This specification sets requirements for the design and fabrication of self-supporting antenna support towers and associated foundations for an air-to-ground communication system. Key details include the Federal Aviation Administration requiring the demolition of four existing 50-foot guyed antenna towers and construction of four new 60-foot free-standing antenna towers located at the Columbia Metropolitan Airport in West Columbia, South Carolina. The contractor shall furnish all required materials, equipment, labor, insurance, permits, and supervision to complete the work according to the attached specifications, drawings, and other contract documents. The solicitation number is 6973GH-21-R-00072, with proposals due by May 14, 2021 to michelle.ctr.abraham@faa.gov. The contract type will be firm-fixed-price. All questions must be submitted in writing by May 7, 2021. Offerors must register with the System for Award Management at www.sam.gov by the proposal due date.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CAE RCAG TOWER REPLACEMENT Revision A - May 2021
COLUMBIA, SC FAA-CAE-1700951
ANTENNA TOWERS 13 10 00 - 1
SECTION 13 10 00 – ANTENNA TOWERS
PART 1 - GENERAL
1.1 SUMMARY
This specification sets forth the requirements for the design and fabrication of self supporting antenna support towers and associated foundations for an air to ground communication system.
1.2 REFERENCES
The current issues of the following documents in effect on the date of the invitation for bid form a part of this specification and are applicable to the extent specified herein.
FEDERAL SPECIFICATIONS
RR-5-001301 Safety Equipment, Climbing RR-G-661 Grating –Bar Type
OSHA 1910.27 Ladders and Platforms
MILITARY SPECIFICATIONS
MIL-M-17194 Metal, Expanded, Steel American Society For Testing And Materials (ASTM)
A-36 Carbon Structural Steel
A-53 Pipe, Steel Black and Hot Dipped, Zinc Coated , Welded and Seamless A-123 Zinc (Hot Galvanized) Coatings on Iron and Steel Products
A-153 Zinc Coating (Hot Dip) on Iron and Steel Hardware A-242 High Strength Low Alloy Structural Steel
A-307 Carbon Steel Bolts and Studs, 60,000 psi Tensile Strength
A-325 Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength A-385 Practice for Providing High Quality Zinc Coatings (Hot Dip)
A-490 Heat Treated Steel Structural Bolts 150 ksi Minimum Tensile Strength A-501 Hot-Formed Welded and Seamless Carbon Steel Structural Tubing A-615 Deformed Billet and Plain Billet Steel Bars for Concrete Reinforcement
A-618 Hot Formed Welded and Seamless High Strength, Low Alloy Steel Tubing B-221 Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ANTENNA TOWERS 13 10 00 - 2
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
Standard Practice for Steel Buildings and Bridges.
AMERICAN IRON AND STEEL INSTITUTE
Cold-Formed Steel Design Manual
AMERICAN WELDING SOCIETY WELDING HANDBOOK
D1.1 Structural Welding Code
ELECTRONIC INDUSTRIES ASSOCIATION
TIA-222-H Structural Standards for Steel Antenna Towers and Structural Supporting Structures
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
B18.22.1 Plain Washers
1.4 SUBMITTALS
1.4.1 Submittal Descriptions (SD)
Submittals are identified by SD numbers and titles as follows.
SD-02 Shop Drawings
Drawings, diagrams and schedules specifically prepared to illustrate some portion of the work.
SD-03 Product Data
Catalog cuts and brochures illustrating size, physical appearance and other characteristics of equipment.
SD-05 Design Data
Calculations, analyses or other data pertaining to a part of work.
ANTENNA TOWERS 13 10 00 - 3
1.4.2 Variations
When proposing a variation, deliver written request to the Contracting Officer, with documentation of the nature and features of the variation and why the variation is desirable and beneficial to Government. If lower cost is a benefit, also include an estimate of the cost saving. In addition to documentation required for variation, include the submittals required for the item. Clearly mark the proposed variation in all documentation. When delivering a variation for approval, Contractor warrants that this contract has been reviewed to establish that the variation, if incorporated, will be compatible with other elements of work.
1.4.3 Format of Submittals
1.4.3.1 Transmittal
Transmit each submittal to office of approving authority.
1.4.3.2 Format for SD-02 Shop Drawings
a. Shop drawings shall not be less than 8 1/2 by 11 inches nor more than 30 by 42 inches.
b. Include on each drawing the drawing title, number, date, and revision numbers and dates.
c. Dimension drawings; Identify materials and products for work shown.
1.4.3.3 Format of SD-03 Product Data
Indicate, by prominent notation, each product which is being submitted; indicate specification section number and paragraph number to which it pertains.
1.4.3.4 Format of SD-05 Design Data and SD-07 Certificates
Provide design data and certificates on 8 1/2 by 11 inches paper
1.4.5 Quantity of Submittals
Submit two copies of submittals for approval by the Contracting Officer.
1.4.6 Submittals Required SD -02 Shop drawings
Tower design fabrication, foundation and erection drawings
ANTENNA TOWERS 13 10 00 - 4
SD -03 Product data
Safety Climbing Devices.
SD - 05 Design Data
Tower structural design calculations
PART 2 - PRODUCTS
2.1 ANTENNA SUPPORT TOWER DESIGN
2.1.1 General
Each tower designed and furnished by the contractor shall be complete in accordance with all specification requirements including antenna supports, anchor bolts, safety rail and climbing device, and all hardware essential for the erection of the tower. The contractor shall provide all materials supplies, equipment and services necessary to design, fabricate and prepare for delivery of all items listed in the contract schedule.
2.1.2 Tower Description
2.1.2.1 Four Leg Tower
The tower shall be a self supporting or guyed steel structure with a platform at the top for mounting and servicing antennas. The tower shall be designed to be shipped knocked down and to be erected in the field using only structural bolts. The tower shall be fabricated in 20 foot plus or minus sections except that a 16.5 foot section shall be provided to obtain the required height (i.e. 60 feet ) The tower members shall be fabricated from angular stock. The tower shall have 4 legs.
2.1.2.2 Support Arms and Antenna Mounts
The antennas will be installed on 2 ½ inch ID (2 7/8” OD) aluminum pipes that extend 6 inches above the top guard rail. The antenna support arms shall be spaced around the work platform to permit the installation of 8 antennas with 8 foot minimum separation. This can be accomplished with a square or rectangular platform with retractable antenna support arms in appropriate lengths and locations to provide the separation. The contractor shall submit designs for the antenna mount and its attachment to the tower.
2.1.2.3 Ladder
A ladder shall be mounted the full height of the tower and extend 4 feet above the work platform. A Dyna-Glide rail system shall be installed along the centerline of the ladder. The ladder and Dyna- Glide rail shall conform to OSHA standards including clearances.
ANTENNA TOWERS 13 10 00 - 5
The FAA requires the toe clearance to be 7” behind the ladder for the entire length of the ladder, except where the ladder penetrates the platform grating. At the platform level the top of the ladder rung must be at the same level as the top of the grating or a maximum of two inches.
The ladder rungs must be a minimum of ¾” diameter, 16” long and spaced not more than 12" and uniform throughout as per OSHA 1910.27 standards.
2.1.2.4 Work Platform and Guard Rails
The platform shall be fabricated of angle framing members and the floor of the platform shall be fabricated from either expanded metal grating or bar type grating. The minimum area for the work platform shall be 64 square feet. The floor shall be secured to the framing. The platform shall be provided with a guard rail composed of vertical posts with a top and intermediate rail located 42 inches and 23 inches respectively above the platform floor. A 4 inch high by 12 gauge toe board shall be secured to the inside of the guard rail posts located ¼” above the floor of the platform. The toe board shall run continuously around the perimeter. The perimeter framing members shall support the rails, toe board as well as the required antenna mounting brackets.
2.1.2.5 Work Platform Access
Access to the tower shall be gained through a suitable trap door with a provision for being padlocked from the bottom. The weight of the trap door shall be 30 lbs or less. It shall be designed so that when opened by a climber, it shall remain fully open without being held by the climber. It shall be possible to fully open and close the trap door when ascending or descending the tower without disengaging from the safety climbing device. The minimum climbing clearances shall be 1’-3” on both sides of the ladder centerline and 2’-6” from the face of the ladder to the back of the opening. The ladder shall be installed on the inside of the tower, then the bracing at the base shall be configured to allow for easy access to the inside of the tower. (Although not required, a trap door constructed from aluminum is preferred to meet the weight requirements. A counter weight that does not impede the opening is also acceptable).
The ladder shall be installed on the oposite side of the conduits and junction boxes.
2.1.2.6 Foundation
Two foundation designs shall be provided for the tower. One design shall be based on a safe soil, ultimate bearing pressure of 2300 pounds per square foot and one on a safe soil, ultimate bearing pressure of 4000 pounds per square foot. Concrete strength shall be based on a 28 day compressive strength of 3000 psi and a maximum slump of 4”. Reinforcing steel shall be intermediate grade billet ASTM A-615 grade 60 deformed bars. Foundation designs shall be oriented toward economical construction based on the costs of labor and materials at the time of the design.
2.1.3 Special Requirements
Unless otherwise indicated EIA Standard TIA-222-H shall govern the design and fabrication of the towers. The design shall be in accordance with AISC and AISI specifications and established engineering practices.
ANTENNA TOWERS 13 10 00 - 6
2.1.4 Service Conditions
Towers with a work platform, eight stacked UHF/VHF standard communications antennas located atop the structure, with 3ea – 4” PVC Schedule 40 conduits on one side shall sustain the maximum stresses imposed by the following ambient conditions without permanent deformation damage or degradation to operations.
Temperature -50°C to 60°C
Wind load 150 mph
Class – III
Exposure - C
Topographic Category - 1
Relative humidity 5% to 100%, including condensation
Environment Salt spray
Urban industrial fumes Wind borne sand and dust
Live Load Platform
250 lb concentrated load over any one sq ft 20 lb/ sq ft Ladder 500 lb at any point on the ladder
FAA Equipment Wind Loads
Eight communications antennas: projected area with .5 ice - 2.3 sq ft. x 8 = 18.4 sq. ft.
Junction box projected area – 6 sq. ft.
4ea - 4 inch PVC conduits from the foundation to the tower platform 2 ea – ¾” lightning rod and down conductor mounted on a 2” diameter steel pipe extending 240 inches above the platform floor.
FAA Equipment Dead Loads
Eight communications antennas: 18lb x 8 = 144lb
Junction Box – 50lbs
PVC Conduit - 1.98 lb/ft x 4ea = 7.92lb/ft of tower (braced by the tower and is supported by the foundation)
ANTENNA TOWERS 13 10 00 - 7
2.1.5 Design requirements
2.1.5.1 Work Required
The contractor shall submit structural design calculations and design fabrication, foundation and erection drawings. All design calculations shall be indexed and arranged in and orderly manner with appropriate sketches so that any element may be easily identified. Complete structural calculations are required covering all parts of the structures and all related items. Tower twist, sway and displacement shall be determined by analytical method. All design loads shall be identified; design methods and assumptions indicated. When computer printouts form a portion of the design calculations, the contractor shall include all input diagrams and information needed to relate the printout to the design elements. The computer programs utilized shall be identified and a brief description of each shall be included. The submittal shall be certified by a Registered Professional Engineer.
2.1.5.1 Tower Drawings
The drawings shall include plan and elevation views antenna mounts grounding system and any pertinent notes. Erection drawings shall indicate member location, bolt sizes and number ladder attachment with safety climbing device, antenna mounts and all other information to clearly depict required elements for field erection a parts list showing the member size and length shall be provided in the erection drawings shall be provided for the installation of the obstruction light system.
2.1.5.1 Foundations Drawings
The foundation drawings shall include both plan and elevation views. Drawings shall include reinforcing bar size, quantity and position anchor bolt size and position and other pertinent information for the constructing the foundations and anchors.
2.2 MATERIALS
2.2.1 General
Unless otherwise indicated materials shall conform to the specifications and other requirements below.
Where no specification is indicated the materials shall be of a good commercial quality suitable for the government’s intended use and shall be subject the approval of the CO the contractor shall furnish all materials and items required that the complete structure an in addition shall furnish nuts, bolts and washers and other minor items in an amount 10% in excess of the quantity required for erection.
2.2.2 Tower Legs
The tower legs shall be fabricated of steel pipe , structural angles or plates. Steel pipe shall have a minimum yield strength of 33,000 lbs per square inch per ASTM A-53 or ASTM A-501. Structural
ANTENNA TOWERS 13 10 00 - 8
angles or plates shall have a minimum yield strength of 36,000 lbs per square inch per ASTM A-36. Legs fabricated from steel having a minimum yield strength of 50,000 shall conform to ASTM A-618 grade 3 for pipe and ASTM A-242 for angles or plates
2.2.3 Tower braces
The tower braces shall be have a minimum yield strength of 33,000 lbs per square inch per ASTM A-53 or ASTM A-501. Structural angles or plates shall have a minimum yield strength of 36,000 lbs per square inch per ASTM A-36.
Horizontal angle members shall be supplied, that can be installed on any face of the tower and that are designed to support the 3 each conduits referenced in section 2.1.4 of this specification. The horizontal members may be no more than 5 feet apart in distance. The horizontal angle members shall be designed to allow grip strut or beam clamps to be attached directly to the horizontals for attaching the PVC conduit
Tower braces shall be chamfered at a 45 degree angle the width of the angle member on the side that will not contact the tower leg to allow members on the inside of the tower legs proper clearance.
2.2.4 Base Section
The base section of all self supporting towers shall be fixed base utilizing load bearing plates drilled to receive anchor bolts cast into the foundation or it may be a short section or integral part of the first tower increment. If a separate base section is used it shall be cast into the foundation and similar in construction to the other tower increments.
2.2.5 Bolts, Nuts and Washers
Bolts, Nuts and Washers, High Strength - Shall conform to ASTM A-325 or A-490.
Bolts, Nuts and Washers, Other Than High Strength - Shall conform to ASTM A-307 Grade A
Plain Washers Other Than Those in Contact With High Strength Bolt Heads and Nuts - Shall conform to ANSI B-18.22.1 Plain Washers Type B
Locknuts.- A jam nut shall be used on each bolt beneath the full nut. Self locking nuts intended for use on exterior bolted connections with any associated lock washers may be substituted for approval as a substitute for the regular nut and jam nut.
ANTENNA TOWERS 13 10 00 - 9
2.2.6 Grating
Expanded Metal Type: Military Specification MIL-M-
17194 Bar Type: Federal Specification RR-G-661
Bearing Bars shall be aluminum alloy 6061-T6. Per ASTM B-221
Cross Rods shall be aluminum alloy 6063-T1. Per ASTM B-221
2.3 SAFETY CLIMBING DEVICES
Ladder Safety System shall be provided by MSA Dyna-Glide® System with a pivot Davit. The system shall include the climbing rail, all mounting attachments and the top pivot with a stop. Provide 2 Fall arresters with an instruction manual and parts list.
Fall Arrester Model No. 506277 Aluminum/Stainless Steel
Pivot Davit Model No.: 506357 Galvanized, 506506 Stainless Steel
All other parts shall be galvanized steel unless specified as stainless steel in the solicitation.
2.4 FABRICATION
2.4.1 General
Fabrication shall be in accordance with the AISC specification. Members shall not have sharp edges which would be hazardous during handling or other irregularities that would interfere with erection.
Welding shall conform to the AWS structural welding code.
2.4.2 Stamping
Each separate member except bolts, washers, etc shall be clearly marked by stamping into the steel the part number shown on the drawings. All parts shall be marked in the same relative position. The mark shall be stamped in the steel before galvanizing and shall be clearly visible in the erected structure.
Each piece shall be marked with one inch high letter/number combination.
ANTENNA TOWERS 13 10 00 - 10
2.5 FINISHES
Galvanizing – All ferrous parts shall be hot dipped galvanized after fabrication in conformance with ASTM A-123 and A-385. Hardware nuts bolts washers and other minor items shall be galvanized by the hot dip method in conformance with ASTM A-153 The projection portions of anchor bolts plus 12 inches shall be galvanized. The interior of all pipe shall be galvanized.
PART 3 EXECUTION
3.1 PREPARATION FOR DELIVERY
The complete system will be packed to insure carrier acceptance and safe delivery at the destination in containers complying with rules and regulations applicable to the mode of transportation
3.2 FIELD QUALITY CONTROL
Quality control shall be in accordance with the American Institute of Steel Construction Specification. All tests and inspections to determine compliance shall be made by the contractor and shall be subject to Government observation or verification. Contractor shall notify the CO five (5) days in advance of the delivery to allow a government representative to inspect the towers upon delivery.
3.3 REPLACEMENT OF DAMAGED OR MISSING PARTS.
Any damaged or missing parts noted at the time of the delivery inspection shall be replaced at no cost to the government. Parts damaged after the acceptance of the shipment shall, when requested, be replaced by the fabricator at a reasonable cost and time schedule.
END OF SECTION 13 10 00