ACP Bid Set Drawings.pdf

PDF 2 MB Posted

Attached to
Constructio Camp Dawson Access Control Point (ACP) Renovatio
Solicitation number
CRFQ 0603 ADJ2700000011 3
Issued by
Kanawha County, West Virginia

About this file

This file comprises construction bid set drawings for renovations to the Camp Dawson Access Control Point (ACP) facility located in Kingwood, West Virginia, prepared for the West Virginia Army National Guard. The project documents include a site plan, site details, and electrical site power and lighting plans created by ZMM, LLC, dated August 6, 2026. The scope of work encompasses replacement of in-ground traffic spikes across a 12-foot width, installation of a new 10-foot arm gate, placement of 8-inch bollards in concrete strips, installation of concrete speed bumps, grading and drainage improvements with PVC storm piping, site lighting system upgrades, traffic signal relocation and replacement, and associated site infrastructure modifications. The project involves coordination with existing utilities including 30-inch and 18-inch HDPE drainage pipes, electrical systems including a 208Y/120V panel, and mechanical equipment such as an existing UPS system and motorized stop arm gate.

The construction documents specify replacement of a 3-phase, 30 kilowatt-hour UPS system with a new unit providing 15 minutes of battery time, replacement of existing 12-volt canopy lighting with new 120-volt fixtures controlled by a photocell, and installation of new red-green traffic signal lights to replace existing red-yellow-green signals. Detailed specifications address concrete work standards including SDR 35 PVC piping, grading slopes, erosion control, and backfill compaction requirements to 98 percent standard Proctor maximum dry density. The contractor is responsible for locating underground utilities prior to excavation, coordinating with Miss Utility of West Virginia at least two working days before digging, and restoring all disturbed areas including lawn seeding, pavement repair, and removal of debris to original conditions unless otherwise noted.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

c by ZMM, INC.

S I T E L O C A T I O N M A P

A R C H I T E C T A N D E N G I N E E R

O W N E R

B U I L D I N G I N F O R M A T I O ND R A W I N G I N D E X

U S E A N D O C C U P A N C Y C L A S S I F I C A T I O N

C O N S T R U C T I O N C L A S S I F I C A T I O N

B U I L D I N G A R E A

SHEET NO. SHEET NAME SHEET NO. SHEET NAMESHEET NO. SHEET NAMESHEET NO. SHEET NAME

PROFESSIONAL SEALS

222 Lee Street, West Charleston, West Virginia 25302

Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

ARCHITECTS

ENGINEERS

8/ 6/

:3

9:

P M

C :\U se rs

\n hs

\D oc um en ts \2

_C am p D aw so n

AC

P_ A_

_n hs zm m

.c om

.rv t

08.06.2026

Renovations to the

CAMP DAWSON - ACCESS CONTROL POINT

Kingwood, West Virginia West Virginia Army National Guard

CO

NS

TR

UC

TIO

N D

OC

UM

EN

TS

GENERAL

G000 COVER SHEET

CIVIL

C200 SITE PLAN

C220 SITE DETAILS

ELECTRICAL

E141 SITE POWER AND LIGHTING PLAN

E141D SITE DEMOLITION PLAN

Kingwood, West Virginia

PROJECT SITE

© 2026 Microsoft Corporation © 2026 Maxar ©CNES (2026) Distribution Airbus DS © 2026 TMAP MOBILITY Earthstar Geographics SIO

4" PVC

4" PVC

4" P

VC

2 TYP.

5' -0

TY

P.

7 TYP.

7 TYP.

5'-0"

TYP.

5'-0"TYP.

4" P

VC

08.06.2026

2025103

BSM BSM

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

CHECKED

DATE

COMM. NO.

DRAWN

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

A

TE

c by ZMM, LLC.

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

C A

M P

D A

W

SO

N

A C

C

ES

S C

O N

TR

O

L

PO

IN

T

R en ov at io ns to th e

Ki ng w oo d, W es t V irg in ia W es t V irg in ia A rm y

N at io na l G ua rd

SCALE: 1" = 10'

0 20

FEET

5 1010

SITE PLAN

C200

KEY NOTES

1 REPLACE IN-GROUND TRAFFIC SPIKES, 12'-0" WIDTH - SEE DETAIL 1 SHT. C220

3 REPLACE ARM GATE, 10'-0" LENGTH - SEE SPECIFICATIONS

8" BOLLARD IN CONCRETE STRIP - SEE DETAIL 2 SHT. C220

4 CONCRETE SPEED BUMPS, COORDINATE LOCATION WITH OWNER - SEE DETAIL 3 SHT. C220

5 LOCATE FIRST BOLLARD AS CLOSE TO EXISTING BOLLARD AS FOUNDATION WILL ALLOW,

5'-0" C-C PREFERRED.

6 COORDINATE LOCATION OF OUTER BOLLARD WITH OWNER AND EXISTING SLOPE.

BOLLARD MAY NOT BE NEEDED BASED ON SLOPE OF EXISTING GROUND IN THAT AREA.

7 REMOVE EXISTING CONCRETE PLANTERS AND REPLACE WITH 6" BOLLARD IN CONCRETE

STRIP. BACKFILL VOID FROM PLANTER BASE AS NEEDED WITH CLASS 1 STONE.

COORDINATE LOCATION AND SPACING OF BOLLARDS WITH OWNER. SEE DETAIL 2 SHT.

C220.

GRADING AND DRAINAGE NOTES

1. GRADE SLOPES BETWEEN SPOT ELEVATIONS PROVIDING A CONTINUOUS SMOOTH SURFACE

WITHOUT SHARP TRANSITIONS. AVOID ABRUPT CHANGES IN GRADE. ROUND SURFACES

PROVIDING SMOOTH TRANSITIONS.

2. BRANCH CONNECTIONS SHALL BE MADE FROM "WYE" FITTINGS.

3. MAXIMUM BENDS FOR STORM LINES SHALL BE 45°

4. PVC STORM PIPES SHALL BE SDR 35 PVC.

5. PIPE SLOPE SHALL BE 1% MINIMUM.

6. NOTIFY ARCHITECT/ENGINEER IF ANY CONFLICTS ARE ENCOUNTERED WITH EXISTING UTILITIES.

7. CONNECT NEW PIPES TO EXISTING STRUCTURES PER SPECIFICATIONS.

8. PROVIDE EROSION CONTROL FIBER MESH FOR DISTURBED AND SEEDED LAWN AREAS.

9. THE CONTRACTOR SHALL SPREAD AND FINE GRADE TOPSOIL AND APPLY PERMANENT SEEDING

TO ALL DISTURBED UNPAVED AND UNMULCHED AREAS. SEE SPECIFICATIONS.

GENERAL NOTES

1. FEATURES SHOWN HAVE BEEN DRAWN FROM RECORD DRAWINGS AND BING MAPPING (C) 2026

MICROSOFT CORPORATION. NO GUARANTEE THAT THE UTILITIES SHOWN COMPRISE ALL SUCH

UTILITIES IN THE AREA, EITHER IN SERVICE OR ABANDONED. THE DRAWINGS FURTHER DO NOT WARRANT THAT THE UTILITIES SHOWN ARE IN THE EXACT LOCATION INDICATED. PRIOR TO ANY

EXCAVATION IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PHYSICALLY LOCATE THE

UNDERGROUND UTILITIES.

2. CONTRACTOR IS RESPONSIBLE FOR LOCATION AND COORDINATION WITH BELOW AND ABOVE

GROUND UTILITIES.

3. CALL MISS UTILITY OF WEST VIRGINIA TWO WORKING DAYS BEFORE DIGGING AT 1-800-245-4848.

4. LAWN AREAS DISTURBED DURING CONSTRUCTION SHALL BE REGRADED, SEEDED, AND

MULCHED TO ORIGINAL CONDITIONS, UNLESS OTHERWISE NOTED. REPAIR RUTS, ETC.

5. ADJACENT BUILDINGS, FENCES, SIDEWALKS, PAVEMENT, AND OTHER SITE FEATURES

DISTURBED DURING CONSTRUCTION SHALL BE CLEANED OR REPAIRED TO ORIGINAL

CONDITION, UNLESS OTHERWISE NOTED.

6. EXISTING ABOVE GROUND AND UNDERGROUND UTILITIES TO REMAIN SHALL BE PROTECTED AT

ALL TIMES UNLESS OTHERWISE NOTED.

7. VOIDS LEFT BY DEMOLITION ACTIVITIES SHALL BE BACKFILLED WITH SOIL, COMPACTED, AND

SEEDED.

INSET 'A' SCALE: 1" = 10'-0"

SEE INSET 'A'

AutoCAD SHX Text

30" HDPE

AutoCAD SHX Text

EXISTING INLET

AutoCAD SHX Text

18" HDPE

AutoCAD SHX Text

30" HDPE

AutoCAD SHX Text

30" HDPE

AutoCAD SHX Text

12" HDPE

AutoCAD SHX Text

18" HDPE

AutoCAD SHX Text

18" HDPE

AutoCAD SHX Text

18" HDPE

AutoCAD SHX Text

12" HDPE

AutoCAD SHX Text

12" HDPE

AutoCAD SHX Text

30" HDPE

AutoCAD SHX Text

12" PVC

AutoCAD SHX Text

24" HDPE

AutoCAD SHX Text

EXISTING INLET

AutoCAD SHX Text M:\WVARNG - Camp Dawson ACP Improvements 25103\_Site\DWG\Sheet Files\C200 Site Plan.dwg

AutoCAD SHX Text August 6, 2026

08.06.2026

2025103

BSM BSM

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

CHECKED

DATE

COMM. NO.

DRAWN

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

A

TE

c by ZMM, LLC.

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

C A

M P

D A

W

SO

N

A C

C

ES

S C

O N

TR

O

L

PO

IN

T

R en ov at io ns to th e

Ki ng w oo d, W es t V irg in ia W es t V irg in ia A rm y

N at io na l G ua rd

SITE DETAILS

C220

CONCRETE

FINISHED GRADE

6"

30"

CONCRETE MAINTENANCE STRIP

PAINT POST (COLOR TO BE

SELECTED BY ARCHITECT)

8" STANDARD STEEL PIPE

2" WIDE, WHITE REFLECTIVE TAPE

PAINT TOP 18" SAFETY YELLOW

FILL POST WITH CONCRETE

1"

6"

8" BOLLARD IN CONCRETE STRIP DETAIL

NOT TO SCALE

IN-GROUND TRAFFIC SPIKES DETAIL

NOT TO SCALE

SECTION VIEW

PLAN VIEW

4"

6X6 W2.9 X W2.9 WWF

OR FIBROUS REINFORCEMENT

48"

SPEED BUMP DETAIL

NOT TO SCALE

SAWCUT EXISTING ASPHALT24"

3"

EXISTING AGGREGATE

STONE BASE

EXISTING SUBBASE

EXISTING ASPHALT

#4 @ 12" EW

4,000 PSI CONCRETE

8' -0

2'-0"

SAWCUT EXISTING ASPHALT

#4 @ 12" EW

3" TYP.

3" T

YP

8"

ROADSHARK GUARDIAN LPS

8" COMPACTED STONE

EXPANSION JOINT, TYP.

8"

EXISTING

ASPHALT

EXISTING

ASPHALT

TRENCH

WIDTH

12" OF 3,000 PSI

CONCRETE

1.5" HMA WEARING COURSE

TYPE 1

NOTES:

1. EXISTING PAVEMENT TO BE SAW CUT. PROVIDE LOAD TRANSFER PROVISIONS

WHERE REQUIRED.

2. BACKFILL TO BE COMPACTED TO 98% OF THE STANDARD PROCTOR MAX. DRY

DENSITY AS DETERMINED BY ASTM D698 IN ALL AREAS UNDER PAVEMENT.

6" STONE MIN.

PIPE BACK FILL

TRENCH PAVEMENT REPAIR DETAIL

NOT TO SCALE

6X6 - W2.0 x W2.0 WWM

12" MIN.12" MIN.

STORM TRENCH DETAIL

NO SCALE:

C220

D"

1' -0

APPROVED BACKFILL

MECHANICALLY COMPACTED

IN 12" LIFTS

BEDDING MATERIAL #8 STONE

TO 6" ABOVE PIPE

PIPE PER PLANS AND

SPECIFICATIONS

COMPACTED SUBGRADE

12"

MIN.

METALLIC LOCATING TAPE

LAY PIPE WITH PIPE SIZE

MARKINGS VISIBLE AT TOP

OF PIPE

PAVEMENT

FINISHED GRADE

6" M

IN

C220

C220

C220

C220

4" PVC DRAIN

8"

AutoCAD SHX Text M:\WVARNG - Camp Dawson ACP Improvements 25103\_Site\DWG\Sheet Files\C220 Site Details.dwg

AutoCAD SHX Text August 6, 2026

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text

EXISTING PAVEMENT

AutoCAD SHX Text

EXISTING PAVEMENT

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

G

G

W M

FH

D I

D I

D I

D I D I

D I

D I

D I

D I

D I

P

PP

P

L

D I

D I

W M

L

L

S

U E U C O M M

U E U C O M M

UE/UCOMM

U E

U E

U C O M M

.5

W A

TE

R

FM

COUNTRY CLUB RD (RT. 7/27)

COUNTRY CLUB RD (RT. 7/27)

ASPHALT

ASPHALT

G R A V E L

ASPHALT

A S P H A

LT

P A R K

IN

G

UNISEX

TOILET

OFFICE

SECURE

PACKAGE

RECEIVING

JANITOR

INCINERATOR

ID

CENTER

ELEC/DATA

CERTIFIED

MAIL

LOBBY

STORAGE

MAIL

ROOM

LARGE

PACKAGE

VESTIBULE

LOBBY

UNISEX

TOILET

BREAK

ROOM

C&P 62

C&P 6249

M P E 4

M P E 4

A P

A P

(3 A

(3 A

M

ULTIPURPO

SE

BUILDING

F.F.E.= 1252.0

PRO

PO

SED

BH-43

BH-44

M O N

ITO

R

IN

G

W

ELL

G U Y

G U Y P O

LE

CA

TV

TEC TEC

TEC

TEC TEC TEC ET

C

ET ET ET ET ET ET

W O O D

W O O D

B R

ID

G E

UT

PAD

UT PAD

UT PAD

UT

PAD

CO

NC

RET

E D

ITC

H

CO

NC

RET

E D

ITC

H

LOA

DING

DO

CK

D O C K

D O C K

M

EC

H A N

IC

A L

EN

C

LO

S U R E

ID

E W A

LK

48"

STR

24"

STR

24"

STR

"S

TR

"S

TR

"S

TR

18"

STR

D I

IN

S

TA

LL N

EW

D I

TIE O

V

ER

EX

IS

T.

" S

TO

R M P

IP

E

12"

STR

C O

C O

18"

STR

CON

CRE

TE

TR

EN

C H D R A

IN

"S

TR

24"S

TR.

"S

TR

IN

S

TA

LL N

EW

D I

G R A S S

LIN

ED

D

ITC

H

G R A S S

LIN

ED

D

ITC

H

G R A S S

LIN

ED

D

ITC

H

"S

TR

G R A S S

LIN

ED

D

ITC

H

36"

STR

24"

STR

C O

24"

STR

24"

STR

TO

P

EL.12

.5

IN

V

.EL.12

.0

TO

P

EL.12

.5

IN

V

.EL.12

1.3

IN

V

.EL.12

.3

G R A S S

LIN

E D

D

IT

C H

"P V C

D I

R A M P

A C

A C

A C

AC

A C

A C

AC

A C

A C

AC

AC

A C

A C

A C

A C

A C

AC

A C

A C

A C

AC

A C

A C

A C

X X X X X X

X

X X X X X X X X X X X X X X X X X X X X

X

X

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

LIFT S

TA

TIO

N

E

E

E

E

E

E

F M

F M

F M

F M

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

G R

EA

S E

TR

A P

C O

S

S

S

S

S

S

TELEP

H O N E

B O X

TELEP

H O N E

B O X

TELEP

H O N E

B O X

TELEP

H O N E

B O X

TELEP

H O N E

B O X

TELEP

H O N E

B O X

ELEC

TR

IC

O U

TLET

TELEP

H O N E

B O X

B U

IL

D

IN

G

FF

E

LE

V.

.4

B U

IL

D

IN

G

BUILDING 414.1

PLA

YGR

OUN

D

CHEAT RIVER

TP-1

TP-7

TP-4

TP-5

TP-3

TP-2

B A

SK

ET

B A

LL

C

O U R T

G R A

VE

L

P A R K

IN

G

G R A

VE

L

P A R K

IN

G

LO

ADING

DO

CK

EL.1251.50

FUTURE DO

RM

FUTURE CO

URT

FUTURE CO

URT

CONCRETE

20' G

RAVEL SERVICE RO

AD

24' GRAVEL SERVICE ROAD

20' G R

AVEL SER

VIC

E R O

AD

SWALE

WALL

WALL

EXISTING ELECTRICAL PANEL,

LIGHTING CONTACTOR, AND

INVERTER LOCATED IN

ELECTRICAL ROOM BELOW

CANOPY.

EXISTING

TRANSFORMER

FOR ACP BUILDING

EXISTING CANOPY MOUNTED

TRAFFIC SIGNAL LIGHT

EXISTING UPS

EXISTING CANOPY LIGHT FIXTURE

(TYP)

EXISTING CANOPY MOUNTED

TRAFFIC SIGNAL LIGHT

EXISTING MOTORIZED STOP ARM GATE

1 2

ACP BUILDING

SITE LIGHTING SYMBOLS LEGEND

HOMERUN TO PANELBOARD.

CANOPY LIGHT

PUSHBUTTON STATION

c by ZMM, LLC.

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

CHECKED

DATE

COMM. NO.

DRAWN

ARCHITECTS

ENGINEERS

8/ 6/

:4

3:

A M

S:

\S ha re d\ ks ha nn on \P ro je ct s

- L oc al \2

_C am p D aw so n

AC

P_ E_

_k sh an no nB

Z3

TX

.rv t

E141D

2025103

03.31.2026

SITE DEMOLITION

PLAN

R en ov at io ns to th e C

A M

P D

A W

SO

N

A

C C

ES

S

C O

N

TR

O L

PO

IN

T W es t V irg in ia A rm y

N at io na l G ua rd Ki ng w oo d, W es t V irg in ia

KPS TFK

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

1/8" = 1'-0"

SITE POWER AND LIGHTING PLAN

KEYED DEMO NOTES

1.

2.

3.

4.

5.

EXISTING TRAFFIC LIGHT IS TO BE RELOCATED ALONG CANOPY FACE IN NEW

WORK PLAN. REMOVE TRAFFIC LIGHT FROM ELECTRICAL CIRCUIT AND RETAIN FOR

REUSE IN NEW WORK PLAN. PROVIDE NEW JUNCTION BOX FOR SPLICING AT

EXISTING LOCATION.

EXISTING RED-YELLOW-GREEN TRAFFIC LIGHT IS TO BE REPLACED WITH NEW RED-

GREEN ONLY TRAFFIC LIGHT. REMOVE TRAFFIC LIGHT FROM EXISTING ELECTRICAL

CIRCUIT, BUT RETAIN EXISTING CIRCUIT FOR REUSE IN NEW WORK PLAN.

EXISTING 12V CANOPY LIGHTING SYSTEM IS TO BE DEMOLISHED AND REPLACED IN

ITS ENTIRETY WITH NEW 120V FIXTURES AND CIRCUITING. REMOVE ALL 12V

FIXTURES FROM ELECTRICAL CIRCUIT. DEMO ALL ASSOCIATED 12V CONDUIT AND

WIRING BACK TO SOURCE.

EXISTING 3-PHASE, 30 kVA UPS IS TO BE REPLACED IN KIND. REMOVE UPS FROM

EXISTING UPSTREAM AND DOWNSTREAM ELECTRICAL FEEDER CONNECTIONS, BUT

RETAIN CONNECTIONS FOR REUSE IN NEW WORK PLAN. EXISTING UPS IS

SCHNEIDER APC MGE GALAXY 3500.

EXISTING 120V, 5.5A STOP ARM GATE IS SCHEDULED TO BE REPLACED IN KIND.

REMOVE ARM GATE FROM CORRESPONDING ELECTRICAL CIRCUIT, BUT RETAIN

EXISTING CIRCUIT FOR REUSE IN NEW WORK PLAN. COORDINATE REMOVAL WITH

CIVIL DRAWINGS.

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

A

TE

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

G

G

W M

FH

D I

D I

D I

D I D I

D I

D I

D I

D I

D I

P

PP

P

L

D I

D I

W M

L

L

S

U E U C O M M

U E U C O M M

UE/UCOMM

U E

U E

U C O M M

.5

W A

TE

R

FM

COUNTRY CLUB RD (RT. 7/27)

COUNTRY CLUB RD (RT. 7/27)

ASPHALT

ASPHALT

G R A V E L

ASPHALT

A S P H A

LT

P A R K

IN

G

UNISEX

TOILET

OFFICE

SECURE

PACKAGE

RECEIVING

JANITOR

INCINERATOR

ID

CENTER

ELEC/DATA

CERTIFIED

MAIL

LOBBY

STORAGE

MAIL

ROOM

LARGE

PACKAGE

VESTIBULE

LOBBY

UNISEX

TOILET

BREAK

ROOM

C&P 62

C&P 6249

M P E 4

M P E 4

A P

A P

(3 A

(3 A

M

ULTIPURPO

SE

BUILDING

F.F.E.= 1252.0

PRO

PO

SED

BH-43

BH-44

M O N

ITO

R

IN

G

W

ELL

G U Y

G U Y P O

LE

CA

TV

TEC TEC

TEC

TEC TEC TEC ET

C

ET ET ET ET ET ET

W O O D

W O O D

B R

ID

G E

UT

PAD

UT PAD

UT PAD

UT

PAD

CO

NC

RET

E D

ITC

H

CO

NC

RET

E D

ITC

H

LOA

DING

DO

CK

D O C K

D O C K

M

EC

H A N

IC

A L

EN

C

LO

S U R E

ID

E W A

LK

48"

STR

24"

STR

24"

STR

"S

TR

"S

TR

"S

TR

18"

STR

D I

IN

S

TA

LL N

EW

D I

TIE O

V

ER

EX

IS

T.

" S

TO

R M P

IP

E

12"

STR

C O

C O

18"

STR

CON

CRE

TE

TR

EN

C H D R A

IN

"S

TR

24"S

TR.

"S

TR

IN

S

TA

LL N

EW

D I

G R A S S

LIN

ED

D

ITC

H

G R A S S

LIN

ED

D

ITC

H

G R A S S

LIN

ED

D

ITC

H

"S

TR

G R A S S

LIN

ED

D

ITC

H

36"

STR

24"

STR

C O

24"

STR

24"

STR

TO

P

EL.12

.5

IN

V

.EL.12

.0

TO

P

EL.12

.5

IN

V

.EL.12

1.3

IN

V

.EL.12

.3

G R A S S

LIN

E D

D

IT

C H

"P V C

D I

R A M P

A C

A C

A C

AC

A C

A C

AC

A C

A C

AC

AC

A C

A C

A C

A C

A C

AC

A C

A C

A C

AC

A C

A C

A C

X X X X X X

X X X X X X X X X X X X X X X X X X X X

X

X

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

EP

LIFT S

TA

TIO

N

E

E

E

E

E

E

F M

F M

F M

F M

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

G R

EA

S E

TR

A P

C O

S

S

S

S

S

S

TELEP

H O N E

B O X

TELEP

H O N E

B O X

TELEP

H O N E

B O X

TELEP

H O N E

B O X

TELEP

H O N E

B O X

TELEP

H O N E

B O X

ELEC

TR

IC

O U

TLET

TELEP

H O N E

B O X

B U

IL

D

IN

G

FF

E

LE

V.

.4

B U

IL

D

IN

G

BUILDING 414.1

PLA

YGR

OUN

D

CHEAT RIVER

TP-1

TP-7

TP-4

TP-5

TP-3

TP-2

B A

SK

ET

B A

LL

C

O U R T

G R A

VE

L

P A R K

IN

G

G R A

VE

L

P A R K

IN

G

LO

ADING

DO

CK

EL.1251.50

FUTURE DO

RM

FUTURE CO

URT

FUTURE CO

URT

CONCRETE

20' G

RAVEL SERVICE RO

AD

24' GRAVEL SERVICE ROAD

20' G R

AVEL SER

VIC

E R O

AD

SWALE

WALL

WALL

EXISTING 208Y/120V PNL CL1

NEW CANOPY MOUNTED

TRAFFIC SIGNAL LIGHTS

NEW PUSH BUTTON TO TIE INTO

EXISTING CRASH ARM

CONTROLS.

5NEW UPS

NEW CANOPY MOUNTED

TRAFFIC SIGNAL LIGHT

NEW MOTORIZED STOP ARM GATE

ACP BUILDING

SITE LIGHTING SYMBOLS LEGEND

HOMERUN TO PANELBOARD.

CANOPY LIGHT

PUSHBUTTON STATION

1. ALL EXTERIOR CANOPY LIGHTS SHALL BE CONNECTED THROUGH LIGHTING

CONTACTOR IN ELECTRICAL ROOM. PROVIDE NEW PHOTOCELL ON CANOPY ROOF

FOR CANOPY LIGHT FIXTURE CONTROL.

GENERAL NOTES THIS SHEET

c by ZMM, LLC.

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

CHECKED

DATE

COMM. NO.

DRAWN

ARCHITECTS

ENGINEERS

8/ 6/

:4

3:

A M

S:

\S ha re d\ ks ha nn on \P ro je ct s

- L oc al \2

_C am p D aw so n

AC

P_ E_

_k sh an no nB

Z3

TX

.rv t

E141

2025103

08.06.2026

SITE POWER AND

LIGHTING PLAN

R en ov at io ns to th e C

A M

P D

A W

SO

N

A

C C

ES

S

C O

N

TR

O L

PO

IN

T W es t V irg in ia A rm y

N at io na l G ua rd Ki ng w oo d, W es t V irg in ia

KPS TFK

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

1/8" = 1'-0"

SITE POWER AND LIGHTING PLAN

KEYED NOTES

1.

2.

3.

4.

5.

6.

7.

NEW TRAFFIC LIGHT TO BE INSTALLED AT NEW LOCATION SHOWN ON PLAN AND

RECONNECTED TO EXISTING CIRCUIT RETAINED FROM DEMO. PROVIDE NEW

CONDUIT AND WIRING SIZED TO MATCH EXISTING TO EXTEND EXISTING

CIRCUITING TO NEW LOCATION. COORDINATE FINAL LOCATION FOR BEST

VISIBILITY FROM ENTRANCE ROAD.

PROVIDE WEATHERPROOF PUSHBUTTON STATION FOR OPERATION OF

MOTORIZED CRASH ARM GATE IN LOCKABLE ENCLOSURE ON EXTERIOR WALL.

STATION IS TO BE AN EXTENSION OF EXISTING INTERIOR STATION; EXTEND

CIRCUITING IN PARALLEL FROM EXISTING CONTROL STATION SUCH THAT EITHER

LOCATION MAY PROVIDE FULL CONTROL OF CRASH ARM GATE. COORDINATE FINAL

LOCATION OF PUSHBUTTON STATION WITH OWNER.

PROVIDE NEW RED-GREEN TRAFFIC SIGNAL LIGHTS AND CONNECT TO EXISTING

TRAFFIC SIGNAL LIGHT CIRCUIT RETAINED FROM DEMO. CONTRACTOR IS TO

VERIFY EXISTING CIRCUIT IS FED FROM EXISTING PANEL CL1. PROVIDE NEW

CONTROL WIRING AND NEW CONTROL STATION IN GUARD BUILDING ADJACENT TO

EXISTING CONTROLS AND REMOVE ANY RESULTING UNUSED CONTROLS AND/OR

WIRING.

NEW CANOPY LIGHT FIXTURES ARE TO BE CONNECTED TO EXISTING 208Y/120V

PANEL CL1 IN ELECTRICAL ROOM. EXISTING CANOPY FIXTURE LOCATIONS ARE TO

BE REUSED. BASIS OF DESIGN LITHONIA VCPGX LED V4 P4 40K 80CRI T5E MVOLT

SRM. PROVIDE NEW 20A/1P BREAKER IN PANEL. PROVIDE NEW #12 CONDUCTORS

AND #12 GROUND IN 3/4" CONDUIT AND CONNECT NEW CANOPY FIXTURES TO NEW

BREAKER. NEW FIXTURES ARE TO BE CONTROLLED BY NEW PHOTOCELL ON ROOF.

PROVIDE NEW 208Y/120V 3-PHASE, 30 kVA UPS AT EXISTING LOCATION. PROVIDE

NEW CONDUIT AND WIRING SIZED TO MATCH EXISTING AS NECESSARY TO

RESTORE UPSTREAM AND DOWNSTREAM ELECTRICAL FEEDER CONNECTIONS

RETAINED FROM DEMO. NEW UPS IS TO HAVE 15 MINUTES OF BATTERY TIME. UPS,

BATTERY, BYPASS, AND DISTRIBUTION ARE ALL TO BE CONTAINED IN SINGLE

CABINET. COORDINATE SCHEDULE OF UPS DOWNTIME WITH OWNER.

NEW MOTORIZED STOP ARM GATE IS TO BE RECONNECTED TO EXISTING CIRCUIT

RETAINED FROM DEMO. NEW STOP ARM GATE MOTOR IS NOT TO EXCEED 1/4 HP.

PROVIDE NEW CONDUIT AND WIRING SIZED TO MATCH EXISTING AS NECESSARY

FOR RECONNECTION. COORDINATE INSTALLATION WITH CIVIL DRAWINGS AND

SPECIFICATIONS.

PROVIDE WEATHERPROOF PUSHBUTTON STATION FOR MANUAL OPERATION OF

CORRESPONDING TRAFFIC LIGHT. STATION IS TO BE AN EXTENSION OF EXISTING

INTERIOR STATION; EXTEND CIRCUITING IN PARALLEL FROM EXISTING CONTROL

STATION SUCH THAT EITHER LOCATION MAY TOGGLE RED-GREEN TRAFFIC LIGHT.

COORDINATE FINAL LOCATION OF PUSHBUTTON STATION WITH OWNER.

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

A

TE

COVER SHEET
Civil
C200 Site Plan
Electrical
E141D - SITE DEMOLITION PLAN
E141 - SITE POWER AND LIGHTING PLAN

File details come from the government source that posted it. Updated .