Attachment C - Leesburg WPCF_SPI-1_Bid-Ready Drawings_Vol 6 of 7.pdf
PDF 37 MB Posted
- Solicitation number
- IFB-124276
- Issued by
- Loudoun County, Virginia
About this file
This document is a bid-ready electrical power and lighting design drawing set for the Town of Leesburg, Virginia's Water Pollution Control Facility Solids Processing Improvements - Phase 1 project. The drawings, prepared by Hazen and Sawyer engineering firm under Job Number 31111-098, provide comprehensive electrical infrastructure plans for multiple facility components including the Primary Sludge Pumping Stations (Nos. 1 and 2), Thickened Sludge Pumping Station, Gravity Thickeners (A, B, and C), Scum Pits (1 and 2), and the Solids Electrical Building. The design scope encompasses power distribution, lighting layouts, hazardous area classifications per NFPA-820-2024, grounding systems, motor control centers, switchgear, panelboards, and associated electrical schematic diagrams. Electrical equipment includes multiple pumps (primary sludge, scum, thickened sludge, centrifuge feed, digester heating water, and recirculation pumps), grinders, mixers, screens, thickening equipment, unit heaters, exhaust fans, and emergency systems. The drawings indicate forced ventilation systems at six to twelve air changes per hour to downgrade hazardous area classifications from Class I Division 1 or 2 to unclassified in select areas.
The electrical design provides detailed specifications for equipment ratings, conductor sizes, conduit routing, control systems with variable frequency drives (VFDs), and integration with a programmable logic controller (PLC-38). Ground systems utilize #4/0 bare copper wire installed thirty inches minimum below finished grade with exothermic welding at crossing points and bonding to structural steel and motor frames. The project includes dual switchgear units (SWGR-SEB-1-A and SWGR-SEB-1-B) each rated at 2500 kVA with 480V, 3-phase, 4-wire configuration, motor control centers (MCC-SEB-1 and MCC-SEB-2), and panelboards supplied by separate transformers. Fire alarm and lightning protection systems are specified under separate specifications (28 46 20 and 26 41 00 respectively). All drawings were issued for bid set in May 2026 and prepared under IFB No. 500640-FY27-02, with the design reflecting coordination requirements with mechanical systems, instrumentation, and vendor-supplied control panels throughout the facility.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
9A-61-1
9A-60-1
9A-60-2
PRIMARY SLUDGE
PUMP NO. 1
PRIMARY SLUDGE
PUMP NO. 2
PRIMARY SLUDGE
GRINDER NO.2
PRIMARY SLUDGE
GRINDER NO. 1
PRIMARY SCUM PUMP
NO. 1
EX SCUM MIXER NO. 1
9A-62-1
9A-63-1
UH-100-1
UH-100-2
BOND TO EXISTING
GROUND GRID
PUMP ROOM
E100
A_______ E100
A_______
9A-61-2
PG/PSH
9A-61-2
9A-61-2
PG/PSL
9A-61-1
PG/PSH
9A-61-1
SUMP PUMP
9A-64-1
WATER HEATER
WH-100-1
CJB-100-01 PJB-100-01
SF-100-1 CMS
VCP-9A-64-1
SF-100-1
EF-100-1
9A-63-1
EX SCUM MIXER NO. 1
EF-100-1 CMS
9A-63-1 DSW
BOND TO
GROUND TRIAD
DB
E5
DB
C8
CJB-100-01 PJB-100-01
LCS-9A-63-1
SEE DRAWING E021
FOR CONTINUATION
DEMOLTION NOTES:
A.
B.
SEE MECHANICAL DRAWINGS FOR EQUIPMENT BEING
DEMOLISHED AND PROVIDE ELECTRICAL SUPPORT AS
REQUIRED.
REMOVE MOTOR CONTROL CENTERS, POWER
PANELS, LIGHTING PANELS, COMBINATION STARTERS,
DISCONNECT SWITCHES, LOCAL CONTROL PANELS,
LIGHTS, RECEPTACLES, AND ALL WIRING ASSOCIATED
WITH DEMOLISHED EQUIPMENT TO THE POWER
SOURCE, UNLESS OTHERWISE NOTED. REMOVE ALL
ASSOCIATED EXPOSED CONDUITS. TAG ABANDONED
CIRCUIT BREAKERS AS "SPARE".
HAZARDOUS AREAS:
SPACE CLASSIFIED PER NFPA-820-2024
EDITION AS FOLLOWS:
UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):
1. PRIMARY SLUDGE PUMPING STATION NO. 1
TABLE 6.2.2(a), ROW 9, LINE b
THE CLASSIFICATION RATING OF THE PRIMARY
SLUDGE PUMPING STATION NO. 1 IS DOWNGRADED
FROM CLASS I, DIVISION 2 TO UNCLASSIFIED BY
FUNCTION OF FORCED VENTILATION AT SIX AIR
CHANGES PER HOUR. SEE NFPA-820 2024 EDITION,
TABLE 6.2.2(a), ROW 9, LINE b FOR FURTHER
CLARIFICATION.
NOTES:
1.
2.
3.
4.
5.
TRANSITION FROM UNDERGROUND DUCTBANK TO
EXPOSED CONDUIT VIA PJB-100-1 AND CJB-100-1.
ROUTE CONDUITS ALONG THE CONCRETE SLAB OVER
TO THE PUMP ROOM. CORE DRILL AS REQUIRED.
GROUND TRIAD CONDUCTOR SHALL BE #4/0 BARE
COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.
ALL GROUND CONDUCTORS TO EQUIPMENT OR
STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.
EACH DUCT BANK GROUND CONDUCTOR CROSSING
THE GROUND RING SHALL BE EXOTHERMICALLY
WELDED TO THE GROUND RING CONDUCTOR.
ALL MOTOR FRAMES SHALL BE BONDED TO THE
GROUND RING CONDUCTOR.
SEE INSTRUMENTATION DRAWING I100 FOR VENDOR
CONTROL PANELS TO BE INSTALLED FOR PUMP
MONITORING, VCP-9X-6X-X.
INDOOR WET PROCESS AREA
INDOOR DRY PROCESS AREA
INDOOR DRY NON-PROCESS AREA
AREA DESIGNATION LEGEND:
9A-62-1 DSW
9A-60-1 DSW
9A-61-1 DSW UH-100-1 DSW
UH-100-2 DSW
9A-60-2 DSW
9A-61-2 DSW
WH-100-1 DSW
LCS-9A-62-1
LCS-9A-61-2
LCS-9A-60-2
LCS-9A-60-1
LCS-9A-61-1
HCP-100-1
9A-64-1 DSW
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
PS
P1
-E .rv t 5/
/2
9:
:1
AM
E100
E. BODNAR
S. SHUGARS
D. WEBER
PRIMARY SLUDGE PUMPING STATION NO. 1
ELECTRICAL
POWER PLANS
3/8" = 1'-0"
BOTTOM POWER PLAN
3/8" = 1'-0"
TOP POWER PLAN
3/8" = 1'-0" 4'21012"
SECTION
3/8" = 1'-0" E100
A
HS-100-1
1 BID SET 05/2026 JTH
5/15/2026
262 342
LC2
CKT# 9
LC2
CKT# 9
LC2
CKT# 9
XW2
CKT# 9
LW1A
CKT# 9
WPCR/GFCI
CKT# 7
CKT# 7
CKT# 7
CKT# 7
LC2
CKT# 9
CKT# 7
CKT# 7
LC2
CKT# 9
LC2
CKT# 9
LC2A
CKT# 9
LC2A
CKT# 9
NOTES:
1.
2.
3.
4.
5.
MOUNT FIXTURE TYPE "LW##" 6" ABOVE DOOR.
MOUNT FIXTURE TYPE "XW#" 6" ABOVE DOOR.
MOUNT FIXTURE TYPE "LL#" 12'-0" AFF.
MOUNT FIXTURE TYPE "LC##" 12'-0" AFF.
UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED
FROM THE CIRCUIT NOTED IN PANEL LP-SEP-2.
LL1
CKT# 9
LL1
CKT# 9
WPCR/GFCI
CKT# 7
LL1
CKT# 9
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
PS
P1
-E .rv t 5/
/2
9:
:1
AM
E101
E. BODNAR
S. SHUGARS
D. WEBER
PRIMARY SLUDGE PUMPING STATION NO. 1
ELECTRICAL
LIGHTING PLANS
3/8" = 1'-0"
BOTTOM LIGHTING PLAN
3/8" = 1'-0" 4'21012"
3/8" = 1'-0"
TOP LIGHTING PLAN
1 BID SET 05/2026 JTH
263 342
9A-63-1
LE/LT
I-100-000
CJB-100-01
PLC-38
FROM ACP-38
SCUM MIXER
NO. 1
PRIMARY
SCUM PUMP
NO. 1
PRIMARY
SLUDGE
PUMP NO. 1
PRIMARY
SLUDGE
PUMP NO. 2
M
SCUM MIXER
NO. 1
C-100-000
VC
P-
9A -6
2-
LC
S-
9A -6
2-
LC
S-
9A -6
3-
9A-63-1
TSH
M
PRIMARY SCUM
PUMP NO. 1
TE
9A-62-1
PRIMARY SLUDGE
PUMP NO. 1
9A-61-1 9A-61-2
PRIMARY SLUDGE
PUMP NO. 2VC
P- 9A
-6 1-
LC
S-
9A -6
1-
VC
P-
9A -6
1-
LC
S-
9A -6
1-
VCP-9A-60-1
PS
L-
9A -6
1-
PS
L-
9A -6
1-
CJB-100-01
LC
S-
9A -6
0-
TSH
M
9A-60-1
PRIMARY SLUDGE
GRINDER NO. 1
VCP-9A-60-2
CJB-100-01
LC
S-
9A -6
0-
TSH
M
9A-60-2
PRIMARY SLUDGE
GRINDER NO. 2
VCP-9A-64-1
CJB-100-01
9A-64-1
LSH
9A-64-1
LSL M
9A-64-1
SUMP
PUMP
9A-64
LSH
9A-101
FIT
HCP-100-1
C-100-032
C-100-034
PS
H
-9 A-
-1
PS
H
-9 A-
-2
CJB-100-01 CJB-100-01 CJB-100-01
MCC-SEB-2
C-100-001 C-100-002
C-100-006
C-100-007 C-100-008
C-100-003
C-100-009 C-100-010 C-100-011
C-100-012
C-100-004
C-100-017
C-100-014 C-100-015 C-100-016
C-100-019
C-100-023 C-100-027
C-100-020
C-100-024 C-100-028
C-100-021
C-100-022
C-100-025
C-100-026 C-100-030
C-100-031
C-100-029
I-100-002
C-100-033 I-100-003
I-100-001 C-100-013 C-100-018
C-100-035
C-100-036C-100-005
C-100-037
C-100-040
PS
L-
9A -6
2-
VENDOR CABLE
PS
H
-9 A-
-1
TSH
M TE
VENDOR CABLE
TSH
M TE
VENDOR CABLE
C-100-038
C-100-039
NOTES:
1. COORDINATE REQUIREMENTS WITH FINAL
APPROVED VENDOR.
2. COORDINATE WITH MOTOR SCHEMATICS ON
SHEETS E459 TO E462.
NO. DATEISSUED FOR APPROVEDBY
PROJ.ENGR.
CHECKED
DRAWN
DESIGNED
SHEET
DATE:
OF
NUMBER
DRAWING
31111-098
MAY 2026
:1
4A
C
D C
\A C
C D oc s\
H az en a nd S aw ye r\3
-0
_W
PC
F
So lid s Pr oc es si ng
Im p
Ph I\
Pr oj ec t F ile s\
_D es ig n\ El ec \E
2.
dw g
L as tS av eB y:
JW
TH
O M
PS
O
N
J. HISE
IFB NO.
500640-
FY27-02
1 05/2026BID SET JTH
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
H & S JOB
NUMBER
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
E102
PRIMARY SLUDGE PUMPING STATION NO. 1
ELECTRICAL
CONTROL RISER DIAGRAM
XX
D. ATKINSON
J. THOMPSON
D. ATKINSON
264 342
DEMOLITION NOTES:
A.
B.
SEE MECHANICAL DRAWING M150 FOR EQUIPMENT
BEING DEMOLISHED AND PROVIDE ELECTRICAL
SUPPORT AS REQUIRED.
REMOVE MOTOR CONTROL CENTERS, POWER
PANELS, LIGHTING PANELS, COMBINATION STARTERS,
DISCONNECT SWITCHES, LOCAL CONTROL PANELS,
LIGHTS, RECEPTACLES, AND ALL WIRING ASSOCIATED
WITH DEMOLISHED EQUIPMENT TO THE POWER
SOURCE, UNLESS OTHERWISE NOTED. REMOVE ALL
ASSOCIATED EXPOSED CONDUITS. TAG ABANDONED
CIRCUIT BREAKERS AS "SPARE".
9B-61-3
9B-61-4
9B-63-2
EX SCUM MIXER NO. 2
9B-60-3
PRIMARY SLUDGE
GRINDER NO.3
BOND TO EXISTING
GROUND GRID
SF-150-1
EX. PRIMARY SCUM
PUMP NO. 2
EX. PRIMARY SCUM
PUMP NO. 3
E150
A_______ E150
A_______
9B-62-2
9B-62-3
LCS-9B-61-3
LCS-9B-62-2
LCS-9B-60-3
UH-150-2
E150
B_______ E150
B_______
PRIMARY SLUDGE
PUMP NO. 3
PRIMARY SLUDGE
PUMP NO. 4
PUMP ROOM
UH-150-1
WATER HEATER
WH-150-1
HS-150-1
9B-63-2
EX SCUM MIXER NO. 2
EF-150-1 DSW
DB
C6
DB
E7
SEE DRAWING
E021 FOR
CONTINUATION
CJB-150-01
PJB-150-01
EF-150-1
LCS-9B-63-2
9B-63-2 DSW
GROUNDING NOTES:
1.
2.
3.
GROUND TRIAD CONDUCTOR SHALL BE #4/0 BARE
COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.
ALL GROUND CONDUCTORS TO EQUIPMENT OR
STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.
EACH DUCT BANK GROUND CONDUCTOR CROSSING
THE GROUND RING SHALL BE EXOTHERMICALLY
WELDED TO THE GROUND RING CONDUCTOR.
ALL MOTOR FRAMES SHALL BE BONDED TO THE
GROUND RING CONDUCTOR.
INDOOR WET PROCESS AREA
INDOOR DRY PROCESS AREA
INDOOR DRY NON-PROCESS AREA
AREA DESIGNATION LEGEND:
UH-150-1
WH-150-1 DSW
UH-150-2 DSW
9B-61-4 DSW9B-61-3 DSW
9B-60-3 DSW
UH-150-1 DSW
9B-64-2 DSW
9B-62-3 DSW
9B-62-2 DSW
LCS-9B-60-3
LCS-9B-62-2 LCS-9B-61-3
LCS 9B-61-4
LCS-9B-62-3
LCS-9B-60-4
HAZARDOUS AREAS:
SPACE CLASSIFIED PER NFPA-820-2024
EDITION AS FOLLOWS:
UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):
1. PRIMARY SLUDGE PUMPING STATION NO. 2
TABLE 6.2.2(a), ROW 9, LINE b
THE CLASSIFICATION RATING OF THE PRIMARY
SLUDGE PUMPING STATION NO. 2 IS DOWNGRADED
FROM CLASS I, DIVISION 2 TO UNCLASSIFIED BY
FUNCTION OF FORCED VENTILATION AT SIX AIR
CHANGES PER HOUR. SEE NFPA-820 2024 EDITION,
TABLE 6.2.2(a), ROW 9, LINE b FOR FURTHER
CLARIFICATION.
NOTES:
1. SEE INSTRUMENTATION DRAWING I150 FOR VENDOR
CONTROL PANELS TO BE INSTALLED FOR PUMP
MONITORING, VCP-9X-6X-X.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
PS
P2
-E .rv t 5/
/2
9:
:2
AM
E150
E. BODNAR
S. SHUGARS
D. WEBER
PRIMARY SLUDGE PUMPING STATION NO. 2
ELECTRICAL
POWER PLANS
3/8" = 1'-0"
BOTTOM POWER PLAN
3/8" = 1'-0"
TOP POWER PLAN
3/8" = 1'-0" 4'21012"
SECTION
3/8" = 1'-0"
ASECTION
3/8" = 1'-0" E150
B
1 BID SET 05/2026 JTH
265 342
LL1
CKT# 1
LL1
CKT# 1
WPCR/GFCI
CKT# 3
WPCR/GFCI
CKT# 3
CJB-150-01
PJB-150-01
LL1
CKT# 1
LL1
CKT# 1
LL1
CKT# 1
WPCR/GFCI
CKT# 3
WPCR/GFCI
CKT# 3
WPCR/GFCI
CKT# 3
WPCR/GFCI
CKT# 3
WPCR/GFCI
CKT# 3
LC2A
CKT# 1
XW2
CKT# 3
LW1A
CKT# 3
LC2
CKT# 1
LC2
CKT# 1
LC2
CKT# 1
LC2A
CKT# 1
LC2
CKT# 1
LC2
CKT# 1
LC2
CKT# 1
CKT# 3
CKT# 3
NOTES:
1.
2.
3.
4.
5.
MOUNT FIXTURE TYPE "LW##" 6" ABOVE DOOR.
MOUNT FIXTURE TYPE "XW#" 6" ABOVE DOOR.
MOUNT FIXTURE TYPE "LL#" 12'-0" AFF.
MOUNT FIXTURE TYPE "LC##" 12'-0" AFF.
UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED
FROM THE CIRCUIT NOTED IN PANEL LP-SEP-2.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
PS
P2
-E .rv t 5/
/2
9:
:2
AM
E151
E. BODNAR
S. SHUGARS
D. WEBER
PRIMARY SLUDGE PUMPING STATION NO. 2
ELECTRICAL
LIGHTING PLANS
3/8" = 1'-0" 4'21012"
3/8" = 1'-0"
TOP LIGHTING PLAN
3/8" = 1'-0"
BOTTOM LIGHTING PLAN
1 BID SET 05/2026 JTH
266 342
CJB-150-01
PLC-38
FROM ACP-38
M
CJB-150-01
MCC-SEB-2
TSH
M TE
VENDOR CABLE
9B-63-2
LE/LT
I-150-000
SCUM MIXER
NO. 2
PRIMARY
SCUM PUMP
NO. 2
PRIMARY
SCUM PUMP
NO. 3
PRIMARY
SLUDGE
PUMP NO. 3
SCUM MIXER
NO. 2
VC
P-
9B -6
2-
LC
S-
9B -6
2-
LC
S-
9B -6
3-
9B-63-2
M
PRIMARY SCUM
PUMP NO. 2
TE
9B-62-2
VC
P-
9B -6
2-
LC
S-
9B -6
2-
PRIMARY SCUM
PUMP NO. 3
9B-62-3 9B-61-3
PRIMARY SLUDGE
PUMP NO. 3 VC
P- 9B
-6 1-
LC
S-
9B -6
1-
PS
L-
9B -6
1-
PS
H
-9 B-
-3
PRIMARY
SLUDGE
PUMP NO. 4
9B-61-4
PRIMARY SLUDGE
PUMP NO. 4 VC
P- 9B
-6 1-
LC
S-
9B -6
1-
PS
L-
9B -6
1-
PS
H
-9 B-
-4
VCP-9B-60-3
CJB-150-01
LC
S-
9B -6
0-
TSH
M
9B-60-3
PRIMARY SLUDGE
GRINDER NO. 3
9B-64
LSH
9B-102
FIT
HCP-150-1
I-150-001 I-150-005
C-150-001
C-150-000
C-150-003 C-150-005
C-150-020
C-150-021
C-150-024
C-150-025
C-150-026
C-150-028
I-150-004
C-150-029 C-150-002 C-150-022
C-150-023
C-150-027
CJB-150-01 CJB-150-01
M
TE TSH
M TE
VENDOR CABLE
C-150-004
C-150-007
C-150-006 C-150-008
C-150-009 C-150-010 C-150-011 C-150-012 C-150-013
C-150-014
C-150-015 C-150-016 C-150-017 C-150-018 C-150-019
NOTES:
1. COORDINATE REQUIREMENTS WITH FINAL
APPROVED VENDOR.
2. COORDINATE WITH MOTOR SCHEMATICS ON
SHEETS E459 TO E462.
NO. DATEISSUED FOR APPROVEDBY
PROJ.ENGR.
CHECKED
DRAWN
DESIGNED
SHEET
DATE:
OF
NUMBER
DRAWING
31111-098
MAY 2026
D C
\A C
C D oc s\
H az en a nd S aw ye r\3
-0
_W
PC
F
So lid s Pr oc es si ng
Im p
Ph I\
Pr oj ec t F ile s\
_D es ig n\ El ec \E
2.
dw g
L as tS av eB y:
JW
TH
O M
PS
O
N
J. HISE
IFB NO.
500640-
FY27-02
1 05/2026BID SET JTH
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
H & S JOB
NUMBER
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
E152
PRIMARY SLUDGE PUMPING STATION NO. 2
ELECTRICAL
CONTROL RISER DIAGRAM
XX
D. ATKINSON
J. THOMPSON
D. ATKINSON
267 342
GRAVITY THICKENER A
(SEE E300 DRAWING SERIES)
GRAVITY THICKENER B
(SEE E320 DRAWING SERIES)
GRAVITY THICKENER C
(SEE E340 DRAWING SERIES)
SPLITTER BOX
SOLIDS ELECTRICAL BUILDING
(SEE E450 DRAWING SERIES)
TX-37-36A
TX-37-36B
DB
E11
DB
C2
DB
E9
DB
C5
DB
E8
DB
E14
DB
C9
DB
E1
DB
E10
DB
C1
STAIRWELL B
DUMPSTER ROOM
STAIRWELL A
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
TS
PS
-E .rv t 5/
/2
9:
:3
AM
E200
E. BODNAR
D. ATKINSON
D. ATKINSON
THICKENED SLUDGE PUMPING STATION
ELETRICAL
AREA PLAN
3/16" = 1'-0"
AREA PLAN
3/16" = 1'-0" 5'0246
SEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
1 BID SET 05/2026 JTH
268 342
UP
31-122-131-122-231-122-331-122-4
E206 2_______
LCS-31-151-1
PUMP ROOM
STAIRWELL A
STAIRWELL B
E206 1_______
E206 1_______
31-151-1
GRINDER
31-122-5
E201 A_______
E201 A_______
UP
GROUNDING NOTES:
A.
B.
C.
D.
E.
F.
G.
REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING
OF GROUND RING TO STRUCTURAL FOUNDATION
REBAR.
GROUND RING CONDUCTOR SHALL BE #4/0 BARE
COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.
ALL GROUND CONDUCTORS TO EQUIPMENT OR
STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.
EACH DUCT BANK GROUND CONDUCTOR CROSSING
THE GROUND RING SHALL BE EXOTHERMICALLY
WELDED TO THE GROUND RING CONDUCTOR.
ALL MOTOR FRAMES SHALL BE BONDED TO THE
GROUND RING CONDUCTOR.
FURNISH AND INSTALL LIGHTNING PROTECTION
SYSTEM FOR THIS FACILITY PER SPECIFICATION
26 41 00.
FURNISH AND INSTALL 1" CONDUITS THROUGH
CONCRETE PAD FOR LIGHTNING PROTECTION DOWN
CONDUCTORS TO GROUND RING. ALL DOWN
CONDUCTORS SHALL BE ROUTED DOWN INSIDE OF
BUILDING.
COORDINATE GROUND SYSTEM INSTALLATION WITH
INSTALLATION OF THE LIGHTNING PROTECTION
SYSTEM.
INDOOR WET PROCESS AREA
INDOOR DRY PROCESS AREA
INDOOR DRY NON-PROCESS AREA
AREA DESIGNATION LEGEND:
NOTES:
1.
2.
IN GENERAL, NOT ALL OF THE REQUIRED JUNCTION
AND PULL BOXES ARE SHOWN ON THE PLANS.
CONTRACTOR SHALL PROVIDE AND FIELD LOCATE
SUCH BOXES AS REQUIRED BY CODE, SITE
CONDITIONS, AND SPECIFICATIONS, FOR PROPER
PULLS AND BENDS, AT NO ADDITIONAL COST TO THE
OWNER.
SEE INSTRUMENTATION DRAWING I201 FOR VENDOR
CONTROL PANELS TO BE INSTALLED FOR PUMP
MONITORING, VCP-31-122-X.
VCP-31-151
FIT
31-152-1
FIT
31-463-1
31-122-4 DSW
31-122-3 DSW
31-122-2 DSW
31-122-1 DSW
LCS-31-122-4
LCS-31-122-3
LCS-31-122-2
LCS-31-122-1
HAZARDOUS AREAS:
SPACE CLASSIFIED PER NFPA-820-2024
EDITION AS FOLLOWS:
UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):
1. PUMP ROOM
TABLE 6.2.2(a), ROW 9, LINE b
THE CLASSIFICATION RATING OF THE PUMP ROOM IS
DOWNGRADED FROM CLASS I, DIVISION 2 TO
UNCLASSIFIED BY FUNCTION OF FORCED VENTILATION
AT SIX AIR CHANGES PER HOUR. SEE NFPA-820 2024
EDITION, TABLE 6.2.2(a), ROW 9, LINE b FOR FURTHER
CLARIFICATION.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
TS
PS
-E .rv t 5/
/2
9:
:3
AM
E201
E. BODNAR
D. ATKINSON
D. ATKINSON
THICKENED SLUDGE PUMPING STATION
ELETRICAL
BOTTOM POWER PLAN
1/4" = 1'-0"
BOTTOM POWER PLAN
GROUND ROD
TEST WELL
GROUND ROD,
TYP
1/4" = 1'-0" 1 1 3 7'0 2
SECTION
1/4" = 1'-0" E201
A
1 BID SET 05/2026 JTH
269 342
MAU-200-1 DSW
DUMPSTER ROOM
STAIRWELL A
STAIRWELL B
EF-200-1
MAU-200-1
EF-200-1 DSW
SF-200-2
SF-200-1 DSW
FACP-TSPS
NOTES:
1.
2.
IN GENERAL, NOT ALL OF THE REQUIRED JUNCTION
AND PULL BOXES ARE SHOWN ON THE PLANS.
CONTRACTOR SHALL PROVIDE AND FIELD LOCATE
SUCH BOXES AS REQUIRED BY CODE, SITE
CONDITIONS, AND SPECIFICATIONS, FOR PROPER
PULLS AND BENDS, AT NO ADDITIONAL COST TO THE
OWNER.
FURNISH AND INSTALL FIRE ALARM SYSTEM FOR THIS
FACILITY PER SPECIFICATION 28 46 20.
INDOOR WET PROCESS AREA
INDOOR DRY PROCESS AREA
INDOOR DRY NON-PROCESS AREA
AREA DESIGNATION LEGEND:
HAZARDOUS AREAS:
SPACE CLASSIFIED PER NFPA-820-2024
EDITION AS FOLLOWS:
UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):
1. DUMPSTER ROOM
TABLE 6.2.2(a), ROW 1
THE CLASSIFICATION RATING OF THE DUMPSTER
ROOM IS UNCLASSIFIED. SEE NFPA-820 2024 EDITION,
TABLE 6.2.2(a), ROW 1 FOR FURTHER CLARIFICATION.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
TS
PS
-E .rv t 5/
/2
9:
:4
AM
E202
E. BODNAR
D. ATKINSON
D. ATKINSON
THICKENED SLUDGE PUMPING STATION
ELETRICAL
TOP POWER PLAN
1/4" = 1'-0"
TOP POWER PLAN
1/4" = 1'-0" 1 1 3 7'0 2
1 BID SET 05/2026 JTH
270 342
SCREENING ROOM
SF-200-1
SF-200-2 DSW
PNEUMATIC PANEL,
TYP
EF-200-2
SF-200-3
UH-200-2
11-142-2
VCP-11-142-1
VCP-11-142-1
11-142-1
11-142-2 DSW
11-142-1 DSW
SF-200-3
UH-200-3 DSW
EF-200-2 DSW
INDOOR WET PROCESS AREA
INDOOR DRY PROCESS AREA
INDOOR DRY NON-PROCESS AREA
AREA DESIGNATION LEGEND:
NOTES:
1. IN GENERAL, NOT ALL OF THE REQUIRED JUNCTION
AND PULL BOXES ARE SHOWN ON THE PLANS.
CONTRACTOR SHALL PROVIDE AND FIELD LOCATE
SUCH BOXES AS REQUIRED BY CODE, SITE
CONDITIONS, AND SPECIFICATIONS, FOR PROPER
PULLS AND BENDS, AT NO ADDITIONAL COST TO THE
OWNER.
HAZARDOUS AREAS:
SPACE CLASSIFIED PER NFPA-820-2024
EDITION AS FOLLOWS:
UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):
1. SCREENING ROOM
TABLE 6.2.2(a), ROW 1
THE CLASSIFICATION RATING OF THE SCREENING
ROOM IS UNCLASSIFIED. SEE NFPA-820 2024 EDITION,
TABLE 6.2.2(a), ROW 1 FOR FURTHER CLARIFICATION.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
TS
PS
-E .rv t 5/
/2
9:
:4
AM
E203
E. BODNAR
D. ATKINSON
D. ATKINSON
THICKENED SLUDGE PUMPING STATION
ELETRICAL
UPPER POWER PLANS
1/4" = 1'-0"
UPPPER POWER PLAN
1/4" = 1'-0" 1 1 3 7'0 2
3/16" = 1'-0" 5'0246
1 BID SET 05/2026 JTH
271 342
LP1
CKT# 15
XW2
CKT#
LC1A
CKT# 15
XW2
CKT#
GFCI
CKT#
GFCI
CKT#
GFCI
CKT#
GFCI
CKT#
GFCI
CKT#
GFCI
CKT#
GFCI
CKT#
GFCI
CKT#
LC1A
CKT# 15
LP1
CKT# 15
LP1
CKT# 15
LP1A
CKT# 15
LP1
CKT# 15
LP1A
CKT# 15
LP1
CKT# 15
LP1
CKT# 15
LP1
CKT# 15
LP1
CKT# 15
LP1
CKT# 15
LP1
CKT# 15
LP1A
CKT# 15
LP1
CKT# 15
LP1
CKT# 15
LP1
CKT# 15
NOTES:
1.
2.
3.
4.
5.
MOUNT FIXTURE TYPES ["LP##" 11'-10" AFF.]
MOUNT FIXTURE TYPES ["LC##" 12'-0" AFF.]
MOUNT FIXTURE TYPE ["XW#" 6" ABOVE DOOR.]
LIGHT FIXTURE TYPES LC1A AND LP1A SHALL REMAIN
UN-SWITCHED AND SERVE AS A NIGHT LIGHT FOR
EGRESS.
UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED
FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
TS
PS
-E .rv t 5/
/2
9:
:4
AM
E204
E. BODNAR
D. ATKINSON
D. ATKINSON
THICKENED SLUDGE PUMPING STATION
ELETRICAL
BOTTOM LIGHTING PLAN
1/4" = 1'-0"
BOTTOM LIGHTING PLAN
1/4" = 1'-0" 1 1 3 7'0 2
1 BID SET 05/2026 JTH
272 342
LP1A
CKT# 39
LW1
CKT# 39
LW1
CKT# 39
LW1
CKT# 39
LW1A
CKT# 39
XW1
CKT#
LW1
CKT# 39
LW1
CKT# 39
XW2
CKT#
XW2
CKT# 1
LW1A
CKT# 39
LW1
CKT# 39
LW1A
CKT# 39
XW1
CKT# 1
LW1
CKT# 39
LW1
CKT# 39
LW1
CKT# 39
WPCR/GFCI
CKT# 9
WPCR/GFCI
CKT#
WPCR/GFCI
CKT#
WPCR/GFCI
CKT#
WPCR/GFCI
CKT#
WPCR/GFCI
CKT#
WPCR/GFCI
CKT#
LP1A
CKT# 39
LL1
CKT# 39
LL1
CKT# 39
LP1
CKT# 39
LP1
CKT# 39
LP1
CKT# 39
LP1
CKT# 39
LP1A
CKT# 39
LC1A
CKT# 39
LC1A
CKT# 39
LP1A
CKT# 39
LP1A
CKT# 39
NOTES:
1.
2.
3.
4.
5.
6.
7.
MOUNT FIXTURE TYPES ["LP##" 12'-0" AFF.]
MOUNT FIXTURE TYPES ["LC##" 12'-0" AFF.]
MOUNT FIXTURE TYPE ["XW#" 6" ABOVE DOOR.]
MOUNT FIXTURE TYPE ["LW##" 6" ABOVE DOOR.]
MOUNT FIXTURE TYPE ["LL#" 10'-0" AFF.]
LIGHT FIXTURE TYPES LC1A AND LP1A SHALL REMAIN
UN-SWITCHED AND SERVE AS A NIGHT LIGHT FOR
EGRESS.
UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED
FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
TS
PS
-E .rv t 5/
/2
9:
:4
AM
E205
E. BODNAR
D. ATKINSON
D. ATKINSON
THICKENED SLUDGE PUMPING STATION
ELETRICAL
TOP LIGHTING PLAN
1/4" = 1'-0"
TOP LIGHTING PLAN
1/4" = 1'-0" 1 1 3 7'0 2
1 BID SET 05/2026 JTH
273 342
XW2
CKT#
LC1A
CKT# 15
XW1
CKT#
LP1A
CKT# 39
LP1A
CKT# 39
LP1A
CKT# 39
LW1
CKT# 39
LW1
CKT# 39
LC1A
CKT# 23
LC1A
CKT# 23
LC1A
CKT# 39
LW1A
CKT# 39
XW1
CKT# 1
LC1A
CKT# 39
LC1A
CKT# 15
LC1A
CKT# 23
XW1
CKT#
WPCR/GFCI
CKT#
WPCR/GFCI
CKT#
WPCR/GFCI
CKT#
WPCR/GFCI
CKT#
LC1A
CKT# 23
LC1
CKT# 23
LC1
CKT# 23
LC1A
CKT# 23
LC1A
CKT# 23
LC1
CKT# 23
LC1
CKT# 23
NOTES:
1.
2.
3.
4.
5.
6.
MOUNT FIXTURE TYPES ["LP##" 12'-0" AFF.]
MOUNT FIXTURE TYPES ["LC##" 12'-0" AFF.]
MOUNT FIXTURE TYPE ["XW#" 6" ABOVE DOOR.]
MOUNT FIXTURE TYPE ["LW##" 6" ABOVE DOOR.]
LIGHT FIXTURE TYPES LC1A AND LP1A SHALL REMAIN
UN-SWITCHED AND SERVE AS A NIGHT LIGHT FOR
EGRESS.
UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED
FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
TS
PS
-E .rv t 5/
/2
9:
:4
AM
E206
E. BODNAR
D. ATKINSON
D. ATKINSON
THICKENED SLUDGE PUMPING STATION
ELETRICAL
UPPER LIGHTING PLAN AND SECTIONS
SECTION
1/4" = 1'-0" E201
2 SECTION
1/4" = 1'-0" E201
1/4" = 1'-0"
UPPER LIGHTING PLAN
1/4" = 1'-0" 1 1 3 7'0 2
1 BID SET 05/2026 JTH
274 342
PLC-38
FROM ACP-38
VCP-11-142-1
TSH
M
PRIMARY SLUDGE
SCREEN NO. 2
M
SH
-1 1-
2-
VCP-11-143-111-142-1A
PIT
11-142-1B
PIT
NSHH
M
31A-121-1
GRAVITY THICKENER
A ROTATING RAKE
NSH NSHH
M
31B-121-1
GRAVITY THICKENER
B ROTATING RAKE
NSH NSHH
M
31C-121-1
GRAVITY THICKENER
C ROTATING RAKE
NSH
C-200-015
THICKENED
SLUDGE
PUMP NO. 1
THICKENED
SLUDGE
PUMP NO. 2
TSH
M
THICKENED
SLUDGE PUMP NO. 1
TE
31-122-1
VC
P-
-1
-1
LC
S-
-1
-1
PS
L-
-1
-1
A
PS
H
-3 1-
2-
1B
C-200-018
TSH
M
THICKENED SLUDGE
PUMP NO. 2
TE
31-122-2
VC
P-
-1
-2
LC
S-
-1
-2
PS
L-
-1
-2
A
PS
H
-3 1-
2-
2B
THICKENED
SLUDGE
PUMP NO. 3
TSH
M
THICKENED SLUDGE
PUMP NO. 3
TE
31-122-3
VC
P-
-1
-3
LC
S-
-1
-3
PS
L-
-1
-3
A
PS
H
-3 1-
2-
3B
THICKENED
SLUDGE
PUMP NO. 4
TSH
M
THICKENED SLUDGE
PUMP NO. 4
TE
31-122-4
VC
P-
-1
-4
LC
S-
-1
-4
PS
L-
-1
-4
A
PS
H
-3 1-
2-
4B
C-200-001
C-200-002 C-200-004 C-200-005
C-200-016 C-200-017
C-200-023 C-200-019 C-200-020
C-200-021 C-200-022
C-200-028 C-200-024 C-200-025
C-200-026 C-200-027
C-200-033 C-200-029 C-200-030
C-200-031 C-200-032
C-300-002 C-320-002 C-340-002
C-200-000
I-200-001 I-200-002
VCP-31A-121-1 VCP-31B-121-1 VCP-31C-121-1
MCC-SEB-1
31-463-1
FE
31-463-1
FIT
HCP-200-2
C-200-036 C-200-037
HCP-200-1
C-200-038 C-200-039
31-152-1
FE
31-152-1
FIT
I-200-008
C-300-000 C-320-000 C-340-000
I-200-006
I-200-007 I-200-009
CJB-300-01 CJB-320-01 CJB-340-01
C-300-001 C-320-001 C-340-001
VCP-38A-119
M
SH
-3 8A
-1
-1
38A-119-1
GRAVITY
THICKENER SCUM
PUMP NO. 1
M
SH
-3 8A
-1
-2
38A-119-2
GRAVITY
THICKENER SCUM
PUMP NO. 2
38A-119-2
LSL
C-400-000
VCP-38B-119
M
SH
-3 8B
-1
-3TSH
M
38B-119-3
GRAVITY
THICKENER SCUM
PUMP NO. 3
M
SH
-3 8B
-1
-4TSH
M
38B-119-4
GRAVITY
THICKENER SCUM
PUMP NO. 4
38B-119-4
LSL
C-400-009 C-400-008
I-400-000 I-400-002
C-400-010
C-400-011
VCP-11-142-2
TSH
M
PRIMARY SLUDGE
SCREEN NO. 2
M
SH
-1 1-
2-
VCP-11-143-211-142-2A
PIT
11-142-2B
PIT
C-200-007
C-200-008 C-200-010 C-200-011
C-200-006
I-200-004 I-200-005
11-142-1 11-142-2
11-142-1
HS
11-142-2
HS
C-200-003 C-200-009
M
31-151-1
PRIMARY SCUM
GRINDER
VCP-31-151-1
C-200-012
LC
S-
-1
-1
PLC-38
SEE BELOW FOR
CONTINUATION
SEE ABOVE FOR
CONTINUATION
VENDOR CABLE VENDOR CABLE VENDOR CABLE VENDOR CABLE
C-200-013 C-200-014
C-200-035 C-200-034
38B-119-3
LSL
C-400-007
38B-119-1
LE/LT
I-400-003
TSH
M
TSH
M
C-400-002 C-400-001
C-400-006
C-400-004 C-400-005
38A-119-1
LSL
C-400-003
38B-119-1
LE/LT
I-400-001
C-400-012 C-400-013
NOTES:
1. COORDINATE REQUIREMENTS WITH FINAL
APPROVED VENDOR.
2. COORDINATE WITH MOTOR SCHEMATICS ON
SHEETS E459 TO E462.
NO. DATEISSUED FOR APPROVEDBY
PROJ.ENGR.
CHECKED
DRAWN
DESIGNED
SHEET
DATE:
OF
NUMBER
DRAWING
31111-098
MAY 2026
D C
\A C
C D oc s\
H az en a nd S aw ye r\3
-0
_W
PC
F
So lid s Pr oc es si ng
Im p
Ph I\
Pr oj ec t F ile s\
_D es ig n\ El ec \E
7.
dw g
L as tS av eB y:
JW
TH
O M
PS
O
N
J. HISE
IFB NO.
500640-
FY27-02
1 05/2026BID SET JTH
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
H & S JOB
NUMBER
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
E207
THICKENED SLUDGE PUMPING STATION
ELECTRICAL
CONTROL RISER DIAGRAMS
XX
D. ATKINSON
J. THOMPSON
D. ATKINSON
275 342
NOTES:
1.
2.
3.
4.
5.
6.
7.
REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING
OF GROUND RING TO STRUCTURAL FOUNDATION
REBAR.
GROUND RING CONDUCTOR SHALL BE #4/0 BARE
COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.
ALL GROUND CONDUCTORS TO EQUIPMENT OR
STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.
EACH DUCT BANK GROUND CONDUCTOR CROSSING
THE GROUND RING SHALL BE EXOTHERMICALLY
WELDED TO THE GROUND RING CONDUCTOR.
ALL MOTOR FRAMES SHALL BE BONDED TO THE
GROUND RING CONDUCTOR.
LOCATE JUNCTION BOX CJB-300-01 AND PJB-300-01 AT
GRADE. TRANSITION TO EXPOSED CONDUITS. ROUTE
CONDUITS BENEATH THE WALKWAY BRIDGE TO THE
EQUIPMENT LOCATED IN THE CENTER OF PLATFORM.
MOUNT FIXTURE TYPE ["LL#" 10'-0" AFF.]
UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED
FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.
CJB-300-01
PJB-300-01
SEE DRAWING E021
FOR CONTINUATION
DB
E11
DB
C2
GROUND ROD TEST WELL
GROUND ROD, TYP
LL1
CKT# 27
SEE DRAWING E021
FOR CONTINUATION
31A-121-1
E300
A_______
E300
A_______
WPCR/GFCI
CKT#
VCP-31A-121-1
PJB-300-01
CJB-300-01
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
G
TA
-E .rv t 5/
/2
9:
:5
AM
E300
K. SIMMONS
D. WEBER
E. FRANCOIS
GRAVITY THICKENER A
ELECTRICAL
POWER AND LIGHTING PLAN
3/8" = 1'-0" 4'21012"
3/8" = 1'-0"
POWER AND LIGHTING PLAN
N
SECTION
3/8" = 1'-0" E300
A
1 BID SET 05/2026 JTH
276 342
HAZARDOUS AREAS:
SPACE CLASSIFIED PER NFPA-820-2024
EDITION AS FOLLOWS:
CLASS I, DIVISION 2 AREAS:
1. GRAVITY THICKENER A
TABLE 6.2.2(a), ROW 8, LINE b
THE CLASSIFICATION RATING OF THE GRAVITY
THICKENER A IS DOWNGRADED FROM CLASS I,
DIVISION 1 TO CLASS I, DIVISION 2 BY FUNCTION OF
FORCED VENTILATION AT 12 AIR CHANGES PER
HOUR. SEE NFPA-820 2024 EDITION, TABLE 6.2.2(a), ROW 8, LINE b FOR FURTHER CLARIFICATION
ENCLOSED - ENTIRE SPACE
2. ODOR CONTROL PIPING
TABLE 5.2.2 ROW 28 &
4.2.2 ROW 18, LINE c
AREAS WITHIN 3FT OF LEAKAGE SOURCES SUCH
AS VENTS, FANS, DAMPERS, FLEXIBLE
CONNECTIONS, FLANGES, PRESSURIZED
UNWELDED DUCTWORK, AND ODOR CONTROL
VESSELS
E301
A_______ E301
A_______
3'
0"
CLASS I, DIV 1
CLASS I, DIV 2
LEGEND:
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
G
TA
-E .rv t 5/
/2
9:
:5
AM
E301
J. THOMPSON
D. ATKINSON
D. ATKINSON
GRAVITY THICKENER A
ELECTRICAL
HAZARDOUS AREA PLANS AND SECTIONS
3/8" = 1'-0" 4'21012"
3/8" = 1'-0"
CLASSIFICATION PLAN SECTION
3/8" = 1'-0" E301
A
1 BID SET 05/2026 JTH
277 342
PJB-320-01
SEE DRAWING E021
FOR CONTINUATION
CJB-320-01
VCP-31B-121-1
GROUND ROD, TYP
GROUND ROD TEST WELL
DB
E12
DB
C3
WPCR/GFCI
CKT#
LL1
CKT# 10
SEE DRAWING E021
FOR CONTINUATION
31B-121-1
E320
A_______
E320
A_______
NOTES:
1.
2.
3.
4.
5.
6.
7.
REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING
OF GROUND RING TO STRUCTURAL FOUNDATION
REBAR.
GROUND RING CONDUCTOR SHALL BE #4/0 BARE
COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.
ALL GROUND CONDUCTORS TO EQUIPMENT OR
STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.
EACH DUCT BANK GROUND CONDUCTOR CROSSING
THE GROUND RING SHALL BE EXOTHERMICALLY
WELDED TO THE GROUND RING CONDUCTOR.
ALL MOTOR FRAMES SHALL BE BONDED TO THE
GROUND RING CONDUCTOR.
LOCATE JUNCTION BOX CJB-320-01 AND PJB-320-01 AT
GRADE. TRANSITION TO EXPOSED CONDUITS. ROUTE
CONDUITS BENEATH THE WALKWAY BRIDGE TO THE
EQUIPMENT LOCATED IN THE CENTER OF PLATFORM.
MOUNT FIXTURE TYPE ["LL#" 10'-0" AFF.]
UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED
FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.CJB-320-01 PJB-320-01
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
G
TB
-E .rv t 5/
/2
9:
:5
AM
E320
K. SIMMONS
D. WEBER
E. FRANCOIS
GRAVITY THICKENER B
ELECTRICAL
POWER AND LIGHTING PLAN
3/8" = 1'-0"
TOP PLAN
3/8" = 1'-0" 4'21012"
N
SECTION
3/8" = 1'-0" E320
A
1 BID SET 05/2026 JTH
278 342
SPACE CLASSIFIED PER NFPA-820-2024
EDITION AS FOLLOWS:
CLASS I, DIVISION 2 AREAS:
1. GRAVITY THICKENER B
TABLE 6.2.2(a), ROW 8, LINE b
THE CLASSIFICATION RATING OF THE GRAVITY
THICKENER B IS DOWNGRADED FROM CLASS I,
DIVISION 1 TO CLASS I, DIVISION 2 BY FUNCTION OF
FORCED VENTILATION AT 12 AIR CHANGES PER
HOUR. SEE NFPA-820 2024 EDITION, TABLE 6.2.2(a), ROW 8, LINE b FOR FURTHER CLARIFICATION
ENCLOSED - ENTIRE SPACE
2. ODOR CONTROL PIPING
TABLE 5.2.2 ROW 28 &
4.2.2 ROW 18, LINE c
AREAS WITHIN 3FT OF LEAKAGE SOURCES SUCH
AS VENTS, FANS, DAMPERS, FLEXIBLE
CONNECTIONS, FLANGES, PRESSURIZED
UNWELDED DUCTWORK, AND ODOR CONTROL
VESSELS
CLASS I, DIV 1
CLASS I, DIV 2
LEGEND:
E321
A_______ E321
A_______
3'
0"
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
G
TB
-E .rv t 5/
/2
9:
:5
AM
E321
J. THOMPSON
D. ATKINSON
D. ATKINSON
GRAVITY THICKENER B
ELECTRICAL
HAZARDOUS AREA PLANS AND SECTIONS
3/8" = 1'-0" 4'21012"
3/8" = 1'-0"
CLASSIFICATION PLAN SECTION
3/8" = 1'-0" E321
A
1 BID SET 05/2026 JTH
279 342
PJB-340-01
FOR CONTINUATION
DB
E13
DB
C4
CJB-340-01
VCP-31C-121-1 GROUND ROD, TYP
GROUND ROD TEST WELL
WPCR/GFCI
CKT# 4
LL1
CKT# 35
SEE DRAWING E021
FOR CONTINUATION
E340
A_______
E340
A_______
31C-121-1
NOTES:
1.
2.
3.
4.
5.
6.
7.
REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING
OF GROUND RING TO STRUCTURAL FOUNDATION
REBAR.
GROUND RING CONDUCTOR SHALL BE #4/0 BARE
COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.
ALL GROUND CONDUCTORS TO EQUIPMENT OR
STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.
EACH DUCT BANK GROUND CONDUCTOR CROSSING
THE GROUND RING SHALL BE EXOTHERMICALLY
WELDED TO THE GROUND RING CONDUCTOR.
ALL MOTOR FRAMES SHALL BE BONDED TO THE
GROUND RING CONDUCTOR.
LOCATE JUNCTION BOX CJB-340-01 AND PJB-340-01 AT
GRADE. TRANSITION TO EXPOSED CONDUITS. ROUTE
CONDUITS BENEATH THE WALKWAY BRIDGE TO THE
EQUIPMENT LOCATED IN THE CENTER OF PLATFORM.
MOUNT FIXTURE TYPE ["LL#" 10'-0" AFF.]
UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED
FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.
CJB-340-01
PJB-340-01
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
G
TC
-E .rv t 5/
/2
9:
:0
AM
E340
K. SIMMONS
D. WEBER
E. FRANCOIS
GRAVITY THICKENER C
ELECTRICAL
POWER AND LIGHTING PLAN
3/8" = 1'-0"
TOP PLAN
3/8" = 1'-0" 4'21012"
SECTION
3/8" = 1'-0" E340
A
1 BID SET 05/2026 JTH
280 342
SPACE CLASSIFIED PER NFPA-820-2024
EDITION AS FOLLOWS:
CLASS I, DIVISION 2 AREAS:
1. GRAVITY THICKENER C
TABLE 6.2.2(a), ROW 8, LINE b
THE CLASSIFICATION RATING OF THE GRAVITY
THICKENER C IS DOWNGRADED FROM CLASS I,
DIVISION 1 TO CLASS I, DIVISION 2 BY FUNCTION OF
FORCED VENTILATION AT 12 AIR CHANGES PER
HOUR. SEE NFPA-820 2024 EDITION, TABLE 6.2.2(a), ROW 8, LINE b FOR FURTHER CLARIFICATION
ENCLOSED - ENTIRE SPACE
2. ODOR CONTROL PIPING
TABLE 5.2.2 ROW 28 &
4.2.2 ROW 18, LINE c
AREAS WITHIN 3FT OF LEAKAGE SOURCES SUCH
AS VENTS, FANS, DAMPERS, FLEXIBLE
CONNECTIONS, FLANGES, PRESSURIZED
UNWELDED DUCTWORK, AND ODOR CONTROL
VESSELS
E341
A_______ E341
A_______
3' - 7 5/8"
3' - 0"
CLASS I, DIV 1
CLASS I, DIV 2
LEGEND:
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
G
TC
-E .rv t 5/
/2
9:
:0
AM
E341
J. THOMPSON
D. ATKINSON
D. ATKINSON
GRAVITY THICKENER C
ELECTRICAL
HAZARDOUS AREA PLANS AND SECTIONS
3/8" = 1'-0" 4'21012"
3/8" = 1'-0"
CLASSIFICATION PLAN SECTION
3/8" = 1'-0" E341
A
1 BID SET 05/2026 JTH
281 342
VCP-38A-119
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
38A-119-1
38A-119-2
NOTES:
1. REFER TO DRAWING E021 SITE LIGHTING FOR AREA
LIGHTING OF SCUM PIT 1.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
SC
P1
-E .rv t 5/
/2
9:
:1
AM
E400
J. THOMPSON
D. ATKINSON
D. ATKINSON
SCUM PIT 1
ELECTRICAL
POWER PLAN
3/4" = 1'-0" 2'106"
3/4" = 1'-0"
POWER PLAN
GRAVITY THICKENER A
GRAVITY THICKENER B
1 BID SET 05/2026 JTH
282 342
SPACE CLASSIFIED PER NFPA-820-2016
EDITION AS FOLLOWS:
CLASS I, DIVISION 1 AREAS:
1. SCUM PIT 1
TABLE 6.2.2(a), ROW 4, LINE a
ENCLOSED - ENTIRE SPACE
CLASS I, DIVISION 2 AREAS:
1. SCUM PIT 1
TABLE 6.2.2(a), ROW 4, LINE c
WITHIN 10FT ENVELOPE AROUND EQUIPMENT AND
OPEN CHANNEL.
CLASS I, DIV 1
CLASS I, DIV 2
LEGEND:
E401 A_______
E401 A_______
10' - 0"
38A-119-1
38A-119-2
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
SC
P1
-E .rv t 5/
/2
9:
:1
AM
E401
J. THOMPSON
D. ATKINSON
D. ATKINSON
SCUM PIT 1
ELECTRICAL
HAZARDOUS AREA PLANS AND SECTIONS
1/2" = 1'-0" 3'1012"
1/2" = 1'-0"
CLASSIFICATION PLAN
SECTION
1/2" = 1'-0" E401
A
1 BID SET 05/2026 JTH
383 342
VCP-38B-119
38B-119-3
38B-119-4
NOTES:
1. REFER TO DRAWING E021 SITE LIGHTING FOR AREA
LIGHTING OF SCUM PIT 2.
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
SC
P2
-E .rv t 5/
/2
9:
:2
AM
E402
J. THOMPSON
D. ATKINSON
D. ATKINSON
SCUM PIT 2
ELECTRICAL
POWER PLAN
3/4" = 1'-0" 2'106"
3/4" = 1'-0"
POWER PLAN
1 BID SET 05/2026 JTH
284 342
SPACE CLASSIFIED PER NFPA-820-2016
EDITION AS FOLLOWS:
CLASS I, DIVISION 1 AREAS:
1. SCUM PIT 2
TABLE 6.2.2(a), ROW 4, LINE a
ENCLOSED - ENTIRE SPACE
CLASS I, DIVISION 2 AREAS:
1. SCUM PIT 2
TABLE 6.2.2(a), ROW 4, LINE c
WITHIN 10FT ENVELOPE AROUND EQUIPMENT AND
OPEN CHANNEL.
CLASS I, DIV 1
CLASS I, DIV 2
LEGEND:
E403 A_______
E403 A_______
10' - 0"
38B-119-4
38B-119-3
N
DESIGNED THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
DATE:
H & S JOB
NUMBER
IFB NO.
500640-
FY27-02
DRAWING
NUMBER
PROJ.ENGR.
DRAWN
CHECKED
NO. ISSUED FOR DATE BY
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
J. HISE
MAY 2026
31111-098
SHEET OF XXAPPROVED
Au to de sk
D oc s:
//3
-0
_W
PC
F So lid s
Pr oc es si ng Im p Ph
I/
1-
8-
0-
SC
P2
-E .rv t 5/
/2
9:
:2
AM
E403
J. THOMPSON
D. ATKINSON
D. ATKINSON
SCUM PIT 2
ELECTRICAL
HAZARDOUS AREA PLANS AND SECTIONS
1/2" = 1'-0" 3'1012"
1/2" = 1'-0"
CLASSIFICATION PLAN
SECTION
1/2" = 1'-0" E403
A
1 BID SET 05/2026 JTH
285 342
NOTES:
1. SWITCHGEAR SHALL CONTAIN ALL SHOWN
CIRCUIT BREAKERS AND CONTAIN 3 PREPARED
SPACES FED FROM BUS A, AND CONTAIN 4
PREPARED SPACED FED FROM SIDE B.
2. SWITCHGEAR DIMENSIONS TO NOT EXCEED THE
SIZES SHOWN ON ELEVATION.
TX-37-36A
2500kVA 4160-480/277V
3P/4W
LIQUID TRANS
PAD MOUNT
3200AF
3200AP
2000AT
E.O.
LSIG
ERMS
N.C.
3200:5 (3)
POWER
METER
SPD
300kA
AF
AT
60 1600AF
1200AP
600AT
E.O.
LSIG
N.C.
FUTURE BNR AND
CLARIFIERS ELEC
BLDG MCC
FUTURE
DENITFIFICATION
FACILITY MCC
1600AF
800AP
400AT
E.O.
LSIG
N.C.
FUTURE TWAS
TANK
ELECTRICAL
ROOM MCC
1600AF
1600AP
1200AT
E.O.
LSIG
N.C.
SOLIDS
ELECTRICAL
BLDG MCC
800AF
800AP
600AT
E.O.
LSIG
N.C.
EMERGENCY
BLOWER BLDG
1600AF
1600AP
1000AT
E.O.
LSIG
N.C.
SOLIDS
PROCESSING
BLDG
800AF
800AP
450AT
E.O.
LSIG
N.C.
ADMIN BLDG
3200AF
3200AP
2000AT
E.O.
LSIG
ERMS
N.O.
FUTURE BNR AND
CLARIFIERS ELEC
BLDG MCC
FUTURE
DENITFIFICATION
FACILITY MCC
FUTURE TWAS
TANK
ELECTRICAL
ROOM MCC
SOLIDS
ELECTRICAL
BLDG MCC
SECTION 1
1A
1B
1C
1A
1B
1C
SECTION 2
2A
2B
2C
800AF
800AP
800AT
E.O.
LSIG
N.C.
SPARE
2A 2B 3A 3C 4A 4B3D
1600AF
1600AP
1600AT
E.O.
LSIG
N.C.
SPARE
SECTION 3
3A
3B
3C
SECTION 4
4A
4B
4C
SECTION 5
5C
5C
2C
1600AF
1600AP
1600AT
E.O.
LSIG
N.C.
SPARE
800AF
800AP
800AT
E.O.
LSIG
N.C.
SPARE
TX-37-36B
2500kVA 4160-480/277V
3P/4W
LIQUID TRANS
PAD MOUNT
3200AF
2500AP
2000AT
E.O.
LSIG
ERMS
N.C.
3200:5 (3)
POWER
METER 9A
9B
SPD
300kA
SWITCHGEAR SWGR-SEB-1 SINGLE LINE DIAGRAM
SOLIDS ELECTRICAL BUILDING
1600AF
1600AP
1600AT
E.O.
LSIG
N.C.
PROCESS
BLOWER
ELECTRICAL
ROOM
PROCESS
BLOWER
ELECTRICAL
ROOM
SOLIDS ELECTRICAL SWITCHGEAR [E450]
3200A, 480V, 3Ø, 3W, 85kA RMS SYMMETRICAL
3200A, 480V, 3Ø, 3W, 85kA RMS SYMMETRICAL
K
K
K
SECTION 6
6A
6B
6C
SECTION 7
7A
7B
7C
SECTION 8
8A
8B
SECTION 9
9A
9B
9C
MCC-800-1-A MCC-400-1-A MCC-950-1-A MCC-SEB-1-A MCC-B3-G SWBD-13-22 MCC-17-26-A
MCC-17-26-B MCC-800-1-B MCC-400-1-B MCC-950-1-B MCC-SEB-1-B MCC-B-1
1600AF
1600AP
600AT
E.O.
LSIG
N.C.
1600AF
1600AP
1600AT
E.O.
LSIG
N.C.
1600AF
1200AP
600AT
E.O.
LSIG
N.C.
1600AF
1600AP
600AT
E.O.
LSIG
N.C.
1600AF
800AP
400AT
E.O.
LSIG
N.C.
1600AF
1600AP
1200AT
E.O.
LSIG
N.C.
FROM
SWGR-45C-34
FROM
SWGR-45C-34
4C
PREPARED
SPACE
PREPARED
SPACE
HMI
EMPTY
EMPTY
MAIN A
TIE
6A 6B 6C 7A 7B 7D 8A 8B 9C
PREPARED
SPACE
PREPARED
SPACE
PREPARED
SPACE
SWITCHGEAR SWGR-SEB-1 ELEVATION
SOLIDS ELECTRICAL BUILDING
MAIN B AF
AT
EMPTY
198" MAXIMUM
EMPTY
MCC-B3-N
1600AF
1600AP
1200AT
E.O.
LSIG
N.C.
SOLIDS
ELECTRICAL
BLDG MCC
3B
MCC-SEB-2-A
SOLIDS
ELECTRICAL
BLDG MCC
MCC-SEB-2-B
1600AF
1600AP
1200AT
E.O.
LSIG
N.C.
7C
3D 7D
SEE BELOW FOR
CONTINUATION
SEE ABOVE FOR
CONTINUATION
P-450-002
P-450-010
P-700-001 P-750-002
P-800-001
SWGR-SEB-1-B
SWGR-SEB-1-A
P-450-001 P-450-000
P-450-003 P-450-006 P-450-005 P-450-004
P-450-007
P-450-009 P-450-008
P-450-013 P-450-012 P-450-011
P-700-000 P-750-001 P-750-000
P-750-003
P-800-000
P-000-001 P-000-000
P-000-001 P-000-000
P-000-003 P-000-002
P-000-007 P-000-006
P-000-009 P-000-008
P-000-011 P-000-010
SEE SHEET E006
P-820-002 P-820-003 P-820-004 P-820-005 P-820-006 P-820-007
P-820-008 P-820-009 P-820-010 P-820-011 P-820-012 P-820-013
P-820-016 P-820-017 P-820-018 P-820-019 P-820-020 P-820-021
P-820-022 P-820-023 P-820-024 P-820-025 P-820-026 P-820-027
SEE SHEET E006
P-450-027 P-450-028
NO. DATEISSUED FOR APPROVEDBY
PROJ.ENGR.
CHECKED
DRAWN
DESIGNED
SHEET
DATE:
OF
NUMBER
DRAWING
31111-098
MAY 2026
D C
\A C
C D oc s\
H az en a nd S aw ye r\3
-0
_W
PC
F
So lid s Pr oc es si ng
Im p
Ph I\
Pr oj ec t F ile s\
_D es ig n\ El ec \E
0.
dw g
L as tS av eB y:
JW
TH
O M
PS
O
N
J. HISE
IFB NO.
500640-
FY27-02
1 05/2026BID SET JTH
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
H & S JOB
NUMBER
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
E450
SOLIDS ELECTRICAL BUILDING
ELECTRICAL
SWGR-SEB-1 SINGLE LINE DIAGRAM
XX
D. WEBER
E. BODNAR
S. MINETT
286 342
30A 3P
30A 3P
DIGESTER B
MIXER
30A 3P
DIGESTER C
MIXER
30A 3P
DIGESTER D
MIXER
AF
AT
VCP-33-125-1A
THICKENING
CENTRIFUGE
5 5 20
SLUDGE
TRANSFER
PUMP NO. 1
MCP
MCP
AF
AT
30A 3P
PRIMARY SCUM
PUMP
NO. 2
30A 3P
7.5
30A 3P
PRIMARY
SLUDGE PUMP
NO. 3
7.5
30A 3P
PRIMARY
SLUDGE PUMP
NO. 4
30A 3P
PRIMARY
SLUDGE
GRINDER NO. 3
30A 3P
PRIMARY
SLUDGE
GRINDER NO. 2
5 1200RPM
30A 3P
SCUM MIXER
NO. 2
PRIMARY SLUDGE
PUMPING STATION #2
PRIMARY SLUDGE
PUMPING STATION #2
7.5
30A 3P
PRIMARY
SLUDGE PUMP
NO. 1
7.5
30A 3P
PRIMARY
SLUDGE PUMP
NO. 2
30A 3P
PRIMARY
SLUDGE
GRINDER NO. 1
30A 3P
SCUM MIXER
NO. 1
30A 3P
PRIMARY SCUM
PUMP NO. 1
PRIMARY SLUDGE
PUMPING STATION #1
PRIMARY SLUDGE
PUMPING STATION #1 DIGESTER BUILDING
DIGESTER BUILDING
MCP
MCP
MCP
MCP
THICKENED
DIGESTER
SLUDGE PUMP
NO.2
MCP
MCP
PRIMARY SCUM
PUMP
NO. 3
2A 2B 2C 2D 2E 3A 3B 3C 3D 4A 4B 4C
10B 10C 10D 11A 11B 11C 11D 12A 12B 12C 12D 13A
1E
FROM
SWGR-SEB-1-B
ETU
1200AF
1200AP
800AT
LSIG
ERMS
N.C. 1200:5
(3)
POWER
METER
SPD
200kA
AF
AT
ET
U
1200AF
1200AP
800AT
LSIG
N.O.
ETU
1200AF
1200AP
800AT
LSIG
ERMS
N.C.1200:5
(3)
POWER
METERK
K
K
SPD
200kA
AF
AT
9A-62-1
9A-63-1
MCP
MCP
AF
AT
AF
AT
AF
AT
SEE BELOW FOR
CONTINUATION
SLUDGE
TRANSFER
PUMP NO. 2
AF
AT
13B
MCP
MCP
RECIRCULATION
PUMP NO. 1
DIGESTER A
MIXER
AF
AT
AF
AT
MCP
SEE ABOVE FOR
CONTINUATION
MCC-SEB-2 SINGLE LINE DIAGRAM
SOLIDS ELECTRICAL BUILDING
MCC-SEB-2-A, 1200A, 480V, 3Ø, 3W, 65kA RMS SYMMETRICAL
MCC-SEB-2-B, 1200A, 480V, 3Ø, 3W, 65kA RMS SYMMETRICAL
FROM
SWGR-SEB-1-A
MCC-SEB-2-B
MCC-SEB-2-A
ETU
400AF
400AP
250AT
LSIG
PP-DSM-1
TX-LP-DSM-1
30kVA 480-120/208V
3P/4W
DRY TRANS
LP-DSM-1
9A-60-1 9A-61-1
9A-61-29A-60-2
9B-60-3 9B-61-3
9B-61-4 9B-63-29B-62-3
9B-62-233-131-1
RECIRCULATION
PUMP NO. 2
33-131-2
RECIRCULATION
PUMP NO. 3
33-131-3
RECIRCULATION
PUMP NO. 4
33-131-4 33-140-1
33-140-233-125-1
33-127-2
THICKENED
DIGESTER
SLUDGE PUMP
NO.1
33-127-1
32A-130-1 32B-130-1
32C-130-1 32D-130-1
P-500-000 P-500-001 P-500-002 P-500-003 P-500-004 P-500-005 P-500-006 P-500-007 P-100-000 P-100-001 P-100-002 P-150-001 P-150-002
P-150-003 P-150-004 P-150-005 P-100-003 P-100-004 P-100-006 P-500-009 P-500-010 P-500-011 P-500-014 P-500-015
P-500-012 P-500-013
P-650-000
P-650-001
P-650-002
CENTRIFUGE
FEED
PUMP NO.1
33-126-1
CENTRIFUGE
FEED
PUMP NO.2
33-126-2
AF
AT
AF
AT
AF
AT
AF
AT
VCP-32A-130-1 VCP-32B-130-1
VCP-32C-130-1 VCP-32D-130-1
AF
AT
AF
AT
AF
AT
AF
AT
VCP-9A-60-1 VCP-9B-60-3
MCP
MCP
MCP
MCP
SEE SHEET E450 SEE SHEET E450
MCP
MCP
AF
AT
MCP
VCP-9A-60-2
0.5
30A 3P
SUMP
PUMP
MCP
9A-64-1
P-100-005
AF
AT
AF
AT
30A 3P
SAMPLE PUMP
NO. 1
30A 3P
SAMPLE PUMP
NO. 2
33-135-1 33-135-2
30A 3P
1.5
POLYMER
MIXING UNIT
33-153-1
VCP-33-153-1
AF
AT
30 MCP
MCP
MCP
30A 3P
DIGESTER
HEATING WATER
PUMP NO. 1
33-248-3
30A 3P
DIGESTER
HEATING WATER
PUMP NO. 2
33-248-4
30A 3P
DIGESTER
HEATING WATER
PUMP NO. 3
33-248-5
30A 3P
DIGESTER
HEATING WATER
PUMP NO. 4
33-248-6
VCP-134
HOT WATER
RECIRCULATION
PUMP NO. 1
33-248-1
HOT WATER
RECIRCULATION
PUMP NO. 2
33-248-2
DIGESTER BUILDING
P-500-016 P-500-017 P-500-019 P-500-020 P-500-022 P-500-023 P-500-024P-500-021 P-500-025
P-500-026
P-500-028 P-500-027
P-150-000
7E
7A
7I
9A
9I
9E8A
10A1B 1C 1D1A 4D 5A 5B 5D
13C 13D 13E 14A 14B 14C 14D 14E12E11E
SPARE
SPARE SPARE SPARE SPARE SPARE SPARE SPARE
VFD
VFD
VFD
VFD
VFD
VFD
P-500-033 P-500-034 P-500-035 P-500-036
P-500-037 P-500-038
NO. DATEISSUED FOR APPROVEDBY
PROJ.ENGR.
CHECKED
DRAWN
DESIGNED
SHEET
DATE:
OF
NUMBER
DRAWING
31111-098
MAY 2026
D C
\A C
C D oc s\
H az en a nd S aw ye r\3
-0
_W
PC
F
So lid s Pr oc es si ng
Im p
Ph I\
Pr oj ec t F ile s\
_D es ig n\ El ec \E
1.
dw g
L as tS av eB y:
JW
TH
O M
PS
O
N
J. HISE
IFB NO.
500640-
FY27-02
1 05/2026BID SET JTH
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
H & S JOB
NUMBER
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
E451
SOLIDS ELECTRICAL BUILDING
ELECTRICAL
MCC-SEB-2 SINGLE LINE DIAGRAM
XX
D. WEBER
E. BODNAR
S. MINETT
287 342
PROPOSED SOLIDS ELEC BLDG MCC
FROM
SWGR-SEB-1-B
ETU
1200AF
1200AP
1200AT
LSIG
ERMS
N.C. 1200:5
(3)
POWER
METER
SPD
200kA
AF
AT
ET
U
1200AF
1200AP
1200AT
LSIG
N.O.
ETU
1200AF
1200AP
1200AT
LSIG
ERMS
N.C.1200:5
(3)
POWER
METERK
K
K
SPD
200kA
MCP
THICKENED
SLUDGE
PUMP NO. 1
30A 3P
MCP
THICKENED
SLUDGE
PUMP NO. 2
30A 3P
MCP
THICKENED
SLUDGE
PUMP NO. 3
30A 3P
MCP
THICKENED
SLUDGE
PUMP NO. 4
30A 3P
AF
AT
PRIMARY
SLUDGE
SCREEN NO. 1
AF
AT
PRIMARY
SLUDGE
SCREEN NO. 2
AF
AT
SPARE 30A
THICKENED SLUDGE
PUMPING STATION
THICKENED SLUDGE
PUMPING STATION
AF
AT
AF
AT
SEE BELOW FOR
CONTINUATION
SPARE
SIZE 1
FVR
MCP
MCC-SEB-1-A, 1200A, 480V, 3Ø, 3W, 65kA RMS SYMMETRICAL
TX-LP-DGB-3
45kVA 480-120/208V
3P/4W
DRY TRANS
LP-DGB-3
AF
AT
S1 S2
L
ATS-SEB-1
480V 250A 3Ø 3W 3P
OPEN TRANSITION
AF
AT
MCC-SEB-1 SINGLE LINE DIAGRAM
SOLIDS ELECTRICAL BUILDING
PP-SEB-1
TX-LP-SEB-1
30kVA 480-120/208V
3P/4W
DRY TRANS
LP-SEB-1
FROM
SWGR-SEB-1-A
PROPOSED SOLIDS ELEC BLDG MCC [E451-E452]
SPARE
MCP
AF
AT
AF
AT
SPARE
PP-SEB-2
0.75
30A 3P
GRAVITY
THICKENER A
ROTATING RAKE
MCP
0.75
30A 3P
GRAVITY
THICKENER B
ROTATING RAKE
MCP
0.75
30A 3P
GRAVITY
THICKENER C
ROTATING RAKE
MCP
30A 3P
PRIMARY SCUM
GRINDER NO. 3
MCP
1A 1B 1C 1D 1E 2A 2B 3D 3E2C 2D 2E 3A 3B 3C 4A
5E
5A
5I
7A
7I
7E
8A
8B 8C 8D 8E 9A 9B 9C 9D 9E
6A
AF
AT
TX-LP-SEB-2
30kVA 480-120/208V
3P/4W
DRY TRANS
LP-SEB-2
ETU
400AF
400AP
250AT
LSIG
ETU
400AF
400AP
250AT
LSIG
31-122-131-122-3
31-122-431-122-2
11-142-1
11-142-2
31-151-131A-121-1 31B-121-1 31C-121-1
SPARE SIZE 1
SEE ABOVE FOR
CONTINUATION
P-200-000 P-200-001 P-200-002 P-400-000P-200-003
P-200-004 P-200-005 P-200-006
P-450-014
P-450-015
P-450-016
P-450-017
P-450-018
P-450-019
P-300-000 P-320-000
P-450-022
P-340-000
P-450-020 P-450-021
MCC-SEB-1-A
MCC-SEB-1-BMCC-SEB-1-B, 1200A, 480V, 3Ø, 3W, 65kA RMS SYMMETRICAL
SEE SHEET E450 SEE SHEET E450
VCP-11-142-1
VCP-11-142-2
VCP-31-151-1
MCP
AF
AT
VCP-38A-119
GRAVITY
THICKENER
SCUM PUMP
NO. 1
38A-119-1
GRAVITY
THICKENER
SCUM PUMP
NO. 2
38A-119-2
VCP-38B-119
GRAVITY
THICKENER
SCUM PUMP
NO. 3
38B-119-3
GRAVITY
THICKENER
SCUM PUMP
NO. 4
38B-119-4
P-400-003
P-400-001 P-400-002
P-400-004 P-400-005
30A 3P
GRAVITY THICKENERS
DIGESTED
SLUDGE
STORAGE MIXING
PUMP NO. 1
AF
AT
34A-147-1
P-650-003
34B-147-2
AF
AT
DIGESTED
SLUDGE
STORAGE MIXING
PUMP NO. 2
SCUM PITSDIGESTED SLUDGE
MIXING BUILDING
SPARE
P-650-004
30A 3P
SPARE
SIZE 1
FVR
MCP
THICKENED
SLUDGE
PUMP NO. 5
30A 3P
31-122-5
P-200-007
PP-DGB-1
P-500-032
XFMR B
45kVA 120/208V
3P/4W
DRY TRANS
XFMR B
45kVA 120/208V
3P/4W
DRY TRANS
LP-DGB-2
P-500-008 P-500-018
LP-DGB-1A LP-DGB-1B
DIGESTER BUILDING
P-450-023
VFD
VFD
P-650-010 P-650-011
NO. DATEISSUED FOR APPROVEDBY
PROJ.ENGR.
CHECKED
DRAWN
DESIGNED
SHEET
DATE:
OF
NUMBER
DRAWING
31111-098
MAY 2026
D C
\A C
C D oc s\
H az en a nd S aw ye r\3
-0
_W
PC
F
So lid s Pr oc es si ng
Im p
Ph I\
Pr oj ec t F ile s\
_D es ig n\ El ec \E
2.
dw g
L as tS av eB y:
JW
TH
O M
PS
O
N
J. HISE
IFB NO.
500640-
FY27-02
1 05/2026BID SET JTH
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
DRAWING.
H & S JOB
NUMBER
HAZEN AND SAWYER
1 SOUTH STREET, SUITE 1150
BALTIMORE, MARYLAND 21202
TOWN OF LEESBURG
LEESBURG, VIRGINIA
WATER POLLUTION CONTROL FACILITY
SOLIDS PROCESSING
IMPROVEMENTS - PHASE 1
E452
SOLIDS ELECTRICAL BUILDING
ELECTRICAL
MCC-SEB-1 SINGLE LINE DIAGRAM
XX
D. WEBER
E. BODNAR
S. MINETT
288 342
SWGR-SEB-1
ATS-SEB-1PLC-38
(FRONT)
MCC-SEB-1
MCC-SEB-2
1 2 3 4 5 6 MAIN
A TIE MAIN
B 10 11 12 13
10 9 8 MAIN
B TIE MAIN
A 4 3 2 1
PP-SEB-1
TX-LP-SEB-1 LP-SEB-1
PP-SEB-2
TX-LP-SEB-2
LP-SEB-2
ELECTRICAL ROOM
HCP-450-1
CP-450-3
CP-450-2
CP-450-1
SEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATIONSEE DRAWING E021
FOR CONTINUATION
SEE DRAWING E021
FOR CONTINUATION
DB
E11
DB
C2
DB
E8
DB
C5
DB
E9
DB
E14
DB
C9
DB
E1
DB
E10
DB
C1
VFD-33-127-2
VFD-33-140-1
VFD-33-127-1
VFD-33-126-2
VFD-33-126-1
VFD-33-140-2
GROUNDING NOTES:
A.
B.
C.
D.
E.
F.
G.
REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING
OF GROUND RING TO STRUCTURAL FOUNDATION
REBAR.
GROUND RING CONDUCTOR SHALL BE #4/0 BARE
COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.
ALL GROUND CONDUCTORS TO EQUIPMENT OR
STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.
EACH DUCT BANK GROUND CONDUCTOR CROSSING
THE GROUND RING SHALL BE EXOTHERMICALLY
WELDED TO THE GROUND RING CONDUCTOR.
ALL TRANSFORMERS, SWITCHGEAR, MOTOR CONTROL
CENTERS, AND PANELBOARDS SHALL BE BONDED TO
THE GROUND RING CONDUCTOR.
FURNISH AND INSTALL LIGHTNING PROTECTION
SYSTEM FOR THIS FACILITY PER SPECIFICATION
26 41 00.
FURNISH AND INSTALL 1" CONDUITS THROUGH
CONCRETE PAD FOR LIGHTNING PROTECTION DOWN
CONDUCTORS TO GROUND RING. ALL DOWN
CONDUCTORS SHALL BE ROUTED DOWN INSIDE OF
BUILDING.
COORDINATE GROUND SYSTEM INSTALLATION WITH
INSTALLATION OF THE LIGHTNING PROTECTION
SYSTEM.
INDOOR WET PROCESS AREA
INDOOR DRY PROCESS AREA
INDOOR DRY NON-PROCESS AREA
AREA DESIGNATION LEGEND:
NOTES:
1. FURNISH AND INSTALL FIRE ALARM SYSTEM FOR THIS
FACILITY PER…