Happy Camp Helibase Operations Facilities Improvements
00010-1 Table of Contents
TABLE OF CONTENTS
DIVISION 1 – GENERAL REQUIREMENTS
01010 – SUMMARY OF WORK
01040 – PROJECT COORDINATION
01060 – REGULATORY REQUIREMENTS
01300 – SHOP DRAWINGS AND SUBMITTALS
01700 – PROJECT CLEAN UP
DIVISION 2 – SITE CONSTRUCTION
02010 – SITE CONDITIONS
02016 – EXISTING UNDERGROUND STRUCTURES
02050 – CLEARING/GRUBBING/DEMOLITION/DEBRIS REMOVAL
02225 – SHORING AND TRENCH SAFETY
02300 – EARTHWORK
02660 – WATER DISTRIBUTION SYSTEM
02705 – PAVING AND RESURFACING
02731 –GRAVITY SEWER LINES
DIVISION 3 – CONCRETE
03100 – CONCRETE FORMWORK
03200 – CONCRETE REINFORCEMENT
03300 – CAST-IN-PLACE CONCRETE
DIVISION 4 – MASONRY
NOT USED
DIVISION 5 – METALS
DIVISION 6 – WOOD AND PLASTICS
06100 – ROUGH CARPENTRY
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
Table of Contents 00010-2
DIVISION 8 – DOORS AND WINDOWS
08111 – STANDARD STEEL DOORS AND FRAMES
08211 – FLUSH WOOD DOORS
08561 – VINYL WINDOWS
08710 – DOOR HARDWARE
08800 – GLASS AND GLAZING
DIVISION 9 – FINISHES
09650 – RESILIENT FLOORING
09680 – CARPET
DIVISION 10 – SPECIALTIES
10155 – TOILET COMPARTMENTS
DIVISION 11 – EQUIPMENT
NOT USED
DIVISION 12 – FURNISHINGS
12356 – CASEWORK
DIVISION 13 – SPECIAL CONSTRUCITON
13121 – PRE-ENGINEERED METAL BUILDINGS
13122 – MODULAR BUILDING
DIVISION 14 – CONVEYING SYSTEMS
NOT USED
DIVISION 15 – MECHANICAL
15010 – GENERAL MECHANICAL REQUIREMENTS
15400 – BUILDING PLUMBING
15487 – LIQUIFIED PETROLEUM GAS SYSTEM
15500 – HVAC
15950 – TESTING, ADJUSTING AND BALANCING
DIVISION 16 – ELECTRICAL
16010 –GENERAL PROVISION ELECTRICAL
16050 – BASIC MATERIALS AND METHODS
**END OF TABLE OF CONTENTS**
06100-1 Rough Carpentry
SECTION 06100
ROUGH CARPENTRY
PART 1 - GENERAL
1.01 SCOPE
A. The scope of this Section includes the following:
1. Framing with dimension lumber.
2. Framing with engineered wood products.
3. Wood nailers, and blocking.
4. Sheathing.
1.02 DEFINITIONS
A. Rough carpentry includes carpentry work not specified as part of other Sections and generally not exposed, unless otherwise specified.
1.03 SUBMITTALS
A. Include lumber certification as part of Section 13122 submittals
1.04 DELIVERY, STORAGE, AND HANDLING
A. Delivery and Storage: Keep materials under cover and dry. Protect against exposure to weather and contact with damp or wet surfaces. Stack lumber as well as plywood and other panels; provide for air circulation within and around stacks and under temporary coverings including polyethylene and similar materials.
1. For lumber and plywood pressure treated with waterborne chemicals, place spacers between each bundle to provide air circulation.
1.05 QUALITY CONTROL
A. Codes and Standards
1. Uniform Building Code Chapter 25, 1997 Edition.
2. Industry Standards
Rough Carpentry 06100-2
a. WCLIB Standard Grading Rules No. 16, for Lumber.
b. WWPA Western Lumber Grading Rules.
c. U.S. Bureau of Standards PS-1, for plywood.
d. Redwood Inspection Service Standard Specifications.
B. Quality of products and installation shall conform to codes and standards referenced above, as applicable.
C. Moisture Content: Air-dry untreated lumber, with sticking both horizontally and vertically, for not less than 30 days prior to installation. Kiln-dry treated lumber to 19 percent moisture content.
D. Grade Stamps: All lumber and plywood shall be grade-stamped.
PART 2 - PRODUCTS
2.01 LUMBER, GENERAL
A. Lumber Standards: Furnish lumber manufactured to comply with PS 20 "American
Softwood Lumber Standard" and with applicable grading rules of inspection agencies certified by American Lumber Standards Committee's (ALSC) Board of Review.
B. Inspection Agencies: Inspection agencies and the abbreviations used to reference them with lumber grades and species include the following:
1. RIS - Redwood Inspection Service.
2. WCLIB - West Coast Lumber Inspection Bureau.
3. WWPA - Western Wood Products Association.
C. Grade Stamps: Provide lumber with each piece factory-marked with grade stamp of inspection agency evidencing compliance with grading rule requirements and identifying grading agency, grade, species, moisture content at time of surfacing, and mill.
D. Nominal sizes are indicated, except as shown by detail dimensions. Provide actual sizes as required by PS 20, for moisture content specified for each use.
1. Provide dressed lumber, S4S, unless otherwise indicated.
2. Provide seasoned lumber with 19 percent maximum moisture content at time of dressing and shipment for sizes 2 inches or less in nominal thickness, unless otherwise indicated.
06100-3 Rough Carpentry
2.02 DIMENSION LUMBER
A. All dimension lumber shall be graded as indicated on the drawings.
B. Sill plates in contact with concrete shall be pressure treated Douglas fir - No. 1 for structural walls and construction grade for non-structural walls. Or at non-structural walls, foundation grade redwood may be substituted.
2.03 MISCELLANEOUS LUMBER
A. General: Provide lumber for support or attachment of other construction including cant strips, bucks, nailers, blocking, furring, grounds, stripping, and similar members.
B. Fabricate miscellaneous lumber from dimension lumber of sizes indicated and into shapes shown.
C. Moisture content: 19 percent maximum for lumber items not specified to receive wood preservative treatment.
D. Grade: "Standard" grade light-framing-size lumber of any species or board-size lumber as required. "No. 3 Common" or "Standard" grade boards per WCLIB or WWPA rules or "No. 2 Boards" per SPIB rules.
2.04 CONSTRUCTION PANELS, (PLYWOOD), GENERAL
A. Construction Panel Standards: Comply with PS 1 "U.S. Product Standard for
Construction and Industrial Plywood" for plywood construction panels and, for products not manufactured under PS 1 provisions, with APA PRP-108.
B. Trademark: Furnish construction panels that are each factory-marked with APA trademark evidencing compliance with grade requirements.
C. Radiant Barriers: Roof sheathing and panels covering gable end walls in attics shall contain a radiant barrier applied to the inside face. The emissivity of the radiant barrier shall not exceed 0.05 according to ASTM text method C-1371-97. The product and installation shall meet all the requirements for radiant barriers contained in the Building Energy Efficiency Standards, California Title 24.
2.05 CONCEALED PERFORMANCE-RATED CONSTRUCTION PANELS
A. General: Where construction panels are indicated for the following concealed types of applications, provide APA Performance-Rated Panels complying with requirements designated under each application for grade designation, span rating, exposure durability classification, edge detail (where applicable), and thickness.
Rough Carpentry 06100-4
B. Trademarks: Factory-mark each construction panel with APA trademark evidencing compliance with grade requirements.
C. Structural Plywood for roof, wall and floor sheathing shall be as indicated on the drawings. Comply with paragraph 2.04(C) above.
2.06 CONSTRUCTION PANELS FOR BACKING
A. Plywood Backing Panels: For mounting electrical or telephone equipment, provide fire-retardant-treated plywood panels with grade designation, APA C-D PLUGGED EXPOSURE 1, in thickness indicated, or, if not otherwise indicated, not less than 15/32 inch.
2.07 AIR INFILTRATION BARRIER
A. Tyvek Housewrap or approved equal.
2.08 FASTENERS
A. General: Provide fasteners of size and type indicated that comply with requirements specified in this article for material and manufacturer.
1. Where rough carpentry is exposed to weather, in ground contact, or in area of high relative humidity, provide fasteners with a hot-dip zinc coating per ASTM A 153 or of AISI Type 304 stainless steel.
B. Nails, Wire, Brads, and Staples: FS FF-N-105.
C. Power Driven Fasteners: National Evaluation Report NER-272.
D. Wood Screws: ANSI B18.6.1.
E. Lag Bolts: ANSI B18.2.1.
F. Bolts: Steel bolts complying with ASTM A 307, Grade A, with ASTM A 563 hex nuts and where indicated, flat washers.
2.09 METAL FRAMING ANCHORS
A. General: Provide metal framing anchors of type, size, metal, and finish indicated that comply with requirements specified including the following:
1. Current Evaluation/Research Reports: Provide products for which model code evaluation/research reports exist that are acceptable to authorities having
06100-5 Rough Carpentry jurisdiction and that evidence compliance of metal framing anchors for application indicated with the building code in effect for this Project.
2. Allowable Design Loads: Provide products for which manufacturer publishes allowable design loads that are determined from empirical data or by rational engineering analysis and that are demonstrated by comprehensive testing performed by a qualified independent testing laboratory.
B. Galvanized Steel Sheet: Steel sheet zinc-coated by hot-dip process on continuous lines prior to fabrication to comply with ASTM A 525 for Coating Designation G60 and with ASTM A 446, Grade A (structural quality); ASTM A 526 (commercial quality); or ASTM A 527 (lock-forming quality); as standard with manufacturer for type of anchor indicated.
1. Use galvanized steel framing anchors for rough carpentry exposed to weather, in ground contact, or in area of high relative humidity, and where indicated.
2.10 MISCELLANEOUS MATERIALS
A. Water Repellent Preservative: NWWDA-tested and -accepted formulation containing
3-iodo-2-propynyl butyl carbonate (IPBC) as its active ingredient.
2.11 PRESERVATIVE WOOD TREATMENT BY PRESSURE PROCESS
A. General: Where lumber or plywood is indicated as preservative-treated wood or is specified herein to be treated, comply with applicable requirements of AWPA Standards C2 (Lumber) and C9 (Plywood). Mark each treated item with the AWPB Quality Mark Requirements.
B. Pressure-treat above-ground items with water-borne preservatives to a minimum retention of 0.25 pcf. For interior uses, after treatment, kiln-dry lumber and plywood to a maximum moisture content, respectively, of 19 percent and 15 percent. Treat indicated items and the following:
1. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.
2. Wood sills, sleepers, blocking, furring, stripping, and similar concealed members in contact with masonry or concrete.
C. Complete fabrication of treated items prior to treatment, where possible. If cut after treatment, coat cut surfaces to comply with AWPA M4. Inspect each piece of lumber or plywood after drying and discard damaged or defective pieces.
Rough Carpentry 06100-6
PART 3 - EXECUTION
3.01 INSTALLATION AND WORKMANSHIP, GENERAL
A. Members shall be accurately cut to required dimensions and shall be firmly secured with metal connectors true to the lines, levels, and dimensions indicated, all in accordance with the UBC.
B. Where there is a significant variation in moisture content between individual members, shrinkage shall be allowed for and final connections shall not be made until moisture content of adjacent members has been stabilized. Allow no construction over framing members until final connections and/or adjustments have been made to achieve maximum strength at connections and minimum future movement from shrinkage or expansion.
C. Discard units of material with defects that impair quality of rough carpentry construction and that are too small to use in fabricating rough carpentry with minimum joints or optimum joint arrangement.
D. Fit rough carpentry to other construction; scribe and cope as required for accurate fit.
Correlate location of furring, nailers, blocking, grounds, and similar supports to allow attachment of other construction.
E. Securely attach rough carpentry work to substrate by anchoring and fastening as indicated.
F. Bore bolt holes true to line and of 1/16 inch greater diameter than bolts. Drive bolts into place with a tight fit and provide with plates or washers as indicated on the Drawings.
Turn up and make tight all nuts, bolts, and lag screws at time of installation and again just before enclosed with other fixed materials, or at the completion of the work, to ensure that shrinkage has been overcome and the fastenings are tight.
G. No lubricant of any kind shall be used on any fastener depending on friction for holding.
H. Screws shall not be driven by hammering.
I. Countersink nail heads on exposed carpentry work and fill holes.
J. Use common wire nails, unless otherwise indicated. Use finishing nails for finish work.
Select fasteners of size that will not penetrate members where opposite side will be exposed to view or will receive finish materials. Make tight connections between members. Install fasteners without splitting of wood; predrill as required.
K. Members (other than all heart Redwood) which are in contact with concrete exposed to weather, shall be treated a distance of 2'-0" along their length from point of contact with
06100-7 Rough Carpentry two flowing coats of 5% Pentachlorophenol (or copper napthenate solution, if not to be stained).
L. Coordinate installation of open web trusses, glue laminated beams, plate connected wood trusses.
M. Tolerances:
1. Framing Members: 1/4 inch maximum from true position.
2. Surface Flatness of Floor: 1/4 inch in 10 feet maximum.
3.02 WOOD GROUNDS, NAILERS, BLOCKING, AND SLEEPERS
A. Provide and install wood grounds, nailers, blocking, and sleepers where shown and where required for screening or attachment of other work. Form to shapes as shown and cut as required for true line and level of work to be attached. Coordinate location with other work involved.
B. Attach to substrates as required to support applied loading. Countersink bolts and nuts flush with surfaces, unless otherwise indicated. Where possible, anchor to formwork before concrete placement.
3.03 WOOD FRAMING, GENERAL
A. Framing Standard: Comply with National Forest Products Association (N.F.P.A.)
"Manual for House Framing," unless otherwise indicated.
B. Install framing members of size and spacing indicated. Coordinate with other framing and to other trades prior to actual construction.
C. Anchor and nail as shown, and to comply with the following:
1. National Evaluation Report No. NER-272 for pneumatic or mechanical driven staples, P-Nails, and allied fasteners.
2. Published requirements of manufacturer of metal framing anchors.
3. "Recommended Nailing Schedule" of referenced framing standard and with
N.F.P.A. "National Design Specifications for Wood Construction."
D. Do not splice structural members between supports.
E. Provide solid blocking at all joist or truss supports (2x framing depth), unless otherwise noted. Install shims where indicated or where required to set work in proper alignment.
Rough Carpentry 06100-8
F. Install blocking where indicated on the Drawings, where required on gypsum board edges, at plywood panel joints where not over a framing member, and wherever required for support of items specified in other sections.
G. Cutting of wood girders, beams, or joists for electrical and mechanical lines shall be limited to cuts and bored holes not deeper than one-fifth of the beam depth from the top and located not further from the support than three times the beam depth and not less than the beam depth. Cuts in excess of this or single bored holes with diameter of more than 1 1/2 inch are not permitted without special provisions. Location of cuts or holes in framing shall receive review by the Contracting Officer prior to approval of holes.
H. Fire stop concealed spaces of wood framed walls and partitions at each floor level and at the ceiling line of the top story. Where fire stops are not automatically provided by the framing system used, use closely fitted wood blocks of nominal 2-inch-thick lumber of the same width as framing members.
3.04 STUD FRAMING
A. Cut studs and posts with square ends, unless otherwise shown, and erect plumb.
B. Studs in walls shall be 2X4, 2X6, or 3X6 as indicated on Drawings.
C. Double studs on each side of all openings, unless noted otherwise.
D. Construct corners and intersections with not less than 3 studs. Install miscellaneous blocking and framing as shown and as required for support of facing materials, fixtures, specialty items, and trim.
E. Openings in stud walls and partitions shall be framed with headers across the top with a minimum size of 6 inches deep x stud width resting on cripple studs, unless otherwise noted.
F. Top plates shall be as indicated, set one at a time; sill plates single, secured as indicated on drawings. Corners where stud wall or partitions meet shall be framed solid. Double top plates shall be lapped at corners. Where openings are cut through plates, install 16-gauge steel strap ties 1-1/4 inches wide at single plate, and 2-5/16 inches wide at double plate extending minimum 9 inches past each cut.
G. Walls and partitions containing plumbing, heating, or other pipes shall be framed to give proper clearances for piping without notching or hacking of studs.
H. Holes through studs exceeding 1/3 the width of the stud are not permitted without review by the Contracting Officer.
06100-9 Rough Carpentry
3.05 FLOOR JOIST FRAMING
A. N/A
3.06 TIMBER FRAMING
A. N/A
3.07 STAIR FRAMING
A. N/A
3.08 INSTALLATION OF CONSTRUCTION PANELS (PLYWOOD)
A. General: Comply with applicable recommendations contained in Form No. E30, "APA
Design/Construction Guide - Residential & Commercial”, for types of construction panels and applications indicated.
B. Layout and Fastening: Plywood shall be nailed to framing as indicated on the drawings.
Sheathing on walls, roofs, and floors shall be supported on framing or blocking on all four edges of each sheet. Joint layout shall be staggered. Butt panel ends and edges to a close, but not tight fit (allow 1/16-inch space). All panels as indicated on the drawings.
C. Wall sheathing shall be installed with face grain perpendicular to the studs. No piece shall be less than 2 feet by 4 feet.
D. Roof and floor sheathing shall be installed with face grain perpendicular to the framing members. No piece shall be smaller than 2 feet by 4 feet.
3.09 AIR INFILTRATION BARRIER
A. Cover sheathing with air infiltration barrier as follows:
1. Tyvek Housewrap or approved equal.
PART 4 – MEASUREMENT AND PAYMENT
Payment for this item shall be included in the Modular Building pay item.
**END OF SECTION 06100**
08111-1 Standard Steel Doors and Frames
SECTION 08111
STANDARD STEEL DOORS AND FRAMES
1.01 SCOPE
A. This Section includes the following products manufactured in accordance with SDI
Recommended Standards:
1. Doors: Seamless, hollow or composite construction standard steel doors for exterior locations.
2. Frames: Pressed steel frames for doors, transoms, sidelights, mullions, interior glazed panels, and other interior and exterior openings of following type:
a. One piece welded type
3. Assemblies: Provide standard steel door and frame assemblies as required for the following:
a. Labeled and fire rated.
b. Thermal rated (insulated).
4. Provide factory primed doors and frames to be field painted.
B. Painting primed doors and frames is specified in Section 13122.
C. Door hardware is specified in Section 08710.
D. Glass and Glazing are specified in Section 08800.
1.02 SUBMITTALS
A. General: Submit the following in accordance with Conditions of Contract and Division 1
Specification Sections.
B. Product data for each type of door and frame specified, including details of construction, materials, dimensions, hardware preparation, core, label compliance, profiles, and finishes.
C. Shop drawings showing fabrication and installation of standard steel doors and frames.
Include details of each frame type, elevations of door design types, conditions at openings, details of construction, location and installation requirements of door and frame hardware and reinforcements, and details of joints and connections. Show anchorage and accessory items.
Standard Steel Doors and Frames 08111-2
1. Provide schedule of doors and frames using same reference numbers for details and openings as those on contract drawings.
2. Indicate coordinate of glazing frames and stops with glass and glazing requirements.
D. Label Construction Certification: For door assemblies required to be fire rated and exceeding limitations of labeled assemblies; submit manufacturer's certification that each door and frame assembly has been constructed to conform to design materials and construction equivalent to requirements for labeled construction.
1.03 QUALITY ASSURANCE
A. Provide doors and frames complying with Steel Door Institute "Recommended
Specifications Standard Steel Doors and Frames" ANSI/SDI-100 and as herein specified.
B. Fire-Rated Door Assemblies: Units that comply with NFPA 80, are identical to door and frame assemblies whose fire resistance characteristics have been determined per ASTM E 152 and which are labeled and listed by UL, Factory Mutual, Warnock Hersey, or other testing and inspecting organization acceptable to authorities having jurisdiction.
1.04 DELIVERY, STORAGE, AND HANDLING
A. Deliver doors and frames cardboard-wrapped or crated to provide protection during transit and job storage. Provide additional protection to prevent damage to finish of factory-finished doors and frames.
B. Inspect doors and frames upon delivery for damage. Minor damages may be repaired provided refinished items are equal in all respects to new work and acceptable to Contracting Officer; otherwise, remove and replace damaged items as directed.
C. Store doors and frames at building site under cover. Place units on minimum 4-inches high wood blocking. Avoid use of non-vented plastic or canvas shelters which could create humidity chamber. If cardboard wrapper on door becomes wet, remove carton immediately. Provide 1/4-inches spaces between stacked doors to promote air circulation.
2.01 ACCEPTABLE MANUFACTURERS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering standard steel doors and frames which may be incorporated in the work include;
but are not limited to, the following:
08111-3 Standard Steel Doors and Frames
1. Standard Steel Doors and Frames:
a. Ceco Corp.
b. Fenestra Corp.
c. Steelcraft Manufacturing Co., or approved equal.
2.02 MATERIALS
A. Hot-Rolled Steel Sheets and Strip: Commercial quality carbon steel, pickled and oiled, complying with ASTM A 569 and ASTM A 568.
B. Cold-Rolled Steel Sheets: Commercial quality carbon steel, complying with ASTM A
366 and ASTM A 568.
C. Galvanized Steel Sheets: Zinc-coated carbon steel sheets of commercial quality, complying with ASTM A 526, or drawing quality, ASTM A 642, hot dipped galvanized in accordance with ASTM A 525, with A60 or G60 coating designation, mill phosphatized.
D. Supports and Anchors: Fabricate of not less than 18-gage sheet steel; galvanized where used with galvanized frames.
E. Inserts, Bolts, and Fasteners: Manufacturer's standard units. Where items are to be built into exterior walls, hot-dip galvanize in compliance with ASTM A 153, Class C or D as applicable.
F. Shop Applied Paint: Apply after fabrication.
1. Primer: Rust-inhibitive enamel or paint, either air-drying or baking, suitable as a base for specified finish paints complying with ANSI A224.1, "Test Procedure and Acceptance Criteria for Prime Painted Steel Surfaces for Steel Doors and Frames."
2.03 DOORS
A. Provide metal doors of SDI grades and models specified below or as indicated on drawings or schedules:
1. Exterior Doors: ANSI/SDI-100, Grade III, extra heavy-duty, Model 2 + 2A, minimum 16-gage galvanized steel faces.
B. Door Louvers: Provide sightproof stationary louvers for interior doors where indicated, constructed of inverted V-shaped or Y-shaped blades formed of 24-gage cold-rolled steel set into minimum 20-gage steel frame.
Standard Steel Doors and Frames 08111-4
2.04 FRAMES
A. Provide metal frames for doors, transoms, sidelights, borrowed lights, and other openings, of types and styles as specified herein or shown on drawings and schedules.
Conceal fastenings, unless otherwise indicated. Fabricate one piece welded interior frames of minimum 18-gage cold-rolled steel and exterior frames with 16 gauge galvanized steel.
B. Door Silencers: Except on weatherstripped frames, drill stops to receive 3 silencers on strike jambs of single-door frames and 2 silencers on heads of double-door frames.
2.05 FABRICATION
A. Fabricate steel door and frame units to be rigid, neat in appearance and free from defects, warp or buckle. Wherever practicable, fit and assemble units in manufacturer's plant. Clearly identify work that cannot be permanently factory-assembled before shipment, to assure proper assembly at project site. Comply with ANSI/SDI-100 requirements.
1. Internal Construction: Manufacturer's standard honeycomb, polyurethane, polystyrene, unitized steel grid, vertical steel stiffeners, or rigid mineral fiber core with internal sound deadener on inside of face sheets where appropriate in accordance with SDI standards.
2. Clearances: Not more than 1/8 inch at jambs and heads except between non-fire-rated pairs of doors not more than 1/4 inch. Not more than 3/4 inch at bottom.
B. Fabricate exposed faces of doors and panels, including stiles and rails of nonflush units, from only cold-rolled steel.
C. Tolerances: Comply with SDI 117 "Manufacturing Tolerances Standard Steel Doors and
Frames."
D. Fabricate frames, concealed stiffeners, reinforcement, edge channels, louvers and moldings from either cold-rolled or hot-rolled steel.
E. Fabricate exterior doors, panels, and frames from galvanized sheet steel in accordance with SDI-112. Close top and bottom edges of exterior doors as integral part of door construction or by addition of minimum 16-gage inverted steel channels.
F. Exposed Fasteners: Unless otherwise indicated, provide countersunk flat or oval heads for exposed screws and bolts.
08111-5 Standard Steel Doors and Frames
G. Thermal-Rated (Insulating) Assemblies: At exterior locations and elsewhere as shown or scheduled, provide doors fabricated as thermal insulating door and frame assemblies and tested in accordance with ASTM C 236 or ASTM C 976 on fully operable door assemblies.
1. Unless otherwise indicated, provide thermal-rated assemblies with U factor of
0.41 Btu/(hr x sq ft x deg F.) or better.
H. Hardware Preparation: Prepare doors and frames to receive mortised and concealed hardware in accordance with final Door Hardware Schedule and templates provided by hardware supplier. Comply with applicable requirements of ANSI A115 Series Specifications for door and frame preparation for hardware.
I. Reinforce doors and frames to receive surface-applied hardware. Drilling and tapping for surface-applied hardware may be done at project site.
J. Locate hardware as indicated on final shop drawings or, if not indicated, in accordance with "Recommended Locations for Builder's Hardware on Standard Steel Doors and Frames," published by Door and Hardware Institute.
K. Shop Painting: Clean, treat, and paint exposed surfaces of steel door and frame units, including galvanized surfaces.
1. Clean steel surfaces of mill scale, rust, oil, grease, dirt, and other foreign materials before application of paint.
2. Apply shop coat of prime paint of even consistency to provide a uniformly finished surface ready to receive finish paint.
L. Glazing Stops: Minimum 20 gage steel or .040-inch-thick aluminum.
1. Provide non-removable stops on outside of exterior doors and on secure side of interior doors for glass, louvers, and other panels in doors.
2. Provide screw applied removable glazing beads on inside of glass, louvers, and other panels in doors.
PART 3 - EXECUTION
3.01 INSTALLATION
A. General: Install standard steel doors, frames, and accessories in accordance with final shop drawings, manufacturer's data, and as herein specified.
Standard Steel Doors and Frames 08111-6
B. Placing Frames: Comply with provisions of SDI-105 "Recommended Erection Instructions For Steel Frames," unless otherwise indicated.
1. Set frames accurately in position, plumbed, aligned, and braced securely until permanent anchors are set. After wall construction is completed, remove temporary braces and spreaders leaving surfaces smooth and undamaged.
2. Install Fire-rated frames in accordance with NFPA Standard No. 80.
3. In all walls and partitions, install one piece welded frames suitable for specified exterior and interior finishes.
C. Door Installation: Fit hollow metal doors accurately in frames, within clearances specified in ANSI/SDI-100.
1. Install fire-rated doors in accordance with NFPA Standard No. 80.
3.02 ADJUST AND CLEAN
A. Prime Coat Touch-up: Immediately after erection, sand smooth any rusted or damaged areas of prime coat and apply touch-up of compatible air-drying primer.
B. Protection Removal: Immediately prior to final inspection, remove protective plastic wrappings from prefinished doors.
C. Final Adjustments: Check and readjust operating hardware items, leaving steel doors and frames undamaged and in complete and proper operating condition.
**END OF SECTION 08111**
08211-1 Flush Wood Doors
SECTION 08211
FLUSH WOOD DOORS
1.01 SECTION REQUIREMENTS
A. Submit samples for factory-finished doors.
B. Quality Standard: NWWDA I.S.1-A.
C. Fire-Rated Wood Doors: Labeled by a testing and inspecting agency acceptable to authorities having jurisdiction based on testing per ASTM E 152.
2.01 FLUSH WOOD DOORS
A. Interior Solid Core Doors for Transparent Finish: Economy Grade, 5-ply, particleboard core.
1. Faces: Red oak, plain sliced.
B. Fire-Rated Solid Core Doors: Core construction to provide fire-rating indicated, faces and grade to match non-fire-rated doors.
1. Composite blocking where required to eliminate through-bolting hardware.
2. Laminated-edge construction.
3. Formed-steel edges and astragals for pairs of fire-rated doors.
2.02 VENEER MATCHING
A. Doors with veneers: book and running matched.
B. Pair matching and set matching.
C. Continuous matching for doors with transoms.
Flush Wood Doors 08211-2
2.03 FABRICATION AND FINISHING
A. Factory fit doors to suit frame-opening sizes indicated and to comply with referenced quality standard.
1. Comply with NFPA 80 for fire-resistance-rated doors.
B. Factory machine doors for hardware that is not surface applied.
C. Cut and trim openings to comply with referenced standards.
1. Trim light openings with moldings indicated.
2. Factory install louvers in prepared openings.
D. Factory finish wood doors with NWWDA Standard grade, System 5, clear semi-gloss polyurethane finish.
3.1 INSTALLATION
A. Install doors to comply with referenced quality standard.
1. Install fire-rated doors to comply with NFPA 80.
B. Align and fit doors in frames with uniform clearances and bevels. Machine doors for hardware. Seal cut surfaces after fitting and machining.
C. Align factory-fitted doors in frames for uniform clearances.
D. Repair, refinish, or replace factory-finished doors damaged during installation, as directed by Architect.
**END OF SECTION 08211**
08561-1 Vinyl Windows
SECTION 08561
VINYL WINDOWS
1.01 DESCRIPTIONS
A. Provide polyvinyl chloride (PVC) windows with integral flashing, and glazing specified in Section 08800, and accessories as required for complete, weathertight installation.
B. Special Coordination: Coordinate installation to ensure watertight installation of flanged type windows and door.
1.02 SECTION REQUIREMENTS
A. Submittals: Submit Product Data, Shop Drawings, and Samples.
2.01 VINYL WINDOWS
A. Milgard StyleLine Series Windows.
B. Provide vinyl windows that comply with AAMA/NWWDA 101/I.S.2.
1. Comply with California Building Code, 1998 Edition and AAMA 101 for each type of window and door indicated.
2. Provide AAMA-certified vinyl windows with an attached label.
3. Provide units labeled and certified according to NFRC's Product Certification Program, with low-e and U-value of 0.34 – 0.35 Btu/sq. ft. as determined according to NFRC 100.
4. Equip units with vinyl-coated glass-fiber mesh insect screens at operable sashes.
5. Window Color: White.
C. Insulated Glass: Refer to SECTION 08800 Glazing.
Vinyl Windows 08561-2
3.01 INSTALLATION
A. Set units level, plumb, and true to line, without warp or rack of frames and panels and anchor securely in place.
B. Set sill members in bed of sealant or with gaskets, as indicated, to provide weathertight construction.
C. Adjust operating panels, screens, and hardware for smooth operation and weathertight closure. Lubricate hardware and moving parts.
3.02 FIELD QUALITY CONTROL
A. On-Site Tests: Conduct tests for air and water infiltration with window manufacturer’s representative present; correct units failing tests.
1. Test: Conduct in accordance with AAMA 502.
2. Air Infiltration: Maximum infiltration of 1.5 times amount specified.
3. Water Penetration: Conduct a t static pressure of 3.00 psf (min.).
**END OF SECTION 08561**
08710-1 Door Hardware
SECTION 08710
DOOR HARDWARE
1.01 RELATED DOCUMENTS
A. Drawings and general provisions of Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.02 SUMMARY
A. This Section includes items known commercially as finish or door hardware that are required for swing, sliding, and folding doors, except special types of unique hardware specified in the same sections as the doors and door frames on which they are installed.
B. This Section includes the following:
1. Hinges.
2. Lock and latch sets.
3. Bolts.
4. Closers.
5. Overhead holders.
6. Miscellaneous door control devices.
7. Door trim units.
8. Protection plates.
9. Weatherstripping for exterior doors.
10. Astragals or meeting seals on pairs of doors.
11. Thresholds.
C. Related Sections: The following Sections contain requirements that relate to this Section:
1. Division 8 Section "Standard Steel Doors and Frames" for silencers integral with hollow metal frames.
D. Products furnished but not installed under this Section include:
1. Cylinders for locks on entrance doors.
2. Final replacement cores and keys to be installed by Government.
Door Hardware 08710-2
E. Selection and Ordering: Furnish door hardware as selected by Contracting Officer and in such quantities as provided for under Division 1 Section "Allowances" and other general provisions of the Contract.
F. Door hardware supplier's responsibilities shall be as follows:
1. Submittals: Submit through Contractor required product data, final hardware schedule, separate keying schedule, and samples as specified in this Section, unless otherwise indicated.
2. Construction Schedule: Inform Contractor promptly of estimated times and dates that will be required to process submittals, to furnish templates, to deliver hardware, and to perform other work associated with furnishing door hardware for purposes of including this data in construction schedule. Comply with this schedule.
3. Coordination and Templates: Assist Contractor as required to coordinate hardware with other work in respect to both fabrication and installation. Furnish Contractor with templates and deliver hardware to proper locations.
4. Product Handling: Package, identify, deliver, and inventory door hardware specified in this Section.
5. Discrepancies: Based on requirements indicated in Contract Documents in effect at time of door hardware selection, furnish types, finishes, and quantities of door hardware, including fasteners, and Government's maintenance tools required to comply with specified requirements and as needed to install and maintain hardware. Furnish or replace any items of door hardware resulting from shortages and incorrect items at no cost to the Government or Contractor. Obtain signed receipts from Contractor for all delivered materials.
G. Contractor's responsibilities shall be as follows:
1. Submittals: Coordinate and process submittals for door hardware in same manner as submittals for other work.
2. Construction Schedule: Cooperate with door hardware supplier in establishing scheduled dates for submittals and delivery of templates and door hardware.
Incorporate in construction schedule the times and dates related to furnishing hardware by door hardware supplier.
3. Coordination: Coordinate door hardware with other Work. Furnish hardware supplier or manufacturer with shop drawings of other work where required or requested. Verify completeness and suitability of hardware with supplier.
4. Product Handling: Provide secure lock-up for hardware delivered to the site.
Inventory hardware jointly with representative of hardware supplier and issue signed receipts for all delivered materials.
5. Installation Information: The general types and approximate quantities of hardware required for this Project are indicated at the end of this Section in order to establish Contractor's costs for installation and other work not included in allowance.
08710-3 Door Hardware
1.03 SUBMITTALS
A. General: Submit the following in accordance with Conditions of Contract and Division 1
Specification sections.
B. Product data including manufacturers' technical product data for each item of door hardware, installation instructions, maintenance of operating parts and finish, and other information necessary to show compliance with requirements.
C. Final hardware schedule coordinated with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware.
1. Final Hardware Schedule Content: Based on hardware indicated, organize schedule into "hardware sets" indicating complete designations of every item required for each door or opening. Include the following information:
a. Type, style, function, size, and finish of each hardware item.
b. Name and manufacturer of each item.
c. Fastenings and other pertinent information.
d. Location of each hardware set cross referenced to indications on Drawings both on floor plans and in door and frame schedule.
e. Explanation of all abbreviations, symbols, and codes contained in schedule.
f. Mounting locations for hardware.
g. Door and frame sizes and materials.
h. Keying information.
2. Submittal Sequence: Submit final schedule at earliest possible date particularly where acceptance of hardware schedule must precede fabrication of other work that is critical in the Project construction schedule. Include with schedule the product data, samples, shop drawings of other work affected by door hardware, and other information essential to the coordinated review of schedule.
3. Keying Schedule: Submit separate detailed schedule indicating clearly how the Government's final instructions on keying of locks has been fulfilled.
D. Templates for doors, frames, and other work specified to be factory prepared for the installation of door hardware. Check shop drawings of other work to confirm that adequate provisions are made for locating and installing door hardware to comply with indicated requirements.
Door Hardware 08710-4
1.04 QUALITY ASSURANCE
A. Single Source Responsibility: Obtain each type of hardware (latch and lock sets, hinges, closers, etc.) from a single manufacturer.
B. Supplier Qualifications: A recognized architectural door hardware supplier, with warehousing facilities in the Project's vicinity, that has a record of successful in-service performance for supplying door hardware similar in quantity, type, and quality to that indicated for this Project and that employs an experienced architectural hardware consultant (AHC) who is available to Contracting Officer and Contractor, at reasonable times during the course of the Work, for consultation.
1. Require supplier to meet with Contracting Officer to finalize keying requirements and to obtain final instructions in writing.
C. Fire-Rated Openings: Provide door hardware for fire-rated openings that complies with
NFPA Standard No. 80 and requirements of authorities having jurisdiction. Provide only items of door hardware that are listed and are identical to products tested by UL, Warnock Hersey, FM, or other testing and inspecting organization acceptable to authorities having jurisdiction for use on types and sizes of doors indicated in compliance with requirements of fire-rated door and door frame labels.
1.05 PRODUCT HANDLING
A. Tag each item or package separately with identification related to final hardware schedule, and include basic installation instructions with each item or package.
B. Packaging of door hardware is responsibility of supplier. As material is received by hardware supplier from various manufacturers, sort and repackage in containers clearly marked with appropriate hardware set number to match set numbers of approved hardware schedule. Two or more identical sets may be packed in same container.
C. Inventory door hardware jointly with representatives of hardware supplier and hardware installer until each is satisfied that count is correct.
D. Deliver individually packaged door hardware items promptly to place of installation
(shop or Project site).
E. Provide secure lock-up for door hardware delivered to the Project, but not yet installed.
Control handling and installation of hardware items that are not immediately replaceable so that completion of the Work will not be delayed by hardware losses both before and after installation.
1.06 MAINTENANCE
A. Maintenance Tools and Instructions: Furnish a complete set of specialized tools and maintenance instructions as needed for Government's continued adjustment, maintenance, and removal and replacement of door hardware.
08710-5 Door Hardware
2.01 MANUFACTURERS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following:
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following or approved equal:
1. Butts and Hinges:
a. Hager Hinge Co.
b. Stanley Hardware, Div. Stanley Works.
2. Cylinders and Locks:
a. Schlage Lock, Div. Ingersoll-Rand Door Hardware Group.
3. Bolts:
b. Stanley Hardware, Div. Stanley Works.
4. Push/Pull Units:
b. Triangle Brass Manufacturing Company (Trimco).
5. Overhead Closers:
a. Dorma Door Controls International.
b. Sargent Manufacturing Company.
c. Yale Security Inc.
d. Glynn-Johnson
6. Door Control Devices:
c. Glynn-Johnson
7. Door Trim Units:
8. Kick Plates:
9. Door Stripping and Seals:
b. Reese Enterprises, Inc.
c. Pemko
Door Hardware 08710-6
10. Thresholds:
a. Hager Hinge Co.
b. Reese Enterprises, Inc.
c. Pemko
2.02 SCHEDULED HARDWARE
A. Requirements for design, grade, function, finish, size, and other distinctive qualities of each type of finish hardware are indicated in the "Hardware Schedule" at the end of this Section. Products are identified by using hardware designation numbers of the following:
1. Manufacturer's Product Designations: The product designation and name of one manufacturer are listed for each hardware type required for the purpose of establishing minimum requirements. Provide either the product designated or, where more than one manufacturer is specified under the Article "Manufacturers" in Part 2 for each hardware type, the comparable product of one of the other manufacturers that complies with requirements.
2. ANSI/BHMA designations used elsewhere in this Section or in schedules to describe hardware items or to define quality or function are derived from the following standards. Provide products complying with these standards and requirements specified elsewhere in this Section.
a. Butts and Hinges: ANSI/BHMA A156.1.
b. Door Controls - Closers: ANSI/BHMA A156.4.
c. Architectural Door Trim: ANSI/BHMA A156.6.
d. Template Hinge Dimensions: ANSI/BHMA A156.7.
e. Door Controls - Overhead Holders: ANSI/BHMA A156.8.
f. Mortise Locks and Latches: ANSI/BHMA A156.13.
g. Materials and Finishes: ANSI/BHMA A156.18.
2.03 MATERIALS AND FABRICATION
A. Manufacturer's Name Plate: Do not use manufacturers' products that have manufacturer's name or trade name displayed in a visible location (omit removable nameplates) except in conjunction with required fire-rated labels and as otherwise acceptable to Contracting Officer.
1. Manufacturer's identification will be permitted on rim of lock cylinders only.
B. Base Metals: Produce hardware units of basic metal and forming method indicated, using manufacturer's standard metal alloy, composition, temper, and hardness, but in no case of lesser (commercially recognized) quality than specified for applicable hardware units by applicable ANSI/BHMA A156 series standards for each type of hardware item and with ANSI/BHMA A156.18 for finish designations indicated. Do not furnish "optional" materials or forming methods for those indicated, except as otherwise specified.
08710-7 Door Hardware
C. Fasteners: Provide hardware manufactured to conform to published templates, generally prepared for machine screw installation. Do not provide hardware that has been prepared for self-tapping sheet metal screws, except as specifically indicated.
D. Furnish screws for installation with each hardware item. Provide Phillips flat-head screws except as otherwise indicated. Finish exposed (exposed under any condition) screws to match hardware finish or, if exposed in surfaces of other work, to match finish of this other work as closely as possible including "prepared for paint" surfaces to receive painted finish.
E. Provide concealed fasteners for hardware units that are exposed when door is closed except to the extent no standard units of type specified are available with concealed fasteners. Do not use thru-bolts for installation where bolt head or nut on opposite face is exposed in other work unless their use is the only means of reinforcing the work adequately to fasten the hardware securely. Where thru-bolts are used as a means of reinforcing the work, provide sleeves for each thru-bolt or use sex screw fasteners.
2.04 HINGES, BUTTS, AND PIVOTS
A. Templates: Provide only template-produced units.
B. Screws: Provide Phillips flat-head screws complying with the following requirements:
1. For metal doors and frames install machine screws into drilled and tapped holes.
2. For fire-rated wood doors install #12 x 1-1/4-inch, threaded-to-the-head steel wood screws.
3. Finish screw heads to match surface of hinges or pivots.
C. Hinge Pins: Except as otherwise indicated, provide hinge pins as follows:
1. Out-Swing Exterior Doors: Non-removable pins.
2. Out-Swing Corridor Doors with Locks: Nonremovable pins.
3. Interior Doors: Nonrising pins.
4. Tips: Flat button and matching plug, finished to match leaves, except where hospital tip (HT) indicated.
D. Number of Hinges: Provide number of hinges indicated but not less than 3 hinges per door leaf for doors 90 inches or less in height and one additional hinge for each 30 inches of additional height.
1. Fire-Rated Doors: Not less than 3 hinges per door leaf for doors 86 inches or less in height with same rule for additional hinges.
Door Hardware 08710-8
2.05 LOCK CYLINDERS AND KEYING
A. Review the keying system with the Contracting Officer and provide the type required.
B. Equip locks with manufacturer's special 6-pin tumbler cylinder with construction masterkey feature that permits voiding of construction keys without cylinder removal.
C. Metals: Construct lock cylinder parts from brass or bronze, stainless steel, or nickel silver.
D. Comply with Contracting Officer's instructions for masterkeying and, except as otherwise indicated, provide individual change key for each lock that is not designated to be keyed alike with a group of related locks.
1. Permanently inscribe each key with number of lock that identifies cylinder manufacturer's key symbol, and notation, G. Key Material: Provide keys of nickel silver only.
E. Key Quantity: Furnish 3 change keys for each lock, 5 master keys for each master system.
1. Furnish one extra blank for each lock.
2. Deliver keys to Contracting Officer.
2.06 LOCKS, LATCHES, AND BOLTS
A. Strikes: Provide manufacturer's standard wrought box strike for each latch or lock bolt, with curved lip extended to protect frame, finished to match hardware set, unless
1. Provide flat lip strikes for locks with 3-piece, antifriction latchbolts as recommended by manufacturer.
2. Provide recess type top strikes for bolts locking into head frames, unless
3. Provide dust-proof strikes for foot bolts, except where special threshold construction provides nonrecessed strike for bolt.
4. Provide roller type strikes where recommended by manufacturer of the latch and lock units.
B. Lock Throw: Provide 5/8-inch minimum throw of latch on pairs of doors. Comply with
UL requirements for throw of bolts and latch bolts on rated fire openings.
1. Provide 1/2-inch minimum throw of latch for other bored and preassembled types of locks and 3/4-inch minimum throw of latch for mortise locks. Provide 1-inch minimum throw for all dead bolts.
08710-9 Door Hardware
C. Flush Bolt Heads: Minimum of 1/2-inch-diameter rods of brass, bronze, or stainless steel with minimum 12-inch-long rod for doors up to 7'-0" in height. Provide longer rods as necessary for doors exceeding 7'-0" in height.
2.07 CLOSERS AND DOOR CONTROL DEVICES
A. Size of Units: Except as otherwise specifically indicated, comply with the manufacturer's recommendations for size of door control unit depending on size of door, exposure to weather, and anticipated frequency of use.
1. Where parallel arms are indicated for closers, provide closer unit one size larger than recommended for use with standard arms.
B. Access-Free Manual Closers: Where manual closers are indicated provide adjustable units complying with ANSI A117.1 provisions for door opening force and delayed action closing.
C. Provide grey resilient parts for exposed bumpers.
2.08 DOOR TRIM UNITS
A. Fasteners: Provide manufacturer's standard exposed fasteners for door trim units consisting of either machine screws or self-tapping screws.
B. Fabricate edge trim of stainless steel to fit door thickness in standard lengths or to match height of protection plates.
C. Fabricate protection plates not more than 1-1/2 inches less than door width on hinge side and not more than 1/2 inch less than door width on pull side by height indicated.
1. Metal Plates: Stainless steel, 0.050 inch (U.S. 18 gage).
2. Plastic Plates: Clear acrylic plastic, 1/8 inch thick.
2.09 WEATHERSTRIPPING AND SEALS
A. General: Provide continuous weatherstripping on exterior doors and smoke,…