Q A_6.23.2016.docx
DOCX document 13 KB Posted
- Attached to
- 480 volt Metal Clad Switchgear Federal contract opportunity
- Solicitation number
- 63095201019
About this file
Q A 6.23.2016
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SD.I.10061-M-1_Appendix_H.pdf | ||
| SD.I.10061-M-1_Appendix_M.pdf | ||
| SD.I.10061-M-1_Appendix_O.pdf | ||
| Q A_6.27.2016.docx | DOCX document | |
| SD.I.10061-M-1_Appendix_E.pdf | ||
| SD.I.10065.pdf | ||
| SD.I.10061-M-1_Appendix_R.pdf | ||
| SD.I.10061-M-1.pdf | ||
| SD.I.10061-M-1_Appendix_U.pdf | ||
| SD.I.10061-M-1_Appendix_N.pdf | ||
| SD.I.10061-M-1_Appendix_Q.pdf | ||
| SOW_Metal_Clad_Switchgear_Upgrade.pdf | ||
| Annunciator_Teminal_Block.pdf | ||
| ASR1554.pdf | ||
| ASR1555.pdf | ||
| 480_Vswitchgear.pdf | ||
| ARS1557.pdf | ||
| ASR1556.pdf | ||
| Q A_6.16.2016.pdf | ||
| 480_Vswitchgear_clear_copy.pdf | ||
| ss3_1.JPG | JPG image | |
| gen2.JPG | JPG image | |
| gen1_1.JPG | JPG image | |
| gen2_1.JPG | JPG image | |
| Qustions_and_answers_6.6.16.pdf | ||
| ss2_1.JPG | JPG image | |
| Qustions_and_answers.pdf | ||
| 480_V_Metal_Clad_ _Electrical_Panel.pdf | ||
| Solicitation_63095201019.pdf | ||
| SOW_Metal_Clad_Switchgear_Upgrade.pdf | ||
| Wage_Detirmination_TX253.pdf |
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. Drawing 0A-4-1186: Note 2 of the drawing states 2-pole breakers on Control Breakers, but the SOW states (8) Single Pole Signal Breakers. What is the controlling document?
Answer: 8 Single pole breakers (120 Volts)
2. Who is providing program setting for Breakers? Is a study required in this SOW?
Answer: Settings would be based on the actual load for each feeder and study shall be provided by contractor
3. What trip unit functions are required for the breakers Long, Short, Instantaneous, and/or ground?
Answer: The trip settings would be instantaneous
4. Is their Cat 5 capability in the control room? “Ethernet Cat 5 connection with external communication modules that provide high-speed.”
Answer: This means contract shall provide feeder status (open/ closed) in the control room
5. Are their existing raceways available for the Cat 5 wiring to the control room?
Answer: Disregard all confusion with Cat 5 wiring
6. If gear is on the Mexican side, do we have to pay an export tax on the gear?
Answer: All the equipment and work is located on the US side
7. What about tools to site? If on Mexican side, how will they be transported and is there and export/import tax?
Answer: All the equipment and work is located on the US side
8. From the SOW Document, “The Contractor shall provide drawings and schematics for new system…” Is that a new one-line drawing or this drawing limited to the SOW and then red-lines of the existing?
Answer: Update the existing schematic drawing with new trip settings, cable size's, cooper or aluminum, etc