This document provides details for a federal solicitation opportunity. The solicitation number is 140F0322R0013 from the Department of the Interior Fish and Wildlife Service for the WA-ABERNATHY FTC REHAB INTAKE STRUCTURE project. The opportunity type is a solicitation seeking proposals to rehabilitate the intake structure at the Abernathy Fish Technology Center. The attached file appears to contain final draft drawings dated July 26, 2022 for the project. No other details are provided regarding response dates, award timing, pricing requirements, or set asides.
View the file
Other files for this federal contract opportunity
Show all 37
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYMBOL DESCRIPTION
DETAIL CALL OUT - A INDICATES DETAIL IDENTIFICATION, E2 INDICATES SHEET
TAKEN FROM, E3 INDICATES SHEET DRAWN ON
WALL MOUNT LIGHT FIXTURE
POLE LIGHT FIXTURE (ARROW INDICATES DIRECTION OF AIMING FOR OPTICS)
DUPLEX RECEPTACLE (E INDICATES EXISTING TO BE REPLACED)
DUPLEX RECEPTACLE (G INDICATES GROUND FAULT CIRCUIT INTERRUPTER)
CONDUIT STUB OUT (PROVIDE CONCRETE MARKER ON EXTERIOR)
DEDICATED CONDUIT HOMERUN TO PANEL & CIRCUIT NUMBERS AS INDICATED ON PLANS
RACEWAY CONCEALED IN WALL OR CEILING
RACEWAY CONCEALED UNDERGROUND OR UNDER FLOOR SLAB, P = PRIMARY , S = SECONDARY
MARKS INDICATE NUMBER OF #12 AWG UNLESS NOTED OTHERWISE
GROUNDING CONDUCTOR
FLEXIBLE CONDUIT
GROUNDING SYSTEM PER CODE
JUNCTION BOX - SIZE PER CODE (F INDICATES FIRE ALARM SYSTEM)
MOTOR CONNECTION
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION DISCONNECT / MAGNETIC MOTOR STARTER
120/208 VOLT PANELBOARD (OR AT RATED VOLTAGE AS NOTED)
SURGE PROTECTIVE DEVICE
UTILITY POLE
METER
CONSTRUCTION NOTES
DEMOLITION NOTES
FLAG NOTE
W INDICATES WEATHERPROOF FOR ALL DEVICES, PROVIDE LOCKING COVER ON RECEPTACLES.
WG INDICATES WIRE GUARD
ALL DEVICES WITH LIGHT LINE WEIGHT INDICATES EXISTING TO BE RETAINED
ALL DEVICES WITH DASH LINE INDICATES EXISTING TO BE REMOVED
WG
W
G
A E2 E3
M
P
SINGLE POLE SWITCH
STANDARD HOUSING FIXED CAMERA (IN ENVIRONMENTALLY RATED HOUSING, VARIABLE FOCUS OR FIXED FOCUS LENS) - WALL MOUNT (C INDICATES CEILING MOUNT, I INDICATES INTERIOR CAMERA, P INDICATES POLE MOUNT, PM INDICATES
PARAPET MOUNT, R INDICATES ROOF MOUNT)
SPD
J
ELECTRICAL ABBREVIATIONS
AIC AMPERE INTERRUPTING CAPACITY
AFC AVAILABLE FAULT CURRENT
AWG AMERICAN WIRE GUAGE
C. CONDUIT
CO CONDUIT ONLY
CU COPPER
EMT ELECTRICAL METALLIC TUBING
FLA FULL LOAD AMPERE(S)
G GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GND GROUND
GR GROUND
HP HORSEPOWER
KVA KILOVOLT-AMPERE(S)
KW KILOWATT(S)
LCP LIGHTING CONTROL PANEL
LED LIGHT-EMITTING DIODE(S)
LTG LIGHTING
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NTS NOT TO SCALE
PH PHASE
REC RECEPTACLE
RECPT RECEPTACLE
SCH SCHEDULE
SL SURFACE MOUNTED LED LIGHT FIXTURE
UG UNDER GROUND
V VOLT(S)
VA VOLT-AMPERE(S)
WR WIRE(S)
XFMR TRANSFORMER
GENERAL ABBREVIATIONS
AFG ABOVE FINISHED GRADE
C MOUNT ABOVE COUNTER
EC ELECTRICAL CONTRACTOR
GC GENERAL CONTRACTOR
GFCI GOVERNMENT FURNISHED, CONTRACTOR
INSTALLED
MFR MANUFACTURER
REQ'D REQUIRED
W WEATHERPROOF
GENERAL NOTES
1. THE CONTRACTOR/INSTALLING VENDOR IS RESPONSIBLE TO VERIFY ALL CMU/CONCRETE WALLS, BRICK WALLS, CABLE
ROUTING AND ALL WORK REQUIRED TO FACILITATE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
2. PANEL DESIGNATIONS AND CIRCUIT NUMBERS ARE ONLY INDICATED ON THE DRAWINGS FOR REFERENCE BY THE ELECTRICAL CONTRACTOR. THE E.C. IS RESPONSIBLE TO PROVIDE ALL CONDUIT, WIRING, JUNCTION BOXES AND MISCELLANEOUS ACCESSORIES TO ACCOMMODATE INSTALLATION AND CONNECTION OF ALL DEVICES INDICATED ON THE CONTRACT DOCUMENTS. ALL WIRING SHALL BE IN HARD CONDUIT BACK TO THE DESIGNATED PANELBOARD. MC TYPE CABLE IS NOT AN ACCEPTABLE WIRING METHOD. ALL JUNCTION BOXES SHALL BE LABELED IDENTIFYING THE PANELBOARD AND CIRCUIT CONTAINED WITHIN. THERE SHALL BE NO MORE THAN (3) CIRCUITS PER HOMERUN. MULTI-WIRE CIRCUITS ARE NOT ALLOWED. EACH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL UNLESS SPECIFICALLY ALLOWED BY THE ENGINEER. ALL WIRING SHALL BE SIZED ACCORDING TO AMPACITY OF THE CIRCUIT BREAKER INDICATED ON THE PANEL SCHEDULES. ALL CONDUIT SHALL BE SIZED PER NEC CODE BASED ON THE CONDUCTOR SIZE, TYPE, QUANTITY AND MINIMUM FILL REQUIREMENTS. CIRCUITS OVER 120 FEET FOR 120V AND 250' FOR 277V SHALL BE UP SIZED ONE WIRE SIZE TO ACCOUNT FOR VOLTAGE DROP. E.C. IS RESPONSIBLE TO SHOW ALL JUNCTION BOX LOCATIONS, CONDUIT ROUTING
AND HOMERUNS ON A SET OF AS-BUILT DRAWINGS.
3. FEED THROUGH GFCI RECEPTACLES SHALL NOT BE USED.
4. ALL SPARE CONDUITS (FOR FUTURE USE) SHALL BE LABELED "SPARE/FUTURE CONDUIT" AT EACH END OF THE CONDUIT
WITH 1/2" TALL LETTERS, USING A PERMANENT MARKER.
5. SEE ALL DETAIL SHEETS AND RISER DIAGRAMS FOR ADDITIONAL WORK. ALL DETAILS AND RISERS ARE APPLICABLE TO
THIS PROJECT WHETHER REFERENCED OR NOT.
6. ALL GROUNDING SHALL CONFORM TO NEC 250.
7. CIRCUITING SHALL BE PROVIDED AS REQUIRED TO MEET THE NEC. ALL SINGLE POLE CIRCUITS SHALL BE PROVIDED WITH
DEDICATED NEUTRALS.
8. PROVIDE CUTTING AND PATCHING OF EXISTING WALLS TO ACCOMMODATE INSTALLATION OF NEW WORK.COORDINATE
WITH G.C.
MULTI-GANGED SWITCH (LOWER CASE LETTERS INDICATES SWITCHING)ba
RADIO ANTENNA
7/1 2/2
ELECTRICAL INDEX
# SHEET TITLE
E-001 ELECTRICAL LEGEND, INDEX, AND ABBREVIATIONS
E-101 OVERALL ELECTRICAL SITE PLAN
E-401 ENLARGED ELECTRICAL SITE PLAN
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL ONE-LINE DIAGRAM & PANEL SCHEDULES
E-001
GA
TE
TR
TRAN
GA
TE
GA
TE
GA
TE
WOOD SHED
FISH LADDER
CO
NC
RE
TE
W
EI
R
INTAKE
ABERNATHY CREEK ROAD
WIEST ROAD
ABERNATHY CREEK
ABERNATHY CREEK
ED
GE O
F W
ATE
R
(9/
/2
8)
ED
GE O
F W
ATE
R
(9/27/2018)
EDGE OF W
ATER
(9/30/2018)
EDGE OF WATER
(9/30/2018)
EDGE OF W
ATER
(9/27/2018)
ED
GE
O F
W
AT
ER
(9
/2 7/
EDGE OF W
ATER
(9/25/2018)
ED
GE O
F W
ATE
R
(9/
/2
8)
EDGE OF W
ATER
(9/28/2018)
EDGE OF WATER
(9/28/2018)
REFELCTOR
STOP
ABERNATHY CREEK ROAD
UNDERSID
E OF
BRIDGE DECK
ELEVATION = 229.6'
UNDERSID
E OF
BRIDGE DECK
ELEVATION = 231.0'
DEBRIS SCREEN
WIEST CREEK
BOULDER WALL
AC
CE
SS
R
OA
D
REFLE
CTOR
REFLE
CTOR
EXISTING
UTILITY POLE
UTILITY SERVICE
TO INTAKE
EXISTING UTILITY
TRANSFORMER
EXISTING
UNDERGROUND
UTILITY PRIMARY
EXISTING
UNDERGROUND
UTILITY PRIMARY
METER
VAULT
JW
PROPERTY
LINE
FTC
INTAKE
A-6
CONSTRUCTION NOTES
PROVIDE (1) JUNCTION BOX FOR CONTROL CABLING AND (1)
JUNCTION BOX FOR POWER CABLING FOR FLOW METER AT
NEW METER VAULT.
PROVIDE (1) 1" CONDUIT FOR CONTROL CABLING AND (1) 1"
CONDUIT FOR POWER CABLING BETWEEN INTAKE SERVICE
POINT AND NEW METER VAULT.
7/1 2/2
0 30' 60'
SCALE: 1"=30'-0"
10'20'
SCALE:
N1 OVERALL ELECTRICAL SITE PLAN
1"=30'-0"
E-101
C
EXISTING CCTV
CAMERA
EXISTING POLE
SEE SITE PLAN
FOR CONTINUATION
M
EXISTING ANTENNA
EXISTING CCTV AND
TELEMETRY
ENCLOSURE
EXISTING
SERVICE PANEL A
a b a
W, a, b
EXISTING
SWITCH
FL1
FL1
INTAKE SCREEN
CLEANER CONTROL
PANEL
EXISTING
METER
EXISTING
SERVICE PANEL A
SEE SITE PLAN
FOR CONTINUATION
PROPERTY
BOUNDARY
1 1
M
G,W
G,W
RECEPTACLE
ON 4"X4" TREATED
WOOD POST
J
POWER AND
CONTROL
CONDUIT
A-3
A-3
A-5
FL1
A-5
A-5
JJ
2" C., POWER
C 43 NEW POST
BRUSH MOTOR
W W b a a
W, a, b
EXISTING
SWITCH
A- 2,4
DEMOLITION NOTES
EXISTING LIGHT AND CONDUIT TO BE REMOVED AND REPLACED
WITH NEW.
EXISTING CCTV AND TELEMETRY PANEL SHALL BE RELOCATED AS
SHOWN INCLUDING ASSOCIATED POWER AND COMMUNICATIONS
CONNECTIONS.
EXISTING CCTV CAMERA AND ANTENNA INCLUDING ASSOCIATED
APPURTENANCES TO BE RELOCATED TO LOCATION SHOWN ON
CONSTRUCTION PLAN.
CONSTRUCTION NOTES
THE CONTRACTOR SHALL MOUNT ALL ELECTRICAL EQUIPMENT
ABOVE THE FLOOD PLANE.
TERMINATE CONTROL CONDUIT INTO EXISTING CCTV CONTROL
CABINET. PROVIDE CONDUIT PLUG TO LIMIT MOISTURE INGRESS.
EXISTING CCTV AND TELEMETRY PANEL REVISED LOCATION.
PROVIDE MOUNTING HARDWARE, CONDUIT, CABEL AND
ASSOCIATED APPURTENANCES FOR A COMPLETE, FUNCTIONAL
CCTV SYSTEM WITH REMOTE TELEMETRY CONNECTION.
NEW POST WITH RELOCATED CCTV CAMERA (6'-0" AFG) AND
ANTENNA (12'-0" AFG) INCLUDING ASSOCIATED APPURTENANCES.
GENERAL NOTES
1. ALL NEW DEVICES SHALL BE CIRCUITED TO THE NEW INTAKE PANEL.
2. ALL NEW CONDUIT AND DEVICES SHALL BE NEMA 3R & OUTDOOR
RATED UNLESS NOTED OTHERWISE.
7/1 2/2
SCALE:
N1 ENLARGED DEMOLITION SITE PLAN
1/4"=1'-0"
4' 2' 0 4' 8'
SCALE: 1/4" = 1'-0"
SCALE:
N2 ENLARGED CONSTRUCTION SITE PLAN
1/4"=1'-0"
4' 2' 0 4' 8'
SCALE: 1/4" = 1'-0"
E-401
8"
BEDDING MATERIAL
SLOPE DETERMINED
BY CONTRACTOR
COMPACTED
BACKFILL TO
95% DENSITY
DEPTH AS REQUIRED
TO AVOID EXISTING
UTILITIES AND MEET
CODE REQUIREMENTS
EXISTING GROUND
REPLACE LANDSCAPE TO MATCH
EXISTING
3" MIN.
4" TOPSOIL
MARKER TAPE LAID
ENTIRE LENGTH WITH
3" MIN. WIDTH
1' 1'
EXISTING PAVEMENT
MATERIAL(S) AND
SECTION MAY VARY
2" ASPHALT CONCRETE
WEARING COURSE
SLOPE DETERMINED
BY CONTRACTOR
6" BASE COURSE
MATERIAL
BEDDING MATERIAL
COMPACTED BACKFILL
TO 95% DENSITY
EXISTING BASE
COURSE
SAWCUT AND
TACK COAT (TYP)
3" ASPHALT CONCRETE
BINDER COURSE
DEPTH AS REQUIRED
TO AVOID EXISTING
UTILITIES AND MEET
CODE REQUIREMENTS
3" MIN.
SCALE:1 TRENCHING DETAIL - ASPHALT AREAS
DIAGRAMMATIC SCALE:2 TRENCHING DETAIL - LANDSCAPE AREAS
DIAGRAMMATIC
CONDUIT PER
PLAN (TYP.)
CONDUIT PER
PLAN (TYP.)
SCALE:3 METER VAULT DETAIL
DIAGRAMMATIC
J J
FLOW METER
WITH TRANSDUCER
CONSTRUCTION NOTES
ALL CONDUIT SHALL BE SUBMERSIBLE TYPE CABLE FOR POWER.
PROVIDE MOUNTING AS REQUIRED.
TO PANEL 'A' OR PREVIOUS DEVICE.
THE SUPPORT FRAME INDICATED IS INTENDED TO CONVEY THE INTENT OF THE
SUPPORT SYSTEM. THE CONTRACTOR SHALL ADJUST THE DESIGN PARAMETERS AS
REQUIRED BASED ON THE EXISTING EQUIPMENT AND CONDITIONS PRESENT FOR A
COMPLETE SUPPORT FRAME SYSTEM. THE SUPPORT POST SHALL BE INSTALLED TO
MATCH THE EXISTING SUPPORT POST FOR CONSISTENCY. THE NEW SUPPORT
FRAME SHALL BE PARALLEL TO THE INTAKE RETAINING WALL AND PROVIDE
SUFFICIENT CLEARANCE REQUIRED FOR THE EQUIPMENT.
METER VAULT
WATER PIPE
A-6
TO PANEL 'A'
FLOW METER
ASSEMBLY
SCALE:4 LIGHT FIXTURE WALL MOUNT
DIAGRAMMATIC
SPLICE BOX
TO NEXT RECEPACTACLE
TO NEXT FIXTURE
EXISTING
CONCRETE WALL
NEW LIGHT FIXTURE
5"X5" TREATED WOOD POST
SPLICE BOX
DUPLEX RECEPTACLE
GRADE
EXISTING PANELEXISTING METER
NEW 5"X5"
TREATED WOOD
POLE
NEW 1 5/8" UNISTRUT,
3' - 8" LONG
EXISTING CCTV
PANEL
SCALE:5 EQUIPMENT SUPPORT DETAIL
1" = 1' - 0"
7/1 2/2
E-501
UTILITY TRANSFORMER
12.47KV-120/240V M
20A/2P
SCREEN
CLEANING
CONTROL
PANEL
INTAKE
SERVICE PANEL 'A'
100A, 120/240V
2"C., (3) #2 CU., #2 CU GND
UTILITY
METER
SCALE:1
EXISTING ONE-LINE DIAGRAM
NTS
FROM
UTILITY
100A/2P
1HP, 240V-3P, SCREEN
CLEANING MOTOR
1"C., WITH CONTROL CABLING
TO NEW METER VAULT
J W
1HP, 240V-3P, SCREEN
CLEANING MOTOR FLOW METER
TRANSDUCTER
GRADE
J
W
20A/2P
3/4"C., (3) #10 CU., #10 CU GND
1/2" C., (2) #10 CU, #10 CU GND
CONSTRUCTION NOTES
CONDUIT BY EC, CABLE BY SCREEN SYSTEM MANUFACTURER. MINIMUM SIZE
(3) #12 CU. W #12 GND IN 1/2" CONDUIT. EC SHALL COORDINATE WITH THE
SCREEN SYSTEM MANUFACTURER PRIOR TO ROUGH-IN.
J
J
7/1 2/2
E-601