cae-1700951-e002 signed.pdf
PDF 409 KB Posted
- Attached to
- West Columbia, SC CAE RCAG Tower Replacement Federal contract opportunity
- Solicitation number
- 6973GH-21-R-00072
About this file
This solicitation is seeking proposals for the demolition of four existing 50-foot guyed antenna towers and construction of four new 60-foot free-standing antenna towers at the Columbia Metropolitan Airport in West Columbia, South Carolina. Contractors must furnish all necessary materials, equipment, labor, insurance, permits and supervision to complete the work in accordance with the specifications, drawings and other attachments. A firm-fixed price construction contract will be awarded. Proposals are due no later than May 14, 2021. All questions must be submitted in writing by May 7, 2021. Contractors must be registered in the System for Award Management to be eligible for award. The Federal Aviation Administration will administer the contract in accordance with the Acquisition Management System in place of the Federal Acquisition Regulation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 6973GH-21-R-00072 Amendment 0004.pdf | ||
| cae-1700951-c004 signed.pdf | ||
| cae-1700951-c003 signed.pdf | ||
| cae-1700951-s001 signed.pdf | ||
| cae-1700951-g001 signed.pdf | ||
| cae-1700951-e001 signed.pdf | ||
| cae-1700951-e007 signed.pdf | ||
| Columbia Amendment 00003 - Revised Drawings.pdf | ||
| Amendment 00002-extension.pdf | ||
| Amendment 00001-revised specs and extension.pdf | ||
| 13 10 00 Antenna Towers Revision A.pdf | ||
| SOW Tower Replacement CAE RCAG Columbia SC.doc | DOC document | |
| COVID Special Contract Requirement.pdf | ||
| Contractor Release Form DOT F 4220.4.pdf | ||
| Drawings to Replace (4) 50ft Guyed Towers with (4) 60ft Free Standing Towers.pdf | ||
| Performance Bond.pdf | ||
| Wage Determination SC20210028.pdf | ||
| 6973GH-21-R-00072.pdf | ||
| Specifications CAE RCAG Tower Replacement Columbia SC.pdf | ||
| Experience Information Form.pdf | ||
| Payment Bonds.doc | DOC document |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
c a e -1
-e
.d g n
/1
/2
:4
:3
A
M O c ta w n C a rt e r
A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
DATE
REDLINE
APVD
A
INSIDE JUNCTION BOX
LEAVE 3' COILED
4/0 BARE IN 1-1/4" PVC
(TYP)
LADDER RUNG
TO TOWER
LADDER ATTACHED
FOUNDATION
TOWER
LEGEND
4/0
6 4 5
TOWER WITH BEAM CLAMPS
1 5/8"x 1 5/8" ATTACH TO
STAINLESS STEEL STRUT
CORNERS
TYPICAL OPPOSITE
TO COUNTERPOISE
2 22
J-BOX
CONDUIT, PVC 4"
CONDUIT, PVC 1-1/4"
A
E002
28R EVERY 3 FT)
CABLE CLAMP, THOMPSON #142 OR EQUAL (SUPPORT THOMPSON
NOTES
4/0 AWG BARE COPPER, 28 STRANDS, WT 660 LBS/1000 FT
PIPE CLAMP, THOMPSON #240X OR EQUAL
PARALLEL CLAMP, THOMPSON #4248 OR EQUAL
GROUND ROD, COPPER CLAD 3/4" DIA x 10'
STANDARD STEEL PIPE, GALV 2"x 21 FEET LONG (WATER PIPE)
AIR TERMINAL, 5/8"x 3', THOMPSON #667 OR EQUAL
VERTICAL CONNECTOR, THOMPSON #690 OR EQUAL10
U-BOLT, 2" WITH SELF LOCKING NUTS, SS
28 STRANDS,
WT 375 LBS/1000'. THOMPSON 28R OR EQUAL DOWN CONDUCTOR,
M A
X
OR EQUAL
THOMPSON NO 690
ELECT CONNECTOR
GALV WATER PIPE
2"x 21'
SEE DRAWING E003
COUNTERPOISE
TIE TO BUILDING
SEE DRAWING E003
COUNTERPOISE
TIE TO BUILDING
SEE NOTE 7
G R
A T
IN
G
H A
T C
H A
C C
E S
S
L A
D D
E R
5 6
THE J-BOX
COILED INSIDE
3'THOMPSON 28R
LEAVE 2 EACH
NOT TO SCALEE002
PLATFORM PLAN VIEW 4
NOT TO SCALEE002
TOWER CONDUIT SECTION 5
NOT TO SCALEE002
AIR TEMINAL ASSEMBLY
NOT TO SCALEE002
TOP OF TOWER JUNCTION BOX ELEVATION 2
NOT TO SCALEE002
TOWER CONDUIT ELEVATION
A
NOT TO SCALEE002
LADDER GROUNDING SECTION
TOWER LEGS
ON OPPOSITE
EACH INSTALLED
(TYP OF 2)
SEE NOTE 8
OF LADDER
4/0 TO BACK
JUNCTION BOX
GROUNDING INTO
CONDUIT FOR
PURPOSES.
INSTALL 4-4 IN PVC CONDUITS, NUMBER OF CONDUITS SHOWN HERE ARE FOR ILUSTRATION 9.
HAZARD.
4/0 AWG EXOTHERMICALLY BOND TO BACK OF LADDER NEAR ITS BASE TO AVOID TRIPPING 8.
THOMPSON 28R CADWELDED TO TOWER FRAME.7.
AND BURIED 2 FT DEEP.
ALL COUNTERPOISE SHALL BE PLACED 2 TO 6 FT AWAY FROM CONCRETE FOUNDATIONS 6.
SECURE DOWN CONDUCTOR T0 4/0, A MINIMUM OF 6" BELOW THE EXOTHERMIC WELD.
EACH,(TYPICALLY OPPOSING LEGS). USE PARALELL CLAMP THOMPSON #4248 OR EQUAL TO
EXOTHERMIC WELD 4/0 AWG TO TOWER LEG A MINIMUM OF 18" ABOVE FOUNDATION, 2 5.
INSTALL LADDER ON OPPOSITE SIDE OF JUNCTION BOX.4.
ALL GROUNDING CONNECTIONS BELOW GRADE BY EXOTHERMIC WELD.3.
THAN 12".
INSTALL DOWN CONDUCTOR WITH A MINIMUM OF BENDS AND NO SHARP BENDS OF LESS 2.
APPROVED EQUAL. CONDUCTOR SHALL REMAIN TIGHT BETWEEN CLAMPS
OF THE PLATFORM, AND DOWN THE TOWER LEG WITH THOMPSON CABLE CLAMP #142 OR
SUPPORT THE DOWN CONDUCTOR AT A MINIMUM OF 3'-0" SPACING AROUND THE PERIMETER 1.
WELD
EXOTHERMIC
TOWER LEGS
ON OPPOSITE
EACH INSTALLED
(TYP OF 2)
SEE NOTE 5
TO COUNTERPOISE
SEE NOTE 9
STRUCTURE (TYP)
CADWELD TO
FIBERGLASS J-BOX
36"x 30"x 10"
SS UNISTRUT FRAME
CAP
PIPE
SEE NOTE 4
JUNCTION BOX,
SEE NOTE 9
E D
M
IS
S
U E
D F
O R
ENGINEERING SERVICES
COMMUNICATIONS
RCAG
ANTENNA TOWER LIGHTNING PROTECTION
TOWER REPLACEMENT
SCCOLUMBIA METROPOLITAN AIRPORTCOLUMBIA
Stacey L. RainesFrancisco J. Cortes
RC
FC
PROJECT ENGINEER MGR: ENGINEERING - CENTER A
05/29/2020 1700951
CAE-1700951-E002 A
05/07/20211700951CONSTRUCTION (J.CORTES) DS05/07/2021A
c a e -1
-e
.d g n
THIS DRAWING PRODUCED ON ASO REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
C O
N S
T R
U C
T
IO
N
ORIGINAL SIGNED BY: ORIGINAL SIGNED BY:
SEE NOTE 9
BOX ON BUILDING
CONDUIT TO JUNCTION
| 2021-05-19T08:35:59-0400 | |
| Francisco Javier Cortes |
File details come from the government source that posted it. Updated .