This document is an invitation for bid for a remodel front entrance project at the Cincinnati VA Medical Center. The project is set aside 100% for service-disabled veteran-owned small businesses and has a magnitude between $500,000 and $1,000,000. The NAICS code is 236220 and businesses must have less than $39.5 million in annual revenue to qualify as small. Offerors must register in VetBiz and SAM and ensure their registrations are accurate and not expired by the bid opening and award dates. The solicitation number is 36C25022B0002 and site visit is scheduled for November 29, 2021. Questions will only be answered if submitted as a request for information by the date listed. The awarded project must be completed within 300 calendar days of receiving notice to proceed and performance and payment bonds are required.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
COVER SHEET
Jason Reeves - Chief Engineer Josh Schneider - COR
100% CONSTRUCTION
DOCUMENTS
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CODE DATA
Jason Reeves - Chief Engineer Josh Schneider - COR
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PHASING PLAN
Jason Reeves - Chief Engineer Josh Schneider - COR
728.388
CNPT
725.781
CNPT
725.566
CNPT
726.866
CNPT
726.570
CNPT
725.550
MH-3-SAN
726.232
SIGNPB
727.103
HEDGES OC*
RIM 725.38
6" INV = 708.18
12" INV = 707.93
RIM 725.38
12" INV = 701.53 & 707.53
18" INV = 701.62
18" INV = 701.18
INV 701.15
RIM 725.99
8" INV = 702.78
21" INV = 702.89
RIM 725.15
21" INV 701.25
18" INV 701.06
18" INV 700.76
RIM 725.81
12" INV 723.03
18" INV 725.46
18" INV 713.63
DOUBLE CB
RIM 725.15
12" INV 719.53
RIM 724.43
8" INV 723.03
RIM 724.37
8" INV 722.70
8" INV 722.54
DIVIDER WALL WITH
12" HOLE
TOP 723.97
8" INV 721.47
12" INV 715.47
48" INV 715.79
RIM 724.37
12" INV 719.28
12" INV 715.31
EX. MH
TOP 726.75
INV UNKWN.
EX. MH
TOP 728.07
10' INV (W) = 724.75
12" INV (E) = 724.56
EX. CB
P 728.07 = 725.55
CINCINNATI VA HOSPITAL
STOP SIGN
HANDICAP WARNING
STRIP
ASPHALT
ASPHALT
ASPHALT
ASPHALT
CONC.
CONC.
STOP SIGN
DECORATIVE
BOLLARDS (TYP.)
NO PARKING
SIGN
BENCH
BENCH
BRICK PAVERS
OVERHANG
OVERHANG
- Existing Storm
- Existing Sanitary Sewer
- Existing Electrical
- Existing Water
- Existing Communications
SYMBOL LEGEND
WV
- Storm Manhole
- Catch Basins
- Curb Inletl
- Sanitary Manhole
- Cleanout
- Water Valve
- Water Meter
- Fire Hydrant
- Water Shutoff Valve
-Post
- Telephone Manholel
- Electic Manhole
- Light Pole
- Gas Valve
- Gas Shutoff Valve
- Gas Regulator
-Signs
-Deciduous Tree
-Evergreen Tree
GV
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Remodel Front Entrance
07/30/2021 JKHPSB
20005.00 539-21-211
Cincinnati VAMC
100% CONSTRUCTION
DOCUMENTS
Revisions Date
Jason Reeves - Cheif Engineer
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 6 7 8 9 10
/1
1/
:1 7:
A
M
B1
FULL SPRINKLERED
Josh Schneider - COR
Office of Construction and Facilities Management
EXISTING CONDITIONS
V-001
728.388
CNPT
725.781
CNPT
725.566
CNPT
726.866
CNPT
726.570
CNPT
725.550
MH-3-SAN
726.232
SIGNPB
727.103
HEDGES OC*
CINCINNATI VA HOSPITAL
STOP SIGN
HANDICAP WARNING
STRIP
ASPHALT
ASPHALT
ASPHALT
ASPHALT
CONC.
CONC.
STOP SIGN
DECORATIVE
BOLLARDS (TYP.)
NO PARKING
SIGN
BENCH
BENCH
BRICK PAVERS
OVERHANG
OVERHANG
UNDERGROUND TANK TO BE REMOVED.
(REFER TO ARCHITECTURAL
DEMOLITION PLAN FOR NOTES)
4 4
- Existing Storm
- Existing Sanitary Sewer
- Existing Electrical
- Existing Water
- Existing Communications
SYMBOL LEGEND
WV
- Storm Manhole
- Catch Basins
- Curb Inletl
- Sanitary Manhole
- Cleanout
- Water Valve
- Water Meter
- Fire Hydrant
- Water Shutoff Valve
-Post
- Telephone Manholel
- Electic Manhole
- Light Pole
- Gas Valve
- Gas Shutoff Valve
- Gas Regulator
-Signs
-Deciduous Tree
-Evergreen Tree
GV
SHEET NOTES
- Bollard to be Removed1
- Water Valve to be Removed and Replaced
- Electric Utility Manhole to be Removed and Replaced
- Neat Saw Cut
- Concrete and Pavement to be Removed
5 - Sign to be Removed
6 - Curb and Gutter to be Removed
- Asphalt Pavement to be Removed for Concrete Forming
7 - Brick Pavers to be Removed
8 - Asphalt to be Removed for Electrical Work
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Remodel Front Entrance
07/30/2021 JKHPSB
20005.00 539-21-211
Cincinnati VAMC
100% CONSTRUCTION
DOCUMENTS
Revisions Date
Jason Reeves - Cheif Engineer
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 6 7 8 9 10
/1
1/
:1 7:
A
M
B1
FULL SPRINKLERED
Josh Schneider - COR
Office of Construction and Facilities Management
DEMOLITION PLAN
CD-101
24.4'R
26'R
725.550
MH-3-SAN
726.232
SIGNPB
727.103
HEDGES OC*
RIM 725.38
6" INV = 708.18
12" INV = 707.93
RIM 725.38
12" INV = 701.53 & 707.53
18" INV = 701.62
18" INV = 701.18
INV 701.15
RIM 725.99
8" INV = 702.78
21" INV = 702.89
RIM 725.15
21" INV 701.25
18" INV 701.06
18" INV 700.76
RIM 725.81
12" INV 723.03
18" INV 725.46
18" INV 713.63
DOUBLE CB
RIM 725.15
12" INV 719.53
RIM 724.43
8" INV 723.03
RIM 724.37
8" INV 722.70
8" INV 722.54
DIVIDER WALL WITH
12" HOLE
TOP 723.97
8" INV 721.47
12" INV 715.47
48" INV 715.79
RIM 724.37
12" INV 719.28
12" INV 715.31
EX. MH
TOP 726.75
INV UNKWN.
EX. MH
TOP 728.07
10' INV (W) = 724.75
12" INV (E) = 724.56
EX. CB
OP 728.07
) = 725.55
CINCINNATI VA HOSPITAL
STOP SIGN
HANDICAP WARNING
STRIP
ASPHALT
ASPHALT
ASPHALT
ASPHALT
CONC.
CONC.
STOP SIGN
DECORATIVE
BOLLARDS (TYP.)
NO PARKING
SIGN
BENCH
BENCH
BRICK PAVERS
OVERHANG
OVERHANG
4 4
BEGIN NEW FLUSH CURB AT
JOINT WHERE EXISTING
TRANSITION FROM RAISED
CURB TO FLUSH CURB ENDS.
BEGIN TRANSITION FROM EXISTING
CURB AND GUTTER TO NEW FLUSH
CURB AT THE NEAREST JOINT TO THE
CURB INLET CATCH BASIN.
AREA OF PROPOSED TANK
REMOVAL AND ELECTRICAL
UTILITY WORK.
(SEE SHEET E101 FOR DETAILS)
VERIFY UTILITIES PRIOR TO
EXCAVATION OF TANK.
6'
1.75'
6'
2'
BEGIN NEW FLUSH
CURB HERE.
1.75'
INV 725.21'
INV 725.3'
28.3'
.5'
26.3'
INV 725.12'
INV 724.97'
INV 724.74'
NEW CANOPY DRAIN
6" STORM LINE
AT 0.5% SLOPE
NEW CANOPY DRAIN
6" STORM LINE
AT 0.5% SLOPE
NEW CANOPY DRAIN
6" STORM LINE
AT 0.5% SLOPE
6'
NEW WATER LINE
REALIGNMENT
3 1
8'
6' 6'
6' 6'
6'
6'
6'6'6'6'6'6' 6'
8'
8'
- Existing Storm
- Existing Sanitary Sewer
- Existing Electrical
- Existing Water
- Existing Communications
SYMBOL LEGEND
WV
- Storm Manhole
- Catch Basins
- Curb Inletl
- Sanitary Manhole
- Cleanout
- Water Valve
- Water Meter
- Fire Hydrant
- Water Shutoff Valve
-Post
- Telephone Manholel
- Electic Manhole
- Light Pole
- Gas Valve
- Gas Shutoff Valve
- Gas Regulator
-Signs
-Deciduous Tree
-Evergreen Tree
GV
SHEET NOTES
- Proposed Shallow Foundation Security Bollard (See Detail 2 / C501)1
- Proposed Reinforced Conrete Planter Barrier (See Detail 3 / C501)
- Proposed Concrete Curb Flush with Pavement (See Detail 1 / C502)
- Proposed Transition from Curb and Gutter to Flush Curb (See Detail 2 / C502)
- Area of New Concrete Sidewalk & Curb
6 - Confirm Existing Utility Depth
- Proposed Security Bollard (See Detail 1 / C501)
- Area of New Asphalt Pavement
7 - Provide Minimum 12" Asphalt patch adjacent to New Curb
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Remodel Front Entrance
07/30/2021 JKHPSB
20005.00 539-21-211
Cincinnati VAMC
100% CONSTRUCTION
DOCUMENTS
Revisions Date
Jason Reeves - Cheif Engineer
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 6 7 8 9 10
/1
1/
:1 7:
A
M
B1
FULL SPRINKLERED
Josh Schneider - COR
Office of Construction and Facilities Management
SITE PLAN
CS-101
3rd POST
2nd POST
FRONT POST
PLANTER BOX
FOOTING
3"
4th POST
SIDE PACKER (2)
REAR PACKER
SLIPPER BOX
SLIPPER BOX EXTENSION
FLANGE OF COVER
AGAINST FRONT POST
2 1/4" REF.
IMPACT
DIRECTION
MOUNTING
PLATE
1'-8 7/16"
IMPACT
DIRECTION
1'-4" 5'-1" (COVER)
PLANTER BOX
PLAN VIEW
IMPACT
DIRECTION
1'-4"
1'-4 5/8"
1'-4 1/4" PLANTER TRAY
1'-8 7/16"
ISOMETRIC VIEW
SEE NOTE 6
ON SHEET 2
2'-1 1/8" TYP.
1'-4 3/16" 1'-4 3/16" −GRADE−
3"TYP.
7'-9"
FRONT VIEW
10 1/2"
CONCRETE
3" TYP
3'-5 1/2"
SIDE VIEW
REBAR
2 1/16" 11 5/16"
1'-2 1/2"
4" SID
EW
ALK
3'-1"
2'-11 7/16" (H O
LD
3"
1'-5 1/4" 1'-10"
(C O
VER
2 1/4" R
EF.
1/2"
7'-9"
IMPACT DIRECTION
3'-5 1/2"
4" SID
EW
ALK
10 1/2"
INSTALL DRAWING
38−16 x 1− 1
STAINLESS STEEL
GROUND COVER
SECURITY SCREW
PLANTER−40 SLIPPER BOX EXTENSION
(BY TYMETAL, SEE NOTE 5)
BOLLARD GROUND COVER
CAST IN PLACE
ANCHOR
NOTES:
1. COPY AND DESIGN RIGHT BELONG TO SAFETYFLEX.
2. TESTED TO BSI PAS 68:2010. SIMILAR TO U.S. DOS K-8 AND ASTMF2656-07 M40.
TESTED FOOTING WAS 39 38" WIDE x 90 12" LONG x 7 78" DEEP.
3. BOLLARD IS REMOVABLE IN THIS INSTALLATION.
4. USE 6000 PSI CONCRETE FOR BOLLARD FOOTING.
5. PLACE SLIPPER BOX EXTENSION BEFORE POURING BOLLARD FOOTING.
6. DRAINAGE TO BE FURNISHED & INSTALLED BY INSTALLATION CONTRACTOR.
ISOMETRIC VIEW OF SLIPPER BOX EXT.
PL-40-003-2
Security Bollard, Model R-1009-04
Ø8 5/8 A
CONCRETE IN BOLLARD
38 1/2
4000 PSI CONCRETE FOUNDATION
Ø19 1/4
36" CONCRETE
DEPTH
SECTION A-A MASONRY BLOCKS OR
CHAIRS TO ELEVATE
BOLLARDS OFF SUBGRADE
NOTES: A
EMBEDMENT DETAILS ARE FOR REFERENCE ILLUSTRATION ONLY. MINIMUM FOUNDATION SIZES DEPEND ON LOCAL SOIL CONDITIONS, WEATHER
CONDITIONS, AND ENGINEERING REQUIREMENTS.
BOLLARD IS PROVIDED AS SHOWN, WITH PARTS LISTED BELOW. CONCRETE FOUNDATION AND/OR INSTALLATION NOT PROVIDED BY MANUFACTURER.
THIS DRAWING IS NOT DRAWN TO SCALE. DIMENSIONS PROVIDED HEREIN IS FOR REFERENCE ONLY. PLEASE CONSULT THE MANUFACTURER IF ANY
DIMENSION IS CRITICAL TO YOUR PARTICULAR INSTALLATION.
RELIANCE FOUNDRY RESERVES THE RIGHT TO AMEND DESIGN AND SPECIFICATIONS WITHOUT PRIOR NOTICE FOR PRODUCT IMPROVEMENT.
PARTS LIST
ITEM
QTY
PART NUMBER
R-1009-04 K4
REBAR 68
DESCRIPTION
BOLLARD R-1009-04 K4
REBAR 1" OD, 68" LENGTH
SPECIFICATIONS:
HEIGHT: 72"
BODY DIAMETER: 19 1/2"
WEIGHT: 420 LBS
MATERIAL: STEEL
CRASH RATING: ASTM F2656-07 M30 P1
K4 RATED FIXED SHALLOW MOUNT BOLLARDS
FIXED BOLLARDS
SELECT DESIRED BOLLARD FINISH:
POWDERCOAT RAL # _________
AS SPECIFIED _______________
SIDE SECTION VIEW
8 5/8"
84"
FRONT SECTION VIEW
NOTES:
1. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
2. DO NOT SCALE DRAWING.
3. THIS DRAWING IS INTENDED FOR USE BY ARCHITECTS, ENGINEERS, CONTRACTORS, CONSULTANTS AND DESIGN PROFESSIONALS
FOR PLANNING PURPOSES ONLY. THIS DRAWING MAY NOT BE USED FOR CONSTRUCTION.
4. ALL INFORMATION CONTAINED HEREIN WAS CURRENT AT THE TIME OF DEVELOPMENT BUT MUST BE REVIEWED AND APPROVED BY
THE PRODUCT MANUFACTURER TO BE CONSIDERED ACCURATE.
CONCRETE FILLED
BOLLARD
CONCRETE
COMPACTED BACKFILL
DIRECTION OF
IMPACT
F3016 - 8" REMOVABLE SHALLOW MOUNT BOLLARD
INTERNAL LOCKING SECURITY BOLLARDS
SECTION A-A FRONT ELEVATION
NOTES:
1. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
2. DO NOT SCALE DRAWING.
3. THIS DRAWING IS INTENDED FOR USE BY ARCHITECTS, ENGINEERS, CONTRACTORS, CONSULTANTS AND DESIGN PROFESSIONALS
FOR PLANNING PURPOSES ONLY. THIS DRAWING MAY NOT BE USED FOR CONSTRUCTION.
4. ALL INFORMATION CONTAINED HEREIN WAS CURRENT AT THE TIME OF DEVELOPMENT BUT MUST BE REVIEWED AND APPROVED BY
THE PRODUCT MANUFACTURER TO BE CONSIDERED ACCURATE.
PLAN VIEW
SPECIFICATIONS:
CRASH RATING: ASTM F3016-S30-P1
MATERIAL: 8" A53 PIPE ASTM A36/992 STEEL BEAM A36 STEEL PLATE ASTM A240 STAINLESS STEEL
PERSPECTIVE
SELECT DESIRED SURFACE FINISH:
STD. ZINC RICH PRIMER _____________
OTHER: RAL # __________________
22"
(4 8"
(Ø8 5/8") A
A
8" ASTM A53 PIPE
ASTM A36 STEEL STIFFENER
ASTM A36/992 STEEL BEAM
ASTM A36 STEEL PLATE
ASTM A36 PLATE
ASTM A240 S.S
EMBEDMENT SLEEVE
ASTM A240 S.S
GRADE FLANGE
C-501
C-501
C-501
NTS
SHALLOW FOUNDATION SECURITY BOLLARD DETAIL
NTS
SECURITY PLANTER DETAIL
NTS
SECURITY BOLLARD DETAIL
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Remodel Front Entrance
07/30/2021 JKHPSB
20005.00 539-21-211
Cincinnati VAMC
100% CONSTRUCTION
DOCUMENTS
Revisions Date
Jason Reeves - Cheif Engineer
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 6 7 8 9 10
/1
1/
:1 7:
A
M
B1
FULL SPRINKLERED
Josh Schneider - COR
Office of Construction and Facilities Management
CONSTRUCTION DETAILS
C-501
CONCRETE SIDEWALK TO BE REMOVED
VARIES
EXISTING ASPHALT PAVEMENT
PAVEMENT TO BE REMOVED TO ALLOW ENOUGH ROOM
TO PROPERLY FORM NEW CONCRETE SIDEWALK, CURB,
AND GUTTER.
C-502 NTS
CURB TRANSITION DETAIL 2
C-502 NTS
FLUSH CURB CONSTRUTION ALONG WALK
3 CURB CONSTRUCTION ALONG WALK
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Remodel Front Entrance
07/30/2021 JKHPSB
20005.00 539-21-211
Cincinnati VAMC
100% CONSTRUCTION
DOCUMENTS
Revisions Date
Jason Reeves - Cheif Engineer
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 6 7 8 9 10
/1
1/
:1 7:
A
M
B1
FULL SPRINKLERED
Josh Schneider - COR
Office of Construction and Facilities Management
CONSTRUCTION DETAILS
C-502
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
DEMOLITION PLAN
Jason Reeves - Chief Engineer Josh Schneider - COR
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
FLOOR PLAN
Jason Reeves - Chief Engineer Josh Schneider - COR
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
REFLECTED CEILING PLAN
Jason Reeves - Chief Engineer Josh Schneider - COR
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
ROOF PLAN
Jason Reeves - Chief Engineer Josh Schneider - COR
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
EXTERIOR ELEVATIONS
Jason Reeves - Chief Engineer Josh Schneider - COR
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
DOOR SCHEDULE & DETAILS
Jason Reeves - Chief Engineer Josh Schneider - COR
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
REVOLVING DOOR
Jason Reeves - Chief Engineer Josh Schneider - COR
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
FINISH SCHEDULE
Jason Reeves - Chief Engineer Josh Schneider - COR
A. CODES AND SPECIFICATIONS
1. 2021 INTERNATIONAL BUILDING CODE.
2. ACI 301-16, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS AS MODIFIED BY THE CONSTRUCTION DOCUMENTS.
3. ADDITIONAL TECHNICAL SPECIFICATIONS IN THE PROJECT MANUAL.
B. DESIGN LOADS
1. PRELIMINARY CANOPY FOUNDATION LOADS WERE FURNISHED BY STRUCTURES UNLIMITED INC, SUBMIT FINAL CANOPY FOUNDATION DESIGN
LOADS TO THE FOUNDATION ENGINEER FOR REVIEW WITH THE FOUNDATION SHOP DRAWINGS.
C. FOUNDATIONS
1. THE FOUNDATION DESIGN IS BASED UPON THE RECOMMENDATIONS BY TERRACON. DRILLED PIERS ARE TO EXTEND A MINIMUM OF 10'-0" INTO
GLACIAL TILL.
2. FOUNDATION ELEVATIONS SHOWN ARE ESTIMATED AND ARE FOR BIDDING ONLY. ACTUAL ELEVATIONS MAY VARY TO SUIT SUBSURFACE SOIL
CONDITIONS.
3. ALL BEARING SURFACES SHALL BE UNDISTURBED, LEVEL (WITHIN 1 IN 12), AND APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO PLACING
CONCRETE.
4. ALL PILE CAPS ARE TO BE POURED NEAT AGAINST EARTH BANKS (WITHOUT SIDE FORMS) UNLESS APPROVED OTHERWISE BY BOTH THE GEOTECHNICAL AND STRUCTURAL ENGINEERS. WHERE EARTH CUTS WILL NOT STAND, SIDES SHALL BE FORMED AND BACKFILLED WITH
COMPACTED MATERIAL, SUBJECT TO ENGINEERS' APPROVAL.
5. PILE FOUNDATIONS ARE TO BE DESIGNED FOR , 10 TON AXIAL AND 5 TON UPLIFT CAPACITY.
6. SET ANCHOR RODS WITH A TEMPLATE PRIOR TO PLACING CONCRETE.
D. CONCRETE
1. CONCRETE STRENGTHS:
a. DRILLED PIERS AND PILE CAPS: 3000 PSI
b. EXTERIOR CONCRETE EXPOSED TO WEATHER: 5000 PSI AE
2. PROVIDE 3/4" BEVELS AT CORNERS OF ALL EXPOSED PIERS.
3. PLACE NO OPENINGS, SLEEVES, INSERTS, ETC. IN CONCRETE WORK UNLESS CRITERIA INDICATED ON THE STRUCTURAL DRAWINGS IS MET, OR
SPECIFIC SIZE AND LOCATION IS APPROVED IN WRITING BY THE STRUCTURAL ENGINEER.
4. CONCRETE CONSTRUCTION TOLERANCES ARE AS SHOWN IN THE PROJECT SPECIFICATIONS.
GENERAL STRUCTURAL NOTES:
E. COORDINATION AND CONSTRUCTION
1. THE CONTRACTOR SHALL COMPLETE ALL WORK REQUIRED AND NECESSARY FOR THE PROJECT IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, DRAWINGS, AND REFERENCED STANDARDS. THE SPECIFICATIONS AND DRAWINGS COMPLEMENT EACH OTHER, THE
CONTRACTOR SHALL THOROUGHLY REVIEW BOTH BEFORE PROCEEDING WITH ANY WORK.
2. SHOP DRAWINGS AND INSTALLATION DRAWINGS SHALL BE PREPARED AND SUBMITTED FOR REVIEW. SUBMITTALS PREPARED BY SUPPLIERS AND SUB CONTRACTORS SHALL BE REVIEWED BY THE TRADE CONTRACTOR AND GENERAL CONTRACTOR OR CONSTRUCTION MANAGER PRIOR TO
SUBMITTING TO ARCHITECT/ENGINEER.
a. FIELD VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS AND CONDITIONS WHICH AFFECT FABRICATION AND SHOW ON SHOP DRAWINGS.
b. SUBMIT COMPLETE SHOP DRAWINGS WITH MANUFACTURERS’ DATA, ETC. SHOW ALL CONNECTIONS AND DETAILS NECESSARY TO FULLY
DESCRIBE AND PROPERLY INSTALL THE WORK.
c. STRUCTURAL ENGINEER’S REVIEW SHALL BE FOR GENERAL ARRANGEMENT AND CONFORMANCE WITH THE STRUCTURAL INTENT ONLY.
3. THE SPECIFICATIONS AND STRUCTURAL DRAWINGS TYPICALLY REFER TO THE FINISHED STRUCTURE. UNLESS NOTED OTHERWISE, THEY DO NOT
PRESCRIBE THE METHOD OF CONSTRUCTION.
4. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. THIS REQUIREMENT
SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO WORKING HOURS.
5. THE ARCHITECT’S AND ENGINEER’S OBSERVATION AND REVIEW OF CONTRACTORS’ PERFORMANCE DOES NOT INCLUDE REVIEW OF ADEQUACY OF
CONTRACTOR'S SAFETY MEASURES IN, ON, OR NEAR THE CONSTRUCTION SITE.
F. UTILITIES
1. PRIOR TO EXCAVATION AND EARTHWORK, VERIFY LOCATIONS OF UNDERGROUND UTILITIES WITH THE UTILITY COMPANIES, CONSTRUCTION MANAGER, AND THE GOVERNMENT. EXCAVATE OR SURVEY TO ESTABLISH EXACT UTILITY LOCATIONS. UTILITY LOCATIONS IF SHOWN ON THE CONTRACT DRAWINGS ARE ONLY APPROXIMATE AND CANNOT BE USED TO ASSURE THE CONTRACTOR OF ADEQUATE CLEARANCE.
2. ALL UTILITIES SHALL BE ADEQUATELY PROTECTED FROM DAMAGE. WHERE UTILITIES ARE ENCOUNTERED, CONTRACTOR SHALL IMMEDIATELY NOTIFY THE UTILITY COMPANY, CONSTRUCTION MANAGER, AND THE GOVERNMENT BEFORE PROCEEDING. ACTIVE UTILITIES ENCOUNTERED SHALL BE PROTECTED, SUPPORTED, OR RELOCATED AS DIRECTED. INACTIVE AND ABANDONED UTILITIES SHALL BE REMOVED, PLUGGED, OR
CAPPED AS DIRECTED.
G. QUALITY CONTROL AND ASSURANCE
1. THE CONTRACTOR SHALL PERFORM QUALITY CONTROL, TESTING AND INSPECTION OF ALL WORK AS REQUIRED BY THE CONTRACT DOCUMENTS, INCLUDING REFERENCED CODES, SPECIFICATIONS AND STANDARDS.
2. THE CONTRACTOR WILL ALSO EMPLOY QUALIFIED SPECIAL INSPECTORS TO PERFORM INSPECTIONS IN ACCORDANCE WITH CHAPTER 17 OF THE BUILDING CODE. THE CONTRACTOR IS RESPONSIBLE FOR SCHEDULING ALL INSPECTIONS AND TESTS. ITEMS REQUIRING SPECIAL INSPECTION ON
THIS PROJECT INCLUDE:
a. SOILS: FOUNDATION BEARINGS.
b. CONCRETE: ALL CONCRETE WORK.
3. THE STRUCTURAL ENGINEER MAY GENERALLY OBSERVE THE PROGRESS OF THE WORK, BUT HIS OBSERVATION SHALL NOT BE CONSTRUED AS
INSPECTION.
A.B. ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
ARCH ARCHITECT
B.L. BUILDING LINE
BLDG BUILDING
BM(S) BEAM(S)
BTWN BETWEEN
C.L. CENTER LINE
C.J. CONSTRUCTION OR CONTROL JOINT
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
D.B. DECK BEARING
DET DETAIL
DWG(S) DRAWING(S)
E.E. EACH END
E.F. EACH FACE
E.S. EACH SIDE
E.W. EACH WAY
E.J. EXPANSION JOINT
ELEV ELEVATION OR ELEVATOR
EMBED EMBEDMENT
ENGR ENGINEER
EQ EQUAL
EXIST EXISTING
F.F. FAR FACE
FNDN FOUNDATION
FL FLOOR
FT FOOT OR FEET
FTG FOOTING
GALV GALVANIZED
H.P. HIGH POINT
HORIZ HORIZONTAL
I.F. INSIDE FACE
IN INCHES
JT JOINT
K KIP (1000 POUNDS)
L ANGLE
L.P. LOW POINT
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
ABBREVIATIONS:
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFGR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
N.F. NEAR FACE
NO NUMBER
O.C. ON CENTER
O.F. OUTSIDE FACE
OPNG OPENING
P.C. PRECAST
P.L. PROPERTY LINE
P.T. POST TENSIONING
PED PEDESTAL
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R RADIUS
R.D. ROOF DRAIN
R.J. RUSTICATION JOINT
REINF REINFORCED OR REINFORCEMENT
SECT SECTION
SHT SHEET
SIM SIMILAR
S.O.G. SLAB ON GRADE
SPECS SPECIFICATIONS
SQ SQUARE
STL STEEL
T&B TOP AND BOTTOM
T/CONC TOP OF CONCRETE
T/FTG TOP OF FOOTING
T/STL TOP OF STEEL
T/SLAB TOP OF SLAB
TEMP TEMPERATURE
t THICKNESS
TYP TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
VERT VERTICAL
W.P. WORK POINT
# NUMBER
f'c SPECIFIED COMPRESSIVE STRENGTH
OF CONCRETE AT 28 DAYS
(C) COMPRESSION
(T) TENSION
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7/
/2
:5 3:
AM
Remodel Front Entrance
7/9/2021
STRUCTURAL GENERAL NOTES
S001
JTBFJE
20005.00 539-21-211
Cincinnati VAMC
B1
100% SUBMITTAL
Revisions Date
SOCKET 10'-0" INTO
GLACIAL TILL.
PIER CAP 42"X42"X36"
DEEP (-10").
15'-2" 12'-6"
'-2
'-6
36" DIA
T/CAP=727'-2"
B/PIER=695'-2"
36" DIA
T/CAP=727'-2"
B/PIER=695'-2"
36" DIA
T/CAP=727'-2"
B/PIER=695'-2"
36" DIA
T/CAP=727'-2"
B/PIER=695'-2"
36" DIA
T/CAP=727'-2"
B/PIER=695'-2"
DRILLED PIER SCHEDULE
PIERS TO EXTEND A MINIMUM OF 10'-0" INTO
GLACIAL TILL UNLESS NOTED OTHERWISE.
CAST BOXOUT AFTER CANOPY
COLUMN IS PLUMB AND GROUTED.
#4 TIE.
1/2" ISOLATION JOINT FULL DEPTH OF SLAB
ALL AROUND BOXOUT.
6 SETS OF DRILLED PIER TIES (3 TIES AT 3" TOP)
IN UPPER SEGMENT.
CONSTRUCTION JOINT
DRILLED PIER REINFORCEMENT PER SCHEDULE.
MINIMUM OF 4 BARS SHALL EXTEND TO BOTTOM OF
SHAFT TO SUPPORT THE CAGE. FABRICATE THESE
BARS 3'-0" LONGER THAN DESIGN LENGTH AND CUT
IN FIELD. REMAINDER OF VERTICAL BARS MAY STOP
AT DESIGN DEPTH. TIES REQUIRED FULL LENGTH OF
PIER. PROVIDE (2) ADDITIONAL TIES TO
ACCOMMODATE UP TO 3'-0" SHAFT EXTENSION.
REFER TO FOUNDATION PLAN FOR ESTIMATED
BOTTOM OF PIER ELEVATION. ELEVATIONS SHOWN
ARE FOR BIDDING PURPOSES ONLY. RAISE OR LOWER
ELEVATIONS IN FIELD AS DIRECTED BY GEOTECHNICAL
ENGINEER.
FORM UPPER SEGMENT OF PIER AS REQUIRED
AND ANY PORTION OF PIER WHICH PROJECTS
ABOVE SUBGRADE. UPPER SEGMENT SQUARE.
NOTE: ALL SHAFTS MUST BE TESTED FOR GAS BEFORE
ENTERING. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION REGARDING, TEMPORARY CASINGS, AND
DOWN-HOLE INSPECTION REQUIREMENTS.
TYPICAL CANOPY COLUMN/DRILLED PIER
STAGGER LAPS AND HOOKS ON OPPOSITE SIDES
OF PIER.
NOTES:
1. CENTER DRILLED PIERS BELOW COLUMNS UNLESS NOTED OTHERWISE.
SIZE VERTICAL BARS TIES
36" DIA (9) #7 #4 AT 18"
CIRCULAR COLUMN BOXOUT,
CAST SEPARATE OF SLAB.
2" MIN. AT CORNER OF BASE PLATE
SLAB ON GRADE
TOP OF DRILLED PIER
BOTTOM OF DRILLED PIER
SHAFT DIAMETER
UN
LE
SS
NO
TE
D
OT
HE
RW
IS
E
CA
P
"X
"X 3'-
0"
LO
W
ER
SE
GM
EN
T
VA
RI
ES
MI
NI
MU
M
LE
NG
TH
NO
TE
D
ON
PL
AN
MI
NI
MU
M
DR
ILL
ED
PI
ER
LE
NG
TH
TO
BE
'-0 "E
XC
EP
TW
HE
RE
LO
NG
ER
TO TIES
3" CLR
OVERLAP
MIN 6"
COLUMN BY CANOPY MANUFACTURE.
PROVIDE ANCHOR BOLTS PER CANOPY
MANUFACTURERS DRAWINGS.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7/
/2
:5 3:
AM
Remodel Front Entrance
7/9/2021
FOUNDATION PLAN
S101
JTBFJE
20005.00 539-21-211
Cincinnati VAMC
B1
100% SUBMITTAL
1/4" = 1'-0"S101
1 LEVEL 1 FOUNDATION PLAN
NORTH
GENERAL NOTES
A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
B. SITE VISIT(S) SHALL BE AS OUTLINED IN PROJECT SPECIFICATIONS.
C. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO
ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
D. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THE
DRAW INGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND
SATISFACTORY ARRANGEMENT FOR THEIR W ORK. THE VARIOUS DRAW INGS
COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT
ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS
OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAW INGS
ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST
BE FOLLOW ED TO EXECUTE THE W ORK AS INTENDED. IF DISCREPANCIES OCCUR,
CONTACT THE COR THROUGH THE CONTRACTING OFFICER FOR CLARIFICATION
BEFORE PROCEEDING.
E. ALL W ORK MUST BE COORDINATED W ITH THE CONTRACTING OFFICER AND (FOR
ALL OTHERS) TO MAINTAIN OPERATION OF THE EXISTING FACILITY.
F. ALL W ORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE W ITH ALL CURRENT
GOVERNING CODES AND STANDARDS.
G. EXISTING CONDITIONS SHOW N HAVE BEEN BASED UPON AVAILABLE DRAW ING
INFORMATION, AND MAY BE AT VARIANCE W ITH ACTUAL W ORK IN PLACE. THE
CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD
VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE W ORK. ANY
DISCREPANCIES BETW EEN EXISTING CONDITIONS AND THE W ORK SHOW N ON THE
CONTRACT DOCUMENTS W HICH MAY IMPACT THE PROGRESS OF THE W ORK SHALL
BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN W RITING
FOR RESOLUTION BEFORE PROCEEDING W ITH THE W ORK.
H. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND
FIRE-RATING OF NEW AND EXISTING W ALL ASSEMBLIES. ALL PENETRATIONS
THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROJECTED AND/OR FIRE-STOPPED
AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED. COORDINATE W ITH ALL
TRADES TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS AND DETAILS
ARE MET.
I. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT AND OTHER SIMILAR PENETRATIONS
OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS
THROUGH 0-HOUR RATED W ALLS AND FLOORS SHALL BE FIRESTOPPED TO RETARD
PASSAGE OF FIRE AND SMOKE.
J. ALL CONDUITS IN FINISHED ROOMS, CORRIDORS, ETC. SHALL BE CONCEALED IN A
W ALL OR ABOVE CEILING.
K. ACCESS PANELS IN NON ACCESSIBLE CEILINGS SHALL BE PROVIDED FOR ALL
ELECTRICAL ITEMS REQUIRING ACCESS.
L. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF
LIGHTS, SPEAKERS, NURSE CALL DEVICES, ETC.
M. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN
THE CONTRACT. REFIN ISH ANY SURFACE DISTURBED UNDER THIS W ORK TO MATCH
EXISTING.
N. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED
BY THE VA SHALL BE REMOVED FROM THE PREMISES AND DISPOSED OF PROPERLY
BY THE CONTRACTOR.
O. THE CONTRACT DRAW INGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL
OFFSET W HICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE W ORK IN
ADVANCE W ITH ALL OTHER TRADES AND REPORT IMMEDIATELY AND DIFFICULTIES
W HICH CAN BE ANTICIPATED.
P. ALL ABANDONED EXTRANEOUS CONDUITS, W IRING, DEVICES, ETC. SHALL BE REMOVED.
Q. REFER TO MECHANICAL DRAW INGS FOR ADDITIONAL INFORMATION CONCERNING
MECHANICAL EQUIPMENT THAT REQUIRES ELECTRICAL CONNECTIONS.
R. REFER TO ARCHITECTURAL PHASING PLANS FOR SEQUENCE OF CONSTRUCTION. EXISTING
POW ER MYST REMAIN ELECTRICALLY CONTINUOUS TO AREAS ADJACENT TO PROJECT TO
REMAIN OPERATIONAL. COORDINATE ALL DEMOLITION AND NEW W ORK W ITH OTHER TRADES
AND COR.
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN . MAINTAIN EXISTING C IRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS W HERE
REQUIRED.
ELECTRICAL CONNECTION.
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).
SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERW ISE) TW O GANG ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R W ITH BOTTOM OUTLET CONTROLLED BY W ALL SW ITCH. (18" MH UNLESS
NOTED OTHERW ISE).
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED
OTHERW ISE).
20A-125V W EATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERW ISE) W ITH
EXTRA DUTY GRAY COVER, VERTICAL MOUNT.
20A-125V W EATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH
UNLESS NOTED OTHERW ISE), W ITH EXTRA DUTY GRAY COVER, VERTICAL MOUNT.
20A-125V POW ERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERW ISE).
20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R, IN FLOOR BOX W ITH COVERPLATE AND HOUSING.
PROVIDE CARPET FLANGE W HERE REQUIRED.
20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERW ISE).
30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERW ISE).
50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERW ISE).
20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERW ISE).
30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERW ISE).
50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERW ISE).
JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED
OTHERW ISE).
SINGLE POLE SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
TW O POLE W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
MULTI-W AY W ALL SW ITCH, # INDICATES NUMBER OF W AYS (46" MH UNLESS NOTED OTHERW ISE).
SW ITCH W ITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERW ISE).
KEY OPERATED W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
OCCUPANCY W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
SW ITCH W ITH RECEPTACLE (46" MH UNLESS NOTED OTHERW ISE) STANDARD TW O-GANG ASSEMBLY OF SW ITCH AND
RECEPTACLE.
FLUSH FRACTIONAL HORSEPOW ER MOTOR STARTER W ITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS
NOTED OTHERW ISE).
HP RATED W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
DISCONNECT SW ITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SW ITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SW ITCHBOARD PER DRAW INGS.
PULL BOX.
CEILING MOUNTED OCCUPANCY SENSOR.
W ALL MOUNTED OCCUPANCY SENSOR.
CEILING MOUNTED DAYLIGHT SENSOR.
GF
W P
W P/GF
T
20A
30A
50A
20A
50A
30A
J
P
K
OS
R
H
OS
M
OS
M
DS
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERW ISE).
M
P/B
LOW -VOLTAGE MOMENTARY W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).L
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SW ITCH
BLDG - BUILD ING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTW N - BETW EEN
CC - CRASH CART
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - C IRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICERS REPRESENTATIVE.
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - D IAMETER
DIM - D IMENSION
DIV - D IVISION
DN - DOW N
DW G - DRAW ING
EA - EACH
EC - ELECTRICAL (D IVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EOB - EMERGENCY OFF BUTTON
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (D IVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL CONTRACTOR
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR
GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POW ER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFD - MULTIFUNCTION DEVICE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MIN IMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MW - MICROW AVE (COORDINATE MOUNTING W ITH ARCHITECT)
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OF - OW NER FURNISHED
OFCI - OW NER FURNISHED CONTRACTOR INSTALLED
OFOI - OW NER FURNISHED OW NER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RF - REFRIGERATOR
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY (DIV 28)
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY (DIV 27)
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TV - TELEVISION (COORDINATE MOUNTING W ITH ARCHITECT)
TYP - TYPICAL
UC/RF - UNDERCABINTE REFRIGERATOR
UNO - UNLESS NOTED OTHERW ISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W / - W ITH
W /O - W ITHOUT
W P - W EATHERPROOF
ZVC - ZONE VALVE CABINET
LUMINAIRE SYMBOLS
LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOW ER CASE LETTER DENOTES
SW ITCHING ARRANGEMENT.
LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY/LIFE SAFETY CIRCUIT.
EXIT LIGHTING FIXTURE, ARROW S AS INDICATED.
A a
W IREMOLD RACEW AY, AS NOTED ON PLANS.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R W ITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERW ISE).
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.LIGHTING FIXTURE ON CRITICAL CIRCUIT.
SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.
J
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, IN FLUSH FLOOR BOX W ITH ROUND COVERPLATE. PROVIDE CARPET
FLANGE W HERE REQUIRED.
E2
B E2
DETAIL: B = DETAIL DESIGNATION
E2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET W HERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
W IRE & CONDUIT IN W ALL OR ABOVE CEILING.
W IRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROW HEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES
CIRCUIT(S).
EXISTING W IRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
X - 1,2
4"
4"
4"
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE). W HEN SHOW N, RECEPTACLE TO HAVE
"CONTROLLED" MARKINGS.
LIGHTING DIM M ER SW ITCH (46" M H UNLESS NOTED OTHERW ISE) 1000 W ATTS UNLESS OTHERW ISE IN DICATED.DM
FLOOR BOX PER DIV 26. # INDICATES TYPE, REFER TO FLOOR BOX (FB) SCHEDULE. SUBSCRIPT "X" INDICATES TECHNOLOGY
DEVICE(S), REFER TO TECHNOLOGY DETAILS.#
X
POKE-THRU PER DIV 26. # INDICATES TYPE, REFER TO POKE-THRU (PT) SCHEDULE. SUBSCRIPT "X" INDICATES TECHNOLOGY
DEVICE(S), REFER TO TECHNOLOGY DETAILS.
X
20A-125V SURFACE MOUNTED DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE). W HEN SHOW N, RECEPTACLE TO HAVE "CONTROLLED" MARKINGS.
AM
C/I
FIRE ALARM SYMBOLS
ADD RESSABLE M ODU LE. SUBSCR IPT "I" INDICATES INPU T. SU BSCRIPT "C" IND ICATES CONTROL.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
NOT FOR CONSTRUCTION
7/
/2
2:
:3
P
M
Remodel Front Entrance
07/09/2021 E001
W JFMSG
20005.00 539-21-211
Cincinnati VAMC
B1
INDEX OF DRAWINGS - ELECTRICAL
SHEET NUMBER SHEET NAME
E001 ABBREVIATIONS, SYMBOLS, GENERAL NOTES & INDEX OF DRAWINGS
E100 PARTIAL FIRST FLOOR PLAN - REMOVALS
E101 PARTIAL FIRST FLOOR PLAN - NEW WORK
E600 SCHEDULES
CCCC
SS
CC
SC
HA
W P/
G F
W P/
G F
J
J
C R
AREA OF WORK
Revolving Door D*1*1
Stair S*1*6
5 TYP.
E101
GENERAL NOTES - DEMOLITION
A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, W IRING DEVICES,
CONDUITS, ETC., SHOW N ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP
CONDUITS AT THE AREA OF W ORK PERIMETER AND REMOVE CONDUIT W ITHIN
THE W ORK AREA, DISCONNECT W IRING AT THE OVERCURRENT PROTECTIVE
DEVICE AND REMOVE W IRING COMPLETELY FROM THE ABANDONED CONDUITS.
B. DISCONNECT ALL ABANDONED W IRING OF ALL TYPES AT THE OVERCURRENT
PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED W IRING.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS
PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
NOT FOR CONSTRUCTION
7/
/2
2:
:3
P
M
Remodel Front Entrance
07/09/2021 E100
W JFMSG
20005.00 539-21-211
Cincinnati VAMC
B1
N Scale: 1/8" = 1'-0"1 PARTIAL FIRST FLOOR PLAN - REMOVALS
KEYPLAN
PLAN NOTES:
1. REMOVE ELECTRICAL POW ER FOR REVOLVING DOOR BACK TO PANELBOARD.
REMOVE ALL ASSOCIATED CONDUIT AND W IRING. MARK BREAKER AS SPARE.
2. REMOVE LIGHT FIXTURE W ALL MOUNTED HIGH ON EXTERIOR W ALL. REMOVE
ELECTRICAL W IRING BACK TO LAST ACTIVE DEVICE OR PANELBOARD.
3. DOOR TO BE REMOVED. DISCONNECT POW ER TO AUTO OPERATOR AND RELOCATE
POW ER AS NECESSARY TO NEW AUTO DOOR OPERATOR.
4. EXISTING HANDICAP DOOR OPERATOR TO BE REMOVED.
5. EXISTING CARD READER TO BE REMOVED.
6. LIGHT FIXTURES TO BE REMOVED. UTILIZE EXISTING CUT OUTS FOR NEW LIGHT
FIXTURES.
CCCC
SS
CC
SC
W P/GF
W P/GF
W P/GF
W P/GF
PC
J J
J
AM
I
W P/
G F
W P/
G F
J
J
HA
C R
J
AREA OF WORK
1F1C1FDPF
1A1L
1EC3
1F2 C1A C1F1
1CEC4
1A1P
Revolving Door D*1*1
Stair S*1*6
W 1
W 1 W 1
TYP.
1A1P - 2
1A1P - 4
ELEC
C109
C1A - 16
4 5
C1F - 32,34
1A1L - 1,3,5
1A1P - 40,42
E101
Sim
F1
F1
F1
F2 F2 F2 F2
1A1P - 6
W 1
96" 96"
96"
96"
E101 W 196"
W 1 96"
W 1
96" W 1
96"
GENERAL NOTES
A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE
OBTAINED FROM THE ARCHITECTURAL PLAN.
1 COVER SHOW N IN OPEN POSITION.
2 ONE-GANG CAST ALUMINUM BOX, RAC O 5343 OR
APPROVED EQUAL, W ITH RACO MX3200 EXTRA-DU TY
W EATHERPROOF COVER FOR GFCI RECEPTACLE
UNLESS IN DICATED OTHER W ISE.
3 CEN TER W ITH BOX.
4 3/4" RIGID CONDU IT SUPPORT.
5 RIGID GALVANIZED STEEL CONDUIT.
6 PVC C ONDUIT, SCHEDULE 40.
7 FINISHED GRADE.
DETAIL NOTES
A VERIFY EXACT LOCATION AND ORIENTATION OF
DEVICE W ITH ARCHITECT PRIOR TO ROUGH-IN.
GENERAL DETAIL NOTES
8" DIA
30"
3"
1"
First Floor 728' - 0"
Second Floor 739' - 11"
B01-FIRST FLOOR
728' - 0"
B01-SECOND
FLOOR
739' - 11"
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
NOT FOR CONSTRUCTION
7/
/2
2:
:4
P
M
Remodel Front Entrance
07/09/2021 E101
W JFMSG
20005.00 539-21-211
Cincinnati VAMC
B1
N Scale: 1/8" = 1'-0"1 PARTIAL FIRST FLOOR PLAN - NEW WORK
PLAN NOTES
1. PROVIDE 1" CONDUIT TO ISLAND UNDER ROAD FOR 120V POW ER. CONCRETE ENCASE
CONDUITS UNDER ROADW AY.
A. ALL EXPOSED CONDUITS ON THE EXTERIOR OF THE BUILDING SHALL BE RIGID METAL
CONDUIT W ITH W ATER TIGHT FITTINGS.
B. ALL UNDERGROUND CONDUIT TO BE PVC SCHEDULE 40.
C. CONDUIT IS ALLOW ED TO TRANSITION TO TYPICAL EMT AFTER PENETRATION INTO
BUILDING.
2. PROVIDE 277V POW ER TO COLUMN MOUNTED LIGHT FIXTURES. PROVIDE CONDUIT AND
POW ER UP HOLLOW COLUMN TO LIGHT FIXTURES.
A. UTILIZE CONDUIT PATH INTO BUILDING AS SHOW N IN DETAIL 3. PROVIDE 1" CONDUIT INTO
BUILDING. UTILIZE SAME CONDUIT REQUIREMENTS AS NOTED IN NOTE #1 (A)(B) AND (C).
3. PROVIDE PHOTOCELL CONTROLS FOR CANOPY LIGHT FIXTURES. MOUNT PHOTOCELL HIGH
ABOVE CANOPY AND AIM SENSOR TOW ARDS NORTH CONCEALED FROM VIEW FROM
GROUND.
4. PROVIDE NEW 208V/1P 20A CIRCUIT TO REVOLVING DOOR.
5. PROVIDE 480V/3P 30A CIRCUIT TO AIR CURTAIN INTEGRAL ELECTRIC HEAT UNIT. PROVIDE
30A/3P DISCONNECT NON-FUSED NEMA 1.
6. PROVIDE 208V/1P 20A CIRCUIT TO AIR CURTAIN MOTOR AND CONTROLS. PROVIDE 30A/2P
DISCONNECT NON-FUSED NEMA 1.
7. PROVIDE FIRE ALARM INTERFACE. REVOLVING DOOR REQUIRES NORMALLY CLOSED DRY
CONTACTS FOR RELEASE OF ALL LOCKING MECHANISMS.
8. RELOCATE EXISTING POW ER TO NEW AUTO DOOR OPERATOR.
9. NEW LOCATION OF HAND OPERATOR FOR NEW REVOLVING DOOR.
10. NEW LOCATION FOR NEW CARD READER TO OPERATE SIDE DOOR.
11. UTILIZE EXISTING CIRCUITRY AND CONTROLS FOR NEW LIGHT FIXTURE. INSTALL NEW LIGHT
FIXTURE IN EXACT LOCATION AND CUTOUT AS EXISTING FIXTURE(S).
A. CONTRACTOR TO MEASURE EXISTING LIGHT FIXTURE AND CUT OUT PRIOR TO ORDERING
NEW FIXTURES.
12. PROVIDE 120V C IRCUIT TO ILLUMINATED SIGN ON CANOPY. PROVIDE TIMECLOCK
CONTROLLER, INSTALL TIME CLOCK CONTROLLER INSIDE ELECTRICAL ROOM.
A. CONDUIT TO BE RAN UP HOLLOW FRAME OF CANOPY AND TO SIGNAGE.
13. PROVIDE A MAX EXPOSED CONDUIT OF 12". CONTRACTOR SHALL LIMIT AS MUCH EXPOSED
CONDUIT AS POSSIBLE.
14. CONDUIT TO RUN UNDER STOREFRONT AND UP ABOVE CEILING ON THE INTERIOR PORTION
OF THE BUILDING. CONDUIT TO BE COVERED BY BREAK METAL TO MATCH STOREFRONT. NO
CONDUIT SHOULD BE VISIBLE ON THE INTERIOR OF THE BUILD ING.
SCALE: NONE
KEYPLAN
EXTERIOR PEDESTAL MOUNTED WP/GF TYPE RECEPTACLE4
CANOPY LIGHTING CALCULATION5
SCALE: 1/4" = 1'-0"
CONDUIT PATH6
Type W 1
SURFACE MOUNT LED CANOPY FIXTURE
MOUNTING - W ET LOCATION OUTLET BOX
HOUSING: ONE PIECE EXTRUDED ALUMINUM HOUSING W ITH
SILICONE GASKETING. TAMPER RESISTANT FASTENERS.
ALL COMPONENTS TO BE NON-CORROSIVE.
FINISH: SEMIGLOSS SILVER POLYESTER POW DER COATING.
OPTICS: TW O-PIECE EXTRUDED ALUMINUM HEAT SINK HOUSING
AND LIGHT ENGINE. ASYMMETRIC OPTICAL LIGHT BAR,
W ATER CLEAR ACRYLIC.
LAMPS: SOLID STATE LED. 60,000 HOUR RATED AT L90, 80 CRI.
4000K
CERTIFICATION: UL1598, UL2108, CSA LABEL. W ET LOCATION LABELED.
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “W 1” 9" LENGTH 3068 LM, 32 W , NOMINAL
W1
Type F1
RECESSED LED 6” DIAMETER OPEN SQUARE DOW NLIGHT FIXTURE
HOUSING: GLAVANIZED STEEL MOUNTING. GALVANIZED STEEL
JUNCTION BOX W ITH BOTTOM HINGED ACCESS
COVERS AND SPRING LATCHES.
REFLECTOR: SEMI-SPECULAR DIFFUSE FINISH.
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L70, 80 CRI.
4000K
CERTIFICATION: CSA LABEL. ENERGY STAR QUALIFIED.
W ET LOCATION LISTED AND IP55 RATED. NON-IC RATING
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “F1” 6” 55DEG 2000 LM, 23 W , NOMINAL
F1
Type F2
RECESSED LED 10” DIAMETER DOW NLIGHT FIXTURE
HOUSING:
REFLECTOR: SEMI-SPECULAR DIFFUSED FINISH. SELF FLANGED
ANODIZED REFLECTOR.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L70, 80 CRI.
4000K
CERTIFICATION: W ET LOCATION LISTED. IP55 RATED.
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “F2” 10” 2000 LM, 23 W , NOMINAL
F2
"1A1L"
EX. DISTRIBUTION PANEL "SW BD "DS-1A"
TO EXIST DIST.
PNL. "US-1X"
480/277 - 800A - 3PH - 4W - 35kAIC
100A/3P
EXISTING FEEDERS TO
EXISTING PANELS
"1A1P"
EX. DISTRIBUTION PANEL "SWBD "DS-1B"
TO EXIST DIST.
PNL. "US-1D"
208/120V - 800A - 3PH - 4W - 35kAIC
150A/3P
EXISTING FEEDERS TO
EXISTING PANELS
"C1A"
EX. DISTRIBUTION PANEL "SWBD "ESB-20"
TO ATS-10
400A
CRITICAL BRANCH
480/277 - 400A - 3PH - 4W - 35kAIC
60A/3P
EXISTING FEEDERS TO
EXISTING PANELS
"C1F"
EX. DISTRIBUTION PANEL "SWBD "ESB-40"
TO ATS-11
600A
EQUIPMENT BRANCH
480/277 - 600A - 3PH - 4W - 35kAIC
150A/3P
EXISTING FEEDERS TO
EXISTING PANELS
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290
VA Project No.
JPA Project No.
NOT FOR CONSTRUCTION
7/
/2
2:
:4
P
M
Remodel Front Entrance
07/09/2021 E600
W JFMSG
20005.00 539-21-211
Cincinnati VAMC
B1
13.77 kVA 13.96 kVA (17 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING CRITICAL POWER PANELBOARD.
1. PROVIDE NEW 20A/1P BREAKER.
Total Est. Demand: 17 A Total Conn.: 17 A
Total Est. Demand: 13960 VA Spare 13000 VA 100.00% 13000 VA Total Conn. Load: 13768 VA
Lighting 768 VA 125.00% 960 VA Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 6.00 kVA 4.26 kVA 3.51 kVA 41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40 37 Space -- -- 0 VA 0 VA -- -- Space 38 35 Space -- -- 0 VA 0 VA -- -- Space 36 33 Space -- -- 0 VA 0 VA -- -- Space 34
31 Space -- -- 0 VA 0 VA -- -- Space 32 29 Space -- -- 0 VA 0 VA -- -- Space 30 27 Space -- -- 0 VA 0 VA -- -- Space 28 25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24 21 Space -- -- 0 VA 0 VA -- -- Space 22 19 Space -- -- 0 VA 0 VA -- -- Space 20 17 Space -- -- 0 VA 0 VA -- -- Space 18
15 Space -- -- 0 VA 256 VA 1 20 A Lighting (NOTE 1) 16
13 EXIST 20 A 1 1000... 1000... 1 20 A EXIST 14
11 EXIST 20 A 1 1000... 1000... 1 20 A EXIST 12
9 EXIST 20 A 1 1000... 1000... 1 20 A EXIST 10
7 EXIST 20 A 1 1000... 1000... 1 20 A EXIST 8
5 EXIST 20 A 1 1000... 512 VA 1 20 A EXIST 6
3 EXIST 20 A 1 1000... 1000... 1 20 A EXIST 4
1 EXIST 20 A 1 1000... 1000... 1 20 A EXIST 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 60 A Supply From: Enclosure: Type 1 Mains Type: MLO
Location: ELEC C109 Mounting: Surface A.I.C. Rating:
Panel: C1A
16.68 kVA 16.68 kVA (46 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING NORMAL POWER PANELBOARD
1. UTILIZE EXISTING SPARE 20A/1P BREAKER FOR NEW CIRCUIT.
2. PROVIDE NEW 20A/2P BREAKER. REMOVE EXISTING SPARE 20A/1P BREAKER.
Total Est. Demand: 46 A Total Conn.: 46 A
Total Est. Demand: 16680 VA Spare 12960 VA 100.00% 12960 VA Total Conn. Load: 16680 VA
Receptacle 3720 VA 100.00% 3720 VA Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 5.40 kVA 5.43 kVA 5.85 kVA 41 Space -- -- 0 VA 750 VA -- -- -- 42
39 Space -- -- 0 VA 750 VA 2 20 A AIR CURTAIN 40
37 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 38
35 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 36
33 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 34
31 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 32
29 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 30
27 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 28
25 Spare 20 A 1 0 VA 720 VA 1 20 A EXISTING 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24 21 Spare 20 A 1 0 VA 720 VA 1 20 A EXISTING 22 19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20 17 Spare 20 A 1 0 VA 720 VA 1 20 A EXISTING 18
15 Spare 20 A 1 0 VA 720 VA 1 20 A EXISTING 16 13 Spare 20 A 1 0 VA 720 VA 1 20 A EXISTING 14 11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12 9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 EXISTING 20 A 1 720 VA 0 VA 1 20 A Spare 8
5 -- -- -- 0 VA 1500... 1 20 A CANOPY SIGN (NOTE 1) 6
3 -- -- -- 0 VA 360 VA 1 20 A Receptacle (NOTE 1) 4 1 Spare 40 A 3 0 VA 360 VA 1 20 A Receptacle (NOTE 1) 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 150 A Supply From: Enclosure: Type 1 Mains Type: MLO
Location: ELEC C109 Mounting: Surface A.I.C. Rating:
Panel: 1A1P
DIST. PANEL "DS-1B"DIST. SW BD "ESW B-20"
21.5 kVA 21 kVA (25 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING NORMAL POWER PANELBOARD
1. PROVIDE NEW 30A/3P BREAKER.
Total Est. Demand: 25 A Total Conn.: 26 A
Total Est. Demand: 21000 VA
Spare 10500 VA 100.00% 10500 VA Total Conn. Load: 21500 VA Receptacle 11000 VA 95.45% 10500 VA Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 8.17 kVA 6.67 kVA 6.67 kVA
23 Space -- -- 0 VA 1500... 1 20 A EXIST 24 21 Space -- -- 0 VA 1500... 1 20 A EXIST 22 19 Space -- -- 0 VA 1500... 1 20 A EXIST 20 17 Space -- -- 0 VA 0 VA -- -- Space 18
15 Space -- -- 0 VA 0 VA -- -- Space 16 13 Space -- -- 0 VA 1500... 1 20 A EXIST 14 11 Space -- -- 0 VA 1500... 1 20 A EXIST 12 9 Space -- -- 0 VA 1500... 1 20 A EXIST 10
7 Space -- -- 0 VA 1500... 1 20 A EXIST 8 5 -- -- -- 3667... 0 VA 1 20 A Spare 6 3 -- -- -- 3667... 0 VA 1 20 A Spare 4 1 AIR CURTAIN HEAT 30 A 3 3667... 0 VA 1 20 A Spare 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: MLO
Location: ELEC C109 Mounting: Surface A.I.C. Rating:
Panel: 1A1L
DIST. PANEL "DS-1A"
NOTE 1
NOTE 1
NOTE 2
EXISTING
EXISTING
EXISTING
2 kVA 2 kVA (6 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING EQUIPMENT POWER PANELBOARD
1. PROVIDE NEW 20A/2P BREAKER.
Total Est. Demand: 6 A Total Conn.: 6 A
Total Est. Demand: 2000 VA Total Conn. Load: 2000 VA
Receptacle 2000 VA 100.00% 2000 VA Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 1.00 kVA 1.00 kVA 0.00 kVA 41 Space -- -- 0 VA 0 VA -- -- -- 42 39 Space -- -- 0 VA 0 VA -- -- -- 40 37 Space -- -- 0 VA 0 VA 3 20 A EXIST 38
35 Space -- -- 0 VA 0 VA -- -- Space 36
33 EXIST 20 A 1 0 VA 1000... -- -- -- 34
31 EXIST 20 A 1 0 VA 1000... 2 20 A REVOLVING DOOR 32
29 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 30
27 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 28
25 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 26
23 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 24
21 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 22
19 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 20
17 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 18
15 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 16
13 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 14
11 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 12
9 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 10
7 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 8
5 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 6
3 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 4
1 EXIST 20 A 1 0 VA 0 VA 1 20 A EXIST 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208…