Attachment C - Leesburg WPCF_SPI-1_Bid-Ready Drawings_Vol 6 of 7.pdf

PDF 37 MB Posted

Attached to
IFB No 500640-FY27-02 Solids Processing Improvements - Phase 1
Solicitation number
IFB-124276
Issued by
Loudoun County, Virginia

About this file

This document is a bid-ready electrical power and lighting design drawing set for the Town of Leesburg, Virginia's Water Pollution Control Facility Solids Processing Improvements - Phase 1 project. The drawings, prepared by Hazen and Sawyer engineering firm under Job Number 31111-098, provide comprehensive electrical infrastructure plans for multiple facility components including the Primary Sludge Pumping Stations (Nos. 1 and 2), Thickened Sludge Pumping Station, Gravity Thickeners (A, B, and C), Scum Pits (1 and 2), and the Solids Electrical Building. The design scope encompasses power distribution, lighting layouts, hazardous area classifications per NFPA-820-2024, grounding systems, motor control centers, switchgear, panelboards, and associated electrical schematic diagrams. Electrical equipment includes multiple pumps (primary sludge, scum, thickened sludge, centrifuge feed, digester heating water, and recirculation pumps), grinders, mixers, screens, thickening equipment, unit heaters, exhaust fans, and emergency systems. The drawings indicate forced ventilation systems at six to twelve air changes per hour to downgrade hazardous area classifications from Class I Division 1 or 2 to unclassified in select areas.

The electrical design provides detailed specifications for equipment ratings, conductor sizes, conduit routing, control systems with variable frequency drives (VFDs), and integration with a programmable logic controller (PLC-38). Ground systems utilize #4/0 bare copper wire installed thirty inches minimum below finished grade with exothermic welding at crossing points and bonding to structural steel and motor frames. The project includes dual switchgear units (SWGR-SEB-1-A and SWGR-SEB-1-B) each rated at 2500 kVA with 480V, 3-phase, 4-wire configuration, motor control centers (MCC-SEB-1 and MCC-SEB-2), and panelboards supplied by separate transformers. Fire alarm and lightning protection systems are specified under separate specifications (28 46 20 and 26 41 00 respectively). All drawings were issued for bid set in May 2026 and prepared under IFB No. 500640-FY27-02, with the design reflecting coordination requirements with mechanical systems, instrumentation, and vendor-supplied control panels throughout the facility.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

9A-61-1

9A-60-1

9A-60-2

PRIMARY SLUDGE

PUMP NO. 1

PRIMARY SLUDGE

PUMP NO. 2

PRIMARY SLUDGE

GRINDER NO.2

PRIMARY SLUDGE

GRINDER NO. 1

PRIMARY SCUM PUMP

NO. 1

EX SCUM MIXER NO. 1

9A-62-1

9A-63-1

UH-100-1

UH-100-2

BOND TO EXISTING

GROUND GRID

PUMP ROOM

E100

A_______ E100

A_______

9A-61-2

PG/PSH

9A-61-2

9A-61-2

PG/PSL

9A-61-1

PG/PSH

9A-61-1

SUMP PUMP

9A-64-1

WATER HEATER

WH-100-1

CJB-100-01 PJB-100-01

SF-100-1 CMS

VCP-9A-64-1

SF-100-1

EF-100-1

9A-63-1

EX SCUM MIXER NO. 1

EF-100-1 CMS

9A-63-1 DSW

BOND TO

GROUND TRIAD

DB

E5

DB

C8

CJB-100-01 PJB-100-01

LCS-9A-63-1

SEE DRAWING E021

FOR CONTINUATION

DEMOLTION NOTES:

A.

B.

SEE MECHANICAL DRAWINGS FOR EQUIPMENT BEING

DEMOLISHED AND PROVIDE ELECTRICAL SUPPORT AS

REQUIRED.

REMOVE MOTOR CONTROL CENTERS, POWER

PANELS, LIGHTING PANELS, COMBINATION STARTERS,

DISCONNECT SWITCHES, LOCAL CONTROL PANELS,

LIGHTS, RECEPTACLES, AND ALL WIRING ASSOCIATED

WITH DEMOLISHED EQUIPMENT TO THE POWER

SOURCE, UNLESS OTHERWISE NOTED. REMOVE ALL

ASSOCIATED EXPOSED CONDUITS. TAG ABANDONED

CIRCUIT BREAKERS AS "SPARE".

HAZARDOUS AREAS:

SPACE CLASSIFIED PER NFPA-820-2024

EDITION AS FOLLOWS:

UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):

1. PRIMARY SLUDGE PUMPING STATION NO. 1

TABLE 6.2.2(a), ROW 9, LINE b

THE CLASSIFICATION RATING OF THE PRIMARY

SLUDGE PUMPING STATION NO. 1 IS DOWNGRADED

FROM CLASS I, DIVISION 2 TO UNCLASSIFIED BY

FUNCTION OF FORCED VENTILATION AT SIX AIR

CHANGES PER HOUR. SEE NFPA-820 2024 EDITION,

TABLE 6.2.2(a), ROW 9, LINE b FOR FURTHER

CLARIFICATION.

NOTES:

1.

2.

3.

4.

5.

TRANSITION FROM UNDERGROUND DUCTBANK TO

EXPOSED CONDUIT VIA PJB-100-1 AND CJB-100-1.

ROUTE CONDUITS ALONG THE CONCRETE SLAB OVER

TO THE PUMP ROOM. CORE DRILL AS REQUIRED.

GROUND TRIAD CONDUCTOR SHALL BE #4/0 BARE

COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.

ALL GROUND CONDUCTORS TO EQUIPMENT OR

STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.

EACH DUCT BANK GROUND CONDUCTOR CROSSING

THE GROUND RING SHALL BE EXOTHERMICALLY

WELDED TO THE GROUND RING CONDUCTOR.

ALL MOTOR FRAMES SHALL BE BONDED TO THE

GROUND RING CONDUCTOR.

SEE INSTRUMENTATION DRAWING I100 FOR VENDOR

CONTROL PANELS TO BE INSTALLED FOR PUMP

MONITORING, VCP-9X-6X-X.

INDOOR WET PROCESS AREA

INDOOR DRY PROCESS AREA

INDOOR DRY NON-PROCESS AREA

AREA DESIGNATION LEGEND:

9A-62-1 DSW

9A-60-1 DSW

9A-61-1 DSW UH-100-1 DSW

UH-100-2 DSW

9A-60-2 DSW

9A-61-2 DSW

WH-100-1 DSW

LCS-9A-62-1

LCS-9A-61-2

LCS-9A-60-2

LCS-9A-60-1

LCS-9A-61-1

HCP-100-1

9A-64-1 DSW

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

PS

P1

-E .rv t 5/

/2

9:

:1

AM

E100

E. BODNAR

S. SHUGARS

D. WEBER

PRIMARY SLUDGE PUMPING STATION NO. 1

ELECTRICAL

POWER PLANS

3/8" = 1'-0"

BOTTOM POWER PLAN

3/8" = 1'-0"

TOP POWER PLAN

3/8" = 1'-0" 4'21012"

SECTION

3/8" = 1'-0" E100

A

HS-100-1

1 BID SET 05/2026 JTH

5/15/2026

262 342

LC2

CKT# 9

LC2

CKT# 9

LC2

CKT# 9

XW2

CKT# 9

LW1A

CKT# 9

WPCR/GFCI

CKT# 7

CKT# 7

CKT# 7

CKT# 7

LC2

CKT# 9

CKT# 7

CKT# 7

LC2

CKT# 9

LC2

CKT# 9

LC2A

CKT# 9

LC2A

CKT# 9

NOTES:

1.

2.

3.

4.

5.

MOUNT FIXTURE TYPE "LW##" 6" ABOVE DOOR.

MOUNT FIXTURE TYPE "XW#" 6" ABOVE DOOR.

MOUNT FIXTURE TYPE "LL#" 12'-0" AFF.

MOUNT FIXTURE TYPE "LC##" 12'-0" AFF.

UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED

FROM THE CIRCUIT NOTED IN PANEL LP-SEP-2.

LL1

CKT# 9

LL1

CKT# 9

WPCR/GFCI

CKT# 7

LL1

CKT# 9

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

PS

P1

-E .rv t 5/

/2

9:

:1

AM

E101

E. BODNAR

S. SHUGARS

D. WEBER

PRIMARY SLUDGE PUMPING STATION NO. 1

ELECTRICAL

LIGHTING PLANS

3/8" = 1'-0"

BOTTOM LIGHTING PLAN

3/8" = 1'-0" 4'21012"

3/8" = 1'-0"

TOP LIGHTING PLAN

1 BID SET 05/2026 JTH

263 342

9A-63-1

LE/LT

I-100-000

CJB-100-01

PLC-38

FROM ACP-38

SCUM MIXER

NO. 1

PRIMARY

SCUM PUMP

NO. 1

PRIMARY

SLUDGE

PUMP NO. 1

PRIMARY

SLUDGE

PUMP NO. 2

M

SCUM MIXER

NO. 1

C-100-000

VC

P-

9A -6

2-

LC

S-

9A -6

2-

LC

S-

9A -6

3-

9A-63-1

TSH

M

PRIMARY SCUM

PUMP NO. 1

TE

9A-62-1

PRIMARY SLUDGE

PUMP NO. 1

9A-61-1 9A-61-2

PRIMARY SLUDGE

PUMP NO. 2VC

P- 9A

-6 1-

LC

S-

9A -6

1-

VC

P-

9A -6

1-

LC

S-

9A -6

1-

VCP-9A-60-1

PS

L-

9A -6

1-

PS

L-

9A -6

1-

CJB-100-01

LC

S-

9A -6

0-

TSH

M

9A-60-1

PRIMARY SLUDGE

GRINDER NO. 1

VCP-9A-60-2

CJB-100-01

LC

S-

9A -6

0-

TSH

M

9A-60-2

PRIMARY SLUDGE

GRINDER NO. 2

VCP-9A-64-1

CJB-100-01

9A-64-1

LSH

9A-64-1

LSL M

9A-64-1

SUMP

PUMP

9A-64

LSH

9A-101

FIT

HCP-100-1

C-100-032

C-100-034

PS

H

-9 A-

-1

PS

H

-9 A-

-2

CJB-100-01 CJB-100-01 CJB-100-01

MCC-SEB-2

C-100-001 C-100-002

C-100-006

C-100-007 C-100-008

C-100-003

C-100-009 C-100-010 C-100-011

C-100-012

C-100-004

C-100-017

C-100-014 C-100-015 C-100-016

C-100-019

C-100-023 C-100-027

C-100-020

C-100-024 C-100-028

C-100-021

C-100-022

C-100-025

C-100-026 C-100-030

C-100-031

C-100-029

I-100-002

C-100-033 I-100-003

I-100-001 C-100-013 C-100-018

C-100-035

C-100-036C-100-005

C-100-037

C-100-040

PS

L-

9A -6

2-

VENDOR CABLE

PS

H

-9 A-

-1

TSH

M TE

VENDOR CABLE

TSH

M TE

VENDOR CABLE

C-100-038

C-100-039

NOTES:

1. COORDINATE REQUIREMENTS WITH FINAL

APPROVED VENDOR.

2. COORDINATE WITH MOTOR SCHEMATICS ON

SHEETS E459 TO E462.

NO. DATEISSUED FOR APPROVEDBY

PROJ.ENGR.

CHECKED

DRAWN

DESIGNED

SHEET

DATE:

OF

NUMBER

DRAWING

31111-098

MAY 2026

:1

4A

C

D C

\A C

C D oc s\

H az en a nd S aw ye r\3

-0

_W

PC

F

So lid s Pr oc es si ng

Im p

Ph I\

Pr oj ec t F ile s\

_D es ig n\ El ec \E

2.

dw g

L as tS av eB y:

JW

TH

O M

PS

O

N

J. HISE

IFB NO.

500640-

FY27-02

1 05/2026BID SET JTH

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

H & S JOB

NUMBER

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

E102

PRIMARY SLUDGE PUMPING STATION NO. 1

ELECTRICAL

CONTROL RISER DIAGRAM

XX

D. ATKINSON

J. THOMPSON

D. ATKINSON

264 342

DEMOLITION NOTES:

A.

B.

SEE MECHANICAL DRAWING M150 FOR EQUIPMENT

BEING DEMOLISHED AND PROVIDE ELECTRICAL

SUPPORT AS REQUIRED.

REMOVE MOTOR CONTROL CENTERS, POWER

PANELS, LIGHTING PANELS, COMBINATION STARTERS,

DISCONNECT SWITCHES, LOCAL CONTROL PANELS,

LIGHTS, RECEPTACLES, AND ALL WIRING ASSOCIATED

WITH DEMOLISHED EQUIPMENT TO THE POWER

SOURCE, UNLESS OTHERWISE NOTED. REMOVE ALL

ASSOCIATED EXPOSED CONDUITS. TAG ABANDONED

CIRCUIT BREAKERS AS "SPARE".

9B-61-3

9B-61-4

9B-63-2

EX SCUM MIXER NO. 2

9B-60-3

PRIMARY SLUDGE

GRINDER NO.3

BOND TO EXISTING

GROUND GRID

SF-150-1

EX. PRIMARY SCUM

PUMP NO. 2

EX. PRIMARY SCUM

PUMP NO. 3

E150

A_______ E150

A_______

9B-62-2

9B-62-3

LCS-9B-61-3

LCS-9B-62-2

LCS-9B-60-3

UH-150-2

E150

B_______ E150

B_______

PRIMARY SLUDGE

PUMP NO. 3

PRIMARY SLUDGE

PUMP NO. 4

PUMP ROOM

UH-150-1

WATER HEATER

WH-150-1

HS-150-1

9B-63-2

EX SCUM MIXER NO. 2

EF-150-1 DSW

DB

C6

DB

E7

SEE DRAWING

E021 FOR

CONTINUATION

CJB-150-01

PJB-150-01

EF-150-1

LCS-9B-63-2

9B-63-2 DSW

GROUNDING NOTES:

1.

2.

3.

GROUND TRIAD CONDUCTOR SHALL BE #4/0 BARE

COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.

ALL GROUND CONDUCTORS TO EQUIPMENT OR

STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.

EACH DUCT BANK GROUND CONDUCTOR CROSSING

THE GROUND RING SHALL BE EXOTHERMICALLY

WELDED TO THE GROUND RING CONDUCTOR.

ALL MOTOR FRAMES SHALL BE BONDED TO THE

GROUND RING CONDUCTOR.

INDOOR WET PROCESS AREA

INDOOR DRY PROCESS AREA

INDOOR DRY NON-PROCESS AREA

AREA DESIGNATION LEGEND:

UH-150-1

WH-150-1 DSW

UH-150-2 DSW

9B-61-4 DSW9B-61-3 DSW

9B-60-3 DSW

UH-150-1 DSW

9B-64-2 DSW

9B-62-3 DSW

9B-62-2 DSW

LCS-9B-60-3

LCS-9B-62-2 LCS-9B-61-3

LCS 9B-61-4

LCS-9B-62-3

LCS-9B-60-4

HAZARDOUS AREAS:

SPACE CLASSIFIED PER NFPA-820-2024

EDITION AS FOLLOWS:

UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):

1. PRIMARY SLUDGE PUMPING STATION NO. 2

TABLE 6.2.2(a), ROW 9, LINE b

THE CLASSIFICATION RATING OF THE PRIMARY

SLUDGE PUMPING STATION NO. 2 IS DOWNGRADED

FROM CLASS I, DIVISION 2 TO UNCLASSIFIED BY

FUNCTION OF FORCED VENTILATION AT SIX AIR

CHANGES PER HOUR. SEE NFPA-820 2024 EDITION,

TABLE 6.2.2(a), ROW 9, LINE b FOR FURTHER

CLARIFICATION.

NOTES:

1. SEE INSTRUMENTATION DRAWING I150 FOR VENDOR

CONTROL PANELS TO BE INSTALLED FOR PUMP

MONITORING, VCP-9X-6X-X.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

PS

P2

-E .rv t 5/

/2

9:

:2

AM

E150

E. BODNAR

S. SHUGARS

D. WEBER

PRIMARY SLUDGE PUMPING STATION NO. 2

ELECTRICAL

POWER PLANS

3/8" = 1'-0"

BOTTOM POWER PLAN

3/8" = 1'-0"

TOP POWER PLAN

3/8" = 1'-0" 4'21012"

SECTION

3/8" = 1'-0"

ASECTION

3/8" = 1'-0" E150

B

1 BID SET 05/2026 JTH

265 342

LL1

CKT# 1

LL1

CKT# 1

WPCR/GFCI

CKT# 3

WPCR/GFCI

CKT# 3

CJB-150-01

PJB-150-01

LL1

CKT# 1

LL1

CKT# 1

LL1

CKT# 1

WPCR/GFCI

CKT# 3

WPCR/GFCI

CKT# 3

WPCR/GFCI

CKT# 3

WPCR/GFCI

CKT# 3

WPCR/GFCI

CKT# 3

LC2A

CKT# 1

XW2

CKT# 3

LW1A

CKT# 3

LC2

CKT# 1

LC2

CKT# 1

LC2

CKT# 1

LC2A

CKT# 1

LC2

CKT# 1

LC2

CKT# 1

LC2

CKT# 1

CKT# 3

CKT# 3

NOTES:

1.

2.

3.

4.

5.

MOUNT FIXTURE TYPE "LW##" 6" ABOVE DOOR.

MOUNT FIXTURE TYPE "XW#" 6" ABOVE DOOR.

MOUNT FIXTURE TYPE "LL#" 12'-0" AFF.

MOUNT FIXTURE TYPE "LC##" 12'-0" AFF.

UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED

FROM THE CIRCUIT NOTED IN PANEL LP-SEP-2.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

PS

P2

-E .rv t 5/

/2

9:

:2

AM

E151

E. BODNAR

S. SHUGARS

D. WEBER

PRIMARY SLUDGE PUMPING STATION NO. 2

ELECTRICAL

LIGHTING PLANS

3/8" = 1'-0" 4'21012"

3/8" = 1'-0"

TOP LIGHTING PLAN

3/8" = 1'-0"

BOTTOM LIGHTING PLAN

1 BID SET 05/2026 JTH

266 342

CJB-150-01

PLC-38

FROM ACP-38

M

CJB-150-01

MCC-SEB-2

TSH

M TE

VENDOR CABLE

9B-63-2

LE/LT

I-150-000

SCUM MIXER

NO. 2

PRIMARY

SCUM PUMP

NO. 2

PRIMARY

SCUM PUMP

NO. 3

PRIMARY

SLUDGE

PUMP NO. 3

SCUM MIXER

NO. 2

VC

P-

9B -6

2-

LC

S-

9B -6

2-

LC

S-

9B -6

3-

9B-63-2

M

PRIMARY SCUM

PUMP NO. 2

TE

9B-62-2

VC

P-

9B -6

2-

LC

S-

9B -6

2-

PRIMARY SCUM

PUMP NO. 3

9B-62-3 9B-61-3

PRIMARY SLUDGE

PUMP NO. 3 VC

P- 9B

-6 1-

LC

S-

9B -6

1-

PS

L-

9B -6

1-

PS

H

-9 B-

-3

PRIMARY

SLUDGE

PUMP NO. 4

9B-61-4

PRIMARY SLUDGE

PUMP NO. 4 VC

P- 9B

-6 1-

LC

S-

9B -6

1-

PS

L-

9B -6

1-

PS

H

-9 B-

-4

VCP-9B-60-3

CJB-150-01

LC

S-

9B -6

0-

TSH

M

9B-60-3

PRIMARY SLUDGE

GRINDER NO. 3

9B-64

LSH

9B-102

FIT

HCP-150-1

I-150-001 I-150-005

C-150-001

C-150-000

C-150-003 C-150-005

C-150-020

C-150-021

C-150-024

C-150-025

C-150-026

C-150-028

I-150-004

C-150-029 C-150-002 C-150-022

C-150-023

C-150-027

CJB-150-01 CJB-150-01

M

TE TSH

M TE

VENDOR CABLE

C-150-004

C-150-007

C-150-006 C-150-008

C-150-009 C-150-010 C-150-011 C-150-012 C-150-013

C-150-014

C-150-015 C-150-016 C-150-017 C-150-018 C-150-019

NOTES:

1. COORDINATE REQUIREMENTS WITH FINAL

APPROVED VENDOR.

2. COORDINATE WITH MOTOR SCHEMATICS ON

SHEETS E459 TO E462.

NO. DATEISSUED FOR APPROVEDBY

PROJ.ENGR.

CHECKED

DRAWN

DESIGNED

SHEET

DATE:

OF

NUMBER

DRAWING

31111-098

MAY 2026

D C

\A C

C D oc s\

H az en a nd S aw ye r\3

-0

_W

PC

F

So lid s Pr oc es si ng

Im p

Ph I\

Pr oj ec t F ile s\

_D es ig n\ El ec \E

2.

dw g

L as tS av eB y:

JW

TH

O M

PS

O

N

J. HISE

IFB NO.

500640-

FY27-02

1 05/2026BID SET JTH

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

H & S JOB

NUMBER

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

E152

PRIMARY SLUDGE PUMPING STATION NO. 2

ELECTRICAL

CONTROL RISER DIAGRAM

XX

D. ATKINSON

J. THOMPSON

D. ATKINSON

267 342

GRAVITY THICKENER A

(SEE E300 DRAWING SERIES)

GRAVITY THICKENER B

(SEE E320 DRAWING SERIES)

GRAVITY THICKENER C

(SEE E340 DRAWING SERIES)

SPLITTER BOX

SOLIDS ELECTRICAL BUILDING

(SEE E450 DRAWING SERIES)

TX-37-36A

TX-37-36B

DB

E11

DB

C2

DB

E9

DB

C5

DB

E8

DB

E14

DB

C9

DB

E1

DB

E10

DB

C1

STAIRWELL B

DUMPSTER ROOM

STAIRWELL A

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

TS

PS

-E .rv t 5/

/2

9:

:3

AM

E200

E. BODNAR

D. ATKINSON

D. ATKINSON

THICKENED SLUDGE PUMPING STATION

ELETRICAL

AREA PLAN

3/16" = 1'-0"

AREA PLAN

3/16" = 1'-0" 5'0246

SEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

1 BID SET 05/2026 JTH

268 342

UP

31-122-131-122-231-122-331-122-4

E206 2_______

LCS-31-151-1

PUMP ROOM

STAIRWELL A

STAIRWELL B

E206 1_______

E206 1_______

31-151-1

GRINDER

31-122-5

E201 A_______

E201 A_______

UP

GROUNDING NOTES:

A.

B.

C.

D.

E.

F.

G.

REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING

OF GROUND RING TO STRUCTURAL FOUNDATION

REBAR.

GROUND RING CONDUCTOR SHALL BE #4/0 BARE

COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.

ALL GROUND CONDUCTORS TO EQUIPMENT OR

STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.

EACH DUCT BANK GROUND CONDUCTOR CROSSING

THE GROUND RING SHALL BE EXOTHERMICALLY

WELDED TO THE GROUND RING CONDUCTOR.

ALL MOTOR FRAMES SHALL BE BONDED TO THE

GROUND RING CONDUCTOR.

FURNISH AND INSTALL LIGHTNING PROTECTION

SYSTEM FOR THIS FACILITY PER SPECIFICATION

26 41 00.

FURNISH AND INSTALL 1" CONDUITS THROUGH

CONCRETE PAD FOR LIGHTNING PROTECTION DOWN

CONDUCTORS TO GROUND RING. ALL DOWN

CONDUCTORS SHALL BE ROUTED DOWN INSIDE OF

BUILDING.

COORDINATE GROUND SYSTEM INSTALLATION WITH

INSTALLATION OF THE LIGHTNING PROTECTION

SYSTEM.

INDOOR WET PROCESS AREA

INDOOR DRY PROCESS AREA

INDOOR DRY NON-PROCESS AREA

AREA DESIGNATION LEGEND:

NOTES:

1.

2.

IN GENERAL, NOT ALL OF THE REQUIRED JUNCTION

AND PULL BOXES ARE SHOWN ON THE PLANS.

CONTRACTOR SHALL PROVIDE AND FIELD LOCATE

SUCH BOXES AS REQUIRED BY CODE, SITE

CONDITIONS, AND SPECIFICATIONS, FOR PROPER

PULLS AND BENDS, AT NO ADDITIONAL COST TO THE

OWNER.

SEE INSTRUMENTATION DRAWING I201 FOR VENDOR

CONTROL PANELS TO BE INSTALLED FOR PUMP

MONITORING, VCP-31-122-X.

VCP-31-151

FIT

31-152-1

FIT

31-463-1

31-122-4 DSW

31-122-3 DSW

31-122-2 DSW

31-122-1 DSW

LCS-31-122-4

LCS-31-122-3

LCS-31-122-2

LCS-31-122-1

HAZARDOUS AREAS:

SPACE CLASSIFIED PER NFPA-820-2024

EDITION AS FOLLOWS:

UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):

1. PUMP ROOM

TABLE 6.2.2(a), ROW 9, LINE b

THE CLASSIFICATION RATING OF THE PUMP ROOM IS

DOWNGRADED FROM CLASS I, DIVISION 2 TO

UNCLASSIFIED BY FUNCTION OF FORCED VENTILATION

AT SIX AIR CHANGES PER HOUR. SEE NFPA-820 2024

EDITION, TABLE 6.2.2(a), ROW 9, LINE b FOR FURTHER

CLARIFICATION.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

TS

PS

-E .rv t 5/

/2

9:

:3

AM

E201

E. BODNAR

D. ATKINSON

D. ATKINSON

THICKENED SLUDGE PUMPING STATION

ELETRICAL

BOTTOM POWER PLAN

1/4" = 1'-0"

BOTTOM POWER PLAN

GROUND ROD

TEST WELL

GROUND ROD,

TYP

1/4" = 1'-0" 1 1 3 7'0 2

SECTION

1/4" = 1'-0" E201

A

1 BID SET 05/2026 JTH

269 342

MAU-200-1 DSW

DUMPSTER ROOM

STAIRWELL A

STAIRWELL B

EF-200-1

MAU-200-1

EF-200-1 DSW

SF-200-2

SF-200-1 DSW

FACP-TSPS

NOTES:

1.

2.

IN GENERAL, NOT ALL OF THE REQUIRED JUNCTION

AND PULL BOXES ARE SHOWN ON THE PLANS.

CONTRACTOR SHALL PROVIDE AND FIELD LOCATE

SUCH BOXES AS REQUIRED BY CODE, SITE

CONDITIONS, AND SPECIFICATIONS, FOR PROPER

PULLS AND BENDS, AT NO ADDITIONAL COST TO THE

OWNER.

FURNISH AND INSTALL FIRE ALARM SYSTEM FOR THIS

FACILITY PER SPECIFICATION 28 46 20.

INDOOR WET PROCESS AREA

INDOOR DRY PROCESS AREA

INDOOR DRY NON-PROCESS AREA

AREA DESIGNATION LEGEND:

HAZARDOUS AREAS:

SPACE CLASSIFIED PER NFPA-820-2024

EDITION AS FOLLOWS:

UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):

1. DUMPSTER ROOM

TABLE 6.2.2(a), ROW 1

THE CLASSIFICATION RATING OF THE DUMPSTER

ROOM IS UNCLASSIFIED. SEE NFPA-820 2024 EDITION,

TABLE 6.2.2(a), ROW 1 FOR FURTHER CLARIFICATION.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

TS

PS

-E .rv t 5/

/2

9:

:4

AM

E202

E. BODNAR

D. ATKINSON

D. ATKINSON

THICKENED SLUDGE PUMPING STATION

ELETRICAL

TOP POWER PLAN

1/4" = 1'-0"

TOP POWER PLAN

1/4" = 1'-0" 1 1 3 7'0 2

1 BID SET 05/2026 JTH

270 342

SCREENING ROOM

SF-200-1

SF-200-2 DSW

PNEUMATIC PANEL,

TYP

EF-200-2

SF-200-3

UH-200-2

11-142-2

VCP-11-142-1

VCP-11-142-1

11-142-1

11-142-2 DSW

11-142-1 DSW

SF-200-3

UH-200-3 DSW

EF-200-2 DSW

INDOOR WET PROCESS AREA

INDOOR DRY PROCESS AREA

INDOOR DRY NON-PROCESS AREA

AREA DESIGNATION LEGEND:

NOTES:

1. IN GENERAL, NOT ALL OF THE REQUIRED JUNCTION

AND PULL BOXES ARE SHOWN ON THE PLANS.

CONTRACTOR SHALL PROVIDE AND FIELD LOCATE

SUCH BOXES AS REQUIRED BY CODE, SITE

CONDITIONS, AND SPECIFICATIONS, FOR PROPER

PULLS AND BENDS, AT NO ADDITIONAL COST TO THE

OWNER.

HAZARDOUS AREAS:

SPACE CLASSIFIED PER NFPA-820-2024

EDITION AS FOLLOWS:

UNCLASSIFIED AREAS (WITH NFPA 820 REQUIREMENTS):

1. SCREENING ROOM

TABLE 6.2.2(a), ROW 1

THE CLASSIFICATION RATING OF THE SCREENING

ROOM IS UNCLASSIFIED. SEE NFPA-820 2024 EDITION,

TABLE 6.2.2(a), ROW 1 FOR FURTHER CLARIFICATION.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

TS

PS

-E .rv t 5/

/2

9:

:4

AM

E203

E. BODNAR

D. ATKINSON

D. ATKINSON

THICKENED SLUDGE PUMPING STATION

ELETRICAL

UPPER POWER PLANS

1/4" = 1'-0"

UPPPER POWER PLAN

1/4" = 1'-0" 1 1 3 7'0 2

3/16" = 1'-0" 5'0246

1 BID SET 05/2026 JTH

271 342

LP1

CKT# 15

XW2

CKT#

LC1A

CKT# 15

XW2

CKT#

GFCI

CKT#

GFCI

CKT#

GFCI

CKT#

GFCI

CKT#

GFCI

CKT#

GFCI

CKT#

GFCI

CKT#

GFCI

CKT#

LC1A

CKT# 15

LP1

CKT# 15

LP1

CKT# 15

LP1A

CKT# 15

LP1

CKT# 15

LP1A

CKT# 15

LP1

CKT# 15

LP1

CKT# 15

LP1

CKT# 15

LP1

CKT# 15

LP1

CKT# 15

LP1

CKT# 15

LP1A

CKT# 15

LP1

CKT# 15

LP1

CKT# 15

LP1

CKT# 15

NOTES:

1.

2.

3.

4.

5.

MOUNT FIXTURE TYPES ["LP##" 11'-10" AFF.]

MOUNT FIXTURE TYPES ["LC##" 12'-0" AFF.]

MOUNT FIXTURE TYPE ["XW#" 6" ABOVE DOOR.]

LIGHT FIXTURE TYPES LC1A AND LP1A SHALL REMAIN

UN-SWITCHED AND SERVE AS A NIGHT LIGHT FOR

EGRESS.

UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED

FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

TS

PS

-E .rv t 5/

/2

9:

:4

AM

E204

E. BODNAR

D. ATKINSON

D. ATKINSON

THICKENED SLUDGE PUMPING STATION

ELETRICAL

BOTTOM LIGHTING PLAN

1/4" = 1'-0"

BOTTOM LIGHTING PLAN

1/4" = 1'-0" 1 1 3 7'0 2

1 BID SET 05/2026 JTH

272 342

LP1A

CKT# 39

LW1

CKT# 39

LW1

CKT# 39

LW1

CKT# 39

LW1A

CKT# 39

XW1

CKT#

LW1

CKT# 39

LW1

CKT# 39

XW2

CKT#

XW2

CKT# 1

LW1A

CKT# 39

LW1

CKT# 39

LW1A

CKT# 39

XW1

CKT# 1

LW1

CKT# 39

LW1

CKT# 39

LW1

CKT# 39

WPCR/GFCI

CKT# 9

WPCR/GFCI

CKT#

WPCR/GFCI

CKT#

WPCR/GFCI

CKT#

WPCR/GFCI

CKT#

WPCR/GFCI

CKT#

WPCR/GFCI

CKT#

LP1A

CKT# 39

LL1

CKT# 39

LL1

CKT# 39

LP1

CKT# 39

LP1

CKT# 39

LP1

CKT# 39

LP1

CKT# 39

LP1A

CKT# 39

LC1A

CKT# 39

LC1A

CKT# 39

LP1A

CKT# 39

LP1A

CKT# 39

NOTES:

1.

2.

3.

4.

5.

6.

7.

MOUNT FIXTURE TYPES ["LP##" 12'-0" AFF.]

MOUNT FIXTURE TYPES ["LC##" 12'-0" AFF.]

MOUNT FIXTURE TYPE ["XW#" 6" ABOVE DOOR.]

MOUNT FIXTURE TYPE ["LW##" 6" ABOVE DOOR.]

MOUNT FIXTURE TYPE ["LL#" 10'-0" AFF.]

LIGHT FIXTURE TYPES LC1A AND LP1A SHALL REMAIN

UN-SWITCHED AND SERVE AS A NIGHT LIGHT FOR

EGRESS.

UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED

FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

TS

PS

-E .rv t 5/

/2

9:

:4

AM

E205

E. BODNAR

D. ATKINSON

D. ATKINSON

THICKENED SLUDGE PUMPING STATION

ELETRICAL

TOP LIGHTING PLAN

1/4" = 1'-0"

TOP LIGHTING PLAN

1/4" = 1'-0" 1 1 3 7'0 2

1 BID SET 05/2026 JTH

273 342

XW2

CKT#

LC1A

CKT# 15

XW1

CKT#

LP1A

CKT# 39

LP1A

CKT# 39

LP1A

CKT# 39

LW1

CKT# 39

LW1

CKT# 39

LC1A

CKT# 23

LC1A

CKT# 23

LC1A

CKT# 39

LW1A

CKT# 39

XW1

CKT# 1

LC1A

CKT# 39

LC1A

CKT# 15

LC1A

CKT# 23

XW1

CKT#

WPCR/GFCI

CKT#

WPCR/GFCI

CKT#

WPCR/GFCI

CKT#

WPCR/GFCI

CKT#

LC1A

CKT# 23

LC1

CKT# 23

LC1

CKT# 23

LC1A

CKT# 23

LC1A

CKT# 23

LC1

CKT# 23

LC1

CKT# 23

NOTES:

1.

2.

3.

4.

5.

6.

MOUNT FIXTURE TYPES ["LP##" 12'-0" AFF.]

MOUNT FIXTURE TYPES ["LC##" 12'-0" AFF.]

MOUNT FIXTURE TYPE ["XW#" 6" ABOVE DOOR.]

MOUNT FIXTURE TYPE ["LW##" 6" ABOVE DOOR.]

LIGHT FIXTURE TYPES LC1A AND LP1A SHALL REMAIN

UN-SWITCHED AND SERVE AS A NIGHT LIGHT FOR

EGRESS.

UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED

FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

TS

PS

-E .rv t 5/

/2

9:

:4

AM

E206

E. BODNAR

D. ATKINSON

D. ATKINSON

THICKENED SLUDGE PUMPING STATION

ELETRICAL

UPPER LIGHTING PLAN AND SECTIONS

SECTION

1/4" = 1'-0" E201

2 SECTION

1/4" = 1'-0" E201

1/4" = 1'-0"

UPPER LIGHTING PLAN

1/4" = 1'-0" 1 1 3 7'0 2

1 BID SET 05/2026 JTH

274 342

PLC-38

FROM ACP-38

VCP-11-142-1

TSH

M

PRIMARY SLUDGE

SCREEN NO. 2

M

SH

-1 1-

2-

VCP-11-143-111-142-1A

PIT

11-142-1B

PIT

NSHH

M

31A-121-1

GRAVITY THICKENER

A ROTATING RAKE

NSH NSHH

M

31B-121-1

GRAVITY THICKENER

B ROTATING RAKE

NSH NSHH

M

31C-121-1

GRAVITY THICKENER

C ROTATING RAKE

NSH

C-200-015

THICKENED

SLUDGE

PUMP NO. 1

THICKENED

SLUDGE

PUMP NO. 2

TSH

M

THICKENED

SLUDGE PUMP NO. 1

TE

31-122-1

VC

P-

-1

-1

LC

S-

-1

-1

PS

L-

-1

-1

A

PS

H

-3 1-

2-

1B

C-200-018

TSH

M

THICKENED SLUDGE

PUMP NO. 2

TE

31-122-2

VC

P-

-1

-2

LC

S-

-1

-2

PS

L-

-1

-2

A

PS

H

-3 1-

2-

2B

THICKENED

SLUDGE

PUMP NO. 3

TSH

M

THICKENED SLUDGE

PUMP NO. 3

TE

31-122-3

VC

P-

-1

-3

LC

S-

-1

-3

PS

L-

-1

-3

A

PS

H

-3 1-

2-

3B

THICKENED

SLUDGE

PUMP NO. 4

TSH

M

THICKENED SLUDGE

PUMP NO. 4

TE

31-122-4

VC

P-

-1

-4

LC

S-

-1

-4

PS

L-

-1

-4

A

PS

H

-3 1-

2-

4B

C-200-001

C-200-002 C-200-004 C-200-005

C-200-016 C-200-017

C-200-023 C-200-019 C-200-020

C-200-021 C-200-022

C-200-028 C-200-024 C-200-025

C-200-026 C-200-027

C-200-033 C-200-029 C-200-030

C-200-031 C-200-032

C-300-002 C-320-002 C-340-002

C-200-000

I-200-001 I-200-002

VCP-31A-121-1 VCP-31B-121-1 VCP-31C-121-1

MCC-SEB-1

31-463-1

FE

31-463-1

FIT

HCP-200-2

C-200-036 C-200-037

HCP-200-1

C-200-038 C-200-039

31-152-1

FE

31-152-1

FIT

I-200-008

C-300-000 C-320-000 C-340-000

I-200-006

I-200-007 I-200-009

CJB-300-01 CJB-320-01 CJB-340-01

C-300-001 C-320-001 C-340-001

VCP-38A-119

M

SH

-3 8A

-1

-1

38A-119-1

GRAVITY

THICKENER SCUM

PUMP NO. 1

M

SH

-3 8A

-1

-2

38A-119-2

GRAVITY

THICKENER SCUM

PUMP NO. 2

38A-119-2

LSL

C-400-000

VCP-38B-119

M

SH

-3 8B

-1

-3TSH

M

38B-119-3

GRAVITY

THICKENER SCUM

PUMP NO. 3

M

SH

-3 8B

-1

-4TSH

M

38B-119-4

GRAVITY

THICKENER SCUM

PUMP NO. 4

38B-119-4

LSL

C-400-009 C-400-008

I-400-000 I-400-002

C-400-010

C-400-011

VCP-11-142-2

TSH

M

PRIMARY SLUDGE

SCREEN NO. 2

M

SH

-1 1-

2-

VCP-11-143-211-142-2A

PIT

11-142-2B

PIT

C-200-007

C-200-008 C-200-010 C-200-011

C-200-006

I-200-004 I-200-005

11-142-1 11-142-2

11-142-1

HS

11-142-2

HS

C-200-003 C-200-009

M

31-151-1

PRIMARY SCUM

GRINDER

VCP-31-151-1

C-200-012

LC

S-

-1

-1

PLC-38

SEE BELOW FOR

CONTINUATION

SEE ABOVE FOR

CONTINUATION

VENDOR CABLE VENDOR CABLE VENDOR CABLE VENDOR CABLE

C-200-013 C-200-014

C-200-035 C-200-034

38B-119-3

LSL

C-400-007

38B-119-1

LE/LT

I-400-003

TSH

M

TSH

M

C-400-002 C-400-001

C-400-006

C-400-004 C-400-005

38A-119-1

LSL

C-400-003

38B-119-1

LE/LT

I-400-001

C-400-012 C-400-013

NOTES:

1. COORDINATE REQUIREMENTS WITH FINAL

APPROVED VENDOR.

2. COORDINATE WITH MOTOR SCHEMATICS ON

SHEETS E459 TO E462.

NO. DATEISSUED FOR APPROVEDBY

PROJ.ENGR.

CHECKED

DRAWN

DESIGNED

SHEET

DATE:

OF

NUMBER

DRAWING

31111-098

MAY 2026

D C

\A C

C D oc s\

H az en a nd S aw ye r\3

-0

_W

PC

F

So lid s Pr oc es si ng

Im p

Ph I\

Pr oj ec t F ile s\

_D es ig n\ El ec \E

7.

dw g

L as tS av eB y:

JW

TH

O M

PS

O

N

J. HISE

IFB NO.

500640-

FY27-02

1 05/2026BID SET JTH

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

H & S JOB

NUMBER

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

E207

THICKENED SLUDGE PUMPING STATION

ELECTRICAL

CONTROL RISER DIAGRAMS

XX

D. ATKINSON

J. THOMPSON

D. ATKINSON

275 342

NOTES:

1.

2.

3.

4.

5.

6.

7.

REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING

OF GROUND RING TO STRUCTURAL FOUNDATION

REBAR.

GROUND RING CONDUCTOR SHALL BE #4/0 BARE

COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.

ALL GROUND CONDUCTORS TO EQUIPMENT OR

STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.

EACH DUCT BANK GROUND CONDUCTOR CROSSING

THE GROUND RING SHALL BE EXOTHERMICALLY

WELDED TO THE GROUND RING CONDUCTOR.

ALL MOTOR FRAMES SHALL BE BONDED TO THE

GROUND RING CONDUCTOR.

LOCATE JUNCTION BOX CJB-300-01 AND PJB-300-01 AT

GRADE. TRANSITION TO EXPOSED CONDUITS. ROUTE

CONDUITS BENEATH THE WALKWAY BRIDGE TO THE

EQUIPMENT LOCATED IN THE CENTER OF PLATFORM.

MOUNT FIXTURE TYPE ["LL#" 10'-0" AFF.]

UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED

FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.

CJB-300-01

PJB-300-01

SEE DRAWING E021

FOR CONTINUATION

DB

E11

DB

C2

GROUND ROD TEST WELL

GROUND ROD, TYP

LL1

CKT# 27

SEE DRAWING E021

FOR CONTINUATION

31A-121-1

E300

A_______

E300

A_______

WPCR/GFCI

CKT#

VCP-31A-121-1

PJB-300-01

CJB-300-01

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

G

TA

-E .rv t 5/

/2

9:

:5

AM

E300

K. SIMMONS

D. WEBER

E. FRANCOIS

GRAVITY THICKENER A

ELECTRICAL

POWER AND LIGHTING PLAN

3/8" = 1'-0" 4'21012"

3/8" = 1'-0"

POWER AND LIGHTING PLAN

N

SECTION

3/8" = 1'-0" E300

A

1 BID SET 05/2026 JTH

276 342

HAZARDOUS AREAS:

SPACE CLASSIFIED PER NFPA-820-2024

EDITION AS FOLLOWS:

CLASS I, DIVISION 2 AREAS:

1. GRAVITY THICKENER A

TABLE 6.2.2(a), ROW 8, LINE b

THE CLASSIFICATION RATING OF THE GRAVITY

THICKENER A IS DOWNGRADED FROM CLASS I,

DIVISION 1 TO CLASS I, DIVISION 2 BY FUNCTION OF

FORCED VENTILATION AT 12 AIR CHANGES PER

HOUR. SEE NFPA-820 2024 EDITION, TABLE 6.2.2(a), ROW 8, LINE b FOR FURTHER CLARIFICATION

ENCLOSED - ENTIRE SPACE

2. ODOR CONTROL PIPING

TABLE 5.2.2 ROW 28 &

4.2.2 ROW 18, LINE c

AREAS WITHIN 3FT OF LEAKAGE SOURCES SUCH

AS VENTS, FANS, DAMPERS, FLEXIBLE

CONNECTIONS, FLANGES, PRESSURIZED

UNWELDED DUCTWORK, AND ODOR CONTROL

VESSELS

E301

A_______ E301

A_______

3'

0"

CLASS I, DIV 1

CLASS I, DIV 2

LEGEND:

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

G

TA

-E .rv t 5/

/2

9:

:5

AM

E301

J. THOMPSON

D. ATKINSON

D. ATKINSON

GRAVITY THICKENER A

ELECTRICAL

HAZARDOUS AREA PLANS AND SECTIONS

3/8" = 1'-0" 4'21012"

3/8" = 1'-0"

CLASSIFICATION PLAN SECTION

3/8" = 1'-0" E301

A

1 BID SET 05/2026 JTH

277 342

PJB-320-01

SEE DRAWING E021

FOR CONTINUATION

CJB-320-01

VCP-31B-121-1

GROUND ROD, TYP

GROUND ROD TEST WELL

DB

E12

DB

C3

WPCR/GFCI

CKT#

LL1

CKT# 10

SEE DRAWING E021

FOR CONTINUATION

31B-121-1

E320

A_______

E320

A_______

NOTES:

1.

2.

3.

4.

5.

6.

7.

REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING

OF GROUND RING TO STRUCTURAL FOUNDATION

REBAR.

GROUND RING CONDUCTOR SHALL BE #4/0 BARE

COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.

ALL GROUND CONDUCTORS TO EQUIPMENT OR

STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.

EACH DUCT BANK GROUND CONDUCTOR CROSSING

THE GROUND RING SHALL BE EXOTHERMICALLY

WELDED TO THE GROUND RING CONDUCTOR.

ALL MOTOR FRAMES SHALL BE BONDED TO THE

GROUND RING CONDUCTOR.

LOCATE JUNCTION BOX CJB-320-01 AND PJB-320-01 AT

GRADE. TRANSITION TO EXPOSED CONDUITS. ROUTE

CONDUITS BENEATH THE WALKWAY BRIDGE TO THE

EQUIPMENT LOCATED IN THE CENTER OF PLATFORM.

MOUNT FIXTURE TYPE ["LL#" 10'-0" AFF.]

UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED

FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.CJB-320-01 PJB-320-01

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

G

TB

-E .rv t 5/

/2

9:

:5

AM

E320

K. SIMMONS

D. WEBER

E. FRANCOIS

GRAVITY THICKENER B

ELECTRICAL

POWER AND LIGHTING PLAN

3/8" = 1'-0"

TOP PLAN

3/8" = 1'-0" 4'21012"

N

SECTION

3/8" = 1'-0" E320

A

1 BID SET 05/2026 JTH

278 342

SPACE CLASSIFIED PER NFPA-820-2024

EDITION AS FOLLOWS:

CLASS I, DIVISION 2 AREAS:

1. GRAVITY THICKENER B

TABLE 6.2.2(a), ROW 8, LINE b

THE CLASSIFICATION RATING OF THE GRAVITY

THICKENER B IS DOWNGRADED FROM CLASS I,

DIVISION 1 TO CLASS I, DIVISION 2 BY FUNCTION OF

FORCED VENTILATION AT 12 AIR CHANGES PER

HOUR. SEE NFPA-820 2024 EDITION, TABLE 6.2.2(a), ROW 8, LINE b FOR FURTHER CLARIFICATION

ENCLOSED - ENTIRE SPACE

2. ODOR CONTROL PIPING

TABLE 5.2.2 ROW 28 &

4.2.2 ROW 18, LINE c

AREAS WITHIN 3FT OF LEAKAGE SOURCES SUCH

AS VENTS, FANS, DAMPERS, FLEXIBLE

CONNECTIONS, FLANGES, PRESSURIZED

UNWELDED DUCTWORK, AND ODOR CONTROL

VESSELS

CLASS I, DIV 1

CLASS I, DIV 2

LEGEND:

E321

A_______ E321

A_______

3'

0"

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

G

TB

-E .rv t 5/

/2

9:

:5

AM

E321

J. THOMPSON

D. ATKINSON

D. ATKINSON

GRAVITY THICKENER B

ELECTRICAL

HAZARDOUS AREA PLANS AND SECTIONS

3/8" = 1'-0" 4'21012"

3/8" = 1'-0"

CLASSIFICATION PLAN SECTION

3/8" = 1'-0" E321

A

1 BID SET 05/2026 JTH

279 342

PJB-340-01

FOR CONTINUATION

DB

E13

DB

C4

CJB-340-01

VCP-31C-121-1 GROUND ROD, TYP

GROUND ROD TEST WELL

WPCR/GFCI

CKT# 4

LL1

CKT# 35

SEE DRAWING E021

FOR CONTINUATION

E340

A_______

E340

A_______

31C-121-1

NOTES:

1.

2.

3.

4.

5.

6.

7.

REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING

OF GROUND RING TO STRUCTURAL FOUNDATION

REBAR.

GROUND RING CONDUCTOR SHALL BE #4/0 BARE

COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.

ALL GROUND CONDUCTORS TO EQUIPMENT OR

STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.

EACH DUCT BANK GROUND CONDUCTOR CROSSING

THE GROUND RING SHALL BE EXOTHERMICALLY

WELDED TO THE GROUND RING CONDUCTOR.

ALL MOTOR FRAMES SHALL BE BONDED TO THE

GROUND RING CONDUCTOR.

LOCATE JUNCTION BOX CJB-340-01 AND PJB-340-01 AT

GRADE. TRANSITION TO EXPOSED CONDUITS. ROUTE

CONDUITS BENEATH THE WALKWAY BRIDGE TO THE

EQUIPMENT LOCATED IN THE CENTER OF PLATFORM.

MOUNT FIXTURE TYPE ["LL#" 10'-0" AFF.]

UNLESS OTHERWISE NOTED EQUIPMENT IS POWERED

FROM THE CIRCUIT NOTED IN PANEL LP-SEB-1.

CJB-340-01

PJB-340-01

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

G

TC

-E .rv t 5/

/2

9:

:0

AM

E340

K. SIMMONS

D. WEBER

E. FRANCOIS

GRAVITY THICKENER C

ELECTRICAL

POWER AND LIGHTING PLAN

3/8" = 1'-0"

TOP PLAN

3/8" = 1'-0" 4'21012"

SECTION

3/8" = 1'-0" E340

A

1 BID SET 05/2026 JTH

280 342

SPACE CLASSIFIED PER NFPA-820-2024

EDITION AS FOLLOWS:

CLASS I, DIVISION 2 AREAS:

1. GRAVITY THICKENER C

TABLE 6.2.2(a), ROW 8, LINE b

THE CLASSIFICATION RATING OF THE GRAVITY

THICKENER C IS DOWNGRADED FROM CLASS I,

DIVISION 1 TO CLASS I, DIVISION 2 BY FUNCTION OF

FORCED VENTILATION AT 12 AIR CHANGES PER

HOUR. SEE NFPA-820 2024 EDITION, TABLE 6.2.2(a), ROW 8, LINE b FOR FURTHER CLARIFICATION

ENCLOSED - ENTIRE SPACE

2. ODOR CONTROL PIPING

TABLE 5.2.2 ROW 28 &

4.2.2 ROW 18, LINE c

AREAS WITHIN 3FT OF LEAKAGE SOURCES SUCH

AS VENTS, FANS, DAMPERS, FLEXIBLE

CONNECTIONS, FLANGES, PRESSURIZED

UNWELDED DUCTWORK, AND ODOR CONTROL

VESSELS

E341

A_______ E341

A_______

3' - 7 5/8"

3' - 0"

CLASS I, DIV 1

CLASS I, DIV 2

LEGEND:

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

G

TC

-E .rv t 5/

/2

9:

:0

AM

E341

J. THOMPSON

D. ATKINSON

D. ATKINSON

GRAVITY THICKENER C

ELECTRICAL

HAZARDOUS AREA PLANS AND SECTIONS

3/8" = 1'-0" 4'21012"

3/8" = 1'-0"

CLASSIFICATION PLAN SECTION

3/8" = 1'-0" E341

A

1 BID SET 05/2026 JTH

281 342

VCP-38A-119

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

38A-119-1

38A-119-2

NOTES:

1. REFER TO DRAWING E021 SITE LIGHTING FOR AREA

LIGHTING OF SCUM PIT 1.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

SC

P1

-E .rv t 5/

/2

9:

:1

AM

E400

J. THOMPSON

D. ATKINSON

D. ATKINSON

SCUM PIT 1

ELECTRICAL

POWER PLAN

3/4" = 1'-0" 2'106"

3/4" = 1'-0"

POWER PLAN

GRAVITY THICKENER A

GRAVITY THICKENER B

1 BID SET 05/2026 JTH

282 342

SPACE CLASSIFIED PER NFPA-820-2016

EDITION AS FOLLOWS:

CLASS I, DIVISION 1 AREAS:

1. SCUM PIT 1

TABLE 6.2.2(a), ROW 4, LINE a

ENCLOSED - ENTIRE SPACE

CLASS I, DIVISION 2 AREAS:

1. SCUM PIT 1

TABLE 6.2.2(a), ROW 4, LINE c

WITHIN 10FT ENVELOPE AROUND EQUIPMENT AND

OPEN CHANNEL.

CLASS I, DIV 1

CLASS I, DIV 2

LEGEND:

E401 A_______

E401 A_______

10' - 0"

38A-119-1

38A-119-2

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

SC

P1

-E .rv t 5/

/2

9:

:1

AM

E401

J. THOMPSON

D. ATKINSON

D. ATKINSON

SCUM PIT 1

ELECTRICAL

HAZARDOUS AREA PLANS AND SECTIONS

1/2" = 1'-0" 3'1012"

1/2" = 1'-0"

CLASSIFICATION PLAN

SECTION

1/2" = 1'-0" E401

A

1 BID SET 05/2026 JTH

383 342

VCP-38B-119

38B-119-3

38B-119-4

NOTES:

1. REFER TO DRAWING E021 SITE LIGHTING FOR AREA

LIGHTING OF SCUM PIT 2.

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

SC

P2

-E .rv t 5/

/2

9:

:2

AM

E402

J. THOMPSON

D. ATKINSON

D. ATKINSON

SCUM PIT 2

ELECTRICAL

POWER PLAN

3/4" = 1'-0" 2'106"

3/4" = 1'-0"

POWER PLAN

1 BID SET 05/2026 JTH

284 342

SPACE CLASSIFIED PER NFPA-820-2016

EDITION AS FOLLOWS:

CLASS I, DIVISION 1 AREAS:

1. SCUM PIT 2

TABLE 6.2.2(a), ROW 4, LINE a

ENCLOSED - ENTIRE SPACE

CLASS I, DIVISION 2 AREAS:

1. SCUM PIT 2

TABLE 6.2.2(a), ROW 4, LINE c

WITHIN 10FT ENVELOPE AROUND EQUIPMENT AND

OPEN CHANNEL.

CLASS I, DIV 1

CLASS I, DIV 2

LEGEND:

E403 A_______

E403 A_______

10' - 0"

38B-119-4

38B-119-3

N

DESIGNED THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

DATE:

H & S JOB

NUMBER

IFB NO.

500640-

FY27-02

DRAWING

NUMBER

PROJ.ENGR.

DRAWN

CHECKED

NO. ISSUED FOR DATE BY

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

J. HISE

MAY 2026

31111-098

SHEET OF XXAPPROVED

Au to de sk

D oc s:

//3

-0

_W

PC

F So lid s

Pr oc es si ng Im p Ph

I/

1-

8-

0-

SC

P2

-E .rv t 5/

/2

9:

:2

AM

E403

J. THOMPSON

D. ATKINSON

D. ATKINSON

SCUM PIT 2

ELECTRICAL

HAZARDOUS AREA PLANS AND SECTIONS

1/2" = 1'-0" 3'1012"

1/2" = 1'-0"

CLASSIFICATION PLAN

SECTION

1/2" = 1'-0" E403

A

1 BID SET 05/2026 JTH

285 342

NOTES:

1. SWITCHGEAR SHALL CONTAIN ALL SHOWN

CIRCUIT BREAKERS AND CONTAIN 3 PREPARED

SPACES FED FROM BUS A, AND CONTAIN 4

PREPARED SPACED FED FROM SIDE B.

2. SWITCHGEAR DIMENSIONS TO NOT EXCEED THE

SIZES SHOWN ON ELEVATION.

TX-37-36A

2500kVA 4160-480/277V

3P/4W

LIQUID TRANS

PAD MOUNT

3200AF

3200AP

2000AT

E.O.

LSIG

ERMS

N.C.

3200:5 (3)

POWER

METER

SPD

300kA

AF

AT

60 1600AF

1200AP

600AT

E.O.

LSIG

N.C.

FUTURE BNR AND

CLARIFIERS ELEC

BLDG MCC

FUTURE

DENITFIFICATION

FACILITY MCC

1600AF

800AP

400AT

E.O.

LSIG

N.C.

FUTURE TWAS

TANK

ELECTRICAL

ROOM MCC

1600AF

1600AP

1200AT

E.O.

LSIG

N.C.

SOLIDS

ELECTRICAL

BLDG MCC

800AF

800AP

600AT

E.O.

LSIG

N.C.

EMERGENCY

BLOWER BLDG

1600AF

1600AP

1000AT

E.O.

LSIG

N.C.

SOLIDS

PROCESSING

BLDG

800AF

800AP

450AT

E.O.

LSIG

N.C.

ADMIN BLDG

3200AF

3200AP

2000AT

E.O.

LSIG

ERMS

N.O.

FUTURE BNR AND

CLARIFIERS ELEC

BLDG MCC

FUTURE

DENITFIFICATION

FACILITY MCC

FUTURE TWAS

TANK

ELECTRICAL

ROOM MCC

SOLIDS

ELECTRICAL

BLDG MCC

SECTION 1

1A

1B

1C

1A

1B

1C

SECTION 2

2A

2B

2C

800AF

800AP

800AT

E.O.

LSIG

N.C.

SPARE

2A 2B 3A 3C 4A 4B3D

1600AF

1600AP

1600AT

E.O.

LSIG

N.C.

SPARE

SECTION 3

3A

3B

3C

SECTION 4

4A

4B

4C

SECTION 5

5C

5C

2C

1600AF

1600AP

1600AT

E.O.

LSIG

N.C.

SPARE

800AF

800AP

800AT

E.O.

LSIG

N.C.

SPARE

TX-37-36B

2500kVA 4160-480/277V

3P/4W

LIQUID TRANS

PAD MOUNT

3200AF

2500AP

2000AT

E.O.

LSIG

ERMS

N.C.

3200:5 (3)

POWER

METER 9A

9B

SPD

300kA

SWITCHGEAR SWGR-SEB-1 SINGLE LINE DIAGRAM

SOLIDS ELECTRICAL BUILDING

1600AF

1600AP

1600AT

E.O.

LSIG

N.C.

PROCESS

BLOWER

ELECTRICAL

ROOM

PROCESS

BLOWER

ELECTRICAL

ROOM

SOLIDS ELECTRICAL SWITCHGEAR [E450]

3200A, 480V, 3Ø, 3W, 85kA RMS SYMMETRICAL

3200A, 480V, 3Ø, 3W, 85kA RMS SYMMETRICAL

K

K

K

SECTION 6

6A

6B

6C

SECTION 7

7A

7B

7C

SECTION 8

8A

8B

SECTION 9

9A

9B

9C

MCC-800-1-A MCC-400-1-A MCC-950-1-A MCC-SEB-1-A MCC-B3-G SWBD-13-22 MCC-17-26-A

MCC-17-26-B MCC-800-1-B MCC-400-1-B MCC-950-1-B MCC-SEB-1-B MCC-B-1

1600AF

1600AP

600AT

E.O.

LSIG

N.C.

1600AF

1600AP

1600AT

E.O.

LSIG

N.C.

1600AF

1200AP

600AT

E.O.

LSIG

N.C.

1600AF

1600AP

600AT

E.O.

LSIG

N.C.

1600AF

800AP

400AT

E.O.

LSIG

N.C.

1600AF

1600AP

1200AT

E.O.

LSIG

N.C.

FROM

SWGR-45C-34

FROM

SWGR-45C-34

4C

PREPARED

SPACE

PREPARED

SPACE

HMI

EMPTY

EMPTY

MAIN A

TIE

6A 6B 6C 7A 7B 7D 8A 8B 9C

PREPARED

SPACE

PREPARED

SPACE

PREPARED

SPACE

SWITCHGEAR SWGR-SEB-1 ELEVATION

SOLIDS ELECTRICAL BUILDING

MAIN B AF

AT

EMPTY

198" MAXIMUM

EMPTY

MCC-B3-N

1600AF

1600AP

1200AT

E.O.

LSIG

N.C.

SOLIDS

ELECTRICAL

BLDG MCC

3B

MCC-SEB-2-A

SOLIDS

ELECTRICAL

BLDG MCC

MCC-SEB-2-B

1600AF

1600AP

1200AT

E.O.

LSIG

N.C.

7C

3D 7D

SEE BELOW FOR

CONTINUATION

SEE ABOVE FOR

CONTINUATION

P-450-002

P-450-010

P-700-001 P-750-002

P-800-001

SWGR-SEB-1-B

SWGR-SEB-1-A

P-450-001 P-450-000

P-450-003 P-450-006 P-450-005 P-450-004

P-450-007

P-450-009 P-450-008

P-450-013 P-450-012 P-450-011

P-700-000 P-750-001 P-750-000

P-750-003

P-800-000

P-000-001 P-000-000

P-000-001 P-000-000

P-000-003 P-000-002

P-000-007 P-000-006

P-000-009 P-000-008

P-000-011 P-000-010

SEE SHEET E006

P-820-002 P-820-003 P-820-004 P-820-005 P-820-006 P-820-007

P-820-008 P-820-009 P-820-010 P-820-011 P-820-012 P-820-013

P-820-016 P-820-017 P-820-018 P-820-019 P-820-020 P-820-021

P-820-022 P-820-023 P-820-024 P-820-025 P-820-026 P-820-027

SEE SHEET E006

P-450-027 P-450-028

NO. DATEISSUED FOR APPROVEDBY

PROJ.ENGR.

CHECKED

DRAWN

DESIGNED

SHEET

DATE:

OF

NUMBER

DRAWING

31111-098

MAY 2026

D C

\A C

C D oc s\

H az en a nd S aw ye r\3

-0

_W

PC

F

So lid s Pr oc es si ng

Im p

Ph I\

Pr oj ec t F ile s\

_D es ig n\ El ec \E

0.

dw g

L as tS av eB y:

JW

TH

O M

PS

O

N

J. HISE

IFB NO.

500640-

FY27-02

1 05/2026BID SET JTH

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

H & S JOB

NUMBER

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

E450

SOLIDS ELECTRICAL BUILDING

ELECTRICAL

SWGR-SEB-1 SINGLE LINE DIAGRAM

XX

D. WEBER

E. BODNAR

S. MINETT

286 342

30A 3P

30A 3P

DIGESTER B

MIXER

30A 3P

DIGESTER C

MIXER

30A 3P

DIGESTER D

MIXER

AF

AT

VCP-33-125-1A

THICKENING

CENTRIFUGE

5 5 20

SLUDGE

TRANSFER

PUMP NO. 1

MCP

MCP

AF

AT

30A 3P

PRIMARY SCUM

PUMP

NO. 2

30A 3P

7.5

30A 3P

PRIMARY

SLUDGE PUMP

NO. 3

7.5

30A 3P

PRIMARY

SLUDGE PUMP

NO. 4

30A 3P

PRIMARY

SLUDGE

GRINDER NO. 3

30A 3P

PRIMARY

SLUDGE

GRINDER NO. 2

5 1200RPM

30A 3P

SCUM MIXER

NO. 2

PRIMARY SLUDGE

PUMPING STATION #2

PRIMARY SLUDGE

PUMPING STATION #2

7.5

30A 3P

PRIMARY

SLUDGE PUMP

NO. 1

7.5

30A 3P

PRIMARY

SLUDGE PUMP

NO. 2

30A 3P

PRIMARY

SLUDGE

GRINDER NO. 1

30A 3P

SCUM MIXER

NO. 1

30A 3P

PRIMARY SCUM

PUMP NO. 1

PRIMARY SLUDGE

PUMPING STATION #1

PRIMARY SLUDGE

PUMPING STATION #1 DIGESTER BUILDING

DIGESTER BUILDING

MCP

MCP

MCP

MCP

THICKENED

DIGESTER

SLUDGE PUMP

NO.2

MCP

MCP

PRIMARY SCUM

PUMP

NO. 3

2A 2B 2C 2D 2E 3A 3B 3C 3D 4A 4B 4C

10B 10C 10D 11A 11B 11C 11D 12A 12B 12C 12D 13A

1E

FROM

SWGR-SEB-1-B

ETU

1200AF

1200AP

800AT

LSIG

ERMS

N.C. 1200:5

(3)

POWER

METER

SPD

200kA

AF

AT

ET

U

1200AF

1200AP

800AT

LSIG

N.O.

ETU

1200AF

1200AP

800AT

LSIG

ERMS

N.C.1200:5

(3)

POWER

METERK

K

K

SPD

200kA

AF

AT

9A-62-1

9A-63-1

MCP

MCP

AF

AT

AF

AT

AF

AT

SEE BELOW FOR

CONTINUATION

SLUDGE

TRANSFER

PUMP NO. 2

AF

AT

13B

MCP

MCP

RECIRCULATION

PUMP NO. 1

DIGESTER A

MIXER

AF

AT

AF

AT

MCP

SEE ABOVE FOR

CONTINUATION

MCC-SEB-2 SINGLE LINE DIAGRAM

SOLIDS ELECTRICAL BUILDING

MCC-SEB-2-A, 1200A, 480V, 3Ø, 3W, 65kA RMS SYMMETRICAL

MCC-SEB-2-B, 1200A, 480V, 3Ø, 3W, 65kA RMS SYMMETRICAL

FROM

SWGR-SEB-1-A

MCC-SEB-2-B

MCC-SEB-2-A

ETU

400AF

400AP

250AT

LSIG

PP-DSM-1

TX-LP-DSM-1

30kVA 480-120/208V

3P/4W

DRY TRANS

LP-DSM-1

9A-60-1 9A-61-1

9A-61-29A-60-2

9B-60-3 9B-61-3

9B-61-4 9B-63-29B-62-3

9B-62-233-131-1

RECIRCULATION

PUMP NO. 2

33-131-2

RECIRCULATION

PUMP NO. 3

33-131-3

RECIRCULATION

PUMP NO. 4

33-131-4 33-140-1

33-140-233-125-1

33-127-2

THICKENED

DIGESTER

SLUDGE PUMP

NO.1

33-127-1

32A-130-1 32B-130-1

32C-130-1 32D-130-1

P-500-000 P-500-001 P-500-002 P-500-003 P-500-004 P-500-005 P-500-006 P-500-007 P-100-000 P-100-001 P-100-002 P-150-001 P-150-002

P-150-003 P-150-004 P-150-005 P-100-003 P-100-004 P-100-006 P-500-009 P-500-010 P-500-011 P-500-014 P-500-015

P-500-012 P-500-013

P-650-000

P-650-001

P-650-002

CENTRIFUGE

FEED

PUMP NO.1

33-126-1

CENTRIFUGE

FEED

PUMP NO.2

33-126-2

AF

AT

AF

AT

AF

AT

AF

AT

VCP-32A-130-1 VCP-32B-130-1

VCP-32C-130-1 VCP-32D-130-1

AF

AT

AF

AT

AF

AT

AF

AT

VCP-9A-60-1 VCP-9B-60-3

MCP

MCP

MCP

MCP

SEE SHEET E450 SEE SHEET E450

MCP

MCP

AF

AT

MCP

VCP-9A-60-2

0.5

30A 3P

SUMP

PUMP

MCP

9A-64-1

P-100-005

AF

AT

AF

AT

30A 3P

SAMPLE PUMP

NO. 1

30A 3P

SAMPLE PUMP

NO. 2

33-135-1 33-135-2

30A 3P

1.5

POLYMER

MIXING UNIT

33-153-1

VCP-33-153-1

AF

AT

30 MCP

MCP

MCP

30A 3P

DIGESTER

HEATING WATER

PUMP NO. 1

33-248-3

30A 3P

DIGESTER

HEATING WATER

PUMP NO. 2

33-248-4

30A 3P

DIGESTER

HEATING WATER

PUMP NO. 3

33-248-5

30A 3P

DIGESTER

HEATING WATER

PUMP NO. 4

33-248-6

VCP-134

HOT WATER

RECIRCULATION

PUMP NO. 1

33-248-1

HOT WATER

RECIRCULATION

PUMP NO. 2

33-248-2

DIGESTER BUILDING

P-500-016 P-500-017 P-500-019 P-500-020 P-500-022 P-500-023 P-500-024P-500-021 P-500-025

P-500-026

P-500-028 P-500-027

P-150-000

7E

7A

7I

9A

9I

9E8A

10A1B 1C 1D1A 4D 5A 5B 5D

13C 13D 13E 14A 14B 14C 14D 14E12E11E

SPARE

SPARE SPARE SPARE SPARE SPARE SPARE SPARE

VFD

VFD

VFD

VFD

VFD

VFD

P-500-033 P-500-034 P-500-035 P-500-036

P-500-037 P-500-038

NO. DATEISSUED FOR APPROVEDBY

PROJ.ENGR.

CHECKED

DRAWN

DESIGNED

SHEET

DATE:

OF

NUMBER

DRAWING

31111-098

MAY 2026

D C

\A C

C D oc s\

H az en a nd S aw ye r\3

-0

_W

PC

F

So lid s Pr oc es si ng

Im p

Ph I\

Pr oj ec t F ile s\

_D es ig n\ El ec \E

1.

dw g

L as tS av eB y:

JW

TH

O M

PS

O

N

J. HISE

IFB NO.

500640-

FY27-02

1 05/2026BID SET JTH

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

H & S JOB

NUMBER

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

E451

SOLIDS ELECTRICAL BUILDING

ELECTRICAL

MCC-SEB-2 SINGLE LINE DIAGRAM

XX

D. WEBER

E. BODNAR

S. MINETT

287 342

PROPOSED SOLIDS ELEC BLDG MCC

FROM

SWGR-SEB-1-B

ETU

1200AF

1200AP

1200AT

LSIG

ERMS

N.C. 1200:5

(3)

POWER

METER

SPD

200kA

AF

AT

ET

U

1200AF

1200AP

1200AT

LSIG

N.O.

ETU

1200AF

1200AP

1200AT

LSIG

ERMS

N.C.1200:5

(3)

POWER

METERK

K

K

SPD

200kA

MCP

THICKENED

SLUDGE

PUMP NO. 1

30A 3P

MCP

THICKENED

SLUDGE

PUMP NO. 2

30A 3P

MCP

THICKENED

SLUDGE

PUMP NO. 3

30A 3P

MCP

THICKENED

SLUDGE

PUMP NO. 4

30A 3P

AF

AT

PRIMARY

SLUDGE

SCREEN NO. 1

AF

AT

PRIMARY

SLUDGE

SCREEN NO. 2

AF

AT

SPARE 30A

THICKENED SLUDGE

PUMPING STATION

THICKENED SLUDGE

PUMPING STATION

AF

AT

AF

AT

SEE BELOW FOR

CONTINUATION

SPARE

SIZE 1

FVR

MCP

MCC-SEB-1-A, 1200A, 480V, 3Ø, 3W, 65kA RMS SYMMETRICAL

TX-LP-DGB-3

45kVA 480-120/208V

3P/4W

DRY TRANS

LP-DGB-3

AF

AT

S1 S2

L

ATS-SEB-1

480V 250A 3Ø 3W 3P

OPEN TRANSITION

AF

AT

MCC-SEB-1 SINGLE LINE DIAGRAM

SOLIDS ELECTRICAL BUILDING

PP-SEB-1

TX-LP-SEB-1

30kVA 480-120/208V

3P/4W

DRY TRANS

LP-SEB-1

FROM

SWGR-SEB-1-A

PROPOSED SOLIDS ELEC BLDG MCC [E451-E452]

SPARE

MCP

AF

AT

AF

AT

SPARE

PP-SEB-2

0.75

30A 3P

GRAVITY

THICKENER A

ROTATING RAKE

MCP

0.75

30A 3P

GRAVITY

THICKENER B

ROTATING RAKE

MCP

0.75

30A 3P

GRAVITY

THICKENER C

ROTATING RAKE

MCP

30A 3P

PRIMARY SCUM

GRINDER NO. 3

MCP

1A 1B 1C 1D 1E 2A 2B 3D 3E2C 2D 2E 3A 3B 3C 4A

5E

5A

5I

7A

7I

7E

8A

8B 8C 8D 8E 9A 9B 9C 9D 9E

6A

AF

AT

TX-LP-SEB-2

30kVA 480-120/208V

3P/4W

DRY TRANS

LP-SEB-2

ETU

400AF

400AP

250AT

LSIG

ETU

400AF

400AP

250AT

LSIG

31-122-131-122-3

31-122-431-122-2

11-142-1

11-142-2

31-151-131A-121-1 31B-121-1 31C-121-1

SPARE SIZE 1

SEE ABOVE FOR

CONTINUATION

P-200-000 P-200-001 P-200-002 P-400-000P-200-003

P-200-004 P-200-005 P-200-006

P-450-014

P-450-015

P-450-016

P-450-017

P-450-018

P-450-019

P-300-000 P-320-000

P-450-022

P-340-000

P-450-020 P-450-021

MCC-SEB-1-A

MCC-SEB-1-BMCC-SEB-1-B, 1200A, 480V, 3Ø, 3W, 65kA RMS SYMMETRICAL

SEE SHEET E450 SEE SHEET E450

VCP-11-142-1

VCP-11-142-2

VCP-31-151-1

MCP

AF

AT

VCP-38A-119

GRAVITY

THICKENER

SCUM PUMP

NO. 1

38A-119-1

GRAVITY

THICKENER

SCUM PUMP

NO. 2

38A-119-2

VCP-38B-119

GRAVITY

THICKENER

SCUM PUMP

NO. 3

38B-119-3

GRAVITY

THICKENER

SCUM PUMP

NO. 4

38B-119-4

P-400-003

P-400-001 P-400-002

P-400-004 P-400-005

30A 3P

GRAVITY THICKENERS

DIGESTED

SLUDGE

STORAGE MIXING

PUMP NO. 1

AF

AT

34A-147-1

P-650-003

34B-147-2

AF

AT

DIGESTED

SLUDGE

STORAGE MIXING

PUMP NO. 2

SCUM PITSDIGESTED SLUDGE

MIXING BUILDING

SPARE

P-650-004

30A 3P

SPARE

SIZE 1

FVR

MCP

THICKENED

SLUDGE

PUMP NO. 5

30A 3P

31-122-5

P-200-007

PP-DGB-1

P-500-032

XFMR B

45kVA 120/208V

3P/4W

DRY TRANS

XFMR B

45kVA 120/208V

3P/4W

DRY TRANS

LP-DGB-2

P-500-008 P-500-018

LP-DGB-1A LP-DGB-1B

DIGESTER BUILDING

P-450-023

VFD

VFD

P-650-010 P-650-011

NO. DATEISSUED FOR APPROVEDBY

PROJ.ENGR.

CHECKED

DRAWN

DESIGNED

SHEET

DATE:

OF

NUMBER

DRAWING

31111-098

MAY 2026

D C

\A C

C D oc s\

H az en a nd S aw ye r\3

-0

_W

PC

F

So lid s Pr oc es si ng

Im p

Ph I\

Pr oj ec t F ile s\

_D es ig n\ El ec \E

2.

dw g

L as tS av eB y:

JW

TH

O M

PS

O

N

J. HISE

IFB NO.

500640-

FY27-02

1 05/2026BID SET JTH

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

DRAWING.

H & S JOB

NUMBER

HAZEN AND SAWYER

1 SOUTH STREET, SUITE 1150

BALTIMORE, MARYLAND 21202

TOWN OF LEESBURG

LEESBURG, VIRGINIA

WATER POLLUTION CONTROL FACILITY

SOLIDS PROCESSING

IMPROVEMENTS - PHASE 1

E452

SOLIDS ELECTRICAL BUILDING

ELECTRICAL

MCC-SEB-1 SINGLE LINE DIAGRAM

XX

D. WEBER

E. BODNAR

S. MINETT

288 342

SWGR-SEB-1

ATS-SEB-1PLC-38

(FRONT)

MCC-SEB-1

MCC-SEB-2

1 2 3 4 5 6 MAIN

A TIE MAIN

B 10 11 12 13

10 9 8 MAIN

B TIE MAIN

A 4 3 2 1

PP-SEB-1

TX-LP-SEB-1 LP-SEB-1

PP-SEB-2

TX-LP-SEB-2

LP-SEB-2

ELECTRICAL ROOM

HCP-450-1

CP-450-3

CP-450-2

CP-450-1

SEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATIONSEE DRAWING E021

FOR CONTINUATION

SEE DRAWING E021

FOR CONTINUATION

DB

E11

DB

C2

DB

E8

DB

C5

DB

E9

DB

E14

DB

C9

DB

E1

DB

E10

DB

C1

VFD-33-127-2

VFD-33-140-1

VFD-33-127-1

VFD-33-126-2

VFD-33-126-1

VFD-33-140-2

GROUNDING NOTES:

A.

B.

C.

D.

E.

F.

G.

REFER TO N.E.C. ARTICLE 250.52(A)(3) FOR BONDING

OF GROUND RING TO STRUCTURAL FOUNDATION

REBAR.

GROUND RING CONDUCTOR SHALL BE #4/0 BARE

COPPER WIRE 30" MINIMUM BELOW FINISHED GRADE.

ALL GROUND CONDUCTORS TO EQUIPMENT OR

STRUCTURAL STEEL SHALL BE BARE COPPER WIRE.

EACH DUCT BANK GROUND CONDUCTOR CROSSING

THE GROUND RING SHALL BE EXOTHERMICALLY

WELDED TO THE GROUND RING CONDUCTOR.

ALL TRANSFORMERS, SWITCHGEAR, MOTOR CONTROL

CENTERS, AND PANELBOARDS SHALL BE BONDED TO

THE GROUND RING CONDUCTOR.

FURNISH AND INSTALL LIGHTNING PROTECTION

SYSTEM FOR THIS FACILITY PER SPECIFICATION

26 41 00.

FURNISH AND INSTALL 1" CONDUITS THROUGH

CONCRETE PAD FOR LIGHTNING PROTECTION DOWN

CONDUCTORS TO GROUND RING. ALL DOWN

CONDUCTORS SHALL BE ROUTED DOWN INSIDE OF

BUILDING.

COORDINATE GROUND SYSTEM INSTALLATION WITH

INSTALLATION OF THE LIGHTNING PROTECTION

SYSTEM.

INDOOR WET PROCESS AREA

INDOOR DRY PROCESS AREA

INDOOR DRY NON-PROCESS AREA

AREA DESIGNATION LEGEND:

NOTES:

1. FURNISH AND INSTALL FIRE ALARM SYSTEM FOR THIS

FACILITY PER…

This is the start of the file's text. The full file is on GovTribe.