7-2025.06.27 SLCC CNA MA Remodel Permit Set.pdf
PDF 8 MB Posted
- Attached to
- SLCC HTC CNA/MA Project State and local contract opportunity
- Solicitation number
- SLCC2025-W1006
- Issued by
- Salt Lake County, Salt Lake City, Utah
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| 10-2025.07.22 SLCC CNA MA Remodel Revised Permit Set.pdf | ||
| 11-tabulation sheet SLCC HTC CNA-MA Project.xlsx | XLSX spreadsheet | |
| 6-SLCC Jordan CNA-MA Project Manual.pdf | ||
| 9-SLCC Jordan Campus Remodel Bid Addendum One 2025-07-22.pdf | ||
| 5-Invitation for Bid - SLCC HTC CNA-MA Project F25015.docx | DOCX document | |
| 1-SALT LAKE COMMUNITY COLLEGE GENERAL BID PROVISIONS.pdf | ||
| 3-Contractors-Agreement (1).docx | DOCX document | |
| 4-Subcontractors+List (1).docx | DOCX document | |
| 2-Certificate-of-Substantial-Completion (1).docx | DOCX document | |
| 8-20250714 130335.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WOOD MOLDING
PLYWOOD (SECTION)
CONCRETE (SECTION)
GYPSUM BOARD (SECTION)
TILE (PLAN)
COMPACTED GRAVEL
(SECTION)
STONE VENEER (PLAN,
SECTION)
BRICK VENEER (PLAN,
SECTION)
CMU (PLAN, SECTION)
STEEL FRAMING (PLAN,
SECTION)
COMPACTED SUBGRADE
RIGID INSULATION
(SECTION)
LANDSCAPE - PLANTING
ROOM
NAME
101A
1i
AEXXX
NAME
ELEVATION
AEXXX
SIM
AEXXX
SIM
SCALE
1 VIEW NAME
SCALEAEXXX
A
ROOM TAG
DOOR TAG
WINDOW TAG
INTERIOR ELEVATION
ELEVATION, (DATUM)
DETAIL
WALL SECTION /
EXTERIOR ELEVATION
DRAWING TITLE
REVISION TAG
GRID HEAD
WALL TYPE
AEXXX
SIM
CENTERLINE
BUILDING SECTION
FLAG
KEYNOTE TAG
WINDOW GLAZING
TAGG3
W-11
ARCHITECT
Galloway & Co.
577 South 200 East Salt Lake City, Utah 84111 (801)533-2100 Ph.
Architect: Jonathon Faull PM: Annette Coleman annettecolmal@GallowayUS.com
MECHANICAL & PLUMBING ENGINEER
WHW Engineers 733 W 9000 S Sandy, Utah 84070
(801) 466-4021 Ph.
Contact: Jacob Sutch jacobs@whw-engineering.com
ELECTRICAL ENGINEER
Envision Engineering 240 E Morris Ave, Suite 200 Salt Lake City, Utah 84115
(801) 534-1130 Ph.
Contact: Alex Ecton aecton@envisioneng.com
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
GENERAL INFORMATION
GI001
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SLCC
SLCC JORDAN CNA/MA REMODEL
3491 W 9000 S
WEST JORDAN, UT 84088
DFCM #25476680
PERMIT SET
06/27/2025
DRAWING INDEXMATERIALS / SYMBOLS DESIGN TEAM
VICINITY MAP
ABBREVIATIONS
GENERAL INFORMATION
GI001 GENERAL INFORMATION
GI100 CODE REVIEW
GI301 STANDARD ACCESSIBILITY DETAILS
GI302 STANDARD ACCESSIBILITY DETAILS
GI401 WALL TYPES
GI402 WALL DETAILS
DEMOLITION
DP101 SECOND LEVEL DEMOLITION PLAN
DP131 SECOND LEVEL DEMO REFLECTED CEILING PLAN
ARCHITECTURAL
AE100 OVERALL SECOND LEVEL FLOOR PLAN
AE101 SECOND LEVEL FLOOR PLAN
AE131 SECOND LEVEL REFLECTED CEILING PLAN
AE401 ENLARGED PLANS AND ELEVATIONS
AE541 REFLECTED CEILING DETAILS
AE601 SCHEDULES
INTERIORS
AI101 SECOND LEVEL FINISH PLAN
AI301 CASEWORK SECTIONS
AI501 INTERIOR FINISH DETAILS
MECHANICAL
MG001 MECHANICAL LEGEND & GENERAL NOTES
MD102 LEVEL 2 MECHANICAL DEMOLITION FLOOR PLAN
ME102 LEVEL 2 MECHANICAL FLOOR PLAN
ME601 MECHANICAL DETAILS & SCHEDULES
PLUMBING
PG001 PLUMBING LEGEND & GENERAL NOTES
PD101 LEVEL 1 PLUMBING DEMOLITION FLOOR PLAN
PD102 LEVEL 2 PLUMBING DEMOLITION FLOOR PLAN
PE102.1 LEVEL 1 PLUMBING FLOOR PLANS
PE102.2 LEVEL 2 PLUMBING FLOOR PLANS
PE601 PLUMBING SCHEDULES & DETAILS
ELECTRICAL
EG001 GENERAL NOTES & SYMBOLS LISTS
EE100 LEVEL 2 - OVERALL
EE101 LEVEL 2 - LIGHTING & ELECTRICAL
EE501 ELECTRICAL DETAILS
EE502 ACCESS CONTROLS & DATA ROUG-IN DETAILS
EE503 LIGHTING WIRING DIAGRAM DETAILS
EE601 ELECTRICAL SCHEDULES
A
ABV ABOVE
AFF ABOVE FINISH FLOOR
AC ACOUSTIC
ADD ADDENDUM
AC AIR CONDITIONING
ALT ALTERNATE
ALUM ALUMINUM
AB ANCHOR BOLT
& AND
ANOD ANODIZED
ARCH ARCHITECT(URAL)
ASPH ASPHALT
@ AT
B
BSMT BASEMENT
BLW BELOW
BM BENCHMARK
BLKG BLOCKING
BD BOARD
BO BOTTOM OF
BLDG BUILDING
C
CAB CABINET
CPT CARPET
CIP CAST IN PLACE
CB CATCH BASIN
CLG CEILING
CL CENTER LINE
CT CERAMIC TILE
CH CHANNEL
CO CLEAN OUT
CLR CLEAR
CL. CLOSET
COL COLUMN
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
COND CONDITION
CONN. CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CJ CONTROL JOINT
D
DP DAMP PROOFING
DB DECK BEARING
DEMO DEMOLISH(ED)
DIAG DIAGONAL
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DWL DOWEL
DN DOWN
DS DOWN SPOUT
DRN. BD. DRAINAGE BOARD
DWG DRAWING
E
EA EACH
EWC ELEC. WATER COOLER
ELEC ELECTRIC
ELEV ELEVATION
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
EJ EXPANSION JOINT
EXT EXTERIOR
F
FT FEET
FIN FINISH(ED)
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER &
CABINET
FIXT FIXTURE
FL FLASHING
FLR FLOOR
FTG FOOTING
FND FOUNDATION
G
GALV GALVANIZED
GA GAUGE
GC GENERAL CONTRACTOR
GSN GENERAL STRUCTURAL
NOTES
GL GLASS OR GLAZING
GD GRADE
GRL GRILLE
GRD GROUND
GYP GYPSUM
H
HDW HARDWARE
HDWD HARDWOOD
HTR HEATER
HT HEIGHT
HP HIGH POINT
HM HOLLOW METAL
HORIZ HORIZONTAL
HB HOSE BIB
HW HOT WATER
HR HOUR
HSK HOUSEKEEPING
I
IN INCH
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
INV INVERT
J
JAN JANITOR
JT JOINT
JST JOIST
L
LAM LAMINATED
LNDG LANDING
LAV LAVATORY
LVR LOUVER
M
MFR. MANUFACTURER
MO MASONRY OPENING
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MEZZ MEZZANINE
MIN MINIMUM
MULL MULLION
N
NG NATURAL GRADE
NOM NOMINAL
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
O
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
OD OUTSIDE DIAMETER
ORD OVERFLOW ROOF DRAIN
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
P
PNT PAINT
PR. PAIR
PNL PANEL
PVMT PAVEMENT
d PENNY
P-LAM PLASTIC LAMINATE
PL PLATE
PLBG PLUMBING
PLYWD PLYWOOD
PSI POUND PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
R
RAD RADIUS
RCP REFLECTED CEILING PLAN
REG REGISTER
REQD REQUIRED
RA RETURN AIR
REV REVISION
RD ROOF DRAIN
RFG ROOFING
RM ROOM
RGH ROUGH
RND ROUND
S
SECT SECTION
SHT SHEET
SIM SIMILAR
SLDG SLIDING
SPEC SPECIFICATION
SPL SPLASH
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STOR STORAGE
STRUC STRUCTURE OR STRUCTURAL
SA SUPPLY AIR
SUSP SUSPENDED
T
TELCO TELEPHONE COMPANY
TG TEMPERED GLASS
T&G TONGUE & GROOVE
T&B TOP & BOTTOM
TO TOP OF
TOC TOP OF CURB
TOD TOP OF DECK
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOW TOP OF WALL
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
V
V VENT
VTR VENT THROUGH ROOF
VERT VERTICAL
VEST VESTIBULE
VCT VINYL COMPOSITION TILE
W
WC WATER CLOSET
WH WATER HEATER
WP WATER PROOF
WR WATER RESISTANT
WWF WELDED WIRE FABRIC
WF WIDE FLANGE
WDW WINDOW
W/ WITH
W/O WITHOUT
WD WOOD
DEFERRED SUBMITTALS
FIRE ALARM SYSTEM
FIRE SPRINKLER SYSTEM
SITE
9000 SOUTH
B A
N G
E R
T E
R H
W Y
OF E UT TA AT HS
No. 14200675-0301
JONATHON FAULL
30JUN2025
3491 W 9000 S
WEST JORDAN, UT 84088
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2021 INTERNATIONAL FIRE CODE
2023 NATIONAL ELECTRIC CODE
2021 INTERNATIONAL PLUMBING CODE
2021 INTERNATIONAL MECHANICAL CODE
2021 INTERNATIONAL FUEL AND GAS CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2017 ANSI A117.1, NFPA 101, NFPA 1221 CURRENT VERSION.
2021 AHJ AMENDMENTS
PROJECT ADDRESS:
APPLICABLE CODES:
FIRE AND SMOKE PROTECTION (CHAPTER 7)PROJECT DESCRIPTION
THE PROJECT SCOPE INCLUDES CONSTRUCTION TO REMODEL THREE EXISTING CLASSROOM FOR USE OF THE CNA PROGRAM. THE NEW CLASSROOMS AND LABS WILL BE OCCUPANCY TYPE B. THE PRINCIPLE USE OF THE CLASSROOMS AND LABS WILL INCLUDE
CLINICAL INSTRUCTION AND TRAINING SPACES.
APPLICABLE CODES
OCCUPANCY CLASSIFICATION AND USE (CHAPTER 3)
MEANS OF EGRESS (CHAPTER 10)
OCCUPANT LOAD CALCULATED (TABLE 1004.1.2)
EXITING REQUIREMENTS
REFER TO GI100 EGRESS PLAN FOR EXITING
SECTION 703.7 - MARKING AND IDENTIFICATION
• WHERE FIRE BARRIERS, FIRE WALLS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
REQUIRED TO HAVE PROTECTED OPENINGS OR PENETRATIONS OCCUR, SUCH ASSEMBLIES SHALL BE PERMANENTLY IDENTIFIED
WITH SIGNS OR STENCILING IN THE CONCEALED SPACE PER SECTION 703.7
SECTION 705 - EXTERIOR WALLS
• EXTERIOR WALLS WITH A FIRE SEPARATION DISTANCE OF > 10 FEET NEED ONLY BE RATED FOR EXPOSURE TO FIRE FROM THE
INSIDE
• OPENINGS IN EXTERIOR WALLS SHALL COMPLY WITH SECTION 705.8.
SECTION 713 - SHAFT ENCLOSURES
• SHAFT ENCLOSURES SHALL NOT BE LESS THAN 1-HOUR FIRE BARRIERS
SECTION 714 - PENETRATIONS
• FIRESTOP ALL PENETRATIONS IN THE FIRE-RATED ASSEMBLIES WITH APPROVED MATERIAL IN ACCORDANCE WITH SECTION 714.
• WALLS WITH THROUGH PENETRATIONS REQUIRE FIRESTOP SYSTEMS SUITABLE FOR THE METHOD OF PENETRATION PER SECTION
714.3.1
• ELECTRICAL BOXES LOCATED ON OPPOSITE SIDES OF THE RATED WALL SHALL BE SEPARATED BY A HORIZONTAL DISTANCE OF 24"
MINIMUM PER SECTION 714.3.2, EXCEPTIONS 1.1 AND 1.2.
• MEMBRANE PENETRATIONS OF THE FIRE-RESISTIVE WALLS SHALL COMPLY WITH SECTION 714.3.2. THE ANNULAR SPACE CREATED
BY THE PENETRATION OF A FIRE SPRINKLER SHALL BE PERMITTED TO BE UNPROTECTED PROVIDED SUCH SPACE IS COVERED BY
A METAL ESCUTCHEON PLATE PER EXCEPTION 5.
• PENETRATIONS THROUGH RATED FLOOR/CEILING ASSEMBLIES REQUIRE PROTECTION BY MEANS OF PROPER MATERIALS AND SEALANT. PROVIDE FIRE DAMPERS OR APPROVED EQUIVALENT AT HVAC OUTLETS WITHIN FLOOR/CEILING ASSEMBLIES.
SECTION 716 - OPENING PROTECTIVES
• OPENING IN FIRE RESISTIVE RATED ASSEMBLIES SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 716.
FIRE PROTECTION SYSTEMS (CHAPTER 9)
YES, EXISTING TO REMAIN
YES
AUTOMATIC SPRINKLER SYSTEM REQUIRED PER 903
DEFERRED SUBMITTAL
YES, EXISTING TO REMAIN
YES
FIRE ALARM AND DETECTION SYSTEM REQUIRED PER 907
DEFERRED SUBMITTAL
YESFIRE EXTINGUISHERS REQUIRED PER 906
EXISTING TO REMAIN, NO PROPOSED CHANGES
THE MEANS OF EGRESS PATH SHALL NOT BE REDUCED UNTIL ARRIVAL AT THE PUBLIC WAY
MAXIMUM EXIT ACCESS TRAVEL DISTANCE (TABLE1017.2)
EXISTING TO REMAIN, NO PROPOSED CHANGES
EMERGENCY RESPONDER RADIO COMMUNICATION SYSTEM
DEFERRED SUBMITTAL
YES, EXISTING TO REMAIN
YES
SECTION 803 - WALL AND CEILING FINISHES
• WHERE ALL WALLS AND CEILINGS ARE REQUIRED TO BE OF FIRE RESISTANCE-RATED CONSTRUCTION OR NON- COMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR CEILING ARE DROPPED DISTANCES GREATER THAN SPECIFIED IN SECTION 803.1.1, CLASS A FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2 SHALL BE USED. THE HANGERS AND ASSEMBLY MEMBERS OF SUCH DROPPED CEILING THAT ARE BELOW THE MAIN CEILING LINE SHALL BE OF NON-COMBUSTIBLE MATERIALS, EXCEPT THOSE IN TYPES III, FRTW SHALL BE PERMITTED AND THE CONSTRUCTION OF EACH SET-OUT WALL SHALL BE OF FIRE
INTERIOR FINISHES (CHAPTER 8)
SECTION 903 - AUTOMATIC SPRINKLER SYSTEMS
• SPRINKLER SYSTEM TO BE NFPA 13 IN ACCORDANCE WITH SECTION 903.3.1.1 AND FM GLOBAL REQUIREMENTS AUTOMATIC
SPRINKLER SYSTEM PLANS SHALL BE SUBMITTED TO DETERMINE COMPLIANCE WITH APPLICABLE BUILDING, PLUMBING, AND FIRE CODES TO THE FIRE DEPARTMENT FOR REVIEW AND APPROVAL. VALVES FOR CONTROLLING THE WATER SUPPLY FOR AUTOMATIC SPRINKLER SYSTEMS AND WATER-FLOW SWITCHES SHALL BE ELECTRONICALLY MONITORED PER SECTION 903.4.
MEANS OF EGRESS SIZING, SECTION 1005
EGRESS WIDTH
WHERE MULTIPLE MEANS OF EGRESS ARE REQUIRED, THEN THEY SHALL BE SIZED SUCH THAT THE LOSS OF ANYONE MEANS OD EGRESS SHALL NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50 PERCENT OF THE REQUIRED CAPACITY MINIMUM REQUIRED EGRESS WIDTH PER SECTION 1005.3.1 EQUALS TOTAL OCCUPANT LOAD SERVED
A. STAIRWAY WIDTH 0.3" PER OCCUPANT
B. OTHER EGRESS COMPONENTS 0.2" PER OCCUPANT
C. DOOR ENCROACHMENT WHEN FULLY OPEN SHALL NOT REDUCE THE REQUIRED MEANS OF EGRESS NOT MORE THAN 7"
NUMBER OF EXITS AND EXIT ACCESS DOORWAYS SECTION 1006
NUMBER OF EXITS AND EXIT ACCESS DOORWAYS REQUIRED WITHIN THE MEANS OF EGRESS SYSTEM SHALL COMPLY WITH THE
PROVISIONS OF SECTION 1006.2
ACCESSIBLE MEANS OF EGRESS, SECTION 1009
EXISTING TO REMAIN, NO PROPOSED CHANGES
STAIRWAYS, SECTION 1011
EXISTING TO REMAIN, NO PROPOSED CHANGES
EXIT SIGNS, SECTION 1013
EXISTING TO REMAIN, NO PROPOSED CHANGES
HANDRAILS, SECTION 1014
EXISTING TO REMAIN, NO PROPOSED CHANGES
GUARDS, SECTION 1015
EXISTING TO REMAIN, NO PROPOSED CHANGES
TYPES OF CONSTRUCTION (CHAPTER 6)
II-BCONSTRUCTION TYPE:
FIRE RESISTANCE RATING REQUIREMENTS (TABLE 601)
N/A N/A
PRIMARY STRUCTURAL FRAME
BEARING WALLS - EXTERIOR
BEARING WALLS - INTERIOR
NONBEARING WALLS & PARTITIONS - EXTERIOR
SEPARATION LESS THAN 5'
SEPARATION BETWEEN 5' & 10'
SEPARATION BETWEEN 10' & 30'
SEPARATION OVER 30'
NONBEARING WALLS & PARTITIONS - INTERIOR
FLOOR CONSTRUCTION & ASSOCIATED SECONDARY MEMBERS
ROOF CONSTRUCTION & ASSOCIATED SECONDARY MEMBERS
GENERAL BUILDING HEIGHT AND AREA (CHAPTER 5)
ACCESSIBILITY - (CHAPTER 11)
ACCESSIBLE ENTRANCES PER SECTION 1105
PUBLIC ENTRANCES: EXISTING TO REMAIN, NO PROPOSED CHANGES
PARKING PER SECTION 1106
EXISTING TO REMAIN, NO PROPOSED CHANGES
PLUMBING SYSTEMS ( CHAPTER 29)
PLUMBING FIXTURES: NO ADDITIONAL FIXTURES ARE REQUIRED, PROPOSED TOILET ROOM FOR VOCATIONAL TRAINING
MIXED OCCUPANCY SEPARATION
BUILDING HEIGHT: 130'-0" - EXISTING TO REMAIN, NO PROPOSED CHANGES
SEPARATION PROVIDE PER TABLE 508.4: A-3/B (1-HOUR)
NUMBER OF STORIES ABOVE GRADE PLANE: 2 STORIES - EXISTING TO REMAIN, NO PROPOSED CHANGES
EXISTING OCCUPANCIES TO REMAIN, SELECT GROSS AREAS TO BE ADJUSTED
ROOM 245: A-3 OCCUPANCY REMAINS THE SAME GROSS AREA REMAINS THE SAME
ROOM 247: A-3 OCCUPANCY REMAINS THE SAME GROSS AREA INCREASED FROM 644 SF TO 847 SF ROOM 249: A-3 OCCUPANCY REMAINS THE SAME GROSS AREA DECREASED FROM 1277 SF TO 1023 SF ROOM 251: B OCCUPANCY REMAINS THE SAME GROSS AREA INCREASED FROM 176 SF TO 249 SF
ROOM 245: OCCUPANCY LOAD REMAINS THE SAME
ROOM 247: OCCUPANCY LOAD - (847/50) = 16.94 = 17
ROOM 249: OCCUPANCY LOAD - (1023/50) = 20.46 = 21
ROOM 251: OCCUPANCY LOAD - (249/300) = 0.83 = 1
862 SF
CLASSROOM
EDNET
EDNET
ELECTRICAL
LANDING
200L
1023 SF
CLASSROOM
CLASSROOM
RR
247AHALL
200K
HALLWAY
EDNET
EQUIPMENT
STORAGE
249A
ROOF
HATCH
249B
STUDY
AREA
847 SF
249 SF
10.04
10.05
02.19
LEGEND:
OCCUPANCY TYPE A-3
OCCUPANCY TYPE B
1 HOUR FIRE BARRIER TO UNDERSIDE OF
FLOOR OR ROOF STRUCTURE, LABEL AND
IDENTIFY WALL IN ACCORDANCE WITH IBC
703.7.
PATH OF EGRESS
COMBINED OCCUPANCY LOAD & MEANS OF
EGRESS
ROOM OCCUPANCY LOAD & MEANS OF
EGRESS
KEY NOTES:?
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:56:02 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
CODE REVIEW
GI100
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
GROSS SQUARE FOOTAGE PER OCCUPANCY PER SOW:
OCCUPANCY GROSS AREA
SCALE 1/8" = 1'-0"GI100
A5 SECOND LEVEL EGRESS PLAN
02.19 EXISTING 36" STAIR ACCESS DOOR TO REMAIN
10.04 EXISTING FIRE EXTINGUISHER
10.05 EXISTING PORTABLE FIRE EXTINGUISHER
OF E UT TA AT HS
No. 14200675-0301
INFORMATION SHOWN FOR REFERENCE ONLY. SIGNAGE PACKAGE TO BE APPROVED BY
DEFERRED SUBMITTAL.
SUBMIT ALL DESIGN DOCUMENTS TO OWNER / ARCHITECT FOR REVIEW PRIOR TO INSTALL /
FABRICATION.
STAIRWAY IDENTIFICATION SIGNS
STAIR 1
1' - 0" MIN.
1'
M
IN
5'
M
IN
NO ROOF ACCESS
DOWN TO LEVEL 1
FOR EXIT DISCHARGE
LETTERING REQUIREMENTS:
STAIR IDENTIFICATION LETTERS - 1 1/2" MIN. IN HEIGHT
FLOOR LEVEL NUMBER - 5" MIN. IN HEIGHT
OTHER LETTERING - 1" MIN. IN HEIGHT
PERMANENT ROOMS AND SPACES SIGNAGE
FLOOR
#2
R A
IS
E
D C
H A
R A
C T
E R
M
IN
T
O B
O T
T O
M O
F L
O W
E S
T
R A
IS
E
D C
H A
R A
C T
E R
M A
X
T O
B O
T T
O M
O F
H
IG
H E
S T
ACCESSIBLE SIGNAGE, RE
ICC 2017 117.1,SECT. 703
GENERAL PUBLIC SIGNAGE,
RE. IBC 2021, SECT1023.9 &
IFC 1023.9.1
RAISED CHARACTERS REQUIREMENTS:
- 5/8" MIN. & 2" MAX.IN HEIGHT
- 1/32" MIN. IN DEPTH
LIBRARY
R A
IS
E
D C
H A
R A
C T
E R
M
IN
T
O B
O T
T O
M O
F L
O W
E S
T
R A
IS
E
D C
H A
R A
C T
E R
M A
X
T O
B O
T T
O M
O F
H
IG
H E
S T
RAISED CHARACTERS REQUIREMENTS:
- 5/8" MIN. & 2" MAX.IN HEIGHT
- 1/32" MIN. IN DEPTH
INFORMATION SHOWN FOR REFERENCE ONLY. SIGNAGE PACKAGE TO BE APPROVED BY
DEFERRED SUBMITTAL.
SUBMIT ALL DESIGN DOCUMENTS TO OWNER / ARCHITECT FOR REVIEW PRIOR TO INSTALL /
FABRICATION.
.0
0°
1' - 6"
M
IN
1'
CLEAR FLOOR SPACE CENTERED ON
TACTILE CHARACTERS AND LOCATED
BEYOND ARC OF DOOR SWING
LOCATION OF SIGNS AT DOORS
2'
M
IN
3'
M
IN
2' - 0" MAX. 4' - 4" MIN. 2' - 0" MAX.
2'
3'
CLEAR WIDTH OF ACCESSIBLE ROUTE AT 1800 TURN
5'
C
LR
. M
IN
3' - 0" CLR. MIN. X<52" 3' - 0" CLR. MIN.
NEW BUILDING - OPTION 1
4'
C
LR
. M
IN
3' - 6" CLR. MIN. X<52" 3' - 6" CLR. MIN.
NEW BUILDING - OPTION 2
3'
C
LR
. M
IN
3' - 7" CLR. MIN. X<52" 3' - 7" CLR. MIN.
NEW BUILDING - OPTION 3
CLEAR WIDTH OF ACCESSIBLE ROUTE AT 900 TURN
3'
C
LR
.M
IN
0' - 4" MIN. 2' - 0" MIN.
0'
M
IN
2'
M
IN
3' - 0" CLR. MIN.
NEW BUILDING - OPTION 1
3'
C
LR
.M
IN
3' - 0" CLR. MIN.
0' - 8" MIN.
NEW BUILDING - OPTION 2
0'
M
IN
3'
C
LR
.M
IN
3' - 0" CLR. MIN.
NEW BUILDING - OPTION 4
3'
C
LR
.M
IN
3' - 2" CLR. MIN.
NEW BUILDING - OPTION 3
CLEAR WIDTH OF ACCESSIBLE ROUTE - NEW BUILDING - INTERIOR
PULL SIDE
*IF BOTH A CLOSER AND LATCH PROVIDED
PUSH SIDE
FRONT APPROACH
SIDE APPROACHES _
PULL SIDE PUSH SIDE
PULL SIDE PUSH SIDE
NOTE:
X = 36" MIN. IF Y = 60";
X = 42" MIN. IF Y = 54"
NOTE:
Y = 48" MIN. IF BOTH A LATCH AND
CLOSER PROVIDED
NOTE:
Y = 54" MINIMUM IF CLOSER
PROVIDED
NOTE:
Y = 48" MINIMUM IF DOOR
HAS BOTH A LATCH AND CLOSER
LATCH SIDE APPROACHES
FRONT APPROACH
LATCH SIDE APPROACH
SLIDE SIDE APPROACH
2' - 0" MIN.
3'
4'
M
IN
3'
M
IN
1' - 10" MIN.
4'
M
IN
2' - 0" MIN. 2' - 0" MIN.
3'
M
IN
X Y
M
IN
Y
4' - 6" MIN.
1' - 6" MIN.
5'
M
IN
SLIDING DOOR
CLEAR WIDTH OF DOORWAYS
MIN.
32" CLR.
MIN.
32" CLR.
HINGED DOOR
RE.: ICC A117.1 , SECT. 404 FOR MORE
INFORMATION REGARDING DOORS IN
ALCOVES AND SERIES OF DOORS
(B) SLIDING AND FOLDING DOORS
(A) SWINGING DOORS
MANEUVERING CLEARANCES AT DOORS
M
IN
. E X
IS
T
. B
LD
G
1' - 0" MIN*
4'
M
IN
E X
IS
T
IN
G
B
LD
G S
M
IN
5' - 0" MIN.
1' - 0"3' - 0" MIN.1' - 0"
5'
M
IN
3'
M
IN
EXISTING BUILDINGS
WHEELCHAIR TURNING FLOOR SPACE
WHEELCHAIR CLEAR FLOOR SPACE
4' - 4" MIN.
2'
M
IN
4' - 0" MIN.
2'
M
IN
NEW CONSTRUCTION EXISTING BLDG
5' - 7"
1' - 0"3' - 0" MIN.1' - 0"
5'
M
IN
3'
M
IN
NEW CONSTRUCTION
2'
M A
X
OVERLAP OF KNEE AND TOE CLEARANCE
1' - 0"3' - 0" MIN.1' - 0"
5'
M
IN
3'
M
IN
0'
0"
M A
X
OVERLAP OF KNEE AND TOE CLEARANCE OPTION 1
1' - 0"3' - 0" MIN.1' - 0"
5'
M
IN
3'
M
IN
OPTION 3 OPTION 2
0' - 11" MIN. 0' - 6" MAX.
8" MIN.
0'
M
IN
2'
M
IN
25" MAX KNEE
1' - 5" -25" TOE
KNEE AND TOE CLEARANCE
PROTECT SHADED AREA
FROM CROSS-TRAFFIC
CANE DETECTION RAIL
OBJECT PROTRUDE
INTO CIRCULATION
PASS
2'
M A
X
6'
REDUCED VERTICAL CLEARANCE
UNOBSTRUCTED FORWARD REACH OBSTRUCTED HIGH FORWARD REACH
UNOBSTRUCTED SIDE REACH
OBSTRUCTED HIGH SIDE REACH
1'
M
IN
. 4'
M A
X
4'
M A
X
1' - 8" MAX.
> 20"-25" MAX.
3'
M A
X
1'
M
IN
. 4'
M A
X
0' - 10" MAX.
0' - 10" MAX.
4'
M A
X
>10"- 2' - 0" MAX.
3'
0"
M A
X
REACH RANGE
OBSTRUCTED HIGH FORWARD REACH
2'
0"
M A
X
OBSTRUCTED HIGH SIDE REACH
5' - 0" MIN.
X
3' - 0" MIN.
X
PARALLEL APPROACH FORWARD APPROACH
MANEUVERING CLEARANCES IN AN ALCOVE PROTRUDING OBJECTS
CHANGE IN LEVEL
VERTICAL CHANGE IN LEVEL
1/ 4"
M A
X 1/ 2"
M A
X
/4
/4
1/ 2"
M A
X
BEVELED CHANGE IN LEVEL
0"
2'
C A
N E
D E
T E
C T
IO
N
Z O
N E
2'
M
IN
0' - 4" MAX.
PROTRUDING OBJECT
CANNOT REDUCE
MIN. WIDTH OF
ACCESSIBLE ROUTE;
CANE DETECTION
MEASURES ON BOTH
SIDES NEEDED
OBJECT ABOVE
CIRCULATION PASS
6'
C
LR
. M
IN
. C
IR
C U
LA
T
IO
N
P A
S S
H E
IG
H
T
CIRCULATION PASS
REQUIRED ACCESSIBLE
ANY WIDTH
X
7"
X
0"
ANY WIDTH
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:56:03 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
STANDARD ACCESSIBILITY
DETAILS
GI301
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 3/8" = 1'-0"GI301
5 SIGNAGE
SCALE 3/8" = 1'-0"GI301
4 ACCESSIBLE ROUTE
SCALE 3/16" = 1'-0"GI301
1 ADA DOORS DOORWAYS & GATES
SCALE 3/8" = 1'-0"GI301
3 ACCESSIBLE CLEAR AND TURNING SPACES
OF E UT TA AT HS
No. 14200675-0301
WALL MOUNTED URINALS
16"-18"
4'
M
IN
5' - 0" MIN.
1' - 0" MAX. 3' - 6" MIN.
-OTHER FIXTURES ARE NOT
ALLOWED IN CLEARANCE AREA
-OTHER FIXTURES CLEARANCE
AREA ALLOWED TO OVERLAP
-PROVIDE SOLID BACKING FOR
GRAB BARS IN ALL STUDWALLS
IN ALL TOILET ROOMS
M A
X
3' - 6" MIN.
3' - 0" 0' - 6" MAX.
54" MIN.
39"-41" MAX.
1'
PARTITION OR
WALL, TYP
3' - 0" CLR.
EQ EQ
MOUNTING HEIGHT AND CONTROLS REACH
M A
X
1'
F
LU
S H
C O
N T
R O
L
A F
F
C
LE
A R
A N
C E
K N
E E
A N
D T
O E
2'
M A
X
M
A X
CLEAR FLOOR SPACE
(WHEELCHAIR APPROACH)
EQ EQ
DRINKING FOUNTAINS
WHEELCHAIR ACCESSIBLE STANDING USE ACCESSIBLE
WATER CLOSET, GRAB BARS AND ACCESSORIES HEIGHTS REQUIREMENTS
3' - 6"
2' - 0"
1'
0'
/2
PROTRUDING
DISPENSER
LOCATION
1'
/2
M
IN
APPROACH, PARTITIONS, URINAL DEPTH
EQ EQ
PROVIDE PROTECTION TO
PREVENT CONTACT WITH HOT
PIPES UNDER LAVATORY; NO
ABRASIVE SURFACES OR SHARP
CORNERS PERMITTED
LAVATORIES AND SINKS _
ALLOW FOR KNEE AND
TOE CLEARANCE
WASHING MACHINES AND CLOTHES DRYERS
2' - 0"
6" 3'
M
A X
FRONT LOADING LAUNDRY EQUIPMENT TOP LOADING LAUNDRY EQUIPMENT
M A
X
4'
M A
X
M
IN
3' - 0" MAX.
2'
0"
M A
X
3'
/4
CLEAR FLOOR SPACE AT WATER CLOSET
BATHTUBS
2'
M
IN
LENGTH OF BATHTUB
C O
N T
R O
L W
A
LL
BACK WALL
H E
A D
W A
LL
1' - 0" MAX.2' - 0" MIN. 2' - 0" MAX.
2'
M
IN
0'
*HEADWALL GRAB
BAR IS NOT REQ.D
WHEN PERMANENT
SEAT IS PROVIDED
1'
M
IN
8"
0'
0"
1' m in
3"
0'
1' - 6"
3' - 0" MIN. CLR.
C O
N T
R O
L W
A
LL
BACK WALL
3'
M
IN
. C
LR
S E
A T
W A
LL
0'
3'
4' - 4"
4' - 4" OPTION 2
OPTION 1
0' - 4" MAX.
TRANSFER SHOWER
TRANSFER SHOWER W/ FOLDING SEAT PLAN
S
ID
E W
A
LL
S E
A T
W A
LL
2'
M
IN
2'
C
LR
. M
IN
5' - 0"
CONTROL WALL
0'
M A
X
0'
M A
X
0' - 6" MAX.EDGE OF SEAT
CONTROL WALL
3' - 0"
1'
0'
3'
1' - 3"
0' - 4" MAX.
1'
3'
GRAB BARS, CONTROLS AND HAND
SHOWER LOCATIONS
STANDARD ROLL-IN
- LAVATORY COMPLYING W/ SECT. 606
PERMITTED IN SHOWER CLEARANCE
- RE. ICC SECT. 608 FOR ALTERNATIVE
ROLL-IN SHOWER REQUIREMENTS
- THRESHOLD TO BE 1/2" MAX. HIGH
CONTROL WALL
1'
M
IN
3"
0'
1' - 4" MIN.
2' - 3" MAX.
3'
M
IN
4'
M A
X
ROLL-IN SHOWER W/ FOLDING SEAT PLAN
GRAB BARS, CONTROLS AND HAND SHOWER LOCATIONS
0' - 2 1/2" MAX. 15"- 1' - 4"
0'
M A
X
0'
/2
M A
X
0'
/2
M A
X
0'
M A
X
0' - 2 1/2" MAX.
THRESHOLD TO BE 1/2" MAX. HIGH
PASS-THROUGH KITCHENS
OR APPLIENCES, OR ISLAND
40" CLR. MIN. TO
WALL, OR CABINETS,
REF.
W O
R K
IN
G
S
U R
F A
C E
DW
2'
C
LR
. M
IN
U-SHAPED KITCHENS
5' - 0" CLR. MIN.
Ref.
DW
WORKING
SURFACE
KITCHENS ISLAND OUTLETS AND SWITCHES
1'
M
IN
3'
M
IN
M A
X
OUTLETS ARE NOT REQ.D IN
CORNER AREA 9 SF MAX.
2'
M A
X
2'
M A
X
3'
M
IN
1'
M
IN
2'
M
A X
M
A X
2'
M
A X
2' - 0" MAX. 3' - 0" MIN.
1 OUTLET FOR FIRST 9 SF
2'
M A
X
ADDITIONAL OUTLET FOR
EVERY ADDITIONAL 18 SF,
OR FRACTION THEREOF
DW
WALL HUNG WATER CLOSET STANDARD COMPARTMENT
WHEELCHAIR ACCESSIBLE COMPARTMENTS
4'
M
IN
3'
C
LR
. M
IN
5' - 0" MIN.
7'
M
IN
5' - 0" MIN.
0' - 4" MAX. OR 4' - 8" MIN.
2' - 8" CLR. MIN.
5'
M
IN
4' - 8" MIN. (WALL HUNG W.C.)
59" MIN. (FLOOR MOUNTED W.C)
WALL HUNG WATER CLOSET ALTERNATE COMPARTMENT
OPTION 3
5'
C
LR
. M
IN
35"- 3' - 1"
AMBULATORY COMPARTMENT
1' - 7" -17"
3'
C
LR
. M
IN
MULTI-USER TOILET ROOM SCOPE REQUIREMENTS:
1. AT LEAST ONE WHEELCHAIR ACCESSIBLE COMPARTMENT
2. IN ADDITION TO #1, AT LEAST ONE AMBULATORY ACCESSIBLE COMPARTMENT IN
RESTROOM WITH AT LEAST 6 TOILET COMPARTMENTS OR TOTAL OF WATER CLOSETS AND
URINALS
3. AT LEAST ONE COMPLAINT URINAL WHERE MORE THAN ONE URINAL PROVIDED
4. AT LEAST ONE COMPLIANT LAVATORY AND AT LEAST ONE COMPLAINT MIRROR, WHERE
PROVIDED
1'
M
IN
0' - 8"
PARTITION TOE CLEARANCE UNDER COMPARTMENT PARTITI
2' - 8" CLR.MIN.
2' - 8" CLR.MIN.
2' - 8" CLR.MIN.
SURFACE
MOUNTED TOILET
PAPER DISPENSER
SURFACE MOUNTED
SANITARY NAPKIN
DISPOSAL
SURFACE-MOUNTED
SEAT-COVER
DISPENSER
1'
M
IN
. 4'
M A
X
M
IN
4'
M A
X
RECESSED
SANITARY NAPKIN
DISPOSAL
4'
M A
X
M
IN
1'
M
IN
. 4'
M A
X
ELECTRICAL OUTLET
(NO OBSTRUCTION)
LIGHT/FAN SWITCH,
THERMOSTAT
(NO OBSTRUCTION)
4'
M A
X
R E
. R E
A C
H R
A N
G E
R E
Q .S
R E
. R E
A C
H R
A N
G E
R E
Q .S
ELECTRICAL OUTLET
(APPROACH
OBSTRUCTED)
LIGHT/FAN SWITCH,
THERMOSTAT
(APPROACH OBSTRUCTED)
R E
. R E
A C
H R
A N
G E
R E
Q .S
ELECTRICAL OUTLET
OVER COUNTERTOP
O V
E R
4"
D E
E P
C A
B
IN
E T
M A
X
(2
1/ 2"
M A
X . C
O N
T E
R T
O P
ELEVATORS
CALL
BUTTON
6'
M
IN
VISIBLE
SIGNALS
4'
M A
X
FE CABINET
O B
JE
C
T R
E Q
.S
T O
C O
M P
LY
W
P
R O
T R
U D
IN
G
T O
B .O
R
E F
LE
C
T
IN
G S
U R
F A
C E
3'
A F
F M
A X
SANITARY NAPKIN
DISPENSER
T O
B .O
R
E F
LE
C
T
IN
G S
U R
F A
C E
2'
A F
F M
A X
MIRROR ABOVE
LAVATORY OR
COUNTERTOP
MIRROR NOT ABOVE
LAVATORY OR
COUNTERTOP
WALL MOUNTED
SOAP DISPENSER
PAPER TOWEL
DISPENSER
4'
M A
X
T O
A N
Y O
P E
R A
B
LE
P A
R T
4'
M A
X
T O
A N
Y O
P E
R A
B
LE
P A
R T
4'
M A
X
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:56:04 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
STANDARD ACCESSIBILITY
DETAILS
GI302
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 3/8" = 1'-0"GI302
A1 ACCESSIBLE PLUMBING FIXTURES
SCALE 3/8" = 1'-0"GI302
A2 ACCESSIBLE SHOWERS & BATHTUBS
SCALE 3/8" = 1'-0"GI302
A3 KITCHENS
SCALE 3/8" = 1'-0"GI302
A5 MULTI-USER RESTROOMS
SCALE 3/8" = 1'-0"GI302
C5
EQUIPMENT AND ACCESSORY MOUNTING
HEIGHTS
OF E UT TA AT HS
No. 14200675-0301
862 SF
CLASSROOM
EDNET
EDNET
ELECTRICAL
LANDING
200L
EDNET
EQUIPMENT
STUDY
AREA
176 SF
STORAGE
A
D P
ROOF
HATCH
HALLWAY
200K
HALLWAY
251A
02.01
02.04
02.01
02.08
TYP.
02.03
02.04
02.0102.01
02.08
02.08
02.20
02.10
02.09
02.09
02.11
02.10
249A
02.05
644 SF
CLASSROOM
1277 SF
CLASSROOM
02.18
02.09
02.09
02.09
22.04
02.10
02.20
DEMO FLOOR PLAN LEGEND:
EXISTING DOOR AND FRAME TO REMAIN.
SEE DOOR HARDWARE SPEC. FOR DOOR
HARDWARE COMPONENTS TO REMAIN.
EXISTING DOOR, FRAME AND HARDWARE TO
BE REMOVED. EXISTING SIDELIGHT TO BE
REMOVED, WHERE OCCURS
EXISTING WALL TO BE REMOVED
EXISTING WALL TO REMAIN
KEY NOTES:?
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:58 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
SECOND LEVEL DEMOLITION
PLAN
DP101
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1/8" = 1'-0"DP101
A2 SECOND LEVEL DEMOLITION PLAN
SCALE 3/8" = 1'-0"DP101
A3 VESTIBULE @ HALL 200K
1. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS, AND
NOTIFY ARCHITECT OF ANY DISCREPANCIES BETWEEN
EXISTING CONDITIONS AND THOSE DOCUMENTED PRIOR TO
COMMENCING DEMOLITION.
2. REFER TO MECHANICAL, ELECTRICAL, AND/OR PLUMBING
DRAWINGS WHEN DEMOLITION REQUIRES REMOVAL OR
TERMINATION OF SUCH UTILITIES.
3 DASHED LINES INDICATE EXISTING WALL, CASEWORK,
FIXTURES, AND/OR OPENINGS WHICH ARE TO BE REMOVED.
U.N.O. REFER TO NOTES FOR CARE OF WORK
REQUIREMENTS
4 THE CONTRACTOR IS TO REVIEW THE COMPLETE
DOCUMENT SET AND COORDINATE THE WORK IDENTIIED IN
THE DEMOLITION DOCUMENTS WITH THE SCOPE OF THE
NEW CONSTRUCTION. ALL DISCREPENCIES WILL BE NOTED
TO THE ARCHITECT IN WRITING PRIOR TO COMMENCING
WITH DEMOLITION ACTIVITIES
5 THE CONTRACTOR IS RESPONSIBLE FOR THE PLACEMENT
AND ERECTION OF ALL TEMPORARY LIFE SAFETY
PROTECTION FOR MEANS OF EGRESS DURING DEMOLITION
AND CONSTRUCTION
6 DO NOT DISTURB, DISRUPT, DAMAGE OR ALTER ANY
STRUCTURAL CONDITION OF THE EXISTING BUILDING
UNLESS SPECIFICALLY INDICATED IN THESE DOCUMENTS
7 THE EXISTING PERIMETER WALL SYSTEMS ARE NOT TO BE
REMOVED, U.N.O. ANY DAMAGE EITHER EXISTING OR AS A
RESULT OF CONSTRUCTION ACTIVITY IS TO BE REPAIRED TO
MATCH EXISTING AND ACCEPT NEW CONTRUCTION WHERE
APPLICABLE
8 REMOVE DEMOLISHED MATERIALS FROM SITE AS WORK
PROGRESSES. UPON COMPLETION OF WORK, LEAVE SITE IN
CLEAN CONDITION, REMOVE ALL DEBRIS IN LEGAL MANNER
9 REMOVE MATERIALS TO BE REINSTALLED OR RETAINED IN A
MANNER TO PREVENT DAMAGE. STORE AND PROTECT TO
PREVENT DAMAGE AND TO ALLOW FOR REINSTALLATION
10 OWNER AND ARCHITECT ASSUME NO RESPONSIBILITY FOR
THE ACTUAL CONDITION OF AREAS TO BE DEMOLISHED
GENERAL NOTES:
02.01 REMOVE EXISTING FLOORING & BASE, PALLETIZE
AND RETURN TO OWNER. PREPARE SURFACE TO
RECIEVE NEW FINISHES.
02.03 REMOVAL OF EXISTING WALL HUNG LOCKERS BY
OWNER. CONTRACTOR TO PATCH AND REPAIR WALL
TO MATCH EXISTING.
02.04 REMOVE EXISTING INSTRUCTOR STATION, OWNER
TO PROVIDE NEW CONNECTIONS LOST FROM
REMOVAL
02.05 REMOVE EXISTING WALL ASSEMBLY, RETAIN DOOR &
FRAME FOR NEW OPENING, SEE AE101 FOR NEW
LOCATION. PATCH & PREPARE FLOOR FOR NEW
FINISHES
02.08 REMOVE WALL HUNG WHITEBOARD & TACK BOARD.
PATCH AND REPAIR WALL FINISH TO MATCH
EXISTING
02.09 REMOVAL OF EXISTING WALL-MOUNTED SPEAKERS
BY OWNER, CONTRACTOR TO PATCH AND REPAIR
WALL TO MATCH EXISTING
02.10 REMOVE EXISTING DOOR & FRAME & RETAIN FOR
OWNER. FRAME IN OPENING MATCH ADJACENT
FINISHES.
02.11 REMOVE EXISTING WALL ASSEMBLY
02.18 REMOVE EXISTING WALL ASSEMBLY TO EXTENT OF
OPENING NEEDED FOR RELOCATED DOOR AND
FRAME
02.20 REMOVE EXISTING WALL ASSEMBLY, RETAIN DOOR &
FRAME FOR OWNER,. PATCH & PREPARE FLOOR
FOR NEW FINISHES
22.04 AREA OF DEMOLITION NEEDED TO TIE-IN TO
PLUMBING ON LEVEL ONE. REFER TO PLUMBING
DRAWINGS FOR EXTENT OF DEMOTION AND WORK
TO BE PERFORMED. PATCH AND REPAIR ALL
FINISHES DISTURBED AS A RESULT OF WORK
PERFORMED
OF E UT TA AT HS
No. 14200675-0301
02.13
02.14
02.13
TYP.
02.13
02.13
02.13
02.13
TYP.
02.15
TYP.
02.15
02.14
02.13
02.14
TYP.
02.15
TYP.
02.13
02.1602.16
02.1602.16
02.1602.16
TYP.
02.13
TYP.
02.15
02.14
02.17
02.1602.16
02.1602.16
ADD ALTERNATE #1
02.1602.16
02.1602.16
02.1602.16
GENERAL NOTES:
1. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS,
AND NOTIFY ARCHITECT OF ANY DISCREPANCIES
BETWEEN EXISTING CONDITIONS AND THOSE
DOCUMENTED PRIOR TO COMMENCING DEMOLITION
2. REFER TO STRUCTURAL, MECHANICAL, ELECTRICAL
AND/OR PLUMBING DRAWINGS WHEN DEMOLITION
REQUIRED REMOVAL OR TERMINATION OF ASSOCIATED
UTILITIES
3. DASHED LINES INDICATE EXISTING WALL, CASEWORK,
FIXTURES, AND/OR OPENINGS WHICH ARE TO BE
REMOVED, U.N.O.. REFER TO NOTES FOR CARE OF
WORK REQUIREMENTS
4. THE CONTRACTOR IS TO REVIEW THE COMPLETE
DOCUMENT SET AND COORDINATE THE WORK
IDENTIFIED IN THE DEMOLITION DOCUMENTS WITH THE
SCOPE OF THE NEW CONSTRUCTION. ALL
DISCREPANCIES WILL BE NOTED TO THE ARCHITECT IN
WRITING PRIOR TO COMMENCING WITH DEMOLITION
ACTIVITIES
5. THE CONTRACTOR IS RESPONSIBLE FOR THE
PLACEMENT OF THE AND ERECTION OF ALL
TEMPORARY LIFE SAFETY PROTECTION FOR MEANS OF
EGRESS AR ALL TIMES DURING DEMOLITION AND
CONSTRUCTION.
6. DO NOT DISTURB, DISRUPT, DAMAGE OR ALTER ANY
STRUCTURAL CONDITION OF THE EXISTING BUILDING
UNLESS SPECIFICALLY INDICATED IN THESE
DOCUMENTS.
7. IN ANY CUTTING, PATCHING OR ALTERING OF THE
EXISTING STRUCTURE OR ITS COMPONENTS THAT MAY
BE REQUIRED FOR THE INSTALLATION OF NEW
CONSTRUCTION, THE CONTRACTOR WILL NOTIFY THE
ARCHITECT IN WRITING , IN ADVANCE OF ALL SUCH
WORK AS MAY BE NECESSARY.
8. THE EXISTING PERIMETER WALL SYSTEMS ARE NOT TO
BE REMOVED, U.N.O.. ANY DAMAGE EITHER EXISTING OR
AS A RESULT OF CONSTRUCTION ACTIVITY IS TO BE
PREPARED TO MATCH EXISTING AND ACCEPT NEW
CONSTRUCTION WHERE APPLICABLE.
9. REMOVE DEMOLISHED MATERIALS FROM SITE AS WORK
PROGRESSIS. UPON COMPLETION OF WORK, LEAVE
SITE IN CLEAN CONDITION, REMOVE ALL DEBRIS IN A
LEGAL MANNER.
10. REMOVE MATERIALS TO BE REINSTALLED OR RETAINED
IN A MANNER TO PREVENT DAMAGE. STORE AND
PROTECT TO PREVENT DAMAGE AND TO ALLOW FOR
REINSTALLATION
11. OWNER AND ARCHITECT ASSUME NO RESPONSIBILITY
FOR THE ACTUAL CONDITION OF AREAS TO BE
DEMOLISHED.
12. ALL WALLS SHOWN DASHED ARE TO BE REMOVED.
13. MAINTAIN A WATER TIGHT BUIDING ENVELOPE DURING
AND AT COMPLETION OF DEMOLITION.
KEY NOTES:?
DEMO REFLECTED CEILING
PLAN LEGEND:
MECHANICAL GRILL TO BE REMOVED
LIGHT FIXTURE TO BE REMOVED
CEILING TO BE REMOVED
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:59 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
SECOND LEVEL DEMO
REFLECTED CEILING PLAN
DP131
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1/8" = 1'-0"DP131
A2 SECOND LEVEL DEMO REFLECTED CEILING PLAN
02.13 REMOVE EXISTING LIGHT FIXTURES, DISCONNECT
EXISTING WIRING, PREPARE EXISTING JUNCTION
BOX FOR NEW FIXTURE
02.14 REMOVE ACOUSTICAL CEILING GRID, PREPARE FOR
NEW GRID AND LIGHT FIXTURES, SEE RCP
02.15 REMOVE EXISTING MECHANICAL GRILL AND SUPPLY,
RETAIN FOR FUTURE USE
02.16 EXISTING ACOUSTICAL CEILING AND LIGHT FIXTURES
TO REMAIN
02.17 REMOVE EXISTING GYP. BD. CEILING AND FRAMING
FRO NEW ACOUSTICAL CEILING
ADD ALTERNATE #1: IN CLASSROOM #245, REMOVE EXISTING
LIGHT FIXTURES AND PREP FOR NEW FIXTURES AND
LOCATIONS, SEE ELECTRICAL DRAWINGS
OF E UT TA AT HS
No. 14200675-0301
DN
DN
OPEN TO
BELOW OPEN TO
BELOW
CLASSROOM
EDNET
EDNET
ELECTRICAL
LANDING
200L
CLASSROOM
CLASSROOM
RR
247A
HALL
200K
EDNET
EQUIPMENT
STORAGE
249A
STUDY
AREA
LEGEND:
EXTENTS OUTSIDE OF PROJECT SCOPE
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:46 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
OVERALL SECOND LEVEL FLOOR
PLAN
AE100
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1/16" = 1'-0"AE100
A4 OVERALL SECOND LEVEL FLOOR PLAN
OF E UT TA AT HS
No. 14200675-0301
862 SF
EDNET
EDNET
ELECTRICAL
LANDING
200L
1023 SF
CLASSROOM
CLASSROOM
RR
247A
HALL
200K
HALLWAY
EDNET
EQUIPMENT
STORAGE
249A
ROOF
HATCH
249B
STUDY
AREA
6' - 9"
AE101
B3
A4
AE401
A5
AE401
A
A E
AE401
B1
7'
AE401
A1
249A
TYP.
10.01
TYP.
10.01
27.01
247A
27.01
A
A
A
B
A
22.03
847 SF
249 SF
2'
EQ EQ
1/2" METAL
REVEAL BEYOND
EXISTING 5/8" GYP BD
3/4" GRANITE SILL WITH
1/4" RADIUS CORNERS
EXISTING GLAZING
EXISTING ALUMINUM
CENTER WINDOW
MULLION
ALUMINUM BRAKE METAL
PARTITION BEYOND
1" 1"
1/
2"
HOLLOW METAL SILL
1/
2"
5"
A3
AE101
LINE OF GYP BD BELOW
EXISTING VERTICAL
MULLION
METAL STUD FRAMING
5/8" GYP BD
1/2" REVEAL
ALUMINUM BRAKE METAL
EXISTING GLAZING
TYP.
09.04
TYP.
09.01
TYP.
09.03
TYP.
09.02
TYP.
09.05
GENERAL NOTES:
1. SEE SHEET GI001 FOR ARCHITECTURAL LEGENDS,
SYMBOLS, AND ABBREVIATIONS.
2. ALL DIMENSIONS ARE TO FACE OF STUD OR CMU IN NEW
CONSTRUCTION, FACE OF FINISH IN EXISTING (U.N.O.).
3. ALL FLOOR FINISH CHANGES OCCUR AT CENTER LINE
OF DOORS IN CLOSED POSITION U.N.O.
4. COORDINATE LOCATIONS OF ALL FLOOR AND ROOF
DRAINS WITH PLUMBING PLANS.
5. SEE SHEET GI401 FOR WALL ASSEMBLIES & DETAILS.
6. SEE SHEET AE601 FOR DOOR SCHEDULE.
7. ALL ANGLED WALLS ARE AT 45°, UNLESS NOTED
OTHERWISE.
8. SEE GI302 FOR TYPICAL TOILET ACCESSORIES
INSTALLATION.
9. CONTRACTOR SHALL NOT SCALE THESE DRAWINGS FOR
CONSTRUCTION PURPOSES.
10. IN THE EVENT OF AN OMITTED NECESSARY DIMENSION,
THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR
ENGINEER.
11. VERIFY ALL DIMENSIONS, CONDITIONS, AND GRADES AT
JOB SITE PRIOR TO COMMENCING WORK.
12. VERIFY SIZE, LOCATION , AND CHARACTERISTICS OF
WORK AND EQUIPMENT FURNISHED BY THE OWNER
WITH MANUFACTURER OR SUPPLIER PRIOR TO
COMMENCING CONSTRUCTION ON WORK PERTAINING
TO THE SAME.
13. EXISTING WALLS TO REMAIN SHALL BE REPAIRED AND
REFINISHED AS REQUIRED BY DAMAGE OR TO PROVIDE
A SMOOTH AND UNIFORM SURFACE FOR THE
APPLICATION OF NEW FINISHES.
KEY NOTES:?
FLOOR PLAN LEGEND:
ROOM
NAME
101A
ROOM TAG, SEE PLAN AE121
DOOR TAG, SEE DOOR SCHEDULE
SHEET AE601
WALL TYPE TAG, SEE SHEET GI401 W-11
1 HR FIRE RATING
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:47 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
SECOND LEVEL FLOOR PLAN
AE101
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1/8" = 1'-0"AE101
A2 OVERALL SECOND LEVEL FLOOR PLAN
SCALE 1 1/2" = 1'-0"AE101
A3 INFILL PARTITION @ WINDOW
SCALE 1 1/2" = 1'-0"AE101
B3 INFILL PARTITION PLAN
SCALE 1/4" = 1'-0"AE101
A4 HALL 200K - ELEVATION
09.01 PAINT WALL PER SCHEDULE, MATCH COLLEGE
STANDARDS
09.02 NEW BASE PER SCHEDULE, MATCH COLLEGE
STANDARDS
09.03 NEW TRIM PER SCHEDULE, MATCH COLLEGE
STANDARDS
09.04 PAINT WALL TO MATCH ADJACENT
09.05 NEW CHAIR RAIL TO MATCH ADJACENT
10.01 LINE OF PRIVACY CURTAIN TRACK, SEE
SPECIFICATIONS FOR INSTALLATION.
22.03 TROUGH SINK, SEE PLUMBING DRAWINGS
27.01 COLLEGE TO PROVIDE CEILING HUNG PROJECTOR
AND SCREEN. PROVIDE 1'-6" CLEAR ON THE PULL
SIDE OF DOOR FOR ADA CLEARANCE. SPACE
ALLOCATED FOR THE PROJECTOR SCREEN IS
APPROXIMATELY 10'-6" +/-
OF E UT TA AT HS
No. 14200675-0301
10' - 0"
C1
10' - 0"
C1
9' - 0"
C2
10' - 0"
C1
CLASSROOM
ADD ALTERNATE #1
KEY NOTES:?
GENERAL NOTES:
1. REFER TO MECHANICAL DRAWINGS FOR HVAC PLAN,
SECTIONS, DUCT SIZES, SUPPLY AND RETURN AIR
GRILLE SIZES.
2. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING
LAYOUT, REQUIREMENTS, AND ADDITIONAL FIXTURE
INFORMATION.
3. DIMENSIONS ARE TAKEN FROM FACE OF FINISH
MATERIAL.
4. FOR EXACT EXTERIOR LIGHT LOCATIONS SEE EXTERIOR
ELEVATIONS.
5. LIGHT FIXTURES IN SUSPENDED CEILING SYSTEM SHALL
BE FASTENED TO METAL GRID SYSTEM WITH (1) 1/8”
BLIND RIVET AT EACH CORNER. EACH CORNER OF THE
LIGHT SHALL BE SUPPORTED FROM THE ROOF
STRUCTURE WITH #12 GA. GALVANIZED ANNEALED
WIRE.
6. SUPPLY AND RETURN DIFFUSERS IN SUSPENDED
CEILINGS SHALL HAVE STRAPS AT OPPOSITE SIDES.
THESE MAY BE SLACK.
7. COORDINATE LIGHT FIXTURE PLACEMENT WITH
MECHANICAL AND STRUCTURAL DRAWINGS.
8. COORDINATE LIGHT FIXTURE PLACEMENT WITH
OVERHEAD DOORS TO ENSURE THAT LIGHTS ARE NOT
BLOCKED BY DOORS IN THE OPEN POSITION.
9. DIMENSIONS ARE TAKEN FROM CENTER LINE FOR ALL
FIXTURES.
REFLECTED CEILING PLAN
LEGEND:
RETURN AIR GRILL - SEE MECH.
SUPPLY AIR GRILL - SEE MECH.
2x2 LIGHT FIXTURE - SEE ELEC.
EXHAUST FAN - SEE MECH.
A
VARIES
RM ROOM NUMBER
CEILING HEIGHT
CEILING TYPE
RECESSED CAN LIGHT - SEE ELEC.
PENDANT LIGHT - SEE ELEC.
C1 - ARMSTRONG CORTEGA
TEGULAR 704 24" x 24" SUSPENDED
ACOUSTICAL CEILING TILE, SEE
DETAILS A1-A4/AE541
CEILING TYPES LEGEND:
C2 - 5/8" PAINTED MOISTURE RESISTANT
GYPSUM BOARD OVER 20 GA. 3 5/8" MTL
STUD FRAMING @ 18" O.C. - PAINT W1
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:48 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
SECOND LEVEL REFLECTED
CEILING PLAN
AE131
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1/8" = 1'-0"AE131
A2 SECOND LEVEL REFLECTED CEILING PLAN
ADD ALTERNATE #1: IN CLASSROOM #245, REMOVE EXISTING
LIGHT FIXTURES AND PREP FOR NEW FIXTURES AND
LOCATIONS, SEE ELECTRICAL DRAWINGS
OF E UT TA AT HS
No. 14200675-0301
2' - 0" 2' - 0" 2' - 6"
A3
AI301
A4
AI301
A1
AI301
2'
6"
2' - 3"2' - 3"2' - 3"2' - 3"2' - 3"2' - 3"2' - 3"2' - 3"2' - 3"2' - 3"2' - 3"2' - 3"
A2
AI301
FILLER FILLER
22.01
10.09
10.08
10.06
2' - 6" 2' - 6"2' - 6"2' - 6"2' - 6"2' - 6"2' - 6"2' - 6" 1' - 6"
A2
AI301
A2
AI301
FILLERFILLER
10.02
22.01
22.02
10.08
10.09
10.07
26.01
10.03
10.06
A
A E
B
A E
B2
AE401
B4
AE401
22.01
10.02
22.02
1'
0"
1' - 6"1' - 10"
10.03
10.09
10.08
10.06
1' - 6"
8' - 1"
9'
10"
KEY NOTES:?
1. ALL MEASUREMENTS ARE TO FINISHED FLOOR
2. ALL ADA ACCESSIBLE FIXTURES TO COMPLY WITH ANSI
A117 LATEST EDITION
3. ENCLOSURE CAN PROTRUDE A MAX OF 19" AND CANNOT
REDUCED THE MIN. REQUIRED CLEAR WIDTH OF
ACCESSIBLE PATH
4. MILLWORK DIMENSIONS ARE FOR BID PURPOSES ONLY
AND MUST BE VERIFIED.
5. SLOPE FLOOR TOWARD DRAIN 1/8" PER FOOT WHERE
FLOOR DRAINS ARE PROVIDED.
6. OWNER SHALL PROVIDE RESTROOM ACCESSORIES -
CONTRACTOR TO INSTALL
GENERAL NOTES:
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:50 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
ENLARGED PLANS AND
ELEVATIONS
AE401
SLA000004
Author
Checker
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1/4" = 1'-0"AE401
A2 EXAM ROOM WASH STATION
SCALE 1/4" = 1'-0"AE401
A4 RM 247 NORTH CASEWORK
SCALE 1/4" = 1'-0"AE401
A5 RM 249 SOUTH CASEWORK
SCALE 1/4" = 1'-0"AE401
B2 RM 247A - NORTH ELEVATION
SCALE 1/4" = 1'-0"AE401
B3 RM 247A - EAST ELEVATION
SCALE 1/4" = 1'-0"AE401
B4 RM 247A - SOUTH ELEVATION
SCALE 1/4" = 1'-0"AE401
B1 RM 247A - ENLAREGED PLAN
SCALE 1/4" = 1'-0"AE401
A1 EXAM ROOM - ENLARGED PLAN
10.02 SPECIMAN PASS-THRU
10.03 SOAP DISPENSER, OFCI
10.06 PAPER TOWEL DISPENSER, OFCI
10.07 MIRROR
10.08 TOILET TISSUE DISPENSER, OFCI
10.09 GRAB BAR
22.01 WATER CLOSET, COORDIANTE WITH PLUMBING
PLANS
22.02 WALL MONTED HAND SINK, COORDINATE WITH
PLUMBING DRAWINGS
26.01 LIGHT FIXTURE, SEE ELECTRICAL DRAWINGS
OF E UT TA AT HS
No. 14200675-0301
SCREW ATTACHEMENT
TO STUDS
7/8" EDGE TRIM WITH CONT.
ACOUSTICAL SEALANT
BETWEEN WALL ASSEMBLY
AND TRIM
SCHEDULED
SUSPENSION SYSTEM
WALL ASSEMBLY
AS SCHEDULED
8" MAX.
7/8"
BERC2 SEISMIC
CLIP OR EQUAL
ICC-ESR-1308 (MANUFACTURE REQUIREMENTS)
5/8" 3/4"
SCHEDULED
CEILING
WEB MEMBERS
BOTTOM
CORD
VERTICAL
HANGER WIRE
SPLAYED SEISMIC
BRACING WIRE
COMPRESSION STRUT AT
INTERSECTION MUST BE PLACED AT
12'-0" O.C. (MAX.) EACH WAY AND
WITHIN 6'-0" OF PERIMETER WALLS
(4) - 12 GA. SPLAY WIRES
CROSS T
MAIN RUNNER
ACOUSTICAL LAY-IN
PANEL CEILING
8'-6"
10'-0"
11'-6"
15'-0"
SINGLE 2 1/2" X 20 GA. METAL
STUD (Imin = 0.18 in4)
BACK TO BACK 2 1/2" X 20 GA. METAL
STUDS SCREWED TOGETHER @ 24" O.C.
1" DIAMETER CONDUIT (EMT)
3/4" DIAMETER CONDUIT (EMT)
STRUT SIZE MAX. LENGTH
2"
45°
7/8" FURRING CHANNELS @ 16" O.C.
5/8" TYPE 'X' GYP. BD.
1 1/2" C.R. CHANNEL @ 48" O.C.
12 GA. HANGER
NOTE:
SEE SPECIFICATION FOR
ADDITIONAL REQUIREMENTS
SCREW ATTACHEMENT
TO STUDS
7/8" EDGE TRIM WITH CONT.
ACOUSTICAL SEALANT
BETWEEN WALL ASSEMBLY
AND TRIM
SCHEDULED
SUSPENSION SYSTEM
SET SCREW AT
EACH CLIP
WALL ASSEMBLY
AS SCHEDULED
8" MAX.
7/8"
BERC2 SEISMIC
CLIP OR EQUAL
ICC-ESR-1308 (MANUFACTURE REQUIREMENTS)
5/8" 3/4"
SCHEDULED
CEILING
SCALE 3" = 1'-0"AE541
A3 TYPICAL COMPRESSION STRUT
SCALE 3" = 1'-0"AE541
A5 SUSPENDED GYP. BD. CEILING SYSTEM
SCALE 3" = 1'-0"AE541
A1
RESTRAINED EDGE DETAIL @
ACOUSTICAL LAY-IN CEILING
SCALE 3" = 1'-0"AE541
A2
UNRESTRAINED EDGE DETAIL @
ACOUSTICAL LAY-IN CEILING
SCALE 3" = 1'-0"AE541
A4 SUSPENDED CEILING DETAIL
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:51 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
REFLECTED CEILING DETAILS
AE541
SLA000004
PRH
AC
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
OF E UT TA AT HS
No. 14200675-0301
WALL AS
SCHEDULED
CONT. SEALANT,
EACH SIDE
H.M. FRAME
DOOR AS
SCHEDULED
WALL AS SCHEDULED
CONT. SEALANT,
EACH SIDE
H.M. FRAME
DOOR AS
SCHEDULED
4"
FACE OF WALL,
WHERE OCCURS
(2) MTL. STUDS.
EXTEND TO B.O.
STRUCTURE
D1
FINISH FLOOR
W
H
D2
W
H
0'
0' - 8"
GLAZING AS
SCHEDULED
A .F
.F . M
A X
FINISH FLOOR
F1
H 0'
0' - 2" W 0' - 2"
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:52 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
SCHEDULES
AE601
SLA000004
Author
Checker
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 3" = 1'-0"AE601
B1 INTERIOR H.M. DOOR HEAD
SCALE 3" = 1'-0"AE601
A1 INTERIOR H.M. DOOR JAMB
DOOR AND FRAME SCHEDULE
DOOR
DOOR FRAME
ACCESS
CONTROL
ASSEMBLY
FIRE RATING NOTES
SIZE
TYPE MATL FINISH GLAZING TYPE MATL FINISH
DETAILS (AE591)
WIDTH HEIGHT HEAD JAMB
247 3' - 6" 7' - 0" D2 HM DF1 G2 F1 HM FACTORY
FINISH
B1/AE601 A1/AE601
Yes
HARDWARE & ACCESS CONTROL TO BE
RELOCATED. CONTRACTOR TO VERIFY
NEW 42" CRASH BAR IS COMPATIBLE WITH
WITH EXISTING HARDWARE
247A 3' - 0" 7' - 0" D1 HM DF1 --- F1 HM FACTORY
FINISH
B1/AE601 A1/AE601
249 3' - 6" 7' - 0" D2 HM DF1 G2 F1 HM FACTORY
FINISH
B1/AE601 A1/AE601
Yes
HARDWARE & ACCESS CONTROL TO BE
RELOCATED. CONTRACTOR TO VERIFY
NEW 42" CRASH BAR IS COMPATIBLE WITH
WITH EXISTING HARDWARE
249A 3' - 0" 7' - 0" EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING B1/AE601 A1/AE601 Yes
HARDWARE & ACCESS CONTROL TO BE
RELOCTED WITH NEW DOOR LOCATION
DOOR TYPES
DOOR FRAME TYPES
GENERAL NOTES:
DOOR FINISH LEGEND
DF1 FACTORY FINISH
DF2 FIELD PAINT
DOOR MATERIAL LEGEND
AL ALUMINUM
FRP FIBERGLASS
GZ GLAZING
HM HOLLOW METAL
WD WOOD
1. WHERE DOOR ASSEMBLIES RESIDE WITHIN SOUND RATED
WALL ASSEMBLIES, DOOR ASSEMBLY STC RATING SHALL
MATCH WALL REQUIREMENTS.
GLAZING SCHEDULE
G1 1/4" CLEAR
G2 1/4" CLEAR - TEMPERED
G3 1" INSULATED CLEAR
G4 1" INSULATED CLEAR - TEMPERED
G5 1" INSULATED - SPANDREL
G6 1" INSULATED - SPANDREL - TEMPERED
DOOR FRAME FINISH LEGEND
FF1 FACTORY FINISH
FF2 FIELD PAINT
FF3
FF4
FF5
DOOR FRAME MATERIAL LEGEND
AL ALUMINUM
FRP FIBERGLASS
HM HOLLOW METAL
WD WOOD
OF E UT TA AT HS
No. 14200675-0301
EDNET
EDNET
ELECTRICAL
LANDING
200L
CLASSROOM
CLASSROOM
RR
247A
HALL
200K
HALLWAY
EDNET
EQUIPMENT
STORAGE
249A
ROOF
HATCH
249B
STUDY
AREA
W1/B1
W /B
W /B
W1/B1
W1/B1
W /B
W /B
W1/B1
W1/B1
W /B
W /B
W1/B1
W1/B1
W /B
W /B
W1/B1
W /B
KEY NOTES:?
GENERAL NOTES:
1. ALL WALL PAINT IS TO HAVE A SATIN FINISH U.N.O..
2. ALL DOOR FRAMES ARE TO HAVE A SEMI-GLOSS FINISH
U.N.O..
3. INSTALLER IS TO REFER TO SPECIFICATION FOR
INSTALLATION METHODS AND REQUIREMENTS
4. ALL EXPOSED GYP. BD. SURFACES ARE TO RECEIVE A
LEVEL 4 FINISH
FINISH PLAN LEGEND:
WALL FINISH TYPE / BASE TYPE, SEE AE122
FLOOR FINISH INSTALLATION
DIRECTIONAL ARROW, SEE AE122
WX/BX
W X
/B X
W X
/B X
WX/BX
T1 THRESHOLD TYPE
W3 - WALL PROTECTION. COORDINATE
LENGTH WITH HEAD WALLS AND PRIVACY
CURTAINS
FINISH SCHEDULE NOTES:
1. EXISTING FINISHES TO REMAIN IN CLASSROOM 245
6'
FLOOR AS SCHEDULED
W1
W2
SCALE 1/4" = 1'-0"AI101
A2 TYPICAL RESTROOM ELEVATION
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:55 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
SECOND LEVEL FINISH PLAN
AI101
SLA000004
Author
Checker
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1/8" = 1'-0"AI101
A1 OVERALL SECOND LEVEL FLOOR PLAN
BASE FINISH SCHEDULE
TYPE DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES
B1 INTEGRAL COVED FORBO MARMOLEUM TBD
B2 WOOD BASE TO MATCH EXISTING
FLOOR FINISH LEGEND
TYPE FILL DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES
F1 VINYL FORBO MAMOLEUM TBD
WALL FINISH LEGEND
TYPE DESCRIPTION MANUFACTURER PRODUCT COLOR NOTES
W1 FIELD PAINT VALLEY PAINT SLCC HTC - MAIN WALL
COLOR
W2 CERAMIC TILE DALTILE COLORWHEEL 4X12 0790 MATTE ARCTIC WHITE SEE A2/AI101 ELEVATION
W3 WALL PROTECTION ACROVYN ALMOND 60" HEIGHT WITH TRIMMED EDGES
OF E UT TA AT HS
No. 14200675-0301
SINK & FAUCET, SEE
PLUMBING DRAWINGS
T O
T O
P R
IM
O
F S
IN
K
2'
0"
2'
2'
3/4" P-LAM DOOR,
FORMICA, COLOR TBD
3/4" P-LAM BOTTOM,
FORMICA, COLOR TBD
(2) 3/4" P-LAM
ADJ. SHELVES
1' - 2"
3"
FULL ROUND EDGE
POST-FORMED P-LAM
COUNTERTOP & BACK
SPLASH W/ COVED
SPLASH JOINT
1 1/4"
SCHEDULED BASE
3/4" P-LAM FRONT,
FORMICA, COLOR TBD
3/4" P-LAM DOOR
FORMICA, COLOR TBD
4"
6"
1/ 2"
4"
2' - 0"
SCHEDULED BASE
FULL ROUND EDGE
POST-FORMED P-LAM
COUNTERTOP & BACK
SPLASH W/ COVED
SPLASH JOINT
(1) 3/4" P-LAM ADJ. SHELF,
FORMICA, COLOR TBD
2'
0"
2'
2'
0'
0'
/2
0'
3"
1 1/4"
1' - 2"
4"
2' - 0"
3/4" P-LAM DOOR,
FORMICA, COLOR TBD
3/4" P-LAM BOTTOM,
FORMICA, COLOR TBD
(2) 3/4" P-LAM ADJ.
SHELVES, FORMICA,
COLOR TBD
3/4" P-LAM FRONT,
FORMICA, COLOR TBD
3/4" P-LAM DOOR,
FORMICA, COLOR TBD
1' - 2"
SCHEDULED BASE
FULL ROUND EDGE
POST-FORMED P-LAM
COUNTERTOP & BACK
SPLASH W/ COVED
SPLASH JOINT
(4) 3/4" P-LAM DRAWER,
FORMICA, COLOR TBD
2'
0"
2'
2'
0'
/2
0'
4"
2' - 0"
3/4" P-LAM DOOR,
FORMICA, COLOR TBD
3/4" P-LAM BOTTOM,
FORMICA, COLOR TBD
(2) 3/4" P-LAM ADJ.
SHELVES, FORMICA,
COLOR TBD
3/4" P-LAM FRONT,
FORMICA, COLOR TBD
3/4" W.R. PLYWOOD SUBSTRATE
OVER STEEL BRACKET
1/4" STEEL PLATE, WELDED
CONSTRUCTION, AT 36"
O.C. MAX. PAINT
POST-FORMED P-LAM COUNTERTOP
& BACK SPLASH W/ COVED SPLASH
JOINT, FORMICA, COLOR TBD
2'
6"
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:55 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
CASEWORK SECTIONS
AI301
SLA000004
Author
Checker
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 1" = 1'-0"AI301
A1 CABINET SECTION SINK
SCALE 1" = 1'-0"AI301
A2 CABINET SECTION DRAWER
SCALE 1" = 1'-0"AI301
A3 CABINET SECTION (4) DRAWER
SCALE 1" = 1'-0"AI301
A4 ADA COUNTER SECTION
OF E UT TA AT HS
No. 14200675-0301
2"
22"
2"
22"
1"
8"
6"
8"
3 1/4"
OPEN END END @ WALL
1" x 1" STEEL
ANGLE
BRACKET
1" x 1/4" STEEL BRACKET
ON 1/4" STEEL PLATE
THRU-BOLT
2x4 WALL
FASTEN @ BOTH ENDS WITH
(4) #8 TAPPING SCREWS
CUT HORIZONTAL
FASTENER FROM STUD
VERTICAL WALL STUDS
NOTE:
COORDINATE LOCATION OF HORIZONTAL FASTENER
WITH MOUNTING HEIGHT OF GRAB BAR
20 GA. x 4" SHEET
MTL. AS REQ'D.
MTL. WALL STUDS
TYPICAL FOR EQUIPMENT
REQUIRING BLOCKING U.N.O.
LE
N
G T
H R
E Q
B
Y M
F R
577 South 200 East
Salt Lake City, Utah
801.533.2100
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/27/2025 1:55:56 PM
A ut od es k D oc s:
//S
LA
-S
LA
-U
T -W
J- Jo rd an
-C am pu s-
C N
A -M
A
B
R
/S
LA
-A
E -3
D -S
LC
C
C N
A _M
A -R
E M
O D
E L.
rv t
INTERIOR FINISH DETAILS
AI501
SLA000004
Author
Checker
W
S
W E
S T
J O
R D
A N
, U T
D F
C M
S
LC
C J
O R
D A
N C
N A
/M A
R E
M O
D E
L
S
LC
C
SCALE 3" = 1'-0"AI501
A3 2-10 MOUNTING BRACKET
SCALE 1 1/2" = 1'-0"AI501
A1 2-12 GRAB BAR BLOCKING DETAIL
SCALE 1 1/2" = 1'-0"AI501
A2 2-14 BLOCKING DETAIL
OF E UT TA AT HS
No. 14200675-0301
ONE LAYER 5/8" TYPE 'X' GYPSUM BOARD APPLIED PARALLEL TO EACH SIDE OF METAL STUDS @ 16" O.C. WITH 1" TYPE 'S' DRYWALL SCREWS @ 8" O.C. TO VERTICAL EDGES AND 12" O.C. ON TOP & BOTTOM RUNNERS AND INTERMEDIATE STUDS. STAGGER ALL VERTICAL AND HORIZONTAL JOINTS
@ 24" O.C. EACH SIDE AND OPPOSITE SIDES
NON-LOAD BEARING
SOUND WALL WHERE OCCURS (SEE FLOOR PLAN): STC 50 MIN.
INCLUDE 3 1/2" SOUND BATT
FIRE WALL WHERE OCCURS (SEE FLOOR PLAN): 1 HR RATING;
COMPLY W/ GA FILE #WP1072
5/8" TYPE 'X'
GYP. BD.
8" 20 GA. MTL.
STUDS @ 16" O.C.
5/8" TYPE 'X'
GYP. BD.
ONE LAYER 5/8" TYPE 'X' GYPSUM BOARD APPLIED PARALLEL TO EACH SIDE OF METAL STUDS @ 16" O.C. WITH 1" TYPE 'S' DRYWALL SCREWS @ 8" O.C.