9-SLCC Jordan Campus Remodel Bid Addendum One 2025-07-22.pdf
PDF 2 MB Posted
- Attached to
- SLCC HTC CNA/MA Project State and local contract opportunity
- Solicitation number
- SLCC2025-W1006
- Issued by
- Salt Lake County, Salt Lake City, Utah
About this file
This document is a Bid Addendum #1 for the SLCC Jordan Campus CNA/MA Remodel project located at 3491 W 9000 S, West Jordan, UT 84088, issued by Galloway on July 22, 2025. The addendum modifies the originally issued project documents dated 06-27-2025 and provides clarifications and responses to several bidder questions. Key items include confirming the deck height between first and second floors is 15'-0", providing a floor prep allowance of $3,620 for 2,120 square feet, and addressing technical specifications for data line raceways, plumbing lines, cabinet construction, and fire alarm contractors.
The addendum includes specific details such as allowing ProPress fittings for copper plumbing lines, confirming Nelson Fire as the preferred fire alarm contractor, and specifying millwork finish materials: PL-1 Cabinets in Formica Graystone 464 with a matte finish and SSF-1 Counters in Hanex Oslo White. The document also clarifies that while AWI certification is not required, cabinets are expected to maintain AWI level construction for commercial use, with drawer construction specified as Baltic birch or equivalent using dovetail construction. Additional mechanical and architectural clarifications are provided, including changes to HVAC dampers in fire-rated walls and updates to architectural drawings.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| 10-2025.07.22 SLCC CNA MA Remodel Revised Permit Set.pdf | ||
| 11-tabulation sheet SLCC HTC CNA-MA Project.xlsx | XLSX spreadsheet | |
| 6-SLCC Jordan CNA-MA Project Manual.pdf | ||
| 1-SALT LAKE COMMUNITY COLLEGE GENERAL BID PROVISIONS.pdf | ||
| 3-Contractors-Agreement (1).docx | DOCX document | |
| 4-Subcontractors+List (1).docx | DOCX document | |
| 5-Invitation for Bid - SLCC HTC CNA-MA Project F25015.docx | DOCX document | |
| 2-Certificate-of-Substantial-Completion (1).docx | DOCX document | |
| 7-2025.06.27 SLCC CNA MA Remodel Permit Set.pdf | ||
| 8-20250714 130335.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(Insert client logo here)
6162 S. Willow Drive, Suite 320
Greenwood Village, CO 80111
303.770.8884 • GallowayUS.com
BID ADDENDUM #1
July 22, 2025
SLCC Jordan Campus CNA/MA Remodel 3491 W 9000 S West Jordan, UT 84088 Architect’s Project Number: SLA000004.30
FROM: Galloway 577 South 200 East
SLC, UT 84111
TO: All Bidders
This addendum forms a part of the Contract Documents and modifies the ISSUED Set of the Project Documents dated 06-27-2025:
Responses:
Sheet Text.
1. What is the deck height between the first and second floor?
15’-0”
2. Can you please provide an allowance or bidding standard for floor prep? It is impossible to verify before demolition and conditions under the existing floor can vary drastically. This will ensure that we will all be bidding apples to apples.
See attached specification 00 4322 – Unit Prices Form.
3. For the data lines raceways, are conduits required all the way back to the data room or are J-
Hooks acceptable once we stub out of the walls with conduit?
See response attached from Engineer
4. Can we use Pro Press for the copper plumbing lines in lieu of soldered?
See attached response from Engineer.
5. Do cabinets need to be AWI certified? The specs call for it but for a job of this size it will have a distinct impact on who will be able to submit bids for millwork and the pricing.
Cabinets do not need AWI certification but will be expected as per the specification to maintain AWI level construction for commercial use. Drawer construction to be Baltic birch or equivalent with dovetail construction as indicated in the spec. Particle board or MDF are not acceptable.
6. Is there a Preferred Fire Alarm Contractor?
Nelson Fire
7. Please provide millwork finish materials and color selections.
PL-1 Cabinets – Formica – Graystone 464 – Matte Finish SSF-1 Counters – Hanex – Oslo White
Client Name Project Name – Bid Addendum Date
Galloway & Company, Inc. Page 2 of 2
8. On AI101, it references W3 Head Walls. However, I cannot find a W3 identified in any detail, please clarify.
Head walls and other locations with W3 are indicated on AI101 w/ a dashed line. See attached updated AI101 for better clarification.
9. Additional HVAC information includes changes in dampers in fire rated walls as per code/permit review. See attached ME101.
END OF ADDENDUM
SLCC Jordan Campus CNA-MA Lab Remodel 00 4322 - 1 Unit Prices Form
SECTION 00 4322
UNIT PRICES FORM
PARTICULARS
1.01 THE FOLLOWING IS THE LIST OF UNIT PRICES REFERENCED IN THE BID SUBMITTED BY:
1.02 (BIDDER) ________________________________
1.03 DATED _________________ AND WHICH IS AN INTEGRAL PART OF THE BID FORM.
UNIT PRICE LIST
2.01 ITEM DESCRIPTION UNIT QUANTITY UNIT PRICE LABOR MATERIAL TOTAL
2.02 FLOOR PREP ALLOWANCE - SF - 2,120 - $1.00 - $2,120 - $1,500 - $3,620
END OF SECTION
RESPONSE TO RFI
QUESTIONS
RESPONSE TO RFI QUESTIONS
To: Annette Coleman From: Alex Ecton
Company: Galloway
Date: 07/22/2025
Project: SLCC HTC CAN/MA
RFI Question
1. Comment: For the data lines raceways, are conduits required all the way back to the data room or are J-Hooks acceptable once we stub out of the walls with conduit?
Response: Detail 4 on sheet EE501 calls for the data conduit to extend to the accessible ceiling.
SLCC IT will utilize j-hooks above the accessible ceiling.
WHW ENGINEERING, LLC.
MECHANICAL
& PLUMBING
E N G I N E E R I N G
WHW ENGINEERING LLC
733 West 9000 South - Sandy, Utah - 84070
p. 801.466.4021
July 22, 2025
GALLOWAY US
Salt Lake City, Utah 84111
ATTN: Annette Coleman RE: SLCC HTC CAN/MA Remodel - Addendum #1
Dear Annette, Please see below for modifications to the project listed above included in Addendum #1.
I. QUESTIONS AND ANSWERS:
4. Can we use ProPress for the copper plumbing lines in lieu of soldered?
Response: Yes, ProPress fittings are allowed and encourages for domestic water piping.
II. CHANGES/CLARIFICATIONS TO DRAWINGS:
ME101: Added transfer with fire damper from the Storage room above the ceiling.
We appreciate the opportunity to work with you on this project. If you need additional information or have any questions, please do not hesitate to contact our office. Thank you.
Sincerely, Brad Lash WHW Engineering
CLASSROOM
CLASSROOM
RR
247A
CLASSROOM
STORAGE
249A
ELECTRICAL
LANDING
200L
EF
4 4
4 4
6"ø EA UP
6"ø EA
6"ø EA
VAV
91H
VAV
90H
VAV
88H
VAV
89H
T
VAV-88H
T
VAV-89H
T
VAV-90H
15T
VAV-91H
10"x10" TA
FD
EXIST
EXIST
EXIST
EXIST
D-3
D-3
D-3
D-3
D-2
D-2
D-2
D-2
D-2
D-2
D-2
D-2
1 1
1 1
1 1
1 1
1 1
1 1 R-1 2
R-1
R-1
R-1
R-1
R-1 2
EF
D-1
R-1
11 11
11 11
GENERAL NOTES
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS.
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS.
CONTRACTOR SHALL FIELD VERIFY
POTENTIAL CONFLICTS BETWEEN
NEW MECHANICAL ELEMENTS AND
EXISTING CONDITIONS PRIOR TO
BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. ALL DEMOLISHED EQUIPMENT AND
MATERIAL SHALL BE BROKEN DOWN
TO FIT THROUGH DESIGNATED
PATHWAYS. FIELD VERIFY EXACT
SCOPE OF DEMOLITION AND REMOVAL
PATH. CONTRACTOR SHALL BE
RESPONSIBLE TO REPAIR ANY
DAMAGE TO BUILDING DURING
REMOVAL OF EQUIPMENT AND
MATERIAL.
3. SOME EXISTING PIPING AND
EXISTING DUCTWORK NOT SHOWN ON
THIS SHEET FOR CLARITY. FIELD
VERIFY EXISTING CONDITIONS PRIOR
TO BID.
4. PROVIDE FULL TEST AND BALANCE
REPORT OF ALL IMPACTED SYSTEMS
BY LICENSED AND APPROVED TEST &
BALANCE CONTRACTOR.
5. DEMOLITION AND CONSTRUCTION
ON LEVEL ONE TO BE COORDINATED
WITH OWNER TO AVOID INTERFERING
WITH SCHEDULED CLASSES. SOME
WORK MAY NEED TO BE PERFORMED
AFTER HOURS.
6. BUILDING SHALL REMAIN
CONDITIONED AND OCCUPIABLE, AND
SHALL MEET CLEAN AIR
REQUIREMENTS OF ASHRAE
STANDARD 62.1 DURING THE ENTIRE
PROJECT.
BRADLEY D.
LASH
No. 8681468
P R
O F
E
SS IONAL ENG
IN
E
E R
S T
A T E
O F U T
A H
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
STAMP
06/27/25
7/22/2025 9:51:38 AM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/2
S
LC
C
C N
A M
A R em od el M
P
.r vt
LEVEL 2 MECHANICAL FLOOR
PLAN
ME101
SLA000004
CSP
JLS
W
S
W E
S T
J O
R D
A N
, U T
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
3/16" = 1'-0"
LEVEL 2 MECHANICAL FLOOR PLAN3/16" = 1'-0"
LEVEL 2 MECHANICAL REFLECTED
CEILING PLAN
SHEET NOTES
1 PROVIDE SUPPLY DIFFUSER IN
THIS APPROXIMATE LOCATION.
COORDINATE PRECISE LOCATION
WITH LIGHTS AND CEILING TYPE.
BALANCE TO CFM SHOWN. FIELD
VERIFY.
2 PROVIDE RETURN GRILLE WITH
SOUND BOOT PER DETAIL 1/ME501
IN THIS APPROXIMATE LOCATION.
COORDINATE PRECISE LOCATION
WITH LIGHTS AND CEILING TYPE.
FIELD VERIFY.
3 PROVIDE CEILING MOUNTED
EXHAUST FAN IN THIS
APPROXIMATE LOCATION.
COORDINATE PRECISE LOCATION
WITH LIGHTS AND CEILING TYPE.
FIELD VERIFY.
4 CONNECT TO EXISTING LOW
PRESSURE SUPPLY DUCT IN THIS
APPROXIMATE LOCATION. FIELD
VERIFY.
5 COORDINATE DUCT ROUTING WITH
EXISTING CONDITIONS. PROVIDE
OFFSETS AS NEEDED. FIELD
VERIFY.
6 EXHAUST DUCT TO RISE UP IN THIS
APPROXIMATE LOCATION AND
TERMINATE ABOVE ROOF WITH
CAP AND BIRD SCREEN. MAINTAIN
A MINIMUM OF 10’ FROM ANY
OUTDOOR AIR INTAKE PER IMC
501.3. COORDINATE WITH NORTH
FACE ROOFING TO MAINTAIN ALL
ROOFING WARRANTIES.
7 EXISTING VAV IN THIS
APPROXIMATE LOCATION TO
REMAIN AND BE REUSED.
REBALANCE TO 2060 MAX CFM,
AND 795 MIN CFM. FIELD VERIFY.
8 EXISTING VAV IN THIS
APPROXIMATE LOCATION TO
REMAIN AND BE REUSED.
REBALANCE TO 2040 MAX CFM,
AND 615 MIN CFM. FIELD VERIFY.
9 EXISTING VAV IN THIS
APPROXIMATE LOCATION TO
REMAIN AND BE REUSED.
REBALANCE TO 1500 MAX CFM,
AND 450 MIN CFM. FIELD VERIFY.
10 EXISTING VAV IN THIS
APPROXIMATE LOCATION TO
REMAIN AND BE REUSED.
REBALANCE TO 1625 MAX CFM,
AND 490 MIN CFM. FIELD VERIFY.
11 EXISTING DIFFUSER SHALL
REMAIN. REBALANCE THE SYSTEM
TO CFM SHOWN.
12 EXISTING TRANSFER DUCTS AND
DAMPERS SHALL REMAIN.
13 EXISTING DUCTWORK SHALL
REMAIN UNLESS OTHERWISE
NOTED.
14 INSTALL SALVAGED THERMOSTAT
IN THIS APPROXIMATE LOCATION.
FIELD VERIFY.
15 EXISTING THERMOSTAT IN THIS
APPROXIMATE LOCATION TO
REMAIN AND BE REUSED.
PRESERVE AND PROTECT DURING
DEMOLITION AND CONSTRUTION.
FIELD VERIFY.
16 EXISTING DAMPER SHALL REMAIN.
17 PROVIDE NEW FIRE DAMPER AND
TRANSFER DUCT THROUGH 1
HOUR FIRE WALL. INSTALL PER
MANUFACTURERS
RECOMMENDATIONS TO MAINTAIN
FIRE RATING.
# Date Issue/Description
1 7/9/25 BCS Response
CLASSROOM
EDNET
EDNET
ELECTRICAL
LANDING
200L
CLASSROOM
CLASSROOM
RR
247A
HALL
200K
HALLWAY
EDNET
EQUIPMENT
STORAGE
249A
ROOF
HATCH
249B
STUDY
AREA
W1/B1
W /B
W /B
W1/B1
W1/B1
W /B
W /B
W1/B1
W1/B1
W /B
W /B
W1/B1
W1/B1
W /B
W /B
W1/B1
W /B
KEY NOTES:?
GENERAL NOTES:
1. ALL WALL PAINT IS TO HAVE A SATIN FINISH U.N.O..
2. ALL DOOR FRAMES ARE TO HAVE A SEMI-GLOSS FINISH
U.N.O..
3. INSTALLER IS TO REFER TO SPECIFICATION FOR
INSTALLATION METHODS AND REQUIREMENTS
4. ALL EXPOSED GYP. BD. SURFACES ARE TO RECEIVE A
LEVEL 4 FINISH
FINISH PLAN LEGEND:
WALL FINISH TYPE / BASE TYPE, SEE AE122
FLOOR FINISH INSTALLATION
DIRECTIONAL ARROW, SEE AE122
WX/BX
W X
/B X
W X
/B X
WX/BX
T1 THRESHOLD TYPE
W3 - WALL PROTECTION. COORDINATE
LENGTH WITH HEAD WALLS AND PRIVACY
CURTAINS
FINISH SCHEDULE NOTES:
1. EXISTING FINISHES TO REMAIN IN CLASSROOM 245
6'
FLOOR AS SCHEDULED
W1
W2
SCALE 1/4" = 1'-0"AI101
A2 TYPICAL RESTROOM ELEVATION
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
7/22/2025 11:44:00 AM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
SECOND LEVEL FINISH PLAN
AI101
SLA000004
Author
Checker
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1/8" = 1'-0"AI101
A1 OVERALL SECOND LEVEL FLOOR PLAN
BASE FINISH SCHEDULE
TYPE DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES
B1 INTEGRAL COVED FORBO MARMOLEUM TBD
B2 WOOD BASE TO MATCH EXISTING
FLOOR FINISH LEGEND
TYPE FILL DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES
F1 VINYL FORBO MAMOLEUM TBD
WALL FINISH LEGEND
TYPE DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES
W1 FIELD PAINT VALLEY PAINT SLCC HTC - MAIN WALL
COLOR
W2 CERAMIC TILE DALTILE COLORWHEEL 4X12 0790 MATTE ARCTIC WHITE SEE A2/AI101 ELEVATION
W3 WALL PROTECTION ACROVYN ALMOND 60" HEIGHT WITH TRIMMED EDGES
2 07.22.2025 Addendum #1
Product Image Feedback
ACROVYN Wall Covering: 48 in Ht, 120 in Lg, 1/16 in Thick, Almond, Acrovyn(R)
Item 55LF77
Mfr. Model WC60410NP920N
Product Details Catalog Page N/A
Brand ACROVYN
Height 48 in
Length 120 in
Thickness 1/16 in
Color Almond
Material Acrovyn(R)
UNSPSC 30102515
Country of Origin USA (subject to change)
Product Details Feedback
Compliance & Restrictions
Documents
Compare
Your Price $384.17 / each
This item requires special shipping, additional charges may apply.
Ship to 84084 | Change
Shipping Weight 18 lbs Ship Availability Terms
Add to List
Add to Quote
Add to Cart1 Qty
Setup Auto Reorder
Ship Pickup
Ships from supplier. Expected to arrive on or before Mon. Jul 29.
This item is restricted for international sale.
Installation Guide
File details come from the government source that posted it. Updated .