUDING HANGERS, ATTACHMENTS, AND ASSOCIATED CONTROLS.

B. PHASE ALL DEMOLITION AND NEW WORK FOR THE ISOLATION EXHAUST SYSTEM IN

ORDER TO MINIMIZE THE DOWNTIME OF EXISTING EXHAUST FUNCTIONALITY. NEW

SYSTEM SHALL BE INSTALLED AND OPERATIONAL PRIOR TO REMOVING ANY EXISTING

ISOLATION EXHAUST SYSTEMS.

C. ALL EQUIPMENT IS TO BE TURNED OVER TO VA FOR PROPER REMOVAL FROM

INVENTORY LIST.

PHASING NOTE:

A. REFER TO THE ARCHITECTURAL DOCUMENTS FOR A SEQUENCE OF

CONSTRUCTION PLAN, WHICH INCLUDES DETAILED NOTES REGARDING THE

REQUIRED PROJECT PHASING. ALL WORK SHALL BE COORDINATED AND

SCHEDULED WITH THIS CONSTRUCTION SEQUENCE. ALL REQUIRED SHUTDOWNS

SHALL BE IDENTIFIED AT THE START OF CONSTRUCTION AND SHALL BE

UP

8x14

16x8 x8

16x8

HAC

A380

Female Locker

A382C

M. Lock.

A382B

Lounge

A382

Tlt.

A382A

Respiratory Therapy

A384

Clean Supply

A397

Pharm.

A386

Sig.

A396

Corridor

C*3*18

Elec.

A395

Soil Utility

A391

Linen Clos.

A389

Tlt.

A388

Equip. Stor.

A392

Nurse Off.

A390

Negative Pressure Patient Room

A387K

Patient Room

A387J

Patient Room

A387I

Shower

A387H

Patient Room

A387G

Patient Room

A387F

Patient Room

A387E

Patient Room

A387D

Patient Room

A387C

Patient Room

A387B

Negative Pressure Patient Room

A387A

Nurse Station

A387

Conference Room

A385

ICU Dir. Off.

C314

Soc. Wrk.

A383

Family Wtng.

C310

Grieve Consult

C313

Lactation

C312

12x12

CR1

?x?

UP?

DN60x16 DN42x24

DN26x72 DN60x20 x1

UP36x14

DN36x14

UP16x16

UP36x16

8x

4x4

8x8

10x8 x1

10x8

8x8

CR1

12x12

CR1

24x24

TO EF

UP8x16

TO EF

TO EF

UP8x16

UP8x16

DN16x8 DN16x8

DN14x8

UP8x14

UP8x14

DN10x10

DN14x14

UP20x8

TO EF

TO EF

TO EF

TO EF

14x8

10x6

DN16x8

DN26x8

TO 1-EF-26

AHU-5 AHU-4

MECHANICAL

VESTIBULE

26x8

8x14 x1

UP14x12

UP19x19

10x10 x1

10x10

AREA OF WORK

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:5

:4

A

M

Renovate MICU/SICU

10/17/2025

PARTIAL THIRD FLOOR PLAN -

MECHANICAL - REMOVALS

MD103

AJGBRB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

PLAN NOTES

N Scale:Scale: 1/8" = 1'-0"1/8" = 1'-0"

PARTIAL THIRD FLOOR PLAN - MECHANICAL - REMOVALS

1. REMOVE EXISTING EXHAUST RISER THRU ROOF. EXISTING ROOF PENETRATION

SHALL BE MODIFIED AND REUSED IN NEW WORK.

2. EXHAUST AIR VALVE AND ASSOCIATED CONTROLS INSTALLED UNDER PROJECT

539-20-102.

3. REMOVE EXISTING DUCTWORK AND ASSOCIATED DAMPERS, SUPPORTS, ETC.

4. REMOVE DUCT RISER AND PATCH ROOF.

5. REMOVE DUCT DROP AND PATCH FLOOR TO MATCH EXISTING RATING.

KEYPLAN

GENERAL NOTES

A. WHERE SHOWN AS HEAVY, BOLD DASHED LINES, REMOVE DUCT SYSTEM

COMPLETELY, INCLUDING HANGERS, ATTACHMENTS, AND ASSOCIATED CONTROLS.

B. PHASE ALL DEMOLITION AND NEW WORK FOR THE ISOLATION EXHAUST SYSTEM IN

ORDER TO MINIMIZE THE DOWNTIME OF EXISTING EXHAUST FUNCTIONALITY. NEW

SYSTEM SHALL BE INSTALLED AND OPERATIONAL PRIOR TO REMOVING ANY EXISTING

ISOLATION EXHAUST SYSTEMS.

C. ALL EQUIPMENT IS TO BE TURNED OVER TO VA FOR PROPER REMOVAL FROM

INVENTORY LIST.

PHASING NOTE:

A. REFER TO THE ARCHITECTURAL DOCUMENTS FOR A SEQUENCE OF

CONSTRUCTION PLAN, WHICH INCLUDES DETAILED NOTES REGARDING THE

REQUIRED PROJECT PHASING. ALL WORK SHALL BE COORDINATED AND

SCHEDULED WITH THIS CONSTRUCTION SEQUENCE. ALL REQUIRED SHUTDOWNS

SHALL BE IDENTIFIED AT THE START OF CONSTRUCTION AND SHALL BE

ACCU-06

14x16

24x24

OPEN TO BELOW

138x38 36x36

1-EF27 DN14x8

DN14x8 DN8x14

DN16x12

DN16x12

DN36x14

24x24

22x36

22x36

24x24

HEPA-1

DN14x8

40x40

104x40

42x38

1-EF-25

DN14x12

EF-1EF-2

1 DN8x16

6 6

24x246

HEPA-2

CU-1

14x12 x1

16x10

16x8

DN6x18

1-EF-26

AREA OF WORK

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:5

:4

A

M

Renovate MICU/SICU

10/17/2025

PARTIAL ROOF PLAN -

MECHANICAL - REMOVALS

MD104

AJGBRB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

N Scale:Scale: 1/8" = 1'-0"1/8" = 1'-0"

PARTIAL ROOF PLAN - MECHANICAL - REMOVALS

PLAN NOTES

1. REMOVE DUCT THROUGH ROOF. MAINTAIN ROOF PENETRATION FOR REUSE.

PROVIDE TEMPORARY WEATHER COVER.

2. ACCU SERVING MULTIPLE VRF FAN-COIL UNITS. EVACUATE REFRIGERANT, AS

REQUIRED, TO PERMIT ADDITION OF ANOTHER FAN-COIL UNIT TO SYSTEM.

3. REMOVE DUCT. PATCH AND REPAIR ROOF DECK, INSULATION, AND ROOFING TO

MATCH EXISTING.

4. EXHAUST FAN AND ALL ASSOCIATED SUPPORTS, CONTROLS, AND ACCESSORIES

INSTALLED UNDER PROJECT 539-20-102.

5. BAG-IN / BAG-OUT HEPA FILTER MODULE AND ALL ASSOCIATED SUPPORTS AND

ACCESSORIES INSTALLED UNDER PROJECT 539-20-102.

6. DUCTWORK INSTALLED UNDER PROJECT 539-20-102.

7. CONDENSING UNIT AND ALL ASSOCIATED SUPPORTS, PIPING, CONTROLS, AND

ACCESSORIES INSTALLED UNDER PROJECT 539-20-102.

8. EXISTING EXHAUST FAN TO REMAIN.

9. REMOVE EXISTISTING EXHAUST FAN FOR RELOCATION IN NEW WORK. REFER TO

SHEETS MD103, MH103, AND MH104 FOR DUCT SYSTEM MODIFICATIONS AND NEW

LOCATION. FILL ROOF PENETRATION AND PATCH ROOF TO MATCH EXISTING.

KEYPLAN

GENERAL NOTES

A. WHERE SHOWN AS HEAVY, BOLD DASHED LINES, REMOVE DUCT SYSTEM

COMPLETELY, INCLUDING HANGERS, ATTACHMENTS, AND ASSOCIATED CONTROLS.

B. PHASE ALL DEMOLITION AND NEW WORK FOR THE ISOLATION EXHAUST SYSTEM IN

ORDER TO MINIMIZE THE DOWNTIME OF EXISTING EXHAUST FUNCTIONALITY. NEW

SYSTEM SHALL BE INSTALLED AND OPERATIONAL PRIOR TO REMOVING ANY EXISTING

ISOLATION EXHAUST SYSTEMS.

C. ALL EQUIPMENT IS TO BE TURNED OVER TO VA FOR PROPER REMOVAL FROM

INVENTORY LIST.

PHASING NOTE:

A. REFER TO THE ARCHITECTURAL DOCUMENTS FOR A SEQUENCE OF

CONSTRUCTION PLAN, WHICH INCLUDES DETAILED NOTES REGARDING THE

REQUIRED PROJECT PHASING. ALL WORK SHALL BE COORDINATED AND

SCHEDULED WITH THIS CONSTRUCTION SEQUENCE. ALL REQUIRED SHUTDOWNS

SHALL BE IDENTIFIED AT THE START OF CONSTRUCTION AND SHALL BE

TT

T

T T

T

T

T

T

T

T

T

T x1

4COORDINATE RELOCATION OF

JUNCTION BOX AND CONDUITS

WITH DIVISION 26.

UP32x16 UP16x6

C116 Waiting

C106

PEA

C116A

PEC

C116B

PEC

C107 Exam

C108 Exam

C116G

PIV

Register

C*1*11 Corridor

C119 Police

C119I Holding

C116C

PEC

14x8

20x10

105 CFM 1 70 CFM 1 70 CFM

1 70 CFM

1 175 CFM

10x8 x8

8x4

8x6

AREA OF WORK

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO. STATE COA FIRM NO.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.jpaarch.com| 937.461.3290

/1 /2

:5

:4

A

M

Renovate MICU/SICU

10/17/2025

PARTIAL FIRST FLOOR PLAN -

DUCTWORK - NEW WORK

MH101

AJGBRB

19018.00

539-20-104

Cincinnati, Ohio

100% CONSTRUCTION

DOCUMENTS

2019-05193 01528

PLAN NOTES

N Scale:Scale: 1/8" = 1'-0"1/8" = 1'-0"

PARTIAL FIRST FLOOR PLAN - DUCTWORK - NEW WORK

1. REBALANCE GRILLE TO INDICATED CFM.

KEYPLAN

GENERAL NOTES

1. LABEL ALL MECHANICAL EQUIPMENT PER SPECIFICATION, INCLUDING EXHAUST FANS,

VALVES, VAV BOXES, AND AIR VALVES. ANY OUTDOOR LABELING SHALL BE

WEATHER- RESISTANT. COORDINATE ALL LABELING WITH THE VA PRIOR TO

ORDERING THE LABELING.

PHASING NOTE:

A. REFER TO THE ARCHITECTURAL DOCUMENTS FOR A SEQUENCE OF

CONSTRUCTION PLAN, WHICH INCLUDES DETAILED NOTES REGARDING THE

REQUIRED PROJECT PHASING. ALL WORK SHALL BE COORDINATED AND

SCHEDULED WITH THIS CONSTRUCTION SEQUENCE. ALL REQUIRED SHUTDOWNS

SHALL BE IDENTIFIED AT THE START OF CONSTRUCTION AND SHALL BE

T TT

T

T

T

T T

T T

T

T

T

T

T

T

T

T

H

T T T

T

H

T H

S P

SP

SP

x1 x1 x8

36x18 x1

12x12

8ø x2 x2 x1

10x6 x1

20x8

14x8

Soiled Utility

A292B

Passageway

C226B

Staff Toilet

A270A A269

Staff

Lounge

Staff Bathroom

A271A

Conference Room

A272

Office

A273

Electrical

A275

HAC

A274

On-Call

A276

Bathroom

A276A

Office

A268

RN Manager

A267

Pharmacy Office

A293

Work Area

A294A

Toilet

A286A

Passageway

C226D

Toilet

A287A

Ante Room

A283B

Nourishment

A291

Corridor

C226

Corridor

C226G

Toilet

A288A

A285

Patient

RoomA286

Negative

Pressure

Patient Room

A287

Patient

Room

A288

Patient

Room

Patient Room

A278

Patient Room

A279

Negative Pressure Patient Room

A280

Equipment Storage

A281

Negative Pressure Bariatric Patient Room

A282

Toilet

A283A

A284

Negative

Pressure

Patient Room

Toilet

A285A

HUC Station

A290

Passageway

C226C

Clean Linen

A277

Ante Room

A280B

Toilet

A282A

A282B Ante Room

Toilet

A280A

Toilet

A279A

Toilet

A278A

Passageway

C226E

Passageway

C226F

Clean Supply

A292

Negative Pressure Bariatric Patient Room

A283

Ante Room

A284B

Toilet

A284A

A250

Comms

Closet

Elevator

2-01

2-05 2-06

2-07

2-11

2-13

2-14

2-17

2-18

2-25

2-21

2-03

2-04

2-122-23

2-22 x8

14x12 x1

12x10 x1

28x16 x8 x1 x8 x8 x8

44x14 40x14 x1

30x12

12x8

12x8

10x10

12x6 x1

12x8 x1 x8 x8

UP18x10 x8

12x8 x8

2-09

2-08

2-20

12x6

UP14x12

UP16x10

12x12

6x10

10ø

CD1

400 CFM

10ø

CD1

400 CFM

8ø

CD1

225 CFM

24x12

200 CFM

CR1

6ø

CD1

125 CFM

8ø

CD1

225 CFM

8ø

CD1

230 CFM

24x12

75 CFM

CR1

24x12

75 CFM

CR1

6ø

CD1

50 CFM

6ø

CD1

100 CFM

6ø

CD1

90 CFM

6ø

CD1

100 CFM

8ø

CD1

175 CFM

8ø

CD1

175 CFM

12x12

75 CFM

CR212x12

75 CFM

CR2

48"L- 8ø

CD3

175 CFM

48"L- 8ø

CD3

175 CFM

8ø

CD1

215 CFM

24x12

135 CFM

CR1

12x8 x4

10x4

48"L- 12ø

ER1

580 CFM

12x12

75 CFM

CR2

8ø

CD2

210 CFM

6ø

CD1

100 CFM

8ø

CD1

125 CFM

6ø

CD1

90 CFM

8ø

CD1

165 CFM

8ø

CD1

175 CFM

12x12

75 CFM

CR2

12x12

75 CFM

CR2

8ø

CD2

210 CFM

12x12

75 CFM

CR2

12x12

135 CFM

CR2

8ø

CD1

185 CFM

8ø

CD2

250 CFM

12x12

75 CFM

CR2

48"L- 10ø

CD7

275 CFM

48"L- 10ø

CD7

275 CFM

24x12

125 CFM

CR26ø

CD2

50 CFM

8ø

CD2

225 CFM 12x12

125 CFM

CR2

48"L- 12ø

ER1

600 CFM

48"L- 12ø

ER1

505 CFM

8ø

CD2

175 CFM

48"L- 10ø

CD4

180 CFM

48"L- 10ø

CD4

225 CFM

12x12

75 CFM

CR2

6ø

CD2

60 CFM

24x12

135 CFM

CR2

24x12

255 CFM

CG1

8ø

CD1

255 CFM

24x12

150 CFM

CR2

6ø

CD2

75 CFM

UP10x10

48"L- 8ø

CD4

210 CFM

RHS-1

EAV-4

EAV-5

EAV-3

EAV-2

EAV-1

RHS-3

UP14x12

RHS-4

RHS-11 RHS-9

RHS-7

RHS-6

RHS-5

RHS-2

2-10

2-15

2-16

16x8

2-24

E

2-02

24x12

125 CFM

CR1

24x12

115 CFM

CR2

6ø

CD2

40 CFM

6ø

CD8

50 CFM

D R

DN32x16

D

R

48"L- 12ø

ER1

575 CFM

D

R UP36x14

8ø

CD1

220 CFM

6ø

CD6

70 CFM

R

10x8

10x6 x1

16x10

12x12

10x14

48"L- 12ø

ER1

650 CFM

C226S

Female

Locker Room x8

24x24

1500 CFM

CG1

48"L- 8ø

CD4

345 CFM

48"L- 10ø

CD5

525 CFM

2-19

DN16x6

48"L- 10ø

CD4

215 CFM

48"L- 8ø

CD3

175 CFM

48"L- 8ø

CD3

190 CFM

48"L- 8ø

CD4

250 CFM

48"L- 8ø

CD3

165 CFM RHS-10

RHS-8

48"L- 8ø

CD4

175 CFM

x8

12x8

B 24.123.117.317.115.913.112.212.111.1

11.1

10.89.26.9

6.5

Q.2

T.1

T.1A

T.2

T.4

T.9

V.6

V.8

V.9

WW.1

W.3

W.7

X

CP

CP

CP

CP

CP

10x6

6ø

CD1

75 CFM

24x12

175 CFM

CR1

x6

10x10

75 CFM

CR2

26x8 EA UP

5UP16x10

6x

2-20

CP6

8 7

ACU-1

6ø

CD8

50 CFM

6ø

CD1

60 CFM

8ø

10x10

UP26x72

TO AH-4

UP42x24

TO AH-5

UP60x20

TO AH-5

14x12

10x6

CP

CP

CP

CP

CP

10x6

6x x1

8x x8

10BID ITEM #2

8x

2-24

13 75 CFM

16x8

16x8

C218

WAITING

C217

TLT.

Male Locker Room

A270

200 CFM

450 CFM

A294B

Gas

Storage x1

225 CFM

65 CFM

1335 CFM

VAV-5-4

VAV

5-3

70 CFM

90 CFM

36x18

6x6

50 CFM

CD9

44x16

10x12

26x16

8ø

EG1

225 CFM

10x10 8ø

EG1

225 CFM

10ø

8ø

EG1

225 CFM

8ø

EG1

225 CFM

8ø

EG1

225 CFM

UP20x8

24x12

220 CFM

CG1

24x12

90 CFM

CG1

10x6

Staff Respite

A271B

6ø

EG2

80 CFM

6ø

CD8

80 CFM

24x12

100 CFM

CG1

24x12

100 CFM

CG1

24x12

215 CFM

CG1

x8

18x8 x1

24x24

455 CFM

CG1

24x12

225 CFM

CG1

8ø

EG1

175 CFM

8x6

8x6

26x8

18x10

24x12

8ø 8x

8x4

9150 CFM

x1

12ø

CD1

415 CFM

12x108x6

14x12 x8

18x8 x1

10x16

46x14

8x8

24x16 32x12

1'-6"x0"-6" 1'-6"x0"-6"1'-6"x0"-6"

1'-6"x0"-6"

2'-0"x1'-0"

1'-6"x0"-6"

4'-0"x0"-6"

4'-0"x0"-6"

1'-6"x0"-6"

1'-6"x0"-6" 2'-6"x1"-0"

6ø

CD2

25 CFM

8x14

6ø

16x10

ABCDE

4a

8a

Da

X-S

W-S

V-S

U-S

T.4-S

T.2-S

Ta-S

9.2-S 10.8-S11-S 12-S12.2-S9-S6.5-S4.2-S

W.7-S

W.5-S

W.3-S

W.1-S

V.9-S

V.8-S

V.6-S

T.9-S

T.1A-S

T.1-S

T -S

Q.2-S

Q -S

P.2-S

6.9-S 11.9-S 13-S 15.9-S 17-S 17.3-S 23-S 24

T.5-S

23.622.2

Original

Original 22.6

22.3 Original

Original

22.13

10.

P-S

Pa.

Oa.

P.

Q.R Original

Ra.

S.

10.6.8.7.

Original

Original

T Original

Original

P-HH

P-II6.4. 5.

BB

CC

AA

A.6A.6

AREA…