9-SLCC Jordan Campus Remodel Bid Addendum One 2025-07-22.pdf

PDF 2 MB Posted

Attached to
SLCC HTC CNA/MA Project State and local contract opportunity
Solicitation number
SLCC2025-W1006
Issued by
Salt Lake County, Salt Lake City, Utah

About this file

This document is a Bid Addendum #1 for the SLCC Jordan Campus CNA/MA Remodel project located at 3491 W 9000 S, West Jordan, UT 84088, issued by Galloway on July 22, 2025. The addendum modifies the originally issued project documents dated 06-27-2025 and provides clarifications and responses to several bidder questions. Key items include confirming the deck height between first and second floors is 15'-0", providing a floor prep allowance of $3,620 for 2,120 square feet, and addressing technical specifications for data line raceways, plumbing lines, cabinet construction, and fire alarm contractors.

The addendum includes specific details such as allowing ProPress fittings for copper plumbing lines, confirming Nelson Fire as the preferred fire alarm contractor, and specifying millwork finish materials: PL-1 Cabinets in Formica Graystone 464 with a matte finish and SSF-1 Counters in Hanex Oslo White. The document also clarifies that while AWI certification is not required, cabinets are expected to maintain AWI level construction for commercial use, with drawer construction specified as Baltic birch or equivalent using dovetail construction. Additional mechanical and architectural clarifications are provided, including changes to HVAC dampers in fire-rated walls and updates to architectural drawings.

View the file

Other files for this state and local contract opportunity

Other files attached to SLCC HTC CNA/MA Project, newest first.
File Type Posted
10-2025.07.22 SLCC CNA MA Remodel Revised Permit Set.pdf PDF
11-tabulation sheet SLCC HTC CNA-MA Project.xlsx XLSX spreadsheet
6-SLCC Jordan CNA-MA Project Manual.pdf PDF
1-SALT LAKE COMMUNITY COLLEGE GENERAL BID PROVISIONS.pdf PDF
3-Contractors-Agreement (1).docx DOCX document
4-Subcontractors+List (1).docx DOCX document
5-Invitation for Bid - SLCC HTC CNA-MA Project F25015.docx DOCX document
2-Certificate-of-Substantial-Completion (1).docx DOCX document
7-2025.06.27 SLCC CNA MA Remodel Permit Set.pdf PDF
8-20250714 130335.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(Insert client logo here)

6162 S. Willow Drive, Suite 320

Greenwood Village, CO 80111

303.770.8884 • GallowayUS.com

BID ADDENDUM #1

July 22, 2025

SLCC Jordan Campus CNA/MA Remodel 3491 W 9000 S West Jordan, UT 84088 Architect’s Project Number: SLA000004.30

FROM: Galloway 577 South 200 East

SLC, UT 84111

TO: All Bidders

This addendum forms a part of the Contract Documents and modifies the ISSUED Set of the Project Documents dated 06-27-2025:

Responses:

Sheet Text.

1. What is the deck height between the first and second floor?

15’-0”

2. Can you please provide an allowance or bidding standard for floor prep? It is impossible to verify before demolition and conditions under the existing floor can vary drastically. This will ensure that we will all be bidding apples to apples.

See attached specification 00 4322 – Unit Prices Form.

3. For the data lines raceways, are conduits required all the way back to the data room or are J-

Hooks acceptable once we stub out of the walls with conduit?

See response attached from Engineer

4. Can we use Pro Press for the copper plumbing lines in lieu of soldered?

See attached response from Engineer.

5. Do cabinets need to be AWI certified? The specs call for it but for a job of this size it will have a distinct impact on who will be able to submit bids for millwork and the pricing.

Cabinets do not need AWI certification but will be expected as per the specification to maintain AWI level construction for commercial use. Drawer construction to be Baltic birch or equivalent with dovetail construction as indicated in the spec. Particle board or MDF are not acceptable.

6. Is there a Preferred Fire Alarm Contractor?

Nelson Fire

7. Please provide millwork finish materials and color selections.

PL-1 Cabinets – Formica – Graystone 464 – Matte Finish SSF-1 Counters – Hanex – Oslo White

Client Name Project Name – Bid Addendum Date

Galloway & Company, Inc. Page 2 of 2

8. On AI101, it references W3 Head Walls. However, I cannot find a W3 identified in any detail, please clarify.

Head walls and other locations with W3 are indicated on AI101 w/ a dashed line. See attached updated AI101 for better clarification.

9. Additional HVAC information includes changes in dampers in fire rated walls as per code/permit review. See attached ME101.

END OF ADDENDUM

SLCC Jordan Campus CNA-MA Lab Remodel 00 4322 - 1 Unit Prices Form

SECTION 00 4322

UNIT PRICES FORM

PARTICULARS

1.01 THE FOLLOWING IS THE LIST OF UNIT PRICES REFERENCED IN THE BID SUBMITTED BY:

1.02 (BIDDER) ________________________________

1.03 DATED _________________ AND WHICH IS AN INTEGRAL PART OF THE BID FORM.

UNIT PRICE LIST

2.01 ITEM DESCRIPTION UNIT QUANTITY UNIT PRICE LABOR MATERIAL TOTAL

2.02 FLOOR PREP ALLOWANCE - SF - 2,120 - $1.00 - $2,120 - $1,500 - $3,620

END OF SECTION

RESPONSE TO RFI

QUESTIONS

RESPONSE TO RFI QUESTIONS

To: Annette Coleman From: Alex Ecton

Company: Galloway

Date: 07/22/2025

Project: SLCC HTC CAN/MA

RFI Question

1. Comment: For the data lines raceways, are conduits required all the way back to the data room or are J-Hooks acceptable once we stub out of the walls with conduit?

Response: Detail 4 on sheet EE501 calls for the data conduit to extend to the accessible ceiling.

SLCC IT will utilize j-hooks above the accessible ceiling.

WHW ENGINEERING, LLC.

MECHANICAL

& PLUMBING

E N G I N E E R I N G

WHW ENGINEERING LLC

733 West 9000 South - Sandy, Utah - 84070

p. 801.466.4021

July 22, 2025

GALLOWAY US

Salt Lake City, Utah 84111

ATTN: Annette Coleman RE: SLCC HTC CAN/MA Remodel - Addendum #1

Dear Annette, Please see below for modifications to the project listed above included in Addendum #1.

I. QUESTIONS AND ANSWERS:

4. Can we use ProPress for the copper plumbing lines in lieu of soldered?

Response: Yes, ProPress fittings are allowed and encourages for domestic water piping.

II. CHANGES/CLARIFICATIONS TO DRAWINGS:

ME101: Added transfer with fire damper from the Storage room above the ceiling.

We appreciate the opportunity to work with you on this project. If you need additional information or have any questions, please do not hesitate to contact our office. Thank you.

Sincerely, Brad Lash WHW Engineering

CLASSROOM

CLASSROOM

RR

247A

CLASSROOM

STORAGE

249A

ELECTRICAL

LANDING

200L

EF

4 4

4 4

6"ø EA UP

6"ø EA

6"ø EA

VAV

91H

VAV

90H

VAV

88H

VAV

89H

T

VAV-88H

T

VAV-89H

T

VAV-90H

15T

VAV-91H

10"x10" TA

FD

EXIST

EXIST

EXIST

EXIST

D-3

D-3

D-3

D-3

D-2

D-2

D-2

D-2

D-2

D-2

D-2

D-2

1 1

1 1

1 1

1 1

1 1

1 1 R-1 2

R-1

R-1

R-1

R-1

R-1 2

EF

D-1

R-1

11 11

11 11

GENERAL NOTES

1. CONTRACTOR SHALL FIELD VERIFY

EXISTING MECHANICAL AND

ARCHITECTURAL CONDITIONS.

INCLUDING, BUT NOT LIMITED TO:

EXISTING ROUTING AND LOCATION OF

DUCTWORK, PIPING, ELECTRICAL AND

STRUCTURAL ELEMENTS.

CONTRACTOR SHALL FIELD VERIFY

POTENTIAL CONFLICTS BETWEEN

NEW MECHANICAL ELEMENTS AND

EXISTING CONDITIONS PRIOR TO

BEGINNING FABRICATION OR

ORDERING EQUIPMENT.

2. ALL DEMOLISHED EQUIPMENT AND

MATERIAL SHALL BE BROKEN DOWN

TO FIT THROUGH DESIGNATED

PATHWAYS. FIELD VERIFY EXACT

SCOPE OF DEMOLITION AND REMOVAL

PATH. CONTRACTOR SHALL BE

RESPONSIBLE TO REPAIR ANY

DAMAGE TO BUILDING DURING

REMOVAL OF EQUIPMENT AND

MATERIAL.

3. SOME EXISTING PIPING AND

EXISTING DUCTWORK NOT SHOWN ON

THIS SHEET FOR CLARITY. FIELD

VERIFY EXISTING CONDITIONS PRIOR

TO BID.

4. PROVIDE FULL TEST AND BALANCE

REPORT OF ALL IMPACTED SYSTEMS

BY LICENSED AND APPROVED TEST &

BALANCE CONTRACTOR.

5. DEMOLITION AND CONSTRUCTION

ON LEVEL ONE TO BE COORDINATED

WITH OWNER TO AVOID INTERFERING

WITH SCHEDULED CLASSES. SOME

WORK MAY NEED TO BE PERFORMED

AFTER HOURS.

6. BUILDING SHALL REMAIN

CONDITIONED AND OCCUPIABLE, AND

SHALL MEET CLEAN AIR

REQUIREMENTS OF ASHRAE

STANDARD 62.1 DURING THE ENTIRE

PROJECT.

BRADLEY D.

LASH

No. 8681468

P R

O F

E

SS IONAL ENG

IN

E

E R

S T

A T E

O F U T

A H

577 South 200 East

Salt Lake City, Utah

801.533.2100

Checked By:

Project No:

Drawn By:

COPYRIGHT

THESE PLANS ARE AN INSTRUMENT OF SERVICE

AND ARE THE PROPERTY OF GALLOWAY, AND MAY

NOT BE DUPLICATED, DISCLOSED, OR

REPRODUCED WITHOUT THE WRITTEN CONSENT

OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS

WILL BE ENFORCED AND PROSECUTED.

STAMP

06/27/25

7/22/2025 9:51:38 AM

A ut od es k D oc s:

//S

LA

-S

LA

-U

T -W

J- Jo rd an

-C am pu s-

C N

A -M

A

B

R

/2

S

LC

C

C N

A M

A R em od el M

P

.r vt

LEVEL 2 MECHANICAL FLOOR

PLAN

ME101

SLA000004

CSP

JLS

W

S

W E

S T

J O

R D

A N

, U T

S

LC

C J

O R

D A

N C

N A

/M A

R E

M O

D E

L

S

LC

C

3/16" = 1'-0"

LEVEL 2 MECHANICAL FLOOR PLAN3/16" = 1'-0"

LEVEL 2 MECHANICAL REFLECTED

CEILING PLAN

SHEET NOTES

1 PROVIDE SUPPLY DIFFUSER IN

THIS APPROXIMATE LOCATION.

COORDINATE PRECISE LOCATION

WITH LIGHTS AND CEILING TYPE.

BALANCE TO CFM SHOWN. FIELD

VERIFY.

2 PROVIDE RETURN GRILLE WITH

SOUND BOOT PER DETAIL 1/ME501

IN THIS APPROXIMATE LOCATION.

COORDINATE PRECISE LOCATION

WITH LIGHTS AND CEILING TYPE.

FIELD VERIFY.

3 PROVIDE CEILING MOUNTED

EXHAUST FAN IN THIS

APPROXIMATE LOCATION.

COORDINATE PRECISE LOCATION

WITH LIGHTS AND CEILING TYPE.

FIELD VERIFY.

4 CONNECT TO EXISTING LOW

PRESSURE SUPPLY DUCT IN THIS

APPROXIMATE LOCATION. FIELD

VERIFY.

5 COORDINATE DUCT ROUTING WITH

EXISTING CONDITIONS. PROVIDE

OFFSETS AS NEEDED. FIELD

VERIFY.

6 EXHAUST DUCT TO RISE UP IN THIS

APPROXIMATE LOCATION AND

TERMINATE ABOVE ROOF WITH

CAP AND BIRD SCREEN. MAINTAIN

A MINIMUM OF 10’ FROM ANY

OUTDOOR AIR INTAKE PER IMC

501.3. COORDINATE WITH NORTH

FACE ROOFING TO MAINTAIN ALL

ROOFING WARRANTIES.

7 EXISTING VAV IN THIS

APPROXIMATE LOCATION TO

REMAIN AND BE REUSED.

REBALANCE TO 2060 MAX CFM,

AND 795 MIN CFM. FIELD VERIFY.

8 EXISTING VAV IN THIS

APPROXIMATE LOCATION TO

REMAIN AND BE REUSED.

REBALANCE TO 2040 MAX CFM,

AND 615 MIN CFM. FIELD VERIFY.

9 EXISTING VAV IN THIS

APPROXIMATE LOCATION TO

REMAIN AND BE REUSED.

REBALANCE TO 1500 MAX CFM,

AND 450 MIN CFM. FIELD VERIFY.

10 EXISTING VAV IN THIS

APPROXIMATE LOCATION TO

REMAIN AND BE REUSED.

REBALANCE TO 1625 MAX CFM,

AND 490 MIN CFM. FIELD VERIFY.

11 EXISTING DIFFUSER SHALL

REMAIN. REBALANCE THE SYSTEM

TO CFM SHOWN.

12 EXISTING TRANSFER DUCTS AND

DAMPERS SHALL REMAIN.

13 EXISTING DUCTWORK SHALL

REMAIN UNLESS OTHERWISE

NOTED.

14 INSTALL SALVAGED THERMOSTAT

IN THIS APPROXIMATE LOCATION.

FIELD VERIFY.

15 EXISTING THERMOSTAT IN THIS

APPROXIMATE LOCATION TO

REMAIN AND BE REUSED.

PRESERVE AND PROTECT DURING

DEMOLITION AND CONSTRUTION.

FIELD VERIFY.

16 EXISTING DAMPER SHALL REMAIN.

17 PROVIDE NEW FIRE DAMPER AND

TRANSFER DUCT THROUGH 1

HOUR FIRE WALL. INSTALL PER

MANUFACTURERS

RECOMMENDATIONS TO MAINTAIN

FIRE RATING.

# Date Issue/Description

1 7/9/25 BCS Response

CLASSROOM

EDNET

EDNET

ELECTRICAL

LANDING

200L

CLASSROOM

CLASSROOM

RR

247A

HALL

200K

HALLWAY

EDNET

EQUIPMENT

STORAGE

249A

ROOF

HATCH

249B

STUDY

AREA

W1/B1

W /B

W /B

W1/B1

W1/B1

W /B

W /B

W1/B1

W1/B1

W /B

W /B

W1/B1

W1/B1

W /B

W /B

W1/B1

W /B

KEY NOTES:?

GENERAL NOTES:

1. ALL WALL PAINT IS TO HAVE A SATIN FINISH U.N.O..

2. ALL DOOR FRAMES ARE TO HAVE A SEMI-GLOSS FINISH

U.N.O..

3. INSTALLER IS TO REFER TO SPECIFICATION FOR

INSTALLATION METHODS AND REQUIREMENTS

4. ALL EXPOSED GYP. BD. SURFACES ARE TO RECEIVE A

LEVEL 4 FINISH

FINISH PLAN LEGEND:

WALL FINISH TYPE / BASE TYPE, SEE AE122

FLOOR FINISH INSTALLATION

DIRECTIONAL ARROW, SEE AE122

WX/BX

W X

/B X

W X

/B X

WX/BX

T1 THRESHOLD TYPE

W3 - WALL PROTECTION. COORDINATE

LENGTH WITH HEAD WALLS AND PRIVACY

CURTAINS

FINISH SCHEDULE NOTES:

1. EXISTING FINISHES TO REMAIN IN CLASSROOM 245

6'

FLOOR AS SCHEDULED

W1

W2

SCALE 1/4" = 1'-0"AI101

A2 TYPICAL RESTROOM ELEVATION

577 South 200 East

Salt Lake City, Utah

801.533.2100

Checked By:

Project No:

Drawn By:

COPYRIGHT

THESE PLANS ARE AN INSTRUMENT OF SERVICE

STAMP

# Date Issue/Description

AND ARE THE PROPERTY OF GALLOWAY, AND MAY

NOT BE DUPLICATED, DISCLOSED, OR

REPRODUCED WITHOUT THE WRITTEN CONSENT

OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS

WILL BE ENFORCED AND PROSECUTED.

7/22/2025 11:44:00 AM

A ut od es k D oc s:

//S

LA

-S

LA

-U

T -W

J- Jo rd an

-C am pu s-

C N

A -M

A

B

R

/S

LA

-A

E -3

D -S

LC

C

C N

A _M

A -R

E M

O D

E L.

rv t

SECOND LEVEL FINISH PLAN

AI101

SLA000004

Author

Checker

W

S

W E

S T

J O

R D

A N

, U T

D F

C M

S

LC

C J

O R

D A

N C

N A

/M A

R E

M O

D E

L

S

LC

C

SCALE 1/8" = 1'-0"AI101

A1 OVERALL SECOND LEVEL FLOOR PLAN

BASE FINISH SCHEDULE

TYPE DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES

B1 INTEGRAL COVED FORBO MARMOLEUM TBD

B2 WOOD BASE TO MATCH EXISTING

FLOOR FINISH LEGEND

TYPE FILL DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES

F1 VINYL FORBO MAMOLEUM TBD

WALL FINISH LEGEND

TYPE DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES

W1 FIELD PAINT VALLEY PAINT SLCC HTC - MAIN WALL

COLOR

W2 CERAMIC TILE DALTILE COLORWHEEL 4X12 0790 MATTE ARCTIC WHITE SEE A2/AI101 ELEVATION

W3 WALL PROTECTION ACROVYN ALMOND 60" HEIGHT WITH TRIMMED EDGES

2 07.22.2025 Addendum #1

Product Image Feedback

ACROVYN Wall Covering: 48 in Ht, 120 in Lg, 1/16 in Thick, Almond, Acrovyn(R)

Item 55LF77

Mfr. Model WC60410NP920N

Product Details Catalog Page N/A

Brand ACROVYN

Height 48 in

Length 120 in

Thickness 1/16 in

Color Almond

Material Acrovyn(R)

UNSPSC 30102515

Country of Origin USA (subject to change)

Product Details Feedback

Compliance & Restrictions

Documents

Compare

Your Price $384.17 / each

This item requires special shipping, additional charges may apply.

Ship to 84084 | Change

Shipping Weight 18 lbs Ship Availability Terms

Add to List

Add to Quote

Add to Cart1 Qty

Setup Auto Reorder

Ship Pickup

Ships from supplier. Expected to arrive on or before Mon. Jul 29.

This item is restricted for international sale.

Installation Guide

File details come from the government source that posted it. Updated .