Addendum 01_12.02.2021_Part2_Drwngs.pdf

PDF 846 KB Posted

Attached to
Z1DA--Remodel Front Entrance (Cin) 539-21-211
Solicitation number
36C25022B0002
Issued by

About this file

This solicitation package includes an invitation for bid for construction services and drawings related to the Remodel Front Entrance project at the Cincinnati VA Medical Center. The scope of work involves demolishing and removing existing structures and equipment at the front entrance, and constructing a new revolving door, canopy, lighting, and associated electrical infrastructure. The bid package specifies requirements for the general contractor such as obtaining security clearance, adhering to a 300-day schedule, and providing performance and payment bonds. As a 100% service-disabled veteran-owned small business set-aside, the awarded contractor must perform a minimum of 25% of the construction work and qualify under the relevant $39.5 million size standard. A pre-bid site visit will be held on November 29, 2021, and questions must be submitted by the date listed in the solicitation. Bids are due in accordance with the schedule in the invitation for bid.

View the file

Other files

File Type Posted
36C25022B0002 0008.docx DOCX document
36C25022B0002 0007.docx DOCX document
Attachment 1 - 539-21-211 100_ BID Dwgs_10.28.2021.pdf PDF
36C25022B0002 0006.docx DOCX document
36C25022B0002 0005.docx DOCX document
Attachment 3 - 2008-12-12_Cincinnati VAMC Boring Profile.pdf PDF
Attachment 4 - 2008-12-20 Geotechnical Report.pdf PDF
36C25022B0002 0004.docx DOCX document
Attachment 2 - Addendum 02.pdf PDF
Attachment 1 - 539-21-211_RFI AE Responses.pdf PDF
36C25022B0002 0003.docx DOCX document
36C25022B0002 0002.docx DOCX document
BN Justification - Johnson Controls - PACS.pdf PDF
Addendum 01_12.02.2021_Part1_Cover Letter.pdf PDF
Pre-Bid Site Visit Sign-In Sheet.pdf PDF
Attachment 3 - 539-21-211 A-E CD Drawings (Rev Format 24Nov21).pdf PDF
36C25022B0002 0001.docx DOCX document
36C25022B0002 IFB Solicitation (Rev 24Nov21).pdf PDF
36C25022B0002_1.docx DOCX document
Attachment 4 - Specifications (539-21-211).pdf PDF
Attachment 6 - RFI.pdf PDF
Attachment 1 - VHA Directive 1192 01.pdf PDF
Attachment 2 - BN Justification - Corbin Russwin Locksets.pdf PDF
Attachment 3 - Drawings (539-21-211).pdf PDF
Attachment 5 - WD OH20210001 (9-24-2021).pdf PDF
Attachment 7 - EMR.docx DOCX document
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CCCC

SS

CC

SC

HA

W P

/G F

W P

/G F

J

J

C R

AREA OF WORK

Revolving Door D*1*1

Stair S*1*6

5 TYP.

E101

GENERAL NOTES - DEMOLITION

A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, W IRING DEVICES,

CONDUITS, ETC., SHOW N ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF W ORK PERIMETER AND REMOVE CONDUIT W ITHIN

THE W ORK AREA, DISCONNECT W IRING AT THE OVERCURRENT PROTECTIVE

DEVICE AND REMOVE W IRING COMPLETELY FROM THE ABANDONED CONDUITS.

B. DISCONNECT ALL ABANDONED W IRING OF ALL TYPES AT THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED W IRING.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

NOT FOR CONSTRUCTION

/2

/2

:4

:4

P

M

Remodel Front Entrance

07/09/2021

PARTIAL FIRST FLOOR PLAN -

REMOVALS

E100

W JFMSG

20005.00

539-21-211

Cincinnati VAMC

B1

Jason Reeves - Chief Engineer Josh Schneider - COR

CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"1

PARTIAL FIRST FLOOR PLAN - REMOVALS

KEYPLAN

PLAN NOTES:

1. REMOVE ELECTRICAL POW ER FOR REVOLVING DOOR BACK TO PANELBOARD.

REMOVE ALL ASSOCIATED CONDUIT AND W IRING. MARK BREAKER AS SPARE.

2. REMOVE LIGHT FIXTURE W ALL MOUNTED HIGH ON EXTERIOR W ALL. REMOVE

ELECTRICAL W IRING BACK TO LAST ACTIVE DEVICE OR PANELBOARD.

3. DOOR TO BE REMOVED. DISCONNECT POW ER TO AUTO OPERATOR AND RELOCATE

POW ER AS NECESSARY TO NEW AUTO DOOR OPERATOR.

4. EXISTING HANDICAP DOOR OPERATOR TO BE REMOVED.

5. EXISTING CARD READER TO BE REMOVED. UTILIZE EXISTING W IRING FOR NEW CARD

READER. REFER TO NEW W ORK PLANS FOR LOCATION.

6. LIGHT FIXTURES TO BE REMOVED. UTILIZE EXISTING CUT OUTS FOR NEW LIGHT

FIXTURES.

Revisions Date

1 ADDENDUM #1 12/02/21

CCCC

SS

CC

SC

W P/GF

W P/GF

W P/GF

W P/GF

PC

J J

J

AM

I

W P

/G F

W P

/G F

J

J

HA

C R

J

AREA OF WORK

1F1C1FDPF

1A1L

1EC3

1F2 C1A C1F1

1CEC4

1A1P

Revolving Door

D*1*1

Stair S*1*6

W 1

W 1 W 1

TYP.

1A1P - 2

1A1P - 4

ELEC

C109

C1A - 16

C1F - 32,34

1A1L - 1,3,5

1A1P - 40,42

E101

Sim

F1

F1

F1

F2 F2 F2 F2

1A1P - 6

W 1

96" 96"

96"

96"

E101 W 196"

W 1 96"

W 1

96" W 1

96"

GENERAL NOTES

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE

OBTAINED FROM THE ARCHITECTURAL PLAN.

1 COVER SHOW N IN OPEN POSITION.

2 ONE-GANG CAST ALUMINUM BOX, RACO 5343 OR

APPROVED EQUAL, W ITH RACO MX3200 EXTRA-DUTY

W EATHERPROOF COVER FOR GFCI RECEPTACLE

UNLESS INDICATED OTHERW ISE.

3 CENTER W ITH BOX.

4 3/4" RIGID CONDUIT SUPPORT.

5 RIGID GALVANIZED STEEL CONDUIT.

6 PVC CONDUIT, SCHEDULE 40.

7 FINISHED GRADE.

DETAIL NOTES

A VERIFY EXACT LOCATION AND ORIENTATION OF

DEVICE W ITH ARCHITECT PRIOR TO ROUGH-IN.

GENERAL DETAIL NOTES

8" DIA

30"

3"

1"

First Floor 728' - 0"

Second Floor 739' - 11"

B01-FIRST FLOOR

728' - 0"

B01-SECOND

FLOOR

739' - 11"

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

NOT FOR CONSTRUCTION

/2

/2

:4

:4

P

M

Remodel Front Entrance

07/09/2021

PARTIAL FIRST FLOOR PLAN - NEW

WORK

E101

W JFMSG

20005.00

539-21-211

Cincinnati VAMC

B1

Jason Reeves - Chief Engineer Josh Schneider - COR

CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"1

PARTIAL FIRST FLOOR PLAN - NEW WORK

PLAN NOTES

1. PROVIDE 1" CONDUIT TO ISLAND UNDER ROAD FOR 120V POW ER. CONCRETE ENCASE

CONDUITS UNDER ROADW AY.

A. ALL EXPOSED CONDUITS ON THE EXTERIOR OF THE BUILDING SHALL BE RIGID METAL

CONDUIT W ITH W ATER TIGHT FITTINGS.

B. ALL UNDERGROUND CONDUIT TO BE PVC SCHEDULE 40.

C. CONDUIT IS ALLOW ED TO TRANSITION TO TYPICAL EMT AFTER PENETRATION INTO

BUILDING.

2. PROVIDE 277V POW ER TO COLUMN MOUNTED LIGHT FIXTURES. PROVIDE CONDUIT AND

POW ER UP HOLLOW COLUMN TO LIGHT FIXTURES.

A. UTILIZE CONDUIT PATH INTO BUILDING AS SHOW N IN DETAIL 3. PROVIDE 1" CONDUIT INTO

BUILDING. UTILIZE SAME CONDUIT REQUIREMENTS AS NOTED IN NOTE #1 (A)(B) AND (C).

3. PROVIDE PHOTOCELL CONTROLS FOR CANOPY LIGHT FIXTURES. MOUNT PHOTOCELL HIGH

ABOVE CANOPY AND AIM SENSOR TOW ARDS NORTH CONCEALED FROM VIEW FROM

GROUND.

4. PROVIDE NEW 208V/1P 20A CIRCUIT TO REVOLVING DOOR.

5. PROVIDE 480V/3P 30A CIRCUIT TO AIR CURTAIN INTEGRAL ELECTRIC HEAT UNIT. PROVIDE

30A/3P DISCONNECT NON-FUSED NEMA 1.

6. PROVIDE 208V/1P 20A CIRCUIT TO AIR CURTAIN MOTOR AND CONTROLS. PROVIDE 30A/2P

DISCONNECT NON-FUSED NEMA 1.

7. PROVIDE FIRE ALARM INTERFACE. REVOLVING DOOR REQUIRES NORMALLY CLOSED DRY

CONTACTS FOR RELEASE OF ALL LOCKING MECHANISMS.

8. RELOCATE EXISTING POW ER TO NEW AUTO DOOR OPERATOR.

9. NEW LOCATION OF HAND OPERATOR FOR NEW REVOLVING DOOR.

10. NEW LOCATION FOR NEW CARD READER TO OPERATE SIDE DOOR. EXTEND EXISTING

W IR ING AS NECESSARY TO NEW CARD READER LOCATION.

11. UTILIZE EXISTING CIRCUITRY AND CONTROLS FOR NEW LIGHT FIXTURE. INSTALL NEW LIGHT

FIXTURE IN EXACT LOCATION AND CUTOUT AS EXISTING FIXTURE(S).

A. CONTRACTOR TO MEASURE EXISTING LIGHT FIXTURE AND CUT OUT PRIOR TO ORDERING

NEW FIXTURES.

12. PROVIDE 120V C IRCUIT TO ILLUMINATED SIGN ON CANOPY. PROVIDE TIMECLOCK

CONTROLLER, INSTALL TIME CLOCK CONTROLLER INSIDE ELECTRICAL ROOM.

A. CONDUIT TO BE RAN UP HOLLOW FRAME OF CANOPY AND TO SIGNAGE.

13. PROVIDE A MAX EXPOSED CONDUIT OF 12". CONTRACTOR SHALL LIMIT AS MUCH EXPOSED

CONDUIT AS POSSIBLE.

14. CONDUIT TO RUN UNDER STOREFRONT AND UP ABOVE CEILING ON THE INTERIOR PORTION

OF THE BUILDING. CONDUIT TO BE COVERED BY BREAK METAL TO MATCH STOREFRONT. NO

CONDUIT SHOULD BE VISIBLE ON THE INTERIOR OF THE BUILD ING.

SCALE: NONE

KEYPLAN

EXTERIOR PEDESTAL MOUNTED WP/GF TYPE RECEPTACLE

CANOPY LIGHTING CALCULATION

SCALE: 1/4" = 1'-0"

CONDUIT PATH

Revisions Date

1 ADDENDUM #1 12/02/21

E100 - PARTIAL FIRST FLOOR PLAN - REMOVALS
E101 - PARTIAL FIRST FLOOR PLAN - NEW WORK

File details come from the government source that posted it. Updated .