A06_AFTC__100__Final_Draft_Drawings__07-26-2022.pdf

PDF 25 MB Posted

Attached to
WA-ABERNATHY FTC REHAB INTAKE STRUCTURE Federal contract opportunity
Solicitation number
140F0322R0013
Issued by
Department of the Interior Fish and Wildlife Service

About this file

This document provides details for a federal solicitation opportunity. The solicitation number is 140F0322R0013 from the Department of the Interior Fish and Wildlife Service for the WA-ABERNATHY FTC REHAB INTAKE STRUCTURE project. The opportunity type is a solicitation seeking proposals to rehabilitate the intake structure at the Abernathy Fish Technology Center. The attached file appears to contain final draft drawings dated July 26, 2022 for the project. No other details are provided regarding response dates, award timing, pricing requirements, or set asides.

View the file

Other files for this federal contract opportunity

Other files attached to WA-ABERNATHY FTC REHAB INTAKE STRUCTURE, newest first.
File Type Posted
Sol_140F0322R0013_Amd_0007.pdf PDF
NWP_Terms_and_Conditions_for_NWP_No__3__05-11-2022_0007.pdf PDF
AFTC__Questions_and_Responses__Amend_7__10-12-2022_0007.pdf PDF
NWP_Verification_Letter__09-23-2022_0007.pdf PDF
Permit_Drawings__06-15-2021_0007.pdf PDF
List_of_Attachments__Nationwide_Permit_No__3_0007.pdf PDF
Sol_140F0322R0013_Amd_0006.pdf PDF
Amendment_No__6__REVISED_Statement_of_Work__09-20-2022_0006.pdf PDF
Amendment_No__6__REVISED_Proposal_Schedule__09-20-2022_0006.xlsx XLSX spreadsheet
B12_AFTC__Questions_and_Responses__Amend_5__09-09-2022_0005.pdf PDF
Sol_140F0322R0013_Amd_0005.pdf PDF
Sol_140F0322R0013_Amd_0004.pdf PDF
B12_AFTC__Questions_and_Responses__Amendment__09_01_2022_0004.pdf PDF
B12_AFTC__Questions_and_Responses__Amendment_08-31-2022_0003.pdf PDF
Sol_140F0322R0013_Amd_0003.pdf PDF
Sol_140F0322R0013_Amd_0002.pdf PDF
Safety_and_Design_Checklists_0001.pdf PDF
Endangered_Species_Act_and_Section_7(a)(2)_Biological_Opinion_(1)_0001.pdf PDF
Cultural_Resources_Survey_and_Report_0001.pdf PDF
B12_AFTC_Nationwide_Permit_3_T___C_s_0001.pdf PDF
Turbidity_Plan_0001.pdf PDF
State_Environmental_Policy_Act_Letter_0001.pdf PDF
Permit_Authorization_and_Conditional_Approval_0001.pdf PDF
Wetland_Delineation_Report_0001.pdf PDF
B12_Certificate_of_Compliance_0001.pdf PDF
Turbidity_Protocol_Details_0001.pdf PDF
JARPA_Application_0001.pdf PDF
Pre-Work_Safety_Checklist_0001.pdf PDF
NEPA_Compliance_Checklist_0001.xlsx XLSX spreadsheet
HPA_Conditional_Approval_Letter_and_Requirements_(1)_0001.pdf PDF
B12_Proposal_Schedule_0001.xlsx XLSX spreadsheet
Sol_140F0322R0013_Amd_0001.pdf PDF
A04_AFTC_Statement_of_Work_7-18-2022.pdf PDF
A06_AFTC_Permit_Drawings.pdf PDF
A06_AFTC__100__Final_Draft_Specifications__07-26-2022.pdf PDF
A06_AFTC_Technical_Requirements__7-18-2022.pdf PDF
Sol_140F0322R0013.pdf PDF
Show all 37

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYMBOL DESCRIPTION

DETAIL CALL OUT - A INDICATES DETAIL IDENTIFICATION, E2 INDICATES SHEET

TAKEN FROM, E3 INDICATES SHEET DRAWN ON

WALL MOUNT LIGHT FIXTURE

POLE LIGHT FIXTURE (ARROW INDICATES DIRECTION OF AIMING FOR OPTICS)

DUPLEX RECEPTACLE (E INDICATES EXISTING TO BE REPLACED)

DUPLEX RECEPTACLE (G INDICATES GROUND FAULT CIRCUIT INTERRUPTER)

CONDUIT STUB OUT (PROVIDE CONCRETE MARKER ON EXTERIOR)

DEDICATED CONDUIT HOMERUN TO PANEL & CIRCUIT NUMBERS AS INDICATED ON PLANS

RACEWAY CONCEALED IN WALL OR CEILING

RACEWAY CONCEALED UNDERGROUND OR UNDER FLOOR SLAB, P = PRIMARY , S = SECONDARY

MARKS INDICATE NUMBER OF #12 AWG UNLESS NOTED OTHERWISE

GROUNDING CONDUCTOR

FLEXIBLE CONDUIT

GROUNDING SYSTEM PER CODE

JUNCTION BOX - SIZE PER CODE (F INDICATES FIRE ALARM SYSTEM)

MOTOR CONNECTION

DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

COMBINATION DISCONNECT / MAGNETIC MOTOR STARTER

120/208 VOLT PANELBOARD (OR AT RATED VOLTAGE AS NOTED)

SURGE PROTECTIVE DEVICE

UTILITY POLE

METER

CONSTRUCTION NOTES

DEMOLITION NOTES

FLAG NOTE

W INDICATES WEATHERPROOF FOR ALL DEVICES, PROVIDE LOCKING COVER ON RECEPTACLES.

WG INDICATES WIRE GUARD

ALL DEVICES WITH LIGHT LINE WEIGHT INDICATES EXISTING TO BE RETAINED

ALL DEVICES WITH DASH LINE INDICATES EXISTING TO BE REMOVED

WG

W

G

A E2 E3

M

P

SINGLE POLE SWITCH

STANDARD HOUSING FIXED CAMERA (IN ENVIRONMENTALLY RATED HOUSING, VARIABLE FOCUS OR FIXED FOCUS LENS) - WALL MOUNT (C INDICATES CEILING MOUNT, I INDICATES INTERIOR CAMERA, P INDICATES POLE MOUNT, PM INDICATES

PARAPET MOUNT, R INDICATES ROOF MOUNT)

SPD

J

ELECTRICAL ABBREVIATIONS

AIC AMPERE INTERRUPTING CAPACITY

AFC AVAILABLE FAULT CURRENT

AWG AMERICAN WIRE GUAGE

C. CONDUIT

CO CONDUIT ONLY

CU COPPER

EMT ELECTRICAL METALLIC TUBING

FLA FULL LOAD AMPERE(S)

G GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GND GROUND

GR GROUND

HP HORSEPOWER

KVA KILOVOLT-AMPERE(S)

KW KILOWATT(S)

LCP LIGHTING CONTROL PANEL

LED LIGHT-EMITTING DIODE(S)

LTG LIGHTING

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NTS NOT TO SCALE

PH PHASE

REC RECEPTACLE

RECPT RECEPTACLE

SCH SCHEDULE

SL SURFACE MOUNTED LED LIGHT FIXTURE

UG UNDER GROUND

V VOLT(S)

VA VOLT-AMPERE(S)

WR WIRE(S)

XFMR TRANSFORMER

GENERAL ABBREVIATIONS

AFG ABOVE FINISHED GRADE

C MOUNT ABOVE COUNTER

EC ELECTRICAL CONTRACTOR

GC GENERAL CONTRACTOR

GFCI GOVERNMENT FURNISHED, CONTRACTOR

INSTALLED

MFR MANUFACTURER

REQ'D REQUIRED

W WEATHERPROOF

GENERAL NOTES

1. THE CONTRACTOR/INSTALLING VENDOR IS RESPONSIBLE TO VERIFY ALL CMU/CONCRETE WALLS, BRICK WALLS, CABLE

ROUTING AND ALL WORK REQUIRED TO FACILITATE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.

2. PANEL DESIGNATIONS AND CIRCUIT NUMBERS ARE ONLY INDICATED ON THE DRAWINGS FOR REFERENCE BY THE ELECTRICAL CONTRACTOR. THE E.C. IS RESPONSIBLE TO PROVIDE ALL CONDUIT, WIRING, JUNCTION BOXES AND MISCELLANEOUS ACCESSORIES TO ACCOMMODATE INSTALLATION AND CONNECTION OF ALL DEVICES INDICATED ON THE CONTRACT DOCUMENTS. ALL WIRING SHALL BE IN HARD CONDUIT BACK TO THE DESIGNATED PANELBOARD. MC TYPE CABLE IS NOT AN ACCEPTABLE WIRING METHOD. ALL JUNCTION BOXES SHALL BE LABELED IDENTIFYING THE PANELBOARD AND CIRCUIT CONTAINED WITHIN. THERE SHALL BE NO MORE THAN (3) CIRCUITS PER HOMERUN. MULTI-WIRE CIRCUITS ARE NOT ALLOWED. EACH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL UNLESS SPECIFICALLY ALLOWED BY THE ENGINEER. ALL WIRING SHALL BE SIZED ACCORDING TO AMPACITY OF THE CIRCUIT BREAKER INDICATED ON THE PANEL SCHEDULES. ALL CONDUIT SHALL BE SIZED PER NEC CODE BASED ON THE CONDUCTOR SIZE, TYPE, QUANTITY AND MINIMUM FILL REQUIREMENTS. CIRCUITS OVER 120 FEET FOR 120V AND 250' FOR 277V SHALL BE UP SIZED ONE WIRE SIZE TO ACCOUNT FOR VOLTAGE DROP. E.C. IS RESPONSIBLE TO SHOW ALL JUNCTION BOX LOCATIONS, CONDUIT ROUTING

AND HOMERUNS ON A SET OF AS-BUILT DRAWINGS.

3. FEED THROUGH GFCI RECEPTACLES SHALL NOT BE USED.

4. ALL SPARE CONDUITS (FOR FUTURE USE) SHALL BE LABELED "SPARE/FUTURE CONDUIT" AT EACH END OF THE CONDUIT

WITH 1/2" TALL LETTERS, USING A PERMANENT MARKER.

5. SEE ALL DETAIL SHEETS AND RISER DIAGRAMS FOR ADDITIONAL WORK. ALL DETAILS AND RISERS ARE APPLICABLE TO

THIS PROJECT WHETHER REFERENCED OR NOT.

6. ALL GROUNDING SHALL CONFORM TO NEC 250.

7. CIRCUITING SHALL BE PROVIDED AS REQUIRED TO MEET THE NEC. ALL SINGLE POLE CIRCUITS SHALL BE PROVIDED WITH

DEDICATED NEUTRALS.

8. PROVIDE CUTTING AND PATCHING OF EXISTING WALLS TO ACCOMMODATE INSTALLATION OF NEW WORK.COORDINATE

WITH G.C.

MULTI-GANGED SWITCH (LOWER CASE LETTERS INDICATES SWITCHING)ba

RADIO ANTENNA

7/1 2/2

ELECTRICAL INDEX

# SHEET TITLE

E-001 ELECTRICAL LEGEND, INDEX, AND ABBREVIATIONS

E-101 OVERALL ELECTRICAL SITE PLAN

E-401 ENLARGED ELECTRICAL SITE PLAN

E-501 ELECTRICAL DETAILS

E-601 ELECTRICAL ONE-LINE DIAGRAM & PANEL SCHEDULES

E-001

GA

TE

TR

TRAN

GA

TE

GA

TE

GA

TE

WOOD SHED

FISH LADDER

CO

NC

RE

TE

W

EI

R

INTAKE

ABERNATHY CREEK ROAD

WIEST ROAD

ABERNATHY CREEK

ABERNATHY CREEK

ED

GE O

F W

ATE

R

(9/

/2

8)

ED

GE O

F W

ATE

R

(9/27/2018)

EDGE OF W

ATER

(9/30/2018)

EDGE OF WATER

(9/30/2018)

EDGE OF W

ATER

(9/27/2018)

ED

GE

O F

W

AT

ER

(9

/2 7/

EDGE OF W

ATER

(9/25/2018)

ED

GE O

F W

ATE

R

(9/

/2

8)

EDGE OF W

ATER

(9/28/2018)

EDGE OF WATER

(9/28/2018)

REFELCTOR

STOP

ABERNATHY CREEK ROAD

UNDERSID

E OF

BRIDGE DECK

ELEVATION = 229.6'

UNDERSID

E OF

BRIDGE DECK

ELEVATION = 231.0'

DEBRIS SCREEN

WIEST CREEK

BOULDER WALL

AC

CE

SS

R

OA

D

REFLE

CTOR

REFLE

CTOR

EXISTING

UTILITY POLE

UTILITY SERVICE

TO INTAKE

EXISTING UTILITY

TRANSFORMER

EXISTING

UNDERGROUND

UTILITY PRIMARY

EXISTING

UNDERGROUND

UTILITY PRIMARY

METER

VAULT

JW

PROPERTY

LINE

FTC

INTAKE

A-6

CONSTRUCTION NOTES

PROVIDE (1) JUNCTION BOX FOR CONTROL CABLING AND (1)

JUNCTION BOX FOR POWER CABLING FOR FLOW METER AT

NEW METER VAULT.

PROVIDE (1) 1" CONDUIT FOR CONTROL CABLING AND (1) 1"

CONDUIT FOR POWER CABLING BETWEEN INTAKE SERVICE

POINT AND NEW METER VAULT.

7/1 2/2

0 30' 60'

SCALE: 1"=30'-0"

10'20'

SCALE:

N1 OVERALL ELECTRICAL SITE PLAN

1"=30'-0"

E-101

C

EXISTING CCTV

CAMERA

EXISTING POLE

SEE SITE PLAN

FOR CONTINUATION

M

EXISTING ANTENNA

EXISTING CCTV AND

TELEMETRY

ENCLOSURE

EXISTING

SERVICE PANEL A

a b a

W, a, b

EXISTING

SWITCH

FL1

FL1

INTAKE SCREEN

CLEANER CONTROL

PANEL

EXISTING

METER

EXISTING

SERVICE PANEL A

SEE SITE PLAN

FOR CONTINUATION

PROPERTY

BOUNDARY

1 1

M

G,W

G,W

RECEPTACLE

ON 4"X4" TREATED

WOOD POST

J

POWER AND

CONTROL

CONDUIT

A-3

A-3

A-5

FL1

A-5

A-5

JJ

2" C., POWER

C 43 NEW POST

BRUSH MOTOR

W W b a a

W, a, b

EXISTING

SWITCH

A- 2,4

DEMOLITION NOTES

EXISTING LIGHT AND CONDUIT TO BE REMOVED AND REPLACED

WITH NEW.

EXISTING CCTV AND TELEMETRY PANEL SHALL BE RELOCATED AS

SHOWN INCLUDING ASSOCIATED POWER AND COMMUNICATIONS

CONNECTIONS.

EXISTING CCTV CAMERA AND ANTENNA INCLUDING ASSOCIATED

APPURTENANCES TO BE RELOCATED TO LOCATION SHOWN ON

CONSTRUCTION PLAN.

CONSTRUCTION NOTES

THE CONTRACTOR SHALL MOUNT ALL ELECTRICAL EQUIPMENT

ABOVE THE FLOOD PLANE.

TERMINATE CONTROL CONDUIT INTO EXISTING CCTV CONTROL

CABINET. PROVIDE CONDUIT PLUG TO LIMIT MOISTURE INGRESS.

EXISTING CCTV AND TELEMETRY PANEL REVISED LOCATION.

PROVIDE MOUNTING HARDWARE, CONDUIT, CABEL AND

ASSOCIATED APPURTENANCES FOR A COMPLETE, FUNCTIONAL

CCTV SYSTEM WITH REMOTE TELEMETRY CONNECTION.

NEW POST WITH RELOCATED CCTV CAMERA (6'-0" AFG) AND

ANTENNA (12'-0" AFG) INCLUDING ASSOCIATED APPURTENANCES.

GENERAL NOTES

1. ALL NEW DEVICES SHALL BE CIRCUITED TO THE NEW INTAKE PANEL.

2. ALL NEW CONDUIT AND DEVICES SHALL BE NEMA 3R & OUTDOOR

RATED UNLESS NOTED OTHERWISE.

7/1 2/2

SCALE:

N1 ENLARGED DEMOLITION SITE PLAN

1/4"=1'-0"

4' 2' 0 4' 8'

SCALE: 1/4" = 1'-0"

SCALE:

N2 ENLARGED CONSTRUCTION SITE PLAN

1/4"=1'-0"

4' 2' 0 4' 8'

SCALE: 1/4" = 1'-0"

E-401

8"

BEDDING MATERIAL

SLOPE DETERMINED

BY CONTRACTOR

COMPACTED

BACKFILL TO

95% DENSITY

DEPTH AS REQUIRED

TO AVOID EXISTING

UTILITIES AND MEET

CODE REQUIREMENTS

EXISTING GROUND

REPLACE LANDSCAPE TO MATCH

EXISTING

3" MIN.

4" TOPSOIL

MARKER TAPE LAID

ENTIRE LENGTH WITH

3" MIN. WIDTH

1' 1'

EXISTING PAVEMENT

MATERIAL(S) AND

SECTION MAY VARY

2" ASPHALT CONCRETE

WEARING COURSE

SLOPE DETERMINED

BY CONTRACTOR

6" BASE COURSE

MATERIAL

BEDDING MATERIAL

COMPACTED BACKFILL

TO 95% DENSITY

EXISTING BASE

COURSE

SAWCUT AND

TACK COAT (TYP)

3" ASPHALT CONCRETE

BINDER COURSE

DEPTH AS REQUIRED

TO AVOID EXISTING

UTILITIES AND MEET

CODE REQUIREMENTS

3" MIN.

SCALE:1 TRENCHING DETAIL - ASPHALT AREAS

DIAGRAMMATIC SCALE:2 TRENCHING DETAIL - LANDSCAPE AREAS

DIAGRAMMATIC

CONDUIT PER

PLAN (TYP.)

CONDUIT PER

PLAN (TYP.)

SCALE:3 METER VAULT DETAIL

DIAGRAMMATIC

J J

FLOW METER

WITH TRANSDUCER

CONSTRUCTION NOTES

ALL CONDUIT SHALL BE SUBMERSIBLE TYPE CABLE FOR POWER.

PROVIDE MOUNTING AS REQUIRED.

TO PANEL 'A' OR PREVIOUS DEVICE.

THE SUPPORT FRAME INDICATED IS INTENDED TO CONVEY THE INTENT OF THE

SUPPORT SYSTEM. THE CONTRACTOR SHALL ADJUST THE DESIGN PARAMETERS AS

REQUIRED BASED ON THE EXISTING EQUIPMENT AND CONDITIONS PRESENT FOR A

COMPLETE SUPPORT FRAME SYSTEM. THE SUPPORT POST SHALL BE INSTALLED TO

MATCH THE EXISTING SUPPORT POST FOR CONSISTENCY. THE NEW SUPPORT

FRAME SHALL BE PARALLEL TO THE INTAKE RETAINING WALL AND PROVIDE

SUFFICIENT CLEARANCE REQUIRED FOR THE EQUIPMENT.

METER VAULT

WATER PIPE

A-6

TO PANEL 'A'

FLOW METER

ASSEMBLY

SCALE:4 LIGHT FIXTURE WALL MOUNT

DIAGRAMMATIC

SPLICE BOX

TO NEXT RECEPACTACLE

TO NEXT FIXTURE

EXISTING

CONCRETE WALL

NEW LIGHT FIXTURE

5"X5" TREATED WOOD POST

SPLICE BOX

DUPLEX RECEPTACLE

GRADE

EXISTING PANELEXISTING METER

NEW 5"X5"

TREATED WOOD

POLE

NEW 1 5/8" UNISTRUT,

3' - 8" LONG

EXISTING CCTV

PANEL

SCALE:5 EQUIPMENT SUPPORT DETAIL

1" = 1' - 0"

7/1 2/2

E-501

UTILITY TRANSFORMER

12.47KV-120/240V M

20A/2P

SCREEN

CLEANING

CONTROL

PANEL

INTAKE

SERVICE PANEL 'A'

100A, 120/240V

2"C., (3) #2 CU., #2 CU GND

UTILITY

METER

SCALE:1

EXISTING ONE-LINE DIAGRAM

NTS

FROM

UTILITY

100A/2P

1HP, 240V-3P, SCREEN

CLEANING MOTOR

1"C., WITH CONTROL CABLING

TO NEW METER VAULT

J W

1HP, 240V-3P, SCREEN

CLEANING MOTOR FLOW METER

TRANSDUCTER

GRADE

J

W

20A/2P

3/4"C., (3) #10 CU., #10 CU GND

1/2" C., (2) #10 CU, #10 CU GND

CONSTRUCTION NOTES

CONDUIT BY EC, CABLE BY SCREEN SYSTEM MANUFACTURER. MINIMUM SIZE

(3) #12 CU. W #12 GND IN 1/2" CONDUIT. EC SHALL COORDINATE WITH THE

SCREEN SYSTEM MANUFACTURER PRIOR TO ROUGH-IN.

J

J

7/1 2/2

E-601