This document contains an inspection report for a fire suppression system and related federal contract opportunity. The inspection report details an annual inspection conducted on August 25, 2018 of a conventional fire alarm and suppression system located at 5000 South 13th Street in Leavenworth, KS. The system passed all tests, which included inspection of control panels, devices such as smoke detectors and pull stations, notification appliances, and an agent cylinder suppression system. Battery and device tests were also completed. The related federal contract opportunity is solicitation number 36C77019R0004 for property management services in Leavenworth, KS issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. No further details are provided on the requirements or period of performance for the property management contract.

36C77019R0004 Attachment 6_cmop--suppression--annual-18-08-25-08-53-50-am.pdf

View the file

Other files for this federal contract opportunity

Other files attached to PROPERTY MANAGEMENT - LEAVENWORTH, newest first.
File Type Posted
36C77019R0004-0003000.docx DOCX document
36C77019R0004-0002003.pdf PDF
36C77019R0004-0002002.docx DOCX document
36C77019R0004-0001000.docx DOCX document
36C77019R0004-015.docx DOCX document
36C77019R0004-027.pdf PDF
36C77019R0004-019.pdf PDF
36C77019R0004-020.pdf PDF
36C77019R0004-016.docx DOCX document
36C77019R0004-023.pdf PDF
36C77019R0004-024.pdf PDF
36C77019R0004-028.pdf PDF
36C77019R0004-017.docx DOCX document
36C77019R0004-018.xlsx XLSX spreadsheet
36C77019R0004-022.pdf PDF
36C77019R0004-025.pdf PDF
36C77019R0004-026.pdf PDF
36C77019R0004-014.docx DOCX document
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection Report

Cmop Suppression Contact Info:

5000 South 13TH Street James Miller

Leavenworth , KS (619) 822-8459

66048 Jmiller@ieinc.net

System Summary:

Manufacturer: Fike

Model Number: Shp Pro

System Type: Conventional

Monitoring Agency: Alarm Central

Monitoring Account No.: F3

Inspection/Testing Results Summary

Site Devices Total Pass Fail

Photo electric smoke detector 4 4 0

Abort station 3 3 0

Manual pull station 2 2 0

Horns/Strobes 1 1 0

Strobes 2 2 0

Inspected By: Connor Robinson on 2018-08-25

2018/08/25

Control Panel

Control Panel - 1 Result

CPU Pass Lamps/LED's Pass Fuses Pass Trouble Signals Pass Ground Fault Monitoring Pass Circuit Supervision Pass Primary Power Supply Pass Secondary Power Supply Pass Disconnect Switches Pass Isolation Modules N/A System Cards Pass Amplifiers N/A LCD Pass

Suppression System

Suppression System - 1 Result

Agent Cylinder Pass Discharge Hose N/A Cylinder Brackets Pass Discharge Nozzle Pass System Piping Pass Enclosure Pass

Battery List

Locations Voltage Amp Rating % Tested

In Panel 12 7 100

In Panel 12 7 100

Device List

Zone 1:

Photo electric smoke detector: EP 3

Device ID Location Floor Time Result Notes

1 East Ceiling Smoke 1 08:53:08 Pass 3 East Subfloor Smoke 1 08:53:10 Pass

Zone 2:

Photo electric smoke detector: EP 3

Device ID Location Floor Time Result Notes

2 West Ceiling Smoke 1 08:53:09 Pass 4 West Subfloor Smoke 1 08:53:10 Pass

Zone 3:

Abort station:

Device ID Location Floor Time Result Notes

5 West Exit Abort 1 08:53:10 Pass 6 East Exit Abort 1 08:53:12 Pass 9 Maintenance Bypass Switch 1 08:53:14 Pass

Zone 4:

Manual pull station: EP 3

Device ID Location Floor Time Result Notes

8 East Exit Manual Pull 1 08:53:12 Pass 7 West Exit Manual Pull 1 08:53:16 Pass

File details come from the government source that posted it. Updated .