Attachment 2 Project Drawings.pdf
PDF 17 MB Posted
- Attached to
- Construct Stanchion Barn and Cattle Working Barn Federal contract opportunity
- Solicitation number
- 12805B24R0035
About this file
This document is Attachment 2 Project Drawings related to a federal contract opportunity for Construct Stanchion Barn and Cattle Working Barn, Solicitation Number 12805B24R0035, issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area.
The key details are: The contractor shall have knowledge of all aspects pertaining to the Statement of Work for constructing a stanchion barn and cattle working barn in Kerrville, TX. There is a mandatory site visit on August 5th. All RFI questions must be submitted in writing to the Point of Contact by 4:00 PM on August 11, 2024, and responses will only be posted on SAM.gov. Questions submitted after August 11th until proposals are due may not receive a response, and if submitted after the site visit, a response will not be provided if the vendor was not an attendee.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
A D
U
NO. DATE BY DESCRIPTION
DATE
PROJECT NO.
MERRICK PROJECT NO.
DESIGNER
DRAWN BY
PROJECT MANAGER
REAL PROPERTY
SAFETY & HEALTH
PPM
EPM
REVISIONS
RESEARCH LABORATORY
A-E FIRM USDA
FACILITIES ENGINEERING BRANCH
5601 SUNNYSIDE AVENUE
BELTSVILLE, MD. 20705-5100
FACILITIES DIVISION
KNIPLING-BUSHLAND U.S. LIVESTOCK INSECTS
Research
Agricultural
Service
J. DELAY
64019927
A. DE LEON
C. MATHER
DR. WURZBERGER
P. PLEISS
S. HELGREN
B994 STANCHION BARN
COVER PAGE
G-000
KNIPLING-BUSHLAND U.S. LIVESTOCK INSECT RESEARCH LABORATORY
CIVIL - ARCHITECTURAL - STRUCTURAL - FIRE PROTECTION
PLUMBING - MECHANICAL - ELECTRICAL - TELECOMMUNICATIONS
MERRICK & COMPANY
5970 GREENWOOD PLAZA BLVD.
GREENWOOD VILLAGE, CO 80111-4703
(303) 751-0741
PACKAGE 5 OF 5: BUILDING B994 – STANCHION BARN & ANCILLARY STRUCTURES
KERRVILLE, TX
DRAWING PACKAGES
PACKAGE 1: SITEWORK & UTILITIES
PACKAGE 2: BUILDING B998 – ADMINISTRATION & LABORATORIES
PACKAGE 3: BUILDING B997 – FLY & TICK RESEARCH
PACKAGE 4: BUILDINGS B995 & B996 – MAINTENANCE SHOPS
PACKAGE 5: BUILDING B994 – STANCHION BARN & ANCILLARY STRUCTURES
(SEE PACKAGE 1 FOR ADDITIONAL SITEWORK AND UTILTY INFORMATION)
DRAWING INDEX
SHEET
NUMBER SHEET NAME
ELECTRICAL
E-001 ELECTRICAL LEGEND, NOTES, AND ABBREVIATIONS
EL101 ELECTRICAL LIGHTING PLAN - STANCHION BARN
EL102 ELECTRICAL LIGHTING PLAN - CATTLE WORKING BARN
EL601 ELECTRICAL LIGHTING SCHEDULES AND DETAILS
EP101 ELECTRICAL POWER PLAN - STANCHION BARN
EP102 ELECTRICAL POWER PLAN - CATTLE WORKING BARN
EP601 ELECTRICAL POWER ONE-LINE AND DETAILS
EP602 ELECTRICAL SCHEDULES
EG101 ELECTRICAL GROUNDING AND LIGHTNING PROTECTION PLAN
EG102 ELECTRICAL EQUIPOTENTIAL GROUNDING PLAN
EG501 ELECTRICAL GROUNDING AND LIGHTNING PROTECTION DETAILS
TELECOMMUNICATIONS
T-001 TELECOMMUNICATIONS LEGEND, NOTES, AND ABBREVIATIONS
T-101 TELECOMMUNICATIONS PLAN
T-601 TELECOMMUNICATIONS RISER DIAGRAM AND DETAILS
SECURITY
TY001 SECURITY LEGEND, NOTES, AND ABBREVIATIONS
TY101 SECURITY PLAN
TY501 SECURITY DETAILS
TY601 SECURITY RISER DIAGRAMS
DRAWING INDEX
SHEET
NUMBER SHEET NAME
FIRE ALARM
FA001 FIRE ALARM LEGEND, NOTES, AND ABBREVIATIONS
FA101 FIRE ALARM PLAN
FA601 FIRE ALARM RISER DIAGRAM
PLUMBING
P-001 PLUMBING LEGEND & ABBREVIATIONS
P-100 PLUMBING UNDERSLAB PLAN-STANCHION BARN
P-100A PLUMBING UNDERSLAB PLAN- CATTLE WORKING BARN
P-101 PLUMBING FIRST FLOOR PLAN - STANCHION BARN
P-102 PLUMBING FIRST FLOOR PLAN - CATTLE WORKING BARN
P-501 PLUMBING DETAILS
P-601 PLUMBING SCHEDULES
P-901 PLUMBING ISOMETRICS
MECHANICAL
M-001 MECHANICAL GENERAL NOTES, LEGEND & ABBREVIATIONS
M-101 MECHANICAL FIRST FLOOR PLAN
M-601 MECHANICAL SCHEDULES & DETAILS
M-700 CONTROLS LEGEND AND NOTES
M-701 BUILDING CONTROLS
DRAWING INDEX
SHEET
NUMBER SHEET NAME
GENERAL
G-000 COVER PAGE
G-100 CODE PLANS
STRUCTURAL
S-001 GENERAL NOTES
S-002 GENERAL NOTES - SHEET 2
S-101 FOUNDATION PLAN
S-102 MISC. FOUNDATIONS
S-501 TYPICAL CONCRETE SECTIONS AND DETAILS
S-502 TYPICAL CONCRETE SECTIONS AND DETAILS - SHEET 2
S-601 WIND LOAD DIAGRAMS
ARCHITECTURE
A-001 ABBREVIATIONS AND SYMBOLS
A-011 SITE PLAN
A-101 PROGRAM & FLOOR PLAN
A-102 WORKING BARN PLAN
A-103 ROOF PLAN
A-201 BUILDING ELEVATIONS
A-202 BUILDING ELEVATIONS
A-301 BUILDING SECTIONS
A-302 BUILDING SECTIONS
A-305 WALL SECTIONS
A-501 DETAILS
A-601 PARTITION TYPES AND SCHEDULES
SOLICITATION NUMBER XXX-3K15-XXXX
A 08-20-19 50% CONSTRUCTION DOCUMENTS
B 01-22-20 75% CONSTRUCTION DOCUMENTS
C 04-01-20 95% CONSTRUCTION DOCUMENTS
D 09-21-20 100% CONSTRUCTION DOCUMENTS
T
S
F
S T
O R
S -1
O .H
D
O O
R
O .H
D
O O
R O
.H
D O
O R
O .H
D
O O
R
FE
4844 SF
BARN / U
OCCUPANCY USE GROUPS
S-1
U
STORAGE - MEDIUM HAZARD USE 300 SF/PER 224 GSF 1 OCC.
UTILITY - AGRICULTURAL USES 300 SF/PER 5,207 GSF 18 OCC.
TOTALS: 5,431 GSF 19 OCC.
E X
IT
E X
IT
EXIT PATH - 79'-0"
ES
EW
TRENCH DRAIN
TRENCH DRAIN
FE
FE FE
EXIT PATH - 90'-0"
32"
33"
2.0"
32"
69"
2.0"
APPLICABLE CODES & STANDARDS
CITY OF KERRVILLE*:
2018 INTERNATIONAL BUILDING CODE (IBC) & LOCAL AMENDMENTS
2015 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) & LOCAL AMENDMENTS
2018 INTERNATIONAL FIRE CODE (IFC)
2018 INTERNATIONAL FUEL GAS CODE (IFGC) & LOCAL AMENDMENTS
2018 INTERNATIONAL MECHANICAL CODE (IMC) & LOCAL AMENDMENTS
2018 INTERNATIONAL PLUMBING CODE (IPC) & LOCAL AMENDMENTS
2017 NFPA-70 - NATIONAL ELECTRICAL CODE (NEC) & LOCAL AMENDMENTS
* NOTE: CODES PRESENTLY ADOPTED BY CITY OF KERRVILLE ARE BASED ON 2006 AND
2008 EDITIONS. CITY OFFICIALS HAVE REPORTED THAT CURRENT EDITIONS (2017,
2018, ETC.) ARE SCHEDULED TO BE ADOPTED BY THE CITY IN BY 2020.
STATE OF TEXAS:
2012 TEXAS ACCESSIBILITY STANDARDS
ADDITIONAL USDA-ARS REQUIRED CODES & STANDARDS:
AMERICANS WITH DISABILITIES ACT (ACT)
ARCHITECTURAL BARRIERS ACT (ABA)
2012 ANSI-Z9.5 - LABORATORY VENTILATION
2014 ANSI Z358.1 - EMERGENCY EYEWASH & SHOWER EQUIPMENT
2018 NATIONAL STANDARD PLUMBING CODE (NSPC)
2018 NFPA-1 - NATIONAL FIRE CODE
2018 NFPA-4 - INTEGRATED FIRE PROTECTION & LIFE SAFETY SYSTEMS
2018 NFPA-10 - PORTABLE FIRE EXTINGUISHERS
2019 NFPA-13 - SPRINKLER SYSTEMS
2019 NFPA-24 - PRIVATE FIRE SERVICE MAINS & APPURTENANCES
2018 NFPA-30 - FLAMMABLE & COMBUSTIBLE LIQUIDS CODE
2019 NFPA-45 - FIRE PROTECTION FOR LABORATORIES
2018 NFPA-54 - NATIONAL FUEL GAS CODE [ANSI-Z223.1]
2020 NFPA-55 - COMPRESSED GASES AND CRYOGENIC FLUIDS
2019 NFPA-72 - NATIONAL FIRE ALARM & SIGNALING CODE
2019 NFPA-80 - FIRE DOORS AND OTHER OPENING PROTECTIVES
2018 NFPA-90A - AIR CONDITIONING & VENTILATION SYSTEMS
2018 NFPA-101 - LIFE SAFETY CODE (FOR EGRESS DOOR LOCKS)
2019 NFPA-110 - EMERGENCY & STANDBY POWER SYSTEMS
2019 NFPA-150 - FIRE & LIFE SAFETY IN ANIMAL FACILITIES
2007 NFPA-704 - IDENTIFICATION OF HAZARDS OF MATERIALS FOR
EMERGENCY RESPONSE
2020 NFPA-731 - INSTALLATION OF ELECTRONIC PREMISES SECURITY
2020 NFPA-780 - LIGHTNING PROTECTION SYSTEMS
V1.4 GREEN BUILDING INSTITUTE (GBI) - GREEN GLOBES
BUILDING SUMMARY
NON-SEPARATED MIXED USE, SINGLE-STORY BUILDINGS, SLAB-ON-GRADE AND PRE-
ENGINEERED STEEL-FRAMED STRUCTURE.
USE & OCCUPANCY (IBC-303, 304, 311, 508.2)
• USE GROUP 'S-1' STORAGE (ACCESSORY USE <10% TOTAL AREA)
• USE GROUP 'U' UTILITY / AGRICULTURAL (IBC RESTRICTIVE USE)
ANIMAL CATEGORY 7A (NFPA-150)
CONSTRUCTION TYPE: II-B (IBC TABLE 601) II-000 (NFPA)
STRUCTURAL FRAME 0 HR
BEARING WALLS 0 HR
NON-BEARING WALLS 0 HR
FLOOR CONSTRUCTION NA
ROOF CONSTRUCTION 0 HR
EXTERIOR WALLS NOT RATED FOR SEPARATION >30' (IBC TABLE 602)
ALLOWABLE HEIGHT: 55-FT (IBC TABLE 504.3, USE 'U')
ACTUAL MAX HEIGHT: 20'-4"
ALLOWABLE STORIES: 2 (IBC TABLE 504.4, USE 'U')
ACTUAL STORIES: 1
ALLOWABLE FLOOR AREA: 8,500 GSF (IBC TABLE 506.2, USE 'U')
(ALLOWANCE INCREASES NOT USED)
ACTUAL MAX FLOOR AREA: 5,431 GSF
USE SEPARATION BETWEEN 'S' AND 'U' NOT REQUIRED; MOST RESTRICTIVE
USE/OCCUPANCY CONDITIONS APPLIED. (IBC 508.3.1)
INTERIOR REQUIREMENTS
COMBUSTIBLE MATERIALS IN CONCEALED SPACES ARE ALLOWED WHEN:
• BLOCKING (IBC-603.1.14)
• NAILING & FURRING STRIPS (IBC-603.1.18)
• EXPOSED IN PLENUMS AND COMPLYING WITH THE I.M.C.-602 (IBC-718.5.2)
• CLASS 'A' INTERIOR FINISHES (IBC-718.5.3)
• PIPING INSTALLED PER THE I.M.C. AND I.P.C. (IBC-718.5.5)
CONCEALED INSULATION MATERIALS (IBC-720.2):
• FLAME SPREAD <25
• SMOKE-INDEX <450
MINIMUM INTERIOR FINISH CLASS (IBC TABLE 803.13)
CORRIDORS ROOMS
• USE GROUP 'S' C C
• USE GROUP 'U' NO RESTRICTIONS
CLASS B: FLAME SPREAD 26-75 SMOKE INDEX 0-450
CLASS C: FLAME SPREAD 76-200 SMOKE INDEX 0-450
FIRE EXTINGUISHERS ARE REQUIRED FOR BUILDING AND ARE PROVIDED PER
NFPA-10.
ORIDINARY HAZARDS: MIN. RATING "2-A" PER EXTINGUISHER
MAX. AREA PER 'A' 1,500 SF
MAX. AREA PER F.E. 11,250
MAX. TRAVEL DIST. 75 FT
EGRESS REQUIREMENTS
EGRESS SIZES -- DOORS, ETC.: 0.20" PER OCC. (IBC-1005.3.2)
MAX. TRAVEL DISTANCES (IBC TABLES 1006.2.1 & 1017.2)
'S-1' USE: 100 FT COMMON PATH 200 FT TOTAL TRAVEL
'U' USE: 75 FT COMMONG PATH 300 FT TOTAL TRAVEL
DOORS WITH SECURITY CONTROL ALWAYS ALLOW FREE EGRESS VIA THE
MECHANICAL DOOR HARDWARE.
FIXTURE REQUIREMENTS
USE 'U' DOES NOT REQUIRE PLUMBING FIXTURES.
BUILDING IS OCCUPIED ONLY DURING WORK ON ANIMALS. OCCUPANTS HAVE
OFFICES, FACILITIES AVAILABLE ELSEWHERE ON CAMPUS (AND ARE COUNTED
THERE AS WELL).
EXIT
EXIT SIGN; REFER TO ELECTRICAL
DRAWINGS
DOOR EGRESS TAGS:
OCCUPANTS EXITING
CALCULATED EGRESS WIDTH REQUIRED
WIDTH PROVIDED
COMPONENT MINIMUM WIDTH REQUIRED32"
34"
29.6"
EXIT PATH
FE
COMMON PATH OF TRAVEL
FIRE EXTINGUISHER (SURFACE)
LIFE SAFETY LEGEND
B994 STANCHION BARNS994 WORKING BARN
RELOCATED
HAY BARN
RELO
CATED
FEED S
IL
O
IN
C
IN
E R
A
TO
R
F.H.
R = 150' - 0" R = 300' - 0"
GAS
METER
PASTURE PEN
PASTURE PEN
ANIMAL PENS
PASTURE PEN
NEW ANIMAL
WASTE LAGOON
ASPHALT
PAVING
34' - 4"
ASHRAE 90.1 2013 SUMMARY
NON-SEPARATED MIXED USE, SINGLE-STORY BUILDINGS, SLAB-ON-GRADE AND PRE-ENGINEERED
STEEL-FRAMED STRUCTURE.
COMPLIANCE:
THE BUILDING ENVELOPE SHALL COMPLY WITH SECTION 5.1, 5.4, 5.7, 5.8, AND INSTALLATION
REQUIREMENTS AND SECTION 5.5
CLIMATE ZONE:
KERR COUNTY IS WITHIN CLIMATE ZONE 3B
PRESCRIPTIVE BUILDING ENVELOPE OPTION
BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 3 (A,B,C) (TABLE 5.5-3)
NONRESIDENTIAL SEMIHEATED
ROOF ASSEMBLY MAX. / MIN. R-VALUE ASSEMBLY MAX. / MIN. R-VALUE
METAL BUILDING U-0.041 R-10 + R-19 FC U-0.096 R-16
PROVIDED: U-0.0223 R-44.84 N/A N/A
WALL ASSEMBLY MAX. / MIN. R-VALUE ASSEMBLY MAX. / MIN. R-VALUE
METAL BUILDING U-0.094 R-0 + R-9.8 C.I. U-0.162 R-13
PROVIDED: U-0.0328 R-30.49 N/A N/A
WALL, BELOW GRADE ASSEMBLY MAX. / MIN. R-VALUE ASSEMBLY MAX. / MIN. R-VALUE
BELOW-GRADE WALL NR NR
SLAB-ON-GRADE FLOORS ASSEMBLY MAX. / MIN. R-VALUE ASSEMBLY MAX. / MIN. R-VALUE
UNHEATED F-0.730 NR NR
PROVIDED: F-0.71
OPAQUE DOORS ASSEMBLY MAX. R-VALUE ASSEMBLY MAX. R-VALUE
SWINGING U-0.700 U-0.700
PROVIDED: U-0.700 N/A
VERTICAL FENESTRATION ASSEMBLY MAX U. / ASSEMBLY MAX. SHGC / ASSEMBLY MIN. VT/SHGC
FIXED 0.42 0.25 1.10
PROVIDED (VITRO): 0.28 0.16 1.18
AIR BARRIER DESIGN (5.4.3.1.1)
AIR BARRIER INTEGRATED PER INSULATED METAL PANEL MRF. JOINTS, INTERCONNECTIONS, AND
PENETRATIONS OF INSULATED PANEL ARE DETAILED ON WALL SECTIONS AND DETAIL SHEETS.
CONTINOUS AIR BARRIER EXTENDS OVER ALL OVER SURFACES OF THE BUILDING ENVELOPE.
DESIGNED TO RESIST POSITIVE AND NEGATIVE PRESSURE FROM WIND, STACK EFFECT, AND
MECHANICAL VENTILATION. PER APPENDIX G, WHOLE-BUILDING LEAKAGE TEST NOT REQUIRED AS THIS ESTABLISHES A METHOD FOR GAINING CREDIT FOR BUILDINGS THAT UNDERGO THE WHOLE
BUILDING TEST.
ACCEPTABLE MATERIALS AND ASSEMBLIES (5.4.3.1.3)
CONTINOUS AIR BARRER MATERIALS AND ASSEMBLIES FOR THE OPAQUE BUILDING ENVELOPE
COMPLY WITH REQUIREMENT (a.); REFER TO DETAILS.
FENESTRATION AND DOORS (5.4.3.2)
AIR LEAKAGE FOR FENESTRATION AND DOORS SHALL BE DETERMINED BY A LABORATORY
ACCREDITED THIRD PARTY BY A NATIONALLY RECOGNIZED ACCREDITATION ORGANIZATION, SUCH AS
NATIONAL FENESTRATION RATING COUNCIL PROVIDED BY MANUFACTURER.
VESTIBULES (5.4.3.4)
NOT APPLICABLE PER EXCEPTION (5.4.3.4)(5.) BUILDING ENTRANCES IN BUILDINGS THAT ARE LOCATED IN CLIMATE ZONE 3, LESS THAN FOUR STORIES ABOVE GRADE, AND LESS THAN 10,000 SF IN GROSS
CONDITIONED FLOOR AREA.
OPAQUE AREAS (5.5.3)
ALL OPAQUE WALL AND ROOF AREAS COMPLY WITH METHOD (a.) MINIMUM RATED R-VALUE OF INSULATION FOR THE THERMAL RESISTANCE OF THE ADDED INSULATION IN FRAMING CAVITIES AND
CONTINOUS INSULATION ONLY. REFER TO BUILDING ENVELOPE REQUIREMENTS TABLE ABOVE.
ROOF SOLAR REFLECTANCE AND THERMAL EMITTANCE (5.5.3.1.1)
NOT APPLICABLE PER EXCEPTION (5.5.3.1.1)(5.) OF HAVING A LOW-SLOPED METAL BUILDING ROOF
(3:12) IN CLIMATE 3.
SUBMITTALS (5.7)
AHJ MAY REQUIRE SUBMITTAL ON COMPLIANCE IN ACCORDANCE WITH 4.2.2
4.2.2.1 CONSTRUCTION DETAILS
4.2.2.2 SUPPLEMENTAL INFORMATION
4.2.2.3 MANUALS
SUBSTANTIAL CONTACT (5.8.1.5)
CONTRACTOR SHALL INSTALL INSULATION IN A PERMANENT MANNER IN SUBSTANTIAL CONTACT WITH
THE INSIDE SURFACE IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS FOR THE
FRAMING SYSTEM USED.
S
A D
U
NO. DATE BY DESCRIPTION
DATE
PROJECT NO.
MERRICK PROJECT NO.
DESIGNER
DRAWN BY
PROJECT MANAGER
REAL PROPERTY
SAFETY & HEALTH
PPM
EPM
REVISIONS
RESEARCH LABORATORY
A-E FIRM USDA
FACILITIES ENGINEERING BRANCH
5601 SUNNYSIDE AVENUE
BELTSVILLE, MD. 20705-5100
FACILITIES DIVISION
KNIPLING-BUSHLAND U.S. LIVESTOCK INSECTS
Research
Agricultural
Service
J. DELAY
64019927
A. DE LEON
C. MATHER
DR. WURZBERGER
F. DE LUNA
S. HELGREN
B994 STANCHION BARN
CODE PLANS
G-100
1/8" = 1'-0"1
LIFE SAFETY PLAN
NORTH
0 2' 4' 8' 16'
1" = 20'-0"2
CODE SITE PLAN
NORTH
0 10' 20' 30' 40'
A 08-20-19 50% CONSTRUCTION DOCUMENTS
B 01-22-20 75% CONSTRUCTION DOCUMENTS
STRUCTURAL PLANS INDICATE ONLY THE APPROXIMATE LOCATION OF MECHANICAL,
ELECTRICAL AND OTHER EQUIPMENT, AS WELL AS THE RELATED AUXILIARY FRAMING
NECESSARY TO SUPPORT SUCH EQUIPMENT. THE FINAL POSITIONING OF THESE ITEMS
IS DEPENDENT UPON THE EQUIPMENT PROVIDED BY THE CONTRACTOR. THE
SUBCONTRACTORS AND CRAFTS IN THIS REGARD, AND PROVIDING NECESSARY
DIMENSIONS IN A TIMELY MANNER TO ALL PARTIES INVOLVED. THE CONTRACTOR SHALL
ROOF AND FLOOR MEMBERS. BRACING MUST BE FULLY EFFECTIVE UNTIL ROOF AND
FLOOR DEAD LOADS ARE IN PLACE.
CONCRETE GRADE WALLS SHALL BE TEMPORARILY BRACED IF BACKFILL IS ONLY ON
ONE SIDE OR BACK FILLED ON BOTH SIDES SIMULTANEOUSLY, WHERE REQUIRED, TO
PREVENT DEFLECTION, CRACKING OR FAILURE OF CONCRETE GRADE WALLS.
11.
12.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WORK BETWEEN
PROVIDE TEMPORARY BRACING AS REQUIRED DURING THE ERECTION OF THE
15.
GENERAL REQUIREMENTS
CONFLICTS: NOTES AND DETAILS ON THE DRAWINGS TAKE PRECEDENCE OVER THE
CODES: ALL MATERIALS AND WORK SHALL CONFORM TO THE REQUIREMENTS OF THE
IBC 2015 AND ASCE 7.
SUBSTITUTIONS: PROVIDE MANUFACTURER'S ICC REPORTS AND A LIST OF ALL PROPOSED
SUBSTITUTIONS TO THE CONTRACTING OFFICER FOR REVIEW BEFORE FABRICATION.
SIMILAR WORK: WHERE CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY
PART OF THE WORK, SUCH DETAILS SHALL BE THE SAME AS FOR SIMILAR WORK SHOWN
PIPES, DUCTS, SLEEVES, CHASES, ETC.: SHALL NOT BE PLACED IN SLABS, BEAMS, OR
WALLS UNLESS SPECIFICALLY SHOWN OR NOTED NOR SHALL ANY STRUCTURAL MEMBER
BE CUT FOR PIPES, DUCTS ETC., UNLESS SPECIFICALLY SHOWN. OBTAIN PRIOR WRITTEN
APPROVAL FROM THE CONTRACTING OFFICER FOR INSTALLATION OF ANY ADDITIONAL
EXCAVATIONS: LOCATE AND PROTECT UNDERGROUND OR CONCEALED CONDUIT,
PLUMBING OR OTHER UTILITIES WHERE NEW WORK IS BEING PERFORMED.
CONSTRUCTION LOADS: MATERIALS SHALL BE EVENLY DISTRIBUTED IF PLACED ON
FRAMED FLOORS OR ROOFS. LOADS SHALL NOT EXCEED THE ALLOWABLE LOADING
FOR THE SUPPORTING MEMBERS AND THEIR CONNECTIONS.
THE STRUCTURAL DRAWINGS ILLUSTRATE THE NEW STRUCTURAL MEMBERS, REFER
TO ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR NON-STRUCTURAL
ITEMS WHICH REQUIRE SPECIAL PROVISIONS DURING THE CONSTRUCTION OF
REFER TO ARCHITECTURAL PLANS FOR FLOOR DEPRESSIONS, SLOPES, DRAINS,
CURBS, PADS, EMBEDDED ITEMS, NON-BEARING PARTITIONS, ETC.
REFER TO MECHANICAL AND ELECTRICAL PLANS FOR SLEEVE AND HANGERS FOR
PIPES, DUCTS AND EQUIPMENT.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
ON DRAWINGS.
STRUCTURAL MEMBERS.
GENERAL NOTES AND TYPICAL DETAILS IN CASE OF CONFLICT.
PIPES, DUCTS, ETC.
PROCEED WITH BACKFILLING OPERATIONS IN A SAFE AND UNIFORM MANNER. SEE13.
STRUCTURAL FRAME.
SPECIFICATIONS FOR REQUIREMENTS.
DO NOT SCALE DRAWINGS.14.
IT IS THE CONTRACTORS RESPONSIBILITY TO COMPLY WITH ALL APPLICABLE LOCAL
SAFETY REQUIREMENTS, AND ALL OSHA REQUIREMENTS.
16.
DESIGN REFERENCES:
ASCE 7, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES.
ANIMAL AREAS.......................................................250 PSF
MECHANICAL AND
ELECTRICAL ROOMS.............................................150 PSF OR ACTUAL
EQUIPMENT WEIGHT
EQUIPMENT PLATFORMS......................................150 PSF
100 PSFALL OTHER AREAS
1.
A)
IBC 2015, INTERNATIONAL BUILDING CODE.B)
MINIMUM DESIGN LIVE LOADS:
FLOOR LIVE LOADS:
2.
A)
ROOF LIVE LOADS (TOP CHORD)..........................20 PSF
ROOF LIVE LOADS:B)
EXPOSURE
INT. PRESS. COEFF. GCpi (FLY AND TICK)
C
WIND LOADS:3.
± 0.18
RESPONSE ACCELERATION
RESPONSE ACCELERATION
SITE CLASS
SEISMIC DESIGN CATEGORY
Ss = 0.057g
SEISMIC LOADS:4.
D A
SHORT PERIOD SPECTRAL
1 SECOND SPECTRAL
S1 = 0.028g
DESIGN AND ANCHORAGE OF ALL NON-BUILDING COMPONENTS SHALL BE PER
ASCE 7 CHAPTER 13.
5.
RISK CATEGORY (STANCHION BARN)........................... II
RISK CATEGORY..............................................................II
1.00IMPORTANCE FACTOR
BASIC WIND SPEED (LAB)...............................................115 MPH
DESIGN CRITERIA
ABV
ADDL
HT
HSH
HSB
HORIZ
HGR
HDR
HD
(H)
GR
GLB
GALV
GA
FTG
FS
FRMG
FOS
FOM
FOC
FN
FLR
FLG
FJ
FF
FDN
EW
ES
EQ
EN
EMBED
ELEV
ELEC
EL
EF
EA
(E)
DWL
DWG
DP
DO
DN
DIM
DIA
DF
DBL
CTRD
CSK
CP
CONT
CONST
CONN
CONC
COL
CLR
CL
CJ
CJ
CIP
CB
C
BTWN
BRG
BP
BOS
BOF
BN
BM
BLW
BLKG
BLK
(B)
AWS
ASSOCIATION
AWPA
TESTING AND MATERIALS
ASTM
ASD
ARCH
ASSOCIATION
APA
ALT
STEEL CONSTRUCTION
AISC
ADJ
WWF
WT
WPJ
WP
WD
W/O W/
WL
VSH
VERT
(V)
UON
UNO
UBC
TYP
TS
TOW
TOT
TOS
TOP
TOC
TO
TN
THRD
THK
TG
T AND B
(T)
STRUC
STL
STIFF
STGR
STD
SQ
SPEC
SOG
SIM
SHTHG
SEP
SECT
SCHED
SC
RF
REF
REQD
REINF
R P.T.
PP
PLYWD
PLCS
PL
PC
ORIG
OPP
OPNG
OH
OF
OC
NTS
NS
NO
NIC
MTL
MISC
MIN
MFR
MECH
MB
MAX
MATL
LT WT
LOC
LDGR
KP
JT
JST
IF
ABBREVIATIONS
AB ANCHOR BOLT ICC INTERNATIONAL CODE
COUNCILABOVE
ADDITIONAL
INSIDE FACEADJACENT
JOISTAMERICAN INSTITUTE OF
JOINT
KING POSTALTERNATE
LEDGERAMERICAN PLYWOOD
LOCATION
LIGHTWEIGHTARCHITECTURAL/ARCHITECT
MATERIAL
MAXIMUM
ALLOWABLE STRESS DESIGN
AMERICAN SOCIETY FOR
MACHINE BOLT
MECHANICALAMERICAN WOOD PRESERVERS
MANUFACTURER
MINIMUM
MISCELLANEOUS
AMERICAN WELDING SOCIETY
BOTTOM
METALBLOCK
NOT IN CONTRACTBLOCKING
NUMBERBELOW
NEAR SIDEBEAM
NOT TO SCALEBOUNDARY NAIL
ON CENTERBOTTOM OF FOOTING
OUTSIDE FACEBOTTOM OF STEEL
OPPOSITE HANDBASE PLATE
OPENINGBEARING
OPPOSITEBETWEEN
ORIGINALCAMBER
PRECASTCARRIAGE BOLTS
PLATE
CAST-IN-PLACE PLACES
CONSTRUCTION JOINT PLYWOOD
CEILING JOIST PARTIAL PENETRATION
CENTER LINE POST-TENSION
CLEAR RADIUS
COLUMN REINFORCEMENT
CONCRETE REQUIRED
CONNECTION REFERENCE
CONSTRUCTION ROOF
CONTINUOUS SHEAR CONNECTOR
COMPLETE PENETRATION SCHEDULE
COUNTER SINK
SECTIONCENTERED
SEPARATIONDOUBLE
SHEATHINGDOUGLAS FIR/LARCH
SIMILARDIAMETER
SLAB ON GRADE
DEEP
SPECIFICATION
DIMENSION
SQUARE
DOWN
STANDARD
DITTO (REPEAT)
STAGGERDRAWING
STIFFENERSDOWEL
STEELEXISTING
STRUCTURALEACH
TOPEACH FACE
TOP AND BOTTOM
ELEVATION TAPERED GIRDER
ELECTRICAL THICKNESS/THICK
ELEVATOR THREADED
EMBEDMENT TOENAIL
EDGE NAIL TOP OF
EQUAL OR EQUIVALENT TOP OF CONCRETE
EACH SIDE TOP OF PARAPET
EACH WAY TOP OF STEEL
FOUNDATION TOTAL
FINISHED FLOOR TOP OF WALL
FLOOR JOIST TUBE STRUCTURAL
FLANGE TYPICAL
FLOOR UNIFORM BUILDING CODE
FIELD NAIL UNLESS NOTED OTHERWISE
FACE OF CONCRETE UNLESS OTHERWISE NOTED
FACE OF MASONRY VERTICAL
FACE OF STUD VERTICAL
FRAMING VERTICAL SLOTTED HOLES
FAR SIDE WIND LOAD
FOOTING WITH
GAUGE
WITHOUT
GALVANIZED
WOOD
GLUED LAMINATED BEAM
WATER PROOF/WORK POINT
GRADE
WEAKENED PLANE JOINT
HORIZONTAL
WEIGHT
HOLDOWN
WELDED WIRE FABRIC
HEADER
HEIGHT
HORIZONTALLY SLOTTED HOLES
HIGH STRENGTH BOLT
HORIZONTAL
HANGER
CGS CENTER OF GRAVITY OF STEEL
GSN GENERAL STRUCTURAL NOTES
5/- INDICATES A SECTION OR DETAIL
THAT APPEARS ON THE SAME SHEET
AS THE REFERING INFORMATION.
EF EDGE FASTENER
FY YIELD STRENGTH
SCJ SHRINKAGE CONTROL JOINT
I.E. INSIDE FACE
87 EQUIVALENT BAR DIAMETERS FOR BOTTOM BUNDLES AND 113 EQUIVALENT
BAR DIAMETERS FOR TOP BUNDLES, WHERE THE EQUIVALENT DIAMETER IS
BASED UPON THE COMBINED AREAS OF THE BARS BUNDLED. LAP LENGTHS
FOR BARS IN BUNDLES OF 4 OR MORE BARS SHALL BE INCREASES AN
ADDITIONAL 11 PERCENT.
WITH E90XX ELECTRODES.
FOOTING OR COLUMNS UNLESS SPECIFICALLY DETAILED.
ADMIXTURES: REVIEWED BY CONTRACTING OFFICER, NO CALCIUM CHLORIDE.
THOROUGHLY CLEAN ALL CONCRETE SURFACES TO RECEIVE NEW CONCRETE.
LOCATION OF JOINTS SHALL BE REVIEWED BY THE CONTRACTING OFFICER. WAIT 48
ACTUAL DIMENSIONS: SLAB, WALL, BEAM AND COLUMN DIMENSIONS SHOWN ARE
ACTUAL DIMENSIONS NOT NOMINAL DIMENSIONS (i.e. A 4 INCH SLAB IS 4 INCHES
THICK, NOT 3-1/2 INCHES.)
INDIVIDUAL SPLICES OF BARS IN A BUNDLE SHALL BE STAGGERED AT LEAST
ALL LAP SPLICES ARE CLASS B UNLESS OTHERWISE NOTED ON PLANS.
WELDED REINFORCEMENT: ASTM A-706, CERTIFIED WELDERS. WELD PER AWS D1.4
PIPES, SLEEVES AND DUCTS: SHALL NOT BE PLACED IN WALLS, BEAMS, SLABS,
CHAMFER: 3/4 INCH ON EXPOSED CORNERS.
CONSTRUCTION JOINTS: HEAVY SANDBLAST (1/4 INCH AMPLITUDE MINIMUM) AND
iv) v)
J)
8.
9.
10.
11.
13.
PLANE JOINTS NOT SPECIFICALLY INDICATED ON THE DRAWINGS SHALL BE REVIEWED
BY THE CONTRACTING OFFICER PRIOR TO THE PLACING OF REINFORCEMENT.
SLAB-ON-GRADE JOINTS: LOCATION OF ALL CONSTRUCTION, CONTROL AND WEAKENED12.
HOURS BETWEEN POURS.
CORNER OF RECTANGULAR HOLES IN SLABS. PLACE BARS DIAGONALLY.
SPLICES IN OTHER BOTTOM REINFORCEMENT; STAGGER SPLICES FOR TOP
REINFORCEMENT SIMILARLY.
SLAB CORNERS: PROVIDE (2)-#4 X 4'-0" AT RE-ENTRANT CORNERS AND EACH
SPLICES (LAPS) U.N.O.
IN NO CASE SHALL LAPS BE LESS THAN 24 INCHES LONG.
STAGGER CONTINUOUS FOOTING BOTTOM SPLICES AT LEAST 6'-0" FROM
H)
I)
i) SEE TABLE A - GENERAL 2/S-5021, FOR SCHEDULE OF TENSION LAP SPLICE
ii) iii)
LENGTHS.
THE SAME SIZE AND SPACING OF REINFORCEMENT AS SHOWN ON THE DRAWINGS
AND IN THE GENERAL NOTES.
COLUMN BEAM SHALL EXTEND TO WITHIN 2" OF THE FACE AND HAVE A 90 DEGREE
HOOK UNLESS OTHERWISE SHOWN.
REINFORCING BARS BUNDLED IN CONTACT TO ACT AS A UNIT IN A LAYER SHALL
NOT BE LESS THAN 1-1/2 TIMES THE NOMINAL DIAMETER OF THE REINFORCEMENT
OR 1-1/3 TIMES MAXIMUM SIZE AGGREGATE, NOR LESS THAN 1-1/2". NORMAL
DIAMETER FOR A UNIT OF BUNDLED BARS SHALL BE THE EQUIVALENT DIAMETER
OF THE COMBINED AREAS OF THE BARS BUNDLED.
CHAIRS, SPACERS AND SAND PLATES: AS REQUIRED TO MAINTAIN CONCRETE
VERTICAL REINFORCEMENT: SHALL BE DOWELED TO SUPPORTING MEMBERS WITH
HORIZONTAL REINFORCEMENT: ALL BARS ENDING AT THE FACE OF A WALL,
SPACING: CLEAR DISTANCE BETWEEN PARALLEL REINFORCEMENT OR PARALLEL
TACK WELDING, WELDING, HEATING OR CUTTING OF BARS: NOT PERMITTED U.N.O.
C)
D)
E)
F)
G)
315 AND ACI 318. SHOP DRAWINGS REVIEWED BY THE CONTRACTING
OFFICER BEFORE FABRICATION.
MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCEMENT:
MIN. COVER,
INCHES
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH
CONCRETE EXPOSED TO EARTH OR WEATHER:
NO. 6 THROUGH NO. 18 BAR
NO. 5 BAR, W31 OR D31 WIRE AND SMALLER
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH
GROUND:
SLABS, WALLS, JOISTS:
NO. 14 AND NO. 18 BAR
NO. 11 BAR AND SMALLER
BEAMS, COLUMNS:
PRIMARY REINFORCEMENT TIES:
REINFORCEMENT:
CAST-IN-PLACE CONCRETE (NON-PRESTRESSED). THE FOLLOWING
STIRRUPS, SPIRALS
6.
A) SHOP DRAWINGS, FABRICATION AND PLACING: SHALL CONFORM TO ACI
B)
1 1/2
1 1/2 3/4
1 1/2
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, MAY BE
INCORPORATED IN THE CONCRETE DESIGN MIXES. A HIGH-RANGE WATER-REDUCING
(HRWR) ADMIXTURE CONFORMING ASTM C494, TYPE F OR G, MAY BE USED IN CONCRETE
MIXES PROVIDING THAT SLUMP DOES NOT EXCEED 9". AN AIR-ENTRAINING AGENT
CONFORMING TO ASTM C260 SHALL BE USED IN CONCRETE MIXES FOR THE EXTERIOR
A WATER-REDUCING ADMIXTURE CONFORMING TO ASTM C494, USED IN STRICT
SURFACES EXPOSED TO COLD WEATHER. THE AMOUNT OF ENTRAINED AIR SHALL BE
5.
6% ± 1% BY VOLUME.
COVER.
CEMENT
AGGREGATE
REINFORCEMENT
ASTM A - 706
ANCHOR BOLTS
ASTM A - 1557
THE CONCRETE STRENGTHS SHOWN IN THE FOLLOWING TABLE ARE THE MINIMUM
COMPRESSIVE STRENGTHS AT 28 DAYS AND THE WATER/CEMENT RATIO IS THE
MAXIMUM. THE SPECIFIED SLUMP IS THE MAXIMUM PRIOR TO THE ADDITION OF
ADMIXTURES. CONCRETE SHALL BE STANDARD WEIGHT CONCRETE (145 PCF).
ITEM OF
CONSTRUCTION
FOUNDATIONS/GRADE WALLS
MINIMUM OF SEVENTY PERCENT OF THE SPECIFIED 28-DAY STRENGTH FOR ANY
CONCRETE CONSTRUCTION REQUIRING SHORING, BRACING OR TO RECEIVE
MATERIALS:
CONCRETE STRENGTHS:
CONTINUOUS SPECIAL INSPECTION IS REQUIRED FOR DESIGN STRENGTHS EXCEEDING.
CONCRETE SHALL BE PROPORTIONED SUCH THAT 7-DAY STRENGTHS ARE A
REINFORCED CONCRETE
1.
2.
3.
4.
ASTM C - 150
ASTM C - 33
ASTM A - 615
REINFORCEMENT
ASTM A - 36
ANCHOR BOLTS
STRENGTH AGG SLUMP WATER/CEMENT
(PSI) (IN) (IN) (LB/LB)
3,000 1 4 0.57
SLABS-ON-GRADE........................... 3,000 1 4 0.57
MAT FOUNDATION........................... 3,000 1 3 0.45
2,500 PSI.
CONSTRUCTION LOADS.
GRADE 60 WELDED
HEADED MACHINE BOLTS
TYPE I I
CRUSHED ROCK
GRADE 60 TYPICAL
HOOKED ANCHOR BOLTS
ELECTRICAL CONDUIT IS NOT ALLOWED TO BE PLACED IN THE CONCRETE SLAB.15.
CONCRETE CURING: SEE SPECIFICATIONS.14.
1.
FOUNDATION
4. CONTRACTOR SHALL PROVIDE FOR DE-WATERING OF EXCAVATIONS FOR EITHER
SURFACE WATER, GROUND WATER, OR SEEPAGE, IF REQUIRED.
5. CONTRACTOR SHALL PROVIDE FOR DESIGN AND INSTALLATION OF ALL CRIBBING,
SHEATHING, AND SHORING REQUIRED AND SHALL BE SOLELY RESPONSIBLE FOR ALL
EXCAVATION PROCEDURES INCLUDING LAGGING, SHORING, AND PROTECTION OF
ADJACENT PROPERTY, STRUCTURES, STREETS, AND UTILITIES IN ACCORDANCE WITH
ALL NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES.
6. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL
BEHIND RETAINING WALLS BEFORE CONCRETE OR GROUT HAS ATTAINED FULL DESIGN
STRENGTH. CONTRACTOR SHALL BRACE OR PROTECT ALL BUILDING AND PIT WALLS
BELOW GRADE FROM LATERAL LOADS UNTIL ATTACHED FLOORS ARE COMPLETELY IN
PLACE AND HAVE ATTAINED FULL STRENGTH. CONTRACTOR SHALL PROVIDE FOR
DESIGN, PERMITS, AND INSTALLATION OF SUCH BRACING.
7. SUBGRADE PREPARATION AND FILL REQUIREMENTS
SUBGRADE PREPARATION FOR SLAB ON GRADE FLOORS SHALL CONSIST OF A)
REMOVING AT LEAST 2 FEET OF EXISTING MATERIAL, AND REPLACING WITH
COMPACTED NONEXPANSIVE BACKFILL MATERIAL, ANY ADDITIONAL FILL REQUIRED
TO REACH FINAL SUBGRADE ELEVATION BELOW THE BUILDING FLOOR SLAB SYSTEM
SHALL BE NONEXPANSIVE MATERIAL AS WELL. THE UPPER 6 INCHES OF EXISTING
SUBGRADE EXPOSED AFTER EXCAVATION OPERATIONS SHALL BE SCARIFIED,
MOISTENED, AND RECOMPACTED TO THE SAME DENSITY AS REQUIRED FOR
NONEXPANSIVE FILL. NONEXPANSIVE FILL SHALL BE PLACED IN CONTROLLED
LIFTS NOT EXCEEDING 8 INCHES IN LOOSE THICKNESS AND COMPACTED TO AT
LEAST 95 PERCENT OF LABORATORY MAXIMUM DENSITY AS DETERMINED IN
ACCORDANCE WITH ASTM D 1557.
TESTING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL ENSUREB)
THAT THE SUBGRADE, FILL, AND BACKFILL MATERIAL ARE PROPERLY COMPACTED.
THE FOLLOWING FREQUENCIES OF TESTING SHALL BE INCLUDED IN THE CONTRACT
AS A MINIMUM:
i) IN-PLACE DENSITY OF THE SUBGRADE, FILLS AND BACKFILLS SHALL BE
PERFORMED FOR EVERY 5000 SQUARE FEET PER LIFT, WITH 3 MIN PER LIFT IN
ACCORDANCE WITH ASTM D 1556 OR ASTM D 6938.
ii) OPTIMUM MOISTURE AND LABORATORY MAXIMUM DENSITY OF NONEXPANSIVE
FILL AND BACKFILL SHALL BE PERFORMED FOR EVERY 500 CUBIC YARDS OR
WHEN ANY CHANGE IN MATERIAL OCCURS.
EXTERIOR GRADING ADJACENT TO BUILDING SHALL BE SLOPED AWAY FROMC)
THE STRUCTURE A MINIMUM OF 5 PERCENT FOR THE FIRST 10 FEET. RUNOFF
FROM THE ROOF SHALL BE ADEQUATELY DISCHARGED AWAY FROM THE
FOUNDATION EDGES. IN NO CASE SHALL WATER BE ALLOWED TO POND ADJACENT
TO THE BUILDING.
8. FOUNDATIONS SHALL BE PLACED AND ESTIMATED ACCORDING TO DEPTHS SHOWN ON
DRAWINGS. SOIL ENCOUNTERED AT THESE DEPTHS SHALL BE APPROVED BY
THE CONTRACTING OFFICER.
9. FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN BUILDING AREA SHALL BE
MECHANICALLY COMPACTED IN LAYERS IN ACCORDANCE WITH THE SOILS REPORT
AND APPROVED BY THE INSPECTOR.
ALL ABANDONED UTILITIES, ETC. SHALL BE REMOVED. NEW FOOTINGS
MUST EXTEND INTO UNDISTURBED SOILS.
MAT SLAB SHALL BE SUPPORTED ON NATURAL GRADE OR COMPACTED FILL
PER THE RECOMMENDATIONS OF THE FOUNDATION AND PAVEMENT DESIGN ANALYSIS.
SOILS INFORMATION BASED ON "GEOTECHNICAL ENGINEERING STUDY - IMPROVEMENTS
TO THE KNIPLIN-BUSHLAND U.S. LIVESTOCK INSECTS RESEARCH LABORATORY (KBUSLIRL)
SITE, KERRVILLE, TEXAS", BY ARIAS GEOPROFESSIONALS, JOB NO. 2018-933, DATED
MAY 29, 2019 (REVISED JULY 3, 2019).
"CONVENTIONAL AND MAT FOUNDATION"
MAT FOUNDATIONS ARE DESIGNED BASED ON THE FOLLOWING INFORMATION:
ALLOWABLE BEARING * = 2500 PSF
2.
PASSIVE EARTH PRESSURE = 1500 PSF
-GRADE REACTION = 100 PCI
* ALLOWABLE BEARING MAY NOT BE INCREASED BY 1/3 FOR WIND AND SEISMIC
LOAD CASES.
3. FOOTING SHALL BEAR ON FIRM SELECT FILL SOILS. MINIMUM DEPTH OF FOOTINGS
BELOW LOWEST ADJACENT FINAL GRADE SHALL BE 18". MINIMUM WIDTH OF FOOTING
SHALL BE 12".
MODULUS OF HORIZONTAL SUB
MAT SLAB
12.
13.
A) FLOOR SLAB CONTROL JOINTS AND CONSTRUCTION JOINTS SHALL BE
PLACED AS SHOWN ON THE SLAB PLANS.
14. RETAINING WALL
LATERAL EARTH ACTIVE PRESSURE = 60 PCFA)
FOUNDATION BACKFILL SHALL BE COMPACTED IN ACCORDANCE WITH THE
GROTECHNICAL REPORT AND APPROVED BY THE GEOTECHNICAL ENGINEER.
16.
REFER TO THE GEOTECHNICAL REPORT FOR ADDITIONAL INFORMATION.17.
SOIL WORK SHALL BE OBSERVED AND TESTED BY THE GEOTECHNICAL ENGINEER
DURING GRADING, EXCAVATION, FOUNDATION CONSTRUCTION AND OTHER
EARTH-RELATED CONSTRUCTION PHASE OF THE PROJECT.
15.
LATERAL AT REST EARTH PRESSURE = 100 PCFB)
10.
11.
PROVIDE 2'-0" MINIMUM IMPORTED SELECT FILL BELOW MAT FOUNDATION, COMPACT18.
COMPACTED TO NOT LESS THAN 98% OF MAX DENSITY ACCORDING TO ASTM D 1557.
MINIMUM BEARING DEPTH = 1'-6", BOTTOM OF MAT SLAB SHALL BE 1'-6"
BELOW TOP OF FINISHED FLOOR.
318 SECTION 6.4 AND THE TYPICAL CONSTRUCTION JOINT DETAILS SHOWN ON
THE STRUCTURAL DRAWINGS.
CHIPS, OR OTHER FOREIGN MATTER PRIOR TO PLACING ADJACENT CONCRETE.
ALL CONSTRUCTION JOINTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH ACI
ALL SURFACES OF CONSTRUCTION JOINTS SHALL BE CLEANED TO REMOVE DUST,
CONSTRUCTION JOINTS
1.
2.
CONCRETE SURFACES TO RECEIVE NEW CONCRETE. LOCATION OF JOINTS SHALL
HEAVY SANDBLAST (1/4 INCH AMPLITUDE MINIMUM) AND THOROUGHLY CLEAN ALL 3.
S
A D
U
NO. DATE BY DESCRIPTION
DATE
PROJECT NO.
MERRICK PROJECT NO.
DESIGNER
DRAWN BY
PROJECT MANAGER
REAL PROPERTY
SAFETY & HEALTH
PPM
EPM
REVISIONS
RESEARCH LABORATORY
A-E FIRM USDA
FACILITIES ENGINEERING BRANCH
5601 SUNNYSIDE AVENUE
BELTSVILLE, MD. 20705-5100
FACILITIES DIVISION
KNIPLING-BUSHLAND U.S. LIVESTOCK INSECTS
Research
Agricultural
Service
J. DELAY
64019927
A. DE LEON
C. MATHER
DR. WURZBERGER
A. MAGINNIS
A. MAGINNIS
B994 STANCHION BARN
GENERAL NOTES
S-001
A 08-20-19 50% CONSTRUCTION DOCUMENTS
B 01-22-20 75% CONSTRUCTION DOCUMENTS
SPECIAL INSPECTIONS AND TESTING IN ACCORDANCE WITH IBC CHAPTER 17 ARE
ARE APPROVED, ON-SITE INSPECTIONIS NOT REQUIRED BUT A CERTIFICATE OF
SEISMIC FORCE RESISTING SYSTEMS SUBJECT TO SPECIAL INSPECTIONS AND
TESTIING INCLUDING:
DESIGNATED SEISMIC SYSTEMS, DEFINED IN THE IBC SECTION 1702 AS
ARCHITECTURAL, ELECTRICAL AND MECHANICAL SYSTEMS AND THEIR COMPONENTS
COMPONENT IMPORTANCE FACTOR Ip GREATER THAN ONE, ARE SUBJECT TO
SPECIAL INSPECTION AND TESTING. CERTIFICATION, AS DESCRIBED IN ASCE 7-10
SECTION 13.2.2, SHALL BE PROVIDED FOR ACTIVE MECHANICAL AND ELECTRICAL
A COMPONENT IMPORTANCE FACTOR OF 1.5. THE SPECIAL INSPECTOR SHALL VERIFY
A. ANCHORAGE OF ELECTRICAL EQUIPMENT FOR EMERGENCY OR STANDBY POWER
SYSTEMS.
COLLECTORS.CORRECTION.
EQUIPMENT THAT MUST OPERABLE FOLLOWING THE DESIGN EARTHQUAKE GROUND
B. INSTALLATION AND ANCHORAGE OF PIPING SYSTEMS DESIGNED TO CARRY
HAZAEDOUS MATERIALS AND THEIR ASSOCIATED MECHANICAL UNITS.
REQUIRED FOR THE ITEMS INDICATED IN THE TABLE ON THE SHEET. IF FABRICATIORS
COMPLETION MUST BE PROVIDED TO THE CONTRACTING OFFICER (IBC 1704.2.5.2).
A. PEMB - MOMENT FRAMES AND ROD BRACING, FRAME ANCHORAGE AND
THAT REQUIRE DESIGN IN ACCORDANCE WITH ASCE 7-10 CHAPTER 13 AND HAVE A
MOTION AND FOR COMPONENTS WITH HAZARDOUS SUBSTANCES AND ASSIGNED
THAT THE LABEL, ANCHORAGE OR MOUNTING CONFORMS TO THE CERTIFICATE OF
COMPLIANCE.
ARCHITECTURAL COMPONENTS: PERIODIC SPECIAL INSPECTION SHALL BE PROVIDED
DURING THE ERECTION AND FASTENING OF EXTERIOR CLADDING, INTERIOR AND
EXCEPTIONS AS NOTED IN THE IBC SECTION 1705.11.5. CERTICIFATION, AS DESCRIBED
IN ASCE 7-10 SECTION 13.2.1, SHALL BE PROVIDED FOR ACHITECTURAL COMPONENTS,
SUPPORTS AND ATTACHMENTS. PERIODIC SPECIAL INSPECTION IS REQUIRED FOR THE
ANCHORAGE OF ACCESS FLOORS.
EXTERIOR NON-BEARING WALLS AND INTERIOR AND EXTERIOR VENEER WITH
MECHANICAL AND ELECTRICAL COMPONENTS: PERIODIC SPECIAL INSPECTION IS
REQUIRED FOR:
C. INSTALLATION AND ANCHORAGE OF DUCTWORK DESIGNED TO CARRY
HAZAEDOUS MATERIALS.
D. INSTALLATION AND ANCHORAGE OF VIBRATION ISOLATION SYSTEMS.
CERTIFICATION, AS DESCRIBED IN ASCE 7-10 SECTION 13.2.1, SHALL BE PROVIDED
FOR MECHANICAL AND ELECTRICAL COMPONENTS, SUPPORTS AND ATTACHMENTS.
ANCHORAGE OF ACCESS FLOORS.
SPECIAL INSPECTION AND TESTING REPORTS, IN ACCORDANCE WITH IBC SECTION
1704.2.4, SHALL BE SUBMITTED TO THE CONTACTING OFFICER.
EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A SEISMIC FORCE
RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM, OR COMPONENT LISTED IN THE
STATEMENT OF SPECIAL INSPECTIONS SHALL SUBMIT A WRITTEN STATEMENT OF
RESPONSIBILITY TO THE CONTRACTING OFFICER PRIOR TO THE COMMENCEMENT
OF WORK ON TH SYSTEM OR COMPONENT. THE WRITTEN STATEMENT SHALL BE IN
ACCORDANCE WITH IBC SECTION 1704.4.
2. INSPECT ANCHORS CAST IN
CONCRETE.
PERIODIC
SPECIAL
INSPECTION
ACI 318 CH.
20, 25.2, 25.3, 26.5.1-26.5.3
IBC
REFERENCE
TABLE 1 - REQUIRED SPECIAL INSPECTIONS
AND TESTS (IBC 2015)
SCHEDULE OR SPECIAL INSPECTION
1. INSPECTION TASKS PRIOR TO BOLTING: (AISC 360 TABLE N5.6-1)
A. MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR
FASTENER MATERIALS
B. FASTENERS MARKED IN ACCORDANCE WITH ASTM
REQUIREMENTS
C. PROPER FASTENERS SELECTED FOR THE JOINT DETAIL
GRADE, TYPE, BOLT LENGTH IF THREADS ARE TO BE
EXCLUDED FROM SHEAR PLANE)
D. PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL
E. CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE
FAYING SURFACE CONDITION AND HOLE PREPARATION, IF
SPECIFIED, MEET APPLICABLE REQUIREMENTS
F. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION
PERSONNEL OBSERVED AND DOCUMENTED FOR FASTENER
ASSEMBLIES AND METHODS USED
G. PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS
AND OTHER FASTENER COMPONENTS
2. INSPECTION TASKS DURING BOLT: (AISC 360 TABLE N5.6-2)
A. FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN
ALL HOLES AND WASHERS (IF REQUIRED) ARE POSITIONED AS
REQUIRED
B. JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO
THE PRETENSIONING OPERATION
C. FASTENER COMPONENT NOT TURNED BY THE WRENCH
REVENTED FROM ROTATING
D. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE
RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS
(RCSC) SPECIFICATION, PROGRESSING SYSTEMATICALLY
FROM THE MOST RIGID POINT TOWARD THE FREE EDGES
3. INSPECTION TASKS AFTER BOLT (AISC 360 TABLE N5.6-3)
A. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED
CONNECTIONS
4. MATERIAL VERIFICATION OF HIGH-STRENGTH BOLTS, NUTS AND
WASHERS:
A. IDENTIFICATION MARKINGS TO CONFORM TO ASTM
STANDARDS SPECIFIED IN THE APPROVED CONSTRUCTION
DOCUMENT
B. MANUFACTURER'S CERTIFICATE OF COMPLIANCE REQUIRED
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X X X
X X X X
X
X X
REFERENCED
STANDARD
1. INSPECT REINFORCEMENT AND VERIFY
PLACEMENT.
CONCRETE CONSTRUCTION:
(IBC TABLE 1705.3)
FABRICATORS (IBC 1704.2.5)
TYPE
CONTINUOUS
SPECIAL
INSPECTION
X
3. INSPECT ANCHORS POST-INSTALLED IN
HARDENED CONCRETE MEMBERS.
A. ADHESIVE ANCHORS INSTALLED IN
HORIZONTALLY OR UPWARDLY
INCLINED ORIENTATIONS TO RESIST
SUSTAINED TENSION LOADS.
B. MECHANICAL ANCHORS AND
ADHESIVE ANCHORS NOT DEFINED
IN 3A.
4. VERFIY USE OF REQUIRED DESIGN MIX.
X
X
X
X
1908.4
1904.1, 1904.2, 1908.2, 1908.3
X
ACI 318: 17.8.2
ACI 318: 7.8.2.4
ACI 318: 17.8.2
ACI 318 CH 19,
26.4.3, 26.4.4
5. PRIOR TO CONCRETE PLACEMENT,
FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP
AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF
THE CONCRETE.
6. INSPECT CONCRETE PLACEMENT FOR
PROPER APPLICATION TECHNIQUES.
7. VERIFY MAINTENANCE OF SPECIFIED
CURING TEMPERATURE AND
TECHNIQUES.
8. INSPECT FORMWORK FOR SHAPE,
LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.
1. VERIFY MATERIALS BELOW SHALLOW
FOUNDATIONS ARE ADEQUATE TO
ACHIEVE THE DESIGN BEARING
CAPACITY.
2. VERIFY EXCAVATIONS ARE EXTENDED
TO PROPER DEPTH AND HAVE REACHED
PROPER MATERIAL.
3. PERFORM CLASSIFICATION AND
TESTING OF COMPACTED FILL
MATERIALS.
4. VERIFY USE OF PROPER MATERIALS,
DENSITIES AND LIFT THICKNESSES
DURING PLACEMENT AND COMPACTION
OF COMPACTED FILL.
5. PRIOR TO PLACEMENT OF COMPACTED
FILL, INSPECT SUBGRADE AND VERIFY
THAT SITE HAS BEEN PREPARED
PROPERLY.
X
X
SOILS: (IBC TABLE 1705.6)
X
X
X
X
X
X
X
1908.10
ACI 318:
26.4.7-26.4.9
ASTM C 172,
ASTM C 31
ACI 318: 26.4.5,
26.12
1908.6, 1908.7, 1908.8
ACI 318: 26.4.5
ACI 318:
26.10.1(b)
1908.9
X
X
X
X
X
X
X
X
F. CONFIGURATION AND FINISH OF ACCESS HOLES
G. FIT-UP OF FILLET WELDS
I. DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
II. CLEANLINESS (CONDITION OF STEEL SURFACES)
III. TACKING (TACK WELD QUALITY AND LOCATION)
2. INSPECTION TASKS DURING WELDING: (AISC 360 TABLE N5.4-2)
A. USE OF QUALIFIED WELDERS
B. CONTROL AND HANDLING OF WELDING CONSUMABLES
I. PACKAGING
II. EXPOSURE CONTROL
C. NO WELDING OVER CRACKED TACK WELDS
D. ENVIRONMENTAL CONDITIONS
I. WIND SPEED WITHIN LIMITS
II. PRECIPITATION AND TEMPERATURE
E. WPS FOLLOWED
I. SETTINGS ON WELDING EQUIPMENT
II. TRAVEL SPEED
III. SELECTED WELDING MATERIALS
IV. SHIELDING GAS TYPE/FLOW RATE
V. PREHEAT APPLIED
VI. INTERPASS TEMPERATURE MAINTAINED (MIN. / MAX.)
VII. PROPER POSITION (F, V, H, OH)
F. WELDING TECHNIQUES
I. INTERPASS AND FINAL CLEANING
II. EACH PASS WITHIN PROFILE LIMITATIONS
III. EACH PASS MEETS QUALITY REQUIREMENTS
3. INSPECTION TASKS AFTER WELDING (AISC 360 TABLE N5.4-3)
A. WELDS CLEANED
B. SIZE, LENGTH AND LOCATION OF WELDS
C. WELDS MEET VISUAL ACCEPTANCE CRITERIA
I. CRACK PROHIBITION
II. WELD/BASE-METAL FUSION
III. CRATER CROSS SECTION
IV. WELD PROFILES
V. WELD SIZE
VI. UNDERCUT
VII. POROSITY
D. ARC STRIKES
E. k-AREA VISUAL INSPECTION OF WEB FOR CRACKS WITHIN 3
INCHES OF WELD.
F. BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED)
G. REPAIR ACTIVITIES
H. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT
OR MEMBER
4. STRUCTURAL STEEL AND COLD-FORMED STEEL DECK WELDS
A. COMPLETE JOINT PENETRATION (CPJ) GROOVE WELDS
B. MULTIPASS FILLET WELDS
C. SINGLE-PASS FILLET WELDS > 5/16"
D. PLUG AND SLOT WELDS
E. SINGLE-PASS FILLET WELDS < 5/16"
F. FLOOR AND ROOF DECK WELDS
STRUCTURAL STEEL BOLTING:
TASK
PERFORM
FOR EACH
WELD
TABLE 2 - REQUIRED SPECIAL INSPECTIONS AND
TESTS (AISC 360-11)
OBSERVE ON
RANDOM
BASIS
STRUCTURAL STEEL WELDING:
X X
X X
X
1. INSPECTION TASKS PRIOR TO WELDING: (AISC 360 TABLE N5.4-1)
A. WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE.
B. MANUFACTURER'S CERTIFICATIONS FOR WELDING
CONSUMABLES AVAILABLE.
C. MATERIAL IDENTIFICATION (TYPE/GRADE)
D. WELDER IDENFICATIONS SYSTEM.
E. FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
I. JOINT PREPARATION
II. DIMENSIONS (ALIGNMENT, ROOT OPNG, ROOT FACE,
BEVEL)
III. CLEANLINESS (CONDITIONOF STEEL SURFACES)
IV. TACKING (TACK WELD QUALITY AND LOCATION)
V. BACKING TYPE AND FIT (IF APPLICABLE)
SPECIAL INSPECTIONS
THE PEMB SHALL BE A MANUFACTURER'S STANDARD PREFABRICATED METAL
PRE-ENGINEERED METAL BUILDING (PEMB) NOTES
1.
STRUCTURE CONFIGURED PER THE ARCHITECTURAL DRAWINGS, EXCEPT AS
NOTED. RIGID FRAMES SHALL BE SPACED AS SHOWN IN THE DRAWINGS, BUT
OVERALL DIMENSIONS AND CONSTRUCTION DETAILS MAY VARY TO SUIT
MANUFACTURER'S STANDARD DESIGN.
A CERTIFICATE TO VERIFY COMPLIANCE WITH AISC SHALL BE SUBMITTED.2.
THE DIMENSIONAL TOLERANCES APPLICABLE TO HOT-ROLLED STEEL UNDER
THE AISC "STANDARD MILL PRACTICE" SECTION SHALL BE REQUIRED IN THE
FABRICATION OF THE STEEL BUILDING FRAMES.
THE PEMB FRAME SHALL BE DESIGNED TO LIMIT THE LATERAL DEFLECTION3.
IN ACCORDANCE WITH THE SPECIFICATION SECTION 13 34 19.
A COMPLETE DESIGN ANALYSIS SHOWING ALL CALCULATIONS OF THE STRUCTURE4.
FOR WIND AND SEISMIC LOADS AND A LAYOUT OF ANCHOR BOLTS AND OTHER
EMBEDDED ITEMS SHALL BE SUBMITTED FOR APPROVAL WITH MAIN MEMBERS,
TYPICAL CONNECTIONS (SHOWING BOLT HOLES AND WELDS), AND ERECTION
DRAWINGS. BOTH THE DESIGN ANALYSIS AND PEMB DRAWINGS SHALL BE SEALED
BY A PROFESSIONAL ENGINEER LISCENSED IN THE STATE OF TEXAS.
THE PEMB SHALL BE DESIGNED TO SUPPORT ALL ELECTRICAL EQUIPMENT AND5.
ALL OTHER SUCH DEVICES AS NEEDED. ADDITIONAL MEMBERS SHALL BE PLACED
IN CONVENIENT LOCATIONS FOR ATTACHMENT OF ALL EQUIPMENT AND
APPURTENANCES.
CONTRACTOR SHALL COORDINATE BETWEEN PEMB MANUFACTURER AND6.
OTHER TRADES FOR INTERFACING AND APPURTENANCE ATTACHMENTS.
CONTRACTOR SHALL COORDINATE LOCATION AND FASTENING REQUIREMENTS7.
FOR FOUNDATION ANCHORING AND PEMB COLUMNS.
LOAD COMBINATIONS AND DESIGN STRESSES SHALL COMPLY WITH AISC8.
SPECIFICATIONS, IBC REQUIREMENTS AND DESIGN CRITERIA SPECIFIED ON
ALL PEMB ANCHOR BOLTS SHALL BE DESIGNED AND FURNISHED BY THE9.
PEMB CONTRACTOR. ANCHOR BOLTS SHALL BE DESIGNED BY A PROFESSIONAL
FURNISHED BY THE PEMB MANUFACTURER AND THE REACTIONS PROVIDED
ON THE DRAWINGS. THE ANCHOR BOLT DESIGN ANALYSIS SHALL BE SUBMITTED
FOR APPROVAL.
THE FOUNDATION SHOWN ON THE DRAWINGS ARE BASED ON DESIGN10.
REACTIONS GENERATED IN-HOUSE. THE ACTUAL REACTIONS SHALL BE
SUBMITTED BY THE PEMB SUPPLIER/DESIGNER FOR REVIEW AND APPROVAL
PRIOR TO CONSTRUCTION. ANY REQUIRED MODIFICATIONS TO THE
FOUNDATION SYSTEM TO MEET THE REQUIRED REACTIONS SHALL BE MADE
THIS SHEET.
AT THAT TIME.
ENGINEER LISCENED IN THE STATE OF TEXAS FOR THE FRAME REACTIONS
S
A D
U
NO. DATE BY DESCRIPTION
DATE
PROJECT NO.
MERRICK PROJECT NO.
DESIGNER
DRAWN BY
PROJECT MANAGER
REAL PROPERTY
SAFETY & HEALTH
PPM
EPM
REVISIONS
RESEARCH LABORATORY
A-E FIRM USDA
FACILITIES ENGINEERING BRANCH
5601 SUNNYSIDE AVENUE
BELTSVILLE, MD. 20705-5100
FACILITIES DIVISION
KNIPLING-BUSHLAND U.S. LIVESTOCK INSECTS
Research
Agricultural
Service
J. DELAY
64019927
A. DE LEON
C. MATHER
DR. WURZBERGER
A. MAGINNIS
A. MAGINNIS
B994 STANCHION BARN
GENERAL NOTES - SHEET 2
S-002
A 01-22-20 75% CONSTRUCTION DOCUMENTS
B 04-01-20 95% CONSTRUCTION DOCUMENTS
C 09-21-20 100% CONSTRUCTION DOCUMENTS
5 4 3 2 1
B
B.2
B.4
B.7
C
B.3
22 2 2 2
(TYP.)
30.00°
(T Y
P
TYP.
7.00° (TYP.)
8' - 0"
8' - 0"
S-501
A
B.5
6 6
6 6
18' - 5 1/2"
22' - 6"
24' - 0" 24' - 0" 24' - 0" 24' - 0"
TYP.
TYP.
12' - 0"
5.9 24' - 0" 24' - 0" 24' - 0" 3' - 0" 21' - 0"
WORKING BARN
STANCHION BARN
TYP.
S-502
TYP. AT COLUMN
S-502
S-502
TYP. BETWEEN COLUMNS
S-502
S-502
TYP. AT COLUMNTYP. BETWEEN COLUMNS
S-502
S-502
TYP. BETWEEN
COLUMNS
TYP. AT COLUMN
S-502
TYP. AT
COLUMN (SIM.)
6' - 4" 3' - 8" 8' - 4"
T H
IC
K
C U
R B
/2 x
T H
IC
K
C U
R B
/2 x
THICK CURB
1' - 8 1/2" x 8"
THICK CURB
1' - 8 1/2" x 8"
THICK CURB
6" x 8"
S-502
SIM.
S-502
OH
S-502
S-502
S-502
SIM.
SIM.
S
A D
U
NO. DATE BY DESCRIPTION
DATE
PROJECT NO.
MERRICK PROJECT NO.
DESIGNER
DRAWN BY
PROJECT MANAGER
REAL PROPERTY
SAFETY & HEALTH
PPM
EPM
REVISIONS
RESEARCH LABORATORY
A-E FIRM USDA
FACILITIES ENGINEERING BRANCH
5601 SUNNYSIDE AVENUE
BELTSVILLE, MD. 20705-5100
FACILITIES DIVISION
KNIPLING-BUSHLAND U.S. LIVESTOCK INSECTS
Research
Agricultural
Service
J. DELAY
64019927
A. DE LEON
C. MATHER
DR. WURZBERGER
A. MAGINNIS
A. MAGINNIS
B994 STANCHION BARN
FOUNDATION PLAN
S-101
1/8" = 1'-0"1
FOUNDATION PLAN
1. TOP OF MAT SLAB EL. 100'-0". SEE CIVIL FOR
ELEVATION RELATIVE TO SEA LEVEL.
2. FOR TYPICAL CONCRETE DETAILS SEE SHEET S-501.
3. SEE ARCH DWGS FOR ADDITIONAL DIMENSIONS.
4. PRIOR TO POURING FOUNDATION CONCRETE,
COORDINATE FLOOR DRAINS, OPENINGS,
DEPRESSIONS AND SLOPES WITH ARCHITECTURAL
AND MECHANICAL DRAWINGS.
5. COORDINATE SIZE AND LOCATION OF MECH AND ELEC
HOUSEKEEPING PADS. VERIFY PAD SIZE WITH ACTUAL
EQUIPMENT FURNISHED PRIOR TO PAD CONCRETE
POUR.
6. SUBGRADE SHALL BE PREPARED PER THE
GEOTECHNICAL ENGINEERING STUDY.
7. CONTRACTOR HAS OPTION TO INSTALL ENTRY
STOOPS AS A SECOND CONCRETE POUR. IF THIS
OPTION IS EXERCISED, RE-ENTRANT CORNER BARS
SHALL BE OMITTED.
8. PROVIDE 2'-0" MINIMUM IMPORTED SELECT FILL BELOW
MAT FOUNDATION, COMPACTED TO NOT LESS THAN
98% OF MAX DENSITY ACCORDING TO ASTM D 1557.
9. PREPARE SLAB FOR PLACEMENT PER THE
GEOTECHNICAL REPORT. SEE DETAIL 9/S-501 FOR
FURTHER GUIDANCE.
10.WHERE CONTRACTOR SEPARATES POURS WITH
CONSTRUCTION JOINTS, 1" DIAMETER x 2'-0" DOWELS
(GREASED ON ONE END) SHALL BE INSTALLED
BETWEEN SLABS AT 1'-0" O.C.
GENERAL NOTES
SHEET KEYNOTES
1 18" THICK MAT SLAB REINFORCED WITH #7 AT 16" O.C.
TOP AND BOTTOM.
2 (2) #7 HAIRPINS WRAPPED AROUND ANCHOR BOLT
GROUP AT 2 1/2" AND 5" BELOW TOP MAT AND
DEVELOPED 10'-0" AS SHOWN (TYP. EACH FRAME
COLUMN).
3 GROUND FLOOR SLOPE CRICKETS SLOPED TO DRAINS.
MAINTAIN 18" THICKNESS OF SLAB AT WHOLE BUILDING
FOOTPRINT. SEE MECHANICAL DRAWINGS FOR DRAIN.
4 TRENCH DRAIN. SEE DETAIL 11/S-501.
5 PRE-ENGINEERED METAL BUILDING COLUMNS (TYP.) BY
MANUFACTURER.
6. WIND POST AT GABLE END (BY MANUFACTURER).
7. 30" DIAMETER BY 40'-0" DEEP REINFORCED CONCRETE
DRILLED PIER REINFORCED WITH (12) #10 BARS AND #3
COLUMN TIES AT 12" O.C. SEE DETAIL 5/S-501 FOR
TYPICAL DRILLED PIER INFORMATION. TOP OF
DRILLED PIER ELEVATION 0'-0" UNLESS NOTED
OTHERWISE. NOTE THAT DRILLED PIER DESIGNS ARE
CURRENTLY FOR ESTIMATING PURPOSES ONLY AND
REQUIRE A GEOTECHNICAL REPORT TO FINALIZE
DESIGN. DO NOT CONSTRUCT DRILLED PIERS AS
DESIGNED.
8. CONSTRUCTION JOINT. SEE 8/S-501.
9. CONSTRUCTION JOINT BETWEEN STANCHION BARN MAT
SLAB AND MAT SLAB AT TRANSITION AREA.
10.USE FELT BETWEEN MAT SLAB AND DRILLED PIER AT
JOINT.
11.18" THICK MAT SLAB REINFORCED WITH #7 AT 16" O.C.
TOP AND BOTTOM. FIELD VERIFY THAT ALL DIMENSIONS
ARE SUITABLE FOR CHOSEN PENNING SYSTEM.
0 2' 4' 8' 16'
NORTH
A 08-20-19 50% CONSTRUCTION DOCUMENTS
B 01-22-20 75% CONSTRUCTION DOCUMENTS
/4
/4
/4
1' - 0" 2' - 3" 4' - 6" 2' - 3"
11' - 0"
1'-6" THICK MAT SLAB
w/ #6 @ 12" O.C. E.W.
TOP & BOTT.
(6) HOPPER SUPPORT
LOCATIONS
NOTES:
1. LOCATION TBD
2. FIELD VERIFY ALL DIMENSIONS
EXISTING HOPPER
BEING RELOCATED
S-102
C L R
C L R
2" CLR
(E) HOPPER SUPPORT
(N) 5/8"⌀ ASTM F1554
ANCHOR ROD w/ HILTI
HIT-HY 200 ADHESIVE
SYSTEM. EMBED MIN. 6"
#6 @ 12" O.C.
1' - 10" 1' - 10"34' - 4"
OUTSIDE FLANGE OF COL. OUTSIDE FLANGE OF COL.
1'-6" THICK MAT SLAB
w/ #6 @ 12" O.C. E.W.
TOP & BOTT.
SA SB
S1
S2
S3
NOTES:
1. LOCATION TBD
2. FIELD VERIFY ALL DIMENSIONS
EXISTING PEMB BEING RELOCATED
S-102
C L R
C L R
2" CLR
(E) BARN COL.
(2) 3/4"⌀ ANCHOR BOLT
w/ 9" EMBED. SEE DETAIL 5/S-501
(E) BASE PL.
REINF PER PLAN
GRID
S
A D
U
NO. DATE BY DESCRIPTION
DATE
PROJECT NO.
MERRICK PROJECT NO.
DESIGNER
DRAWN BY
PROJECT MANAGER
REAL PROPERTY
SAFETY & HEALTH
PPM
EPM
REVISIONS
RESEARCH LABORATORY
A-E FIRM USDA
FACILITIES ENGINEERING BRANCH
5601 SUNNYSIDE AVENUE
BELTSVILLE, MD. 20705-5100
FACILITIES DIVISION
KNIPLING-BUSHLAND U.S. LIVESTOCK INSECTS
Research
Agricultural
Service
J. DELAY
64019927
A. DE LEON
C. MATHER
DR. WURZBERGER
A. MAGINNIS
A. MAGINNIS
B994 STANCHION BARN
MISC. FOUNDATIONS
S-102
0 6" 1' 2' 4' 0 3" 6" 12" 24"
0 1' 2' 4' 8' 0 3" 6" 12" 24"
1. REFER TO SHEETS S-501 FOR TYPICAL CONCRETE AND
FOUNDATION DETAILS.
2. SEE ARCH DWGS FOR ADDITIONAL DIMENSIONS.
3. PRIOR TO POURING FOUNDATION CONCRETE, COORDINATE FLOOR
DRAINS, OPENINGS, DEPRESSIONS AND SLOPES WITH ARCH DWGS.
GENERAL NOTES
1/2" = 1'-0"1
HOPPER BIN FOUNDATION
1" = 1'-0"2
HOPPER BIN SECTION
1/4" = 1'-0"3
HAY STORAGE BARN FOUNDATION
1 1/2" = 1'-0"4
HAY STORAGE BARN FOUNDATION SECTION
A 01-22-20 75% CONSTRUCTION DOCUMENTS
"D d b
6db*O R3" M
IN
135° HOOK
BAR SIZE D'
1 1/2"
2"
1/2"
#3
#4
#5
"D" d b
90° HOOK
* PROVIDE 10db EXTENSIONS IN LIEU OF 6db AT ALL FRAME COLUMNS, GIRDERS, SHEAR WALLS AND
SHEAR
WALL BOUNDARY MEMBERS.
TIES & STIRRUPS HOOKS
ONLY
TYPICAL COLUMN
BAR OFFSET"D"
d b d b
U .N
.O d b
OR 2 1/2"
STANDARD HOOKS
90° HOOK180° HOOK
40 DIA IN MASONRY
30 DIA. IN
CONCRETE
2'-0" MIN. U.N.O.
TYP. COMPRESSION LAP
SPLICE
BAR SIZE "D"
6d
8d
10d
#3 THRU #8
#9 THRU #11
#14 THRU #18
NOTE:
FOR TENSION SPLICE
SEE X/S-XXX.
4db MIN.
"D b b b
BAR DESCRIPTION
AND LOCATION IN
STRUCTUTE
BAR WITH
SPACING > 2 x d
CLEAR COVER >d
OR BEAM & COLUMN
BARS WITH
SPACING > d
CLEAR COVER > d b b b b
OTHER CASES
TOP
BOTTOM
TOP
BOTTOM
CONCRETE
STRENGTH
psi
BAR SIZE
LAP CLASS
#3 #4 #5 #6 #7 #8 #9
A B A B A B A B A B A B A B
1'-7"
1'-3"
2'-1"
1'-7"
2'-1"
1'-7"
2'-9"
2'-4"
2'-7"
2'-0"
3'-5"
2'-7"
3'-1"
2'-5"
4'-1"
3'-1"
4'-6"
3'-6"
5'-11"
4'-6"
5'-2"
4'-0"
6'-9"
5'-2"
5'-10"
4'-6"
7'-7"
5'-10"
2'-4"
1'-10"
3'-1"
2'-4"
3'-1"
2'-5"
2'-9"
3'-1"
3'-11"
3'-0"
5'-1"
3'-11"
4'-8"
3'-7"
6'-1"
4'-8"
6'-9"
5'-3"
8'-10"
6'-9"
7'-9"
6'-0"
10'-1"
7'-9"
8'-9"
6'-9"
11'-4"
8'-9"
NOTES:
1.
2.
3.
4.
d
USE THIS TABLE FOR BAR SPLICES UNLESS SPECIFICALLY DETAILED
AND DIMENSIONED ON PLANS.
THIS SCHEDULE IS NOT APPLICABLE TO DUCTILE MONENT FRAME
MEMBERS RESISTING SEISMIC FORCES.
FOR TENSION DEVELOPMENT LENGTHS "L ", USE CLASS "B" SPLICE
LENGTHS.
ALL SPLICES SHALL BE CLASS "B" UNLESS NOTED OTHERWISE ON
PLANS.
5.
6.
7.
8.
TOP BARS ARE HORIZONTAL REINFORCEMENT WITH MORE THAN
12" OF CONCRETE CAST BELOW BAR.
BOTTOM BARS ARE VERTICAL BARS, ALL HORIZONTAL WALL
REINFORCEMENT, AND HORIZONTAL REINFORCEMENT WITH LESS
THAN 12" OF CONCRETE CAST BELOW BARS.
COVER DESIGNATES CLEAR CONCRETE COVER FROM SPLICED
BAR TO FACE OF MEMBER, SPACING DESIGNATES CLEAR
DIMESION BETWEEN SPLICED BARS.
SHEARWALLS WITH TWO CURTAINS OF REINFORCING SHALL NOT
HAVE EACH CURTAIN OF HORIZONTAL BARS SPLICED AT SAME
LOCATION.
GRADE 60
GRADE 60
5/8" DIA.x1'-0"
GREASED DOWELAT
1'-0" O.C.(TYP.)
REMOVE CAP AND
FILL WITH SEALANT
STOP REINFORCING
AT JOINT. SEE
FOUNDATION PLAN
FOR REINF. SIZE
REINFORCED
CONCRETE SLAB
4" COMPACTED FREE
DRAINING GRANULAR
MATERIAL
COMPACTED
SUBGRADE
VAPOR
BARRIER
REINFORCED CONCRETE
SLAB. SEE FOUNDATION
PLAN FOR THICKNESS.
VAPOR
BARRIER
4" COMPACTED FREE
DRAINING GRANULAR
MATREIAL
COMPACTED
SUBGRADE PER
FOUNDATION
GENERAL NOTES
11'-0" M
IN.
8'-0" MIN.
'-0
M
IN
(8) #5 AT 12" O.C.
TOP
#5 AT 12" O.C.
BOTTOM
NOTE:
PROVIDE AT ALL SLAB
CORNERS UNO, TYP.
T.O.C.
EL. = RE: PLAN
CONC. PAD, SEE PLUMBING
MECHANICAL AND
ELECTRICAL DRAWINGS
FOR SIZE AND LOCATION#4 AT
18" O.C.
ROUGHEN SURFACE OF
SLAB BEFORE POURING
PAD
C O
O R
D
IN
A T
E w
A
R C
H D
W G
S
A T
H O
U S
E K
E E
P
IN
G P
A D
C L R
6" MIN.
#4 AT 18" O.C.
BENT DOWELS
A N
D M
E C
H D
W G
S
STANCHION FLOOR
100' - 0"
1' - 0"
V A
R
IE
S
PRE-MANUFACTURED
TRENCH DRAINS (SEE
PLUMBING DRAWINGS)
TOP OF SLAB (SEE STRUCT AND
ARCH PLANS FOR SLOPE LINES)
TYPICAL SIZE
AND SPACING OF
MAT SLAB REBAR
#7 (CONT.) (TYP.)
#7 AT 16" O.C.
NOTE: COORDINATE ALL TRENCH DRAIN CONCRETE VOID DIMENSIONS WITH MANUFACTURER.
5'-11"5'-11"
2" 2"
(6) #5 x 4'-0" REBAR @ 6" O.C.
(3) AT 2" CLR TOP AND (3) AT
3" CLR BOTT OF SLAB
2"
RE: PLAN
C L R
M
IN
3" CLEAR, TYP.
TIES, RE: PLAN
TIES, RE: PLAN
PIER SHAFT
RE: PLANS
T.O. FIN GRADE
5/
3'
/2
8 1/
2 5 6"
1/
2"
C L R
NOTES:
1. TEMPORARY CASINGS MAY BE REQ'D FOR CONSTRUCTION.
2. MIN EMBEDMENT INTO BEDROCK SHALL BE PER THE GEOTECHNICAL REPORT.
3. THIS DETAIL IS FOR ESTIMATING PURPOSES, NOT FOR CONSTRUCTION. A
GEOTECHNICAL REPORT IS REQUIRED TO FINALIZE DESIGN.
1/
8" B
E D
R O
C K
E M
B E
D M
E N
T R
E
N O
T E
RE: PLAN
(4) TIES AT 3" O.C.
'-0
RE: PLANS
T.O. CONC. PIER EL.
6"
'-0
MAX.
4' - 0"
M A
X
4'
2" CLR, TYP
(2) #6 BARS AT T&B
OF SLAB, TYPICAL
(1) #6 BAR AT T&B.
EXTEND TRIMMER
BARS 2'-6" BEYOND
SIDES OF OPENING
OR AS FAR AS
POSSIBLE & HOOK
NOTES:
1.
2.
3.
2'
- 6
2'
- 6
THIS DETAIL APPLIES TO CIRCULAR AND RECTANGULAR
OPENINGS.
PROVIDE EXTRA BARS (NOT SHOWN) PARALLEL TO SIDES OF
OPENING EQUAL TO AREA OF INTERRUPTED SLAB BARS,
EXTEND FULL LENGTH OF SPAN.
THIS DETAIL IS TYPICAL AT OPENINGS UP TO 4'-0" MAX.
DIMENSIONS UNLESS NOTED OTHERWISE ON PLANS.
S
A D
U
NO. DATE BY DESCRIPTION
DATE
PROJECT NO.
MERRICK PROJECT NO.
DESIGNER
DRAWN BY
PROJECT MANAGER
REAL PROPERTY
SAFETY & HEALTH
PPM
EPM
REVISIONS
RESEARCH LABORATORY
A-E FIRM USDA
FACILITIES ENGINEERING BRANCH
5601 SUNNYSIDE AVENUE
BELTSVILLE, MD. 20705-5100
FACILITIES DIVISION
KNIPLING-BUSHLAND U.S. LIVESTOCK INSECTS
Research
Agricultural
Service
J. DELAY
64019927
A. DE LEON
C. MATHER
DR. WURZBERGER
A. MAGINNIS
A. MAGINNIS
B994 STANCHION BARN
TYPICAL CONCRETE SECTIONS AND
DETAILS
S-501
N.T.S.1
TYPICAL REINFORCING BAR BENDS
N.T.S.2
SPLICE TABLE A - GENERAL
N.T.S.8
TYP CONSTRUCT JT
N.T.S.9
TYP. SLAB-ON-GRADE-DETAIL
N.T.S.4
TYPICAL SLAB CORNER REINF
N.T.S.10
TYPICAL HOUSEKEEPING PAD
1" = 1'-0"11
TRENCH DRAIN SECTION
0 3" 6" 12" 24"
N.T.S.6
TYP REENTRANT CORNER REINFORCING
N.T.S.5
DRILLED PIER
N.T.S.3
SUPPLIMENTAL REINF AT SMALL OPNG
A 08-20-19 50% CONSTRUCTION DOCUMENTS
B 01-22-20 75% CONSTRUCTION DOCUMENTS
STANCHION FLOOR
100' - 0"
B
BASE PLATE (BY PEMB MANUFACTURER)
COORDINATE WIDTH OF CURB WITH
BASE PLATE SIZE AND LOCATION
ANCHOR BOLTS (BY
PEMB MANUFACTURER)
PEMB COLUMN (BY
MAUFACTURER)METAL PANEL
CLADDING (SEE ARCH.)
#5 (CONT.)
#4 DOWELS AT 12" O.C.
(HOOKED AT BOTTOM MAT)
PROVIDE FELT JOINT
AROUND COLUMN TO
ISOLATE FROM CONCRETE
SEE CIVIL FOR
EXTERIOR GRADE
TYPICAL MAT SLAB
REINF. (SEE PLAN)
C L R
C L R