Text version

General Services Administration

USBS Coburn Gore

Asbestos Survey Report

March 26, 2012

USBS Coburn Gore State Route 27

Coburn Gore, ME 04936

Prepared By

Federal Occupational Health JFK Building Room E‐110 Government Center Boston, MA 02203 i

GSA 2012 Draft Asbestos Survey Report – USBS Coburn Gore

ASBESTOS SURVEY REPORT

USBS Coburn Gore

Coburn Gore, ME 04936

For

New England Region

10 Causeway Street

Boston, MA 02222‐1077

March 26, 2012

Jacob Borchin ____________________________ Asbestos Inspector Signature

Michael J. Reeder ____________________________ Asbestos Inspector Signature

Dennis L. Hunter ____________________________ Senior Project Manager Signature

Earl C. McIntosh _____________________________ Senior Program Manager Signature

Prepared by:

Federal Occupational Health JFK Building Room E‐110 Government Center Boston, MA 02203

Table of Contents

I. List of Abbreviations

II. Executive Summary

Table 1 ‐ SUMMARY OF ACM IDENTIFIED AT THE SITE

III. Introduction and Background

IV. Project Tasks

V. Sample Locations & Sample Analysis

Table 2 ‐ SUMMARY OF PLM ANALYTICAL DATA

VI. ACM Condition Assessment

Table 3 – SUMMARY OF ACM PHYSICAL CONDITION

Table 4 – POTENTIAL FOR DISTURBANCE OF SUSPECT MATERIAL

VII. Sampling Protocol

Asbestos Sample Collection

VIII. Analytical Methods

Asbestos Samples

IX. Waste Management

X. Record Keeping

XI. Summary and Recommendations

XII. References

Attachments:

Appendix – A: Asbestos Containing Materials – Certified Laboratory Analytical Results Appendix – B: Photographs of ACM Building Materials Sampled Appendix – C: Asbestos Sampling Locations – Floor Plans and Drawings Appendix – D: Inspector Licenses and Company Certifications

I. List of Abbreviations

ACM Asbestos‐Containing Material

AHERA Asbestos Hazard Emergency Response Act

DS Dispersion Staining

EA Each

EPA Environmental Protection Agency

Flame AAS Flame Atomic Absorption Spectroscopy

FOH Federal Occupational Health

GSA Government Services Administration HA Homogeneous Area LF Linear Feet NESHAP National Emissions Standards for Hazardous Air Pollutants OSHA Occupational Safety and Health Administration O&M Operation & Maintenance PLM Polarized Light Microscopy PPE Personal Protective Equipment SF Square Feet SOW Scope of Work TEM Transmission Electron Microscopy US United States USEPA United States Environmental Protection Agency MDEP Maine Department of Environmental Protection

II. Executive Summary

On March 2, 2012, Mr. Jacob Borchin and Mr. Michael J. Reeder, who are representatives of the Federal Occupational Health (FOH) on behalf of the General Services Administration (GSA), conducted an asbestos survey of the USBS Coburn Gore located at State Route 27 in Coburn Gore, Maine (Site).

The purpose of this assessment was to determine if asbestos containing material (ACM) is present at the Site by collecting non‐destructive samples of accessible suspect ACM throughout the interior of the Site.

The exterior of the Site was not evaluated as part of this survey. Additionally, historic asbestos inspection report(s) or drawings and specifications for original construction and renovation regarding the installation of suspect ACM were not provided or available when the inspectors were conducting the asbestos survey at the Site.

During the collection of suspect ACM samples, the FOH representatives implemented controls, techniques, and protocols to minimize occupational exposure to asbestos, which are in accordance with the New Hampshire Department of Health and other applicable laws and regulations. All sampling and analysis of the suspect ACMs were performed in accordance with applicable requirements by qualified FOH inspectors and by laboratories accredited by the EPA.

During the course of the asbestos survey, FOH asbestos inspector(s) were accompanied by:

Mr. Lyndon Millet, GSA Building Manager and/or designated representative.

The FOH asbestos inspectors collected a total of sixty (60) individual suspected ACM samples throughout accessible areas of the Site. According to analytical results (Appendix B), asbestos was identified in twenty‐seven (27) of the sixty samples collected. The ACMs and associated quantities identified at the Site are summarized in the following Table 1:

Table 1 ‐ SUMMARY OF ACM IDENTIFIED AT THE SITE

SAMPLE

NUMBER

162288‐

MATERIAL

TYPE

MATERIAL

LOCATION

ASBESTOS

CONTENT

QUANTITY

(SF/LF/EA)

1B

1D

2B

3B

3D

Sheetrock & Joint

Compound/Paint

Unit 3 Bedroom 3

Unit 3 Bedroom 2

Unit 3 Living Room

1‐2% Chrysotile

1‐3% Chrysotile

1‐3% Chrysotile

3,600 SF

Gray Insulation on Tank

Unit 3 Basement

25‐30% Chrysotile

50 SF

13A

13B

14A

14B

15A

15B

9” X 9” Tan Floor Tile

W/ Black Mastic

Unit 3 Basement Stair

Landing

3‐5% Chrysotile

8‐10% Chrysotile

3‐5% Chrysotile

8‐10% Chrysotile

3‐5% Chrysotile

25 SF

19B

20B

20D

21B

Sheetrock &

Joint Compound/Paint

Unit 4 Bedroom 3 Closet

Unit 4 Living Room Closet

Unit 4 Master Bedroom

22A

22B

23A

23B

24A

24B

Unit 4 Kitchen

3‐5% Chrysotile

8‐10% Chrysotile

3‐5% Chrysotile

400 SF

NUMBER

162288‐

MATERIAL

TYPE

MATERIAL

LOCATION

ASBESTOS

CONTENT

QUANTITY

(SF/LF/EA)

Gray Sink Coating

Unit 2 Kitchen

Unit 1 Kitchen

10‐15% Chrysotile 2 EA

2‐3% Chrysotile

37B

37D

38B

38D

39B

39D

Unit 2 Bedroom 1

Unit 2 Living Room

Unit 2 Bedroom 2

1‐2% Chrysotile

1‐2% Chrysotile

TSI Pipe Insulation

Unit 1 Basement

15‐20% Chrysotile

10‐15% Amosite

150 LF

Assumed 400 SF

Unit 1

Assumed 3,600 SF

Note: All Quantities are estimates. SF=Square Feet, LF=Linear Feet, and EA = Each

* Considered Homogenous to Previous Identified ACM in units 2, 3 and 4.

III. Introduction and Background

According to supplied information, the Site includes an approximate 122,807‐square foot; five‐story building with a penthouse and basement.

IV. Project Tasks

Project tasks included:

Reviewing existing drawings and specifications provided by the GSA for original construction and renovation information (as available) regarding the installation of suspect ACM.

Reviewing historic asbestos inspection reports (as available) to determine the existence of previously identified homogeneous areas (HAs) at each functional space.

Verify if previously conducted asbestos inspection was performed in accordance with the Asbestos Hazard Emergency Response Act (AHERA) regulations. If not, the number of additional bulk samples necessary for compliance with the AHERA regulations will be calculated.

Developing sampling protocols in accordance to AHERA regulations.

Sampling and analyzing various interior building materials to determine if ACMs are present.

Developing maps for each floor showing areas where suspect ACM samples were collected and ACM was identified.

Note all areas identified as inaccessible (e.g., pipe chases, wall voids, elevator shafts, locked doors, etc.) during the sampling event.

Asbestos bulk samples of various building materials and surfaces were collected at the Site and submitted to the FOH Denver Asbestos Laboratory to undergo Polarized Light Microscopy with Dispersion Staining (PLM/DS) analysis in accordance with the “Method for the Determination of Asbestos in Bulk Building Materials” (US EPA Method 600/R‐93/116, July 1993).

V. Sample Locations & Sample Analysis

FOH’s accredited asbestos inspectors conducted the survey and collected samples of suspected ACM in general accordance with the Environmental Protection Agency’s (EPA’s) interpretations and guidelines of AHERA. The inspectors surveyed the Site and collected samples of all suspected ACM. The PLM analytical data of asbestos samples collected at the Site is summarized in Table 2.

Table 2 ‐ SUMMARY OF PLM ANALYTICAL DATA

NUMBER

162288‐

MATERIAL

TYPE

MATERIAL

LOCATION

ASBESTOS

CONTENT

QUANTITY

(SF/LF/EA)

01A

01B

01C

01D

02A

02B

03A

03B

03C

03D

Sheetrock & Joint

Compound

Paper

Compound/Paint

Sheetrock & Joint

Compound

Sheetrock & Joint

Compound

Paper

Unit 3 Bedroom 3

Unit 3 Bedroom 2

Unit 3 Living Room

ND

ND

1‐2% Chrysotile

ND

1‐3% Chrysotile

ND

1‐3% Chrysotile

Insulation

Unit 3 Attic

ND NA

Tan Sheet flooring

Unit 3 Kitchen

Unit 3 Basement

25‐30% Chrysotile 50 SF

14A

14B

Unit 3 Basement Stair Landing

3‐5% Chrysotile

8‐10% Chrysotile

3‐5% Chrysotile

25 SF

162288‐

MATERIAL

TYPE

MATERIAL

LOCATION

ASBESTOS

CONTENT

White Sheet Flooring

Unit 4 Bathroom

19A

19B

20A

20B

20C

20D

21A

21B

Sheetrock & Joint

Compound

Sheetrock & Joint

Compound

Paper

Compound/Paint

Unit 4 Bedroom 3

Unit 4 Living Room

Unit 4 Master Bedroom

ND

1‐2% Chrysotile

ND

1‐2% Chrysotile

23A

23B

Unit 4 Kitchen

3‐5% Chrysotile

8‐10% Chrysotile

3‐5% Chrysotile

Insulation

Unit 4 Attic

White Sheet Flooring

10‐15% Chrysotile

2 EA

162288‐

MATERIAL

TYPE

MATERIAL

LOCATION

ASBESTOS

CONTENT

34A

34B

35A

35B

36A

36B

37A

37C

37D

38A

38B

38C

38D

39A

39B

39C

Compound

Paper

Compound/Paint

Sheetrock & Joint

Compound

Paper

Compound/Paint

Sheetrock & Joint

Compound

Paper

Unit 2 Bedroom 1

Unit 2 Living Room

Unit 2 Bedroom 2

ND

1‐2% Chrysotile

ND

1‐2% Chrysotile

ND

1‐2% Chrysotile

ND

1‐2% Chrysotile

ND

White Pipe Wrap

15‐20% Chrysotile

10‐15% Amosite

150 LF

162288‐

MATERIAL

TYPE

MATERIAL

LOCATION

ASBESTOS

CONTENT

QUANTITY

(SF/LF/EA)

12”’ X 12” Tan Floor Tile

1st Floor Main Office

1st Floor Office 2

1st Floor Main Office

49A

49B

50A

50B

51A

51B

Joint Compound

1st Floor Stair Case

2nd Floor Stair Case

1st Floor Restroom

2’ X 2’ White Ceiling Tile

2nd Floor Main Room

2nd Floor Main Room

2nd Floor Bedroom 2

ND NA

Gray Duct Mastic

Basement

2’ X 4’ White Ceiling Tile

Note: All Quantities are estimates. SF=Square Feet, LF=Linear Feet, EA = Each, ND=Non‐Detected

VI. ACM Condition Assessment

The FOH asbestos inspector(s) categorized the various suspect ACMs (Surfacing Material, Miscellaneous

Material, and Thermal System Insulation) collected at the Site by visual inspection and classified these materials by referencing the following definitions:

Surfacing and Miscellaneous Material

Good Condition (GC) – Material with no visible damage or deterioration, or showing only very limited damage or deterioration.

Damaged (D) – The surface is crumbling, blistered, water‐stained, gouged, marred or otherwise abraded over less than one‐tenth (1/10) of the surface if the damage is evenly distributed (one‐quarter if the damage is localized).

Significantly Damaged (SG) – The surface is crumbling or blistered over at least 1/10 of the surface if the damaged is evenly distributed (one‐quarter if the damage is localized); 1/10

(one‐quarter, if localized) of material hanging from surface, deteriorated, or showing adhesive failure; and/or water stains, gouges, or mars over at least 1/10 of the surface if the damage is evenly distributed (one‐quarter if the damage is localized).

AHERA Definition of Damaged Friable Surfacing Miscellaneous ACM:

“Friable surfacing miscellaneous ACM, which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or, if applicable, which has delaminated such that the bond to the substrate (adhesion) is adequate or which for any other reason lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.”

Thermal System Insulation

Good Condition (GC) – Material with no visible damage or deterioration, or showing only very limited damage or deterioration.

Damaged (D) – A few water stains or less than 1/10 of insulation with missing jackets and/or crushed insulation or water stains, gouges, punctures, or mars on up to 1/10 of the insulation if the damage is evenly distributed (or up to one‐quarter if the damaged is localized).

Significantly Damaged (SG) – Missing jackets on at least 1/10 of the piping or equipment and/or crushed or heavily gouged or punctured insulation on at least 1/10 of pipe runs/risers, boiler, tank, duct, etc., if the damage is evenly distributed (or up to one‐quarter if the damaged is localized).

Note: Accumulation of powder, dust, or debris similar in appearance to the suspect material on surfaces beneath the pipe/boiler/tank/duct, etc. can be used as confirmatory evidence.

AHERA Definition of Damaged or Significantly Damaged Thermal System Insulation:

“Thermal system insulation ACM on pipes, boilers, tanks, ducts, and other thermal system insulation equipment which has lost its structural integrity, or its covering, in whole or in part, is crushed, water‐ stained, gouged, punctured, missing, or not intact such that is not able to contain fibers. Damage may be further illustrated by occasional punctures, gouges, or other signs of physical injury to ACM;

occasional water damage on the protective coverings/jackets; or exposed ACM ends or joints. Asbestos debris, originating from the ACBM in question may also indicate damage.”

Table 3 – SUMMARY OF ACM PHYSICAL CONDITION

SAMPLE

NUMBER

162288‐

MATERIAL

TYPE

Surfacing Material Thermal System Insulation Miscellaneous Material

Friable Non‐

Friable

Condt. Friable Non‐

Friable

Condt. Friable Non‐

Friable

Condt.

1B

1D

2B

3B

3D

√ GC

Gray Insulation on

Tank

14A

14B

162288‐

MATERIAL

TYPE

Surfacing Material Thermal System Insulation Miscellaneous Material

Friable Non‐

Friable

Condt. Friable Non‐

Friable

Condt. Friable Non‐

23A

23B

38B

38D

162288‐

MATERIAL

TYPE

Surfacing Material Thermal System Insulation Miscellaneous Material

Friable Non‐

Friable

Condt. Friable Non‐

Friable

Condt. Friable Non‐

Note: GC = Good Condition, D = Damaged, and SD = Significantly Damaged

* Considered Homogenous to Previous Identified ACM.

The FOH asbestos inspector(s) also determined the ACMs potential for contact, the influence of vibration, and the potential for air erosion by referencing the following definitions:

Potential for Contact with the Material

High: Service workers work in the vicinity of the material more than once per week, or

The material is in a public area (e.g., hallway, corridor, auditorium) and accessible to building occupants.

Moderate: Service workers work in the vicinity of the material once per month to once per week, or

The material is in a room or office and accessible to the occupants.

Low: Service workers work in the vicinity of the material less than once per month, or

The material is visible but not within reach of building occupants.

Influence of Vibration

High: Loud motors or engines present (e.g., some fan rooms), or

Intrusive noises or easily sensed vibrations (e.g., major airports, a major highway).

Moderate: Motors or engines present but not obtrusive (e.g., ducts vibrating but no fan in the area), or

Occasional loud sounds (e.g., a music room)

Low/None: None of the above.

Potential for Air Erosion

High: High velocity air (e.g., elevator shaft, fan room).

Moderate: Noticeable movement of air (e.g., air shaft, ventilator air stream).

Low/None: None of the above.

Table 4 – POTENTIAL FOR DISTURBANCE OF SUSPECT MATERIAL

NUMBER

162288‐

MATERIAL

TYPE

Potential for Contact Influence of Vibration Potential for Air Erosion

High Moderate Low High Moderate Low High Moderate Low

1B

1D

2B

3B

3D

Gray Insulation on

Tank

14A

14B

9” X 9” Tan Floor

Tile

23A

23B

162288‐

MATERIAL

TYPE

Potential for Contact Influence of Vibration Potential for Air Erosion

High Moderate Low High Moderate Low High Moderate Low

38B

38D

* Considered Homogenous to Previous Identified ACM in units 2, 3 and 4.

VII. Sampling Protocol

Asbestos Sample Collection

Representative bulk samples of suspect asbestos containing building materials (ACMBs) were collected at the Site building. The building was divided into separate and distinct project areas. For the purpose of this survey, each area was inspected and sampled as a separate functional space having separate and distinct homogenous materials. Homogenous material determination was based on the following criteria:

Similar physical characteristics (same color and texture, etc.)

Application (sprayed‐on, troweled‐on, assembly into a system etc.)

Material function (thermal insulation, floor tile, wallboard system etc.)

Samples of suspected ACM were collected and placed into sealed plastic bags and shipped via overnight delivery to the FOH Denver Asbestos Laboratory to undergo PLM/DS analysis in accordance with the

“Method for the Determination of Asbestos in Bulk Building Materials” (US EPA Method 600/R‐93/116, July 1993).

VIII. Analytical Methods

Asbestos Samples

Polarized Light Microscopy Analysis Methodology

The FOH Denver Asbestos Laboratory, which is a National Voluntary Laboratory Accreditation Program certified laboratory, provided the asbestos analytical services. The laboratory analyzed the suspected

ACM by PLM utilizing the EPAs Test Methods: Methods for the determination of Asbestos in Bulk

Building Materials (EPA 600/R‐93/116, July 1993) and the McCrone Research Institute’s The Asbestos

Particle Atlas as method references. Additional treatment and tests may be required to accurately define the sample composition (i.e. ashing, extraction, acetone treatment, and transmission electron microscopy).

The sample analysis was performed by using the bulk sample for visual observation and slide preparation(s) for microscopic examination and identification. The lab analyzed the samples for asbestos (chrysotile, amosite, crocidolite, anthophyllite, and actinolite/tremolite), fibrous non‐asbestos constituents (mineral wool, cellulose, etc.) and non‐fibrous constituents. Using a stereoscope, the microscopist visually estimated relative amounts of each constituent by determining the volume of each constituent in proportion to the total volume of the sample.

IX. Waste Management

FOH representatives did not generate any waste material while conducting the asbestos survey at the

Site. The small amount of material collected while conducting these surveys was submitted to the laboratories for analysis, and there was no excess amount of material left that required disposal.

X. Record Keeping

In order to document the progress of this project, the FOH inspector maintained field notes, developed site sketches, and made notations on site diagrams and floor plans as the fieldwork progressed. Copies of the certified laboratory asbestos analytical reports and chain–of‐custodies are included in Appendix

A. Photos of the suspected ACM are included in Appendix B. Copies of asbestos sample locations are included in Appendix C and company certifications and inspector licenses are included in Appendix D.

XI. Summary and Recommendations

On March 2, 2012 FOH inspectors collected a total of sixty (60) individual suspected ACM samples at the

Site. Analytical results of the asbestos samples collected indicated that twenty‐seven (27) of the sixty suspected ACM samples contained at least one percent or more of asbestos. ACM identified at the Site include the following materials, which are defined and quantified in Table 1 and Table 2 of this report:

Sheetrock & Joint Compound/Paint

TSI Pipe Insulation

9” X 9” Tan Floor Tile W/ Black Mastic

Since asbestos was identified in concentrations greater than one percent, any construction or renovation activities performed in the future are subject to applicable rules and regulation concerning the disturbance or removal of the ACM. The Maine Depart of Environmental Protection rules apply to all buildings which are subject to public occupancy, or to which the general public has access. Any person disturbing, removing, or encapsulating asbestos in any public building including, renovation, dismantling, or demolition, shall notify the Maine Depart of Environmental Protection in writing ten (10) working days prior to the start date of the abatement project. It is the responsibility of the building

Owner or it’s Representative to ensure that only current Maine State license asbestos abatement companies and workers engage in asbestos related activities.

The U.S. EPA regulations do not require removal of asbestos‐containing materials that are in good condition. However, personnel who may be involved with building renovations will need to be advised of the presence of asbestos, and appropriate measures may be warranted in order to assure the identified ACM in the building are not disturbed during renovation activities. If the ACM left in place is disturbed during renovation activities, the materials must be handled and disposed of in accordance with the applicable State and Federal regulations.

References

EPA, Guidance on Systematic Planning Using the Data Quality Objective Process, EPA, QA/G-4, February 2006.

EPA, Guidance for Quality Assurance Project Plans, EPA QA/G-5, December 2002.

EPA, Framework for Investigating Asbestos-Contaminated Superfund Sites, OSWER Directive #9200.0-

68, September 2008.

EPA, Guidance on Choosing a Sampling Design for Environmental Data Collection, EPA QA/G-5S, December 2002.

Appendix – A

AsbestosContainingMaterials
CertifiedLaboratoryAnalyticalResults

Appendix – B

Photographs of ACM Building Materials Sampled

GSA 2011 Asbestos Survey Report – USBS Coburn Gore Photographs of ACM Building Materials Sampled

1. Sample Number 162288-01, 02 & 03, which includes Sheetrock & Joint Compound/Paint

2. Sample Number 162288-10, which includes Gray Tank Insulation.

3 Sample Number 162288-11, which includes Gray Tank

4. Sample Number 162288-12, which includes Gray Tank

5. Sample Number 162288-13, 14 & 15, which includes 9” X 9” Tan Floor Tile W/ Black Mastic.

6. Sample Number 162288-19, which includes Sheetrock & Joint Compound/Paint.

7. Sample Number 162288-20 which includes Sheetrock & Joint Compound/Paint.

8. Sample Number 162288-22, 23 &24, which includes 9” X 9” Tan Floor Tile W/ Black Mastic.

9. Sample Number 162288-31 which includes Gray Sink Coating.

10. Sample Number 162288-32, which includes Gray Sink Coating.

11. Sample Number 162288-33, which includes Gray Sink Coating.

12. Sample Number 162288-37, which includes Sheetrock & Joint Compound/Paint.

13. Sample Number 162288-38, which includes Sheetrock & Joint Compound/Paint.

14. Sample Number 162288-43 which includes TSI Pipe Insulation.

15. Sample Number 16288-44, which includes TSI Pipe Insulation.

16. Sample Number 162288-45, which includes TSI Pipe

Appendix – C

Asbestos Sampling Locations – Floor Plans and Drawings

Asbestos Survey

USBS Coburn Gore

Coburn Gore, ME

Sample Locations

ACM Locations

Non ACM Locations

Stairs

Down

Generator/

Outside Air

Fire Sprinkler

Storage Tanks

Water

Heater

Boiler

USBS Coburn Gore st Floor

Men’s

Women’s

Entry

Hall

Garage

#2

Garage

#1

Main

Office

Office

#1

Stairs

Up

Stairs

Down

Restroom

#2

Restroom

#1

Office 2

US Border Station nd

Floor

Up

Bed

#1

Bed

#2

Bed

#3 Bed

#4

Closet

#1

Closet

#2

StorageBathroom

USBS Coburn Cove

Unit #1

Down

44 45

TSI Pipe Insulation

ACM 9" X 9" Tan Floor Tile W/ Black

Mastic on Stair Case Landing

USBS Coburn Gore

Unit #1

First Floor

Entry

Kitchen Dinning

Living Room

RR

Bedroom 1

Bedroom 2

9" X 9" Tan Floor Tile

W/ Black Mastic

ACM Sheetrock &

Joint Compound Throughout

Gray Sink Coating

USBS Coburn Gore

Unit #2

Down

ACM 9" X 9" Tan Floor Tile W/ Black

Mastic on Stair Case Landing

USBS Coburn Gore

Unit #2

31,32,33 34,35,36

Bathroom

Bedroom

#1 Bedroom

#2

Kitchen Flooring

Living

Room

9" X 9" Tan Floor Tile

W/ Black Mastic

Gray Sink Coating

ACM Sheetrock &

Joint Compound Throughout

USBS Coburn Gore

Unit #3

Down

Water

Heater

Heater

13,14, 9" X 9" Tan Floor Tile

Gray Tank Insulation

USBS Coburn Gore

Down

Kitchen

Dining Room

Living Room

Master

Bedroom

Bedroom

#2

Bedroom

#3

Bathroom

USBS Coburn Gore

Attic

Ladder to attic

Plywood

USBS Coburn Gore

Unit #4

Down

Water

Heater Heater

9" X 9" Tan Floor Tile

USBS Coburn Gore

Down

Kitchen

Dining

Room

Living

Room

Master

Bedroom Bedroom

#2

Bedroom

#3

Bathroom

17 18

9" X 9" Tan Floor Tile

W/ Black Mastic

USBS Coburn Gore

Ladder

To Attic

Appendix – D

Inspector Licenses and Company Certifications