36C77019R0004-020.pdf
PDF 8 KB Posted
- Attached to
- PROPERTY MANAGEMENT - LEAVENWORTH Federal contract opportunity
- Solicitation number
- 36C77019R0004
About this file
This document is a system record of inspection and testing for a fire alarm system at a property in Kansas City, Missouri. The inspection was conducted by Keller Fire & Safety on August 25, 2018 and tested the Fike Shp Pro control unit, secondary battery power supply, initiating devices, notification appliances, and interface equipment. All components passed visual and functional testing according to NFPA 72 standards. The property representative from Cmop Suppression accepted the inspection report.
The related federal contract opportunity was a combined synopsis/solicitation from the Department of Veterans Affairs for property management services in Leavenworth, Kansas. No other details were provided on requirements, response dates, incumbent, or award information.
36C77019R0004 Attachment 5_cmop--suppression--NFPA-18-08-25-08-53-50-am.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C77019R0004-0003000.docx | DOCX document | |
| 36C77019R0004-0002003.pdf | ||
| 36C77019R0004-0002002.docx | DOCX document | |
| 36C77019R0004-0001000.docx | DOCX document | |
| 36C77019R0004-015.docx | DOCX document | |
| 36C77019R0004-027.pdf | ||
| 36C77019R0004-021.pdf | ||
| 36C77019R0004-019.pdf | ||
| 36C77019R0004-016.docx | DOCX document | |
| 36C77019R0004-023.pdf | ||
| 36C77019R0004-024.pdf | ||
| 36C77019R0004-028.pdf | ||
| 36C77019R0004-017.docx | DOCX document | |
| 36C77019R0004-018.xlsx | XLSX spreadsheet | |
| 36C77019R0004-022.pdf | ||
| 36C77019R0004-025.pdf | ||
| 36C77019R0004-026.pdf | ||
| 36C77019R0004-014.docx | DOCX document |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYSTEM RECORD OF INSPECTION AND TESTING
This form is to be completed by the system inspection and testing contractor at the time of a system test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Attach additional sheets, data, or calculations as necessary to provide a complete record.
Inspection/Test Start Date/Time: 2018-08-25 Inspection/Test Completion Date/Time: 2018-08-25
Supplemental Form(s) Attached: Yes (yes/no)
1. PROPERTY INFORMATION
Name of Property: Cmop Suppression
Address: 5000 South 13TH Street
Description of property:
Name of property representative: James Miller
Address:
Phone: (619) 822-8459 Fax: Email: Jmiller@ieinc.net
2. TESTING AND MONITORING INFORMATION
Testing organization: Keller Fire & Safety
Address: 1138 Kansas Ave, Kansas City
Phone: (913) 371-8494 Fax: Email: info@kellerfire.com
Monitoring organization: Alarm Central
Address: 5100 sw 31st
Phone: (816) 861-1500 Fax: Email:
Account number: F3 Phone line 1: Phone line 2:
Means of transmission: Dry contact
Entity to which alarms are retransmitted: Building Panel Phone:
3. DOCUMENTATION
On-site location of the required record documents and site-specific software: Site Office
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
Manufacturer: Fike Model Number: Shp Pro
4.2 Software and Firmware
Firmware revision number:
4.3 System Power
4.3.1 Primary (Main) Power
Nominal voltage: 0 Amps: 20A Location:
Overcurrent protection type: Amps: 20A Disconnecting means location:
4.3.2 Secondary Power
Type: Location:
Battery type (if applicable):
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
2018/08/25
SYSTEM RECORD OF INSPECTION AND TESTING (continued)
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring Organization Contact: Main panel Time: 08:00
Building Management Contact: Tony Time: 08:00
Building Occupants Contact: All Time: 08:00
Authority Having Jurisdiction Contact: Time:
Other Contact: Time:
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Description Visual Inspection Functional Test Comments
LCD See Attached
CPU See Attached
Lamps/LED's See Attached
Fuses See Attached
Trouble Signals See Attached
Disconnect Switches See Attached
Ground Fault Monitoring See Attached
Circuit Supervision See Attached
Isolation Modules See Attached
Primary Power Supply See Attached
Secondary Power Supply See Attached
System Cards See Attached
Amplifiers See Attached
6.2 Secondary Power
Description Visual Inspection Functional Test Comments
Battery condition See Attached
Load voltage See Attached
Discharge test N/A
Charger test N/A
Remote panel batteries N/A
6.3 Alarm and Supervisory Alarm Initiating Device
Attach supplementary device test sheets for all initiating devices.
6.4 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances.
6.5 Interface Equipment
Attach supplementary interface component test sheets for all interface components
Circuit Interface / Signaling Line Circuit Interface / Fire Alarm Control Interface
6.6 Supervising Station Monitoring
Description Yes No Time Comments
Alarm Signal
Alarm Restoration
Trouble Signal
Trouble Restoration
Supervisory Signal
Supervisory Restoration
6.7 Public Emergency Alarm Reporting System
Description Yes No Time Comments
Alarm Signal
Alarm Restoration
Trouble Signal
Trouble Restoration
Supervisory Signal
Supervisory Restoration
7. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring Organization Contact: Main panel Time: 08:45
Building Management Contact: Tony Time: 08:45
Building Occupants Contact: All Time: 08:45
Authority Having Jurisdiction Contact: Time:
Other Contact: Time:
8. SYSTEM RESTORED TO NORMAL OPERATION
Date: 2018-08-25 Time 08:45
9. CERTIFICATION
This system as specified herin has been inspected and tested according to NFPA 72, 2013 edition, Chapter 14.
Signed: Printed name: Connor Robinson Date: 2018-08-25
Organization: Keller Fire & Safety Title: Technician Phone: (816) 824-5347
Qualifications (refer to 10.5.3): Technician
10. DEFECTS OR MALFUNCTIONS NOT CORRECTED AT CONCLUSION OF SYSTEM INSPECTION,
TESTING, OR MAINTENANCE
(See Attached)
10.1 Acceptance by Owner or Owner's Representative:
The undersigned accepted the test report for the system as specified herein:
Signed: Printed name: James Miller Date: 25-08-2018
Organization: Cmop Suppression Title: Phone: (619) 822-8459
File details come from the government source that posted it. Updated .