This inspection report documents the results of testing performed on the fire alarm system located at 5000 S. 13th Street in Leavenworth, Kansas. The system is addressable and monitored by Alarm Central. It includes duct detectors, manual pull stations, tamper switches, water flow switches, and photoelectric smoke detectors connected to notification appliances throughout the building. The control panel, annunciator, batteries and over 100 devices were inspected and passed testing on August 25, 2018. The report indicates that the fire alarm system is in good working order.
The combined synopsis solicitation seeks proposals for property management services at the Department of Veterans Affairs facility located at 5000 S. 13th Street in Leavenworth, Kansas, the address referenced in the inspection report. Offerors are invited to submit proposals by the date listed to provide property management at this location.
36C77019R0004 Attachment 4_cmop-annual-18-08-25-09-53-10-am.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C77019R0004-0003000.docx | DOCX document | |
| 36C77019R0004-0002002.docx | DOCX document | |
| 36C77019R0004-0002003.pdf | ||
| 36C77019R0004-0001000.docx | DOCX document | |
| 36C77019R0004-021.pdf | ||
| 36C77019R0004-020.pdf | ||
| 36C77019R0004-016.docx | DOCX document | |
| 36C77019R0004-028.pdf | ||
| 36C77019R0004-017.docx | DOCX document | |
| 36C77019R0004-018.xlsx | XLSX spreadsheet | |
| 36C77019R0004-022.pdf | ||
| 36C77019R0004-025.pdf | ||
| 36C77019R0004-026.pdf | ||
| 36C77019R0004-015.docx | DOCX document | |
| 36C77019R0004-027.pdf | ||
| 36C77019R0004-023.pdf | ||
| 36C77019R0004-024.pdf | ||
| 36C77019R0004-014.docx | DOCX document |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection Report
CMOP Contact Info:
5000 S. 13th Tony Crisp
Leavenworth, KS (913) 727-4831
66048 tony.crisp@va.gov
System Summary:
Manufacturer: Bosch
Model Number: D7024
System Type: Addressable
Monitoring Agency: Alarm Central
Monitoring Account No.: F9-449
Inspection/Testing Results Summary
Site Devices Total Pass Fail
Duct detector 45 45 0
Manual pull station 11 11 0
Tamper switch 1 1 0
Water flow switch 1 1 0
Photo electric smoke detector 1 1 0
Horns/Strobes 32 32 0
Strobes 8 8 0
Inspected By: Connor Robinson on 2018-08-25
2018/08/25
Annunciator
Annunciator - 1 Result
CPU Pass Lamps/LED's Pass Fuses Pass Trouble Signals Pass Disconnect Switches N/A LCD Pass
Control Panel
Control Panel - 1 Result
CPU Pass Lamps/LED's Pass Fuses Pass Trouble Signals Pass Ground Fault Monitoring Pass Circuit Supervision Pass Primary Power Supply Pass Secondary Power Supply Pass Disconnect Switches N/A Isolation Modules N/A System Cards Pass Amplifiers N/A LCD Pass
Notification Extender
Notification Extender - 1 Result
CPU Pass Lamps/LED's Pass Fuses Pass Trouble Signals Pass Ground Fault Monitoring Pass Circuit Supervision Pass Primary Power Supply Pass Secondary Power Supply Pass
Battery List
Locations Voltage Amp Rating % Tested
In Panel 12 7 100
In Fcps 12 7 100
In Altronics Panel 12 7 100
In Fcps 12 7 100
In Panel 12 7 100
In Altronics panel 12 7 100
Device List
Loop 1:
Duct detector: EP 3,19
Device ID Location Floor Time Result Notes
49 RTU 7 Supply 1 09:25:45 Pass 50 RTU 7 Return 1 09:25:46 Pass 51 RTU 4 Supply 1 09:25:49 Pass 52 RTU 4 Return 1 09:25:52 Pass 53 RTU 11 Supply 1 09:25:55 Pass 54 RTU 11 Return 1 09:25:58 Pass 55 RTU 12 Supply 1 09:26:02 Pass 56 RTU 12 Return 1 09:26:05 Pass 57 RTU 13 Supply 1 09:26:08 Pass 58 RTU 13 Return 1 09:26:11 Pass 59 RTU 14 Supply 1 09:26:22 Pass 60 RTU 14 Return 1 09:26:26 Pass 61 RTU 18 Supply 1 09:26:26 Pass 62 RTU 18 Return 1 09:26:27 Pass 63 RTU 21 Supply 1 09:26:28 Pass 64 RTU 21 Return 1 09:26:30 Pass 65 RTU 23 Supply 1 09:26:32 Pass 66 RTU 23 Return 1 09:26:34 Pass 67 RTU 23 Supply 1 09:26:37 Pass 23 RTU 3 Supply 1 09:27:17 Pass 24 RTU 3 Return 1 09:27:20 Pass 25 RTU 2 Supply 1 09:27:23 Pass 26 RTU 2 Return 1 09:27:26 Pass 27 RTU 1 Supply 1 09:27:29 Pass 28 RTU 1 Return 1 09:27:34 Pass 31 RTU 10 Supply 1 09:27:36 Pass 32 RTU 10 Return 1 09:27:39 Pass 33 RTU 6 Supply 1 09:27:42 Pass 34 RTU 6 Return 1 09:27:45 Pass 35 RTU 16 Supply 1 09:27:48 Pass 36 RTU 16 Return 1 09:27:51 Pass 37 RTU 19 Supply 1 09:27:55 Pass 38 RTU 19 Return 1 09:27:58 Pass 39 RTU 20 Supply 1 09:28:01 Pass 40 RTU 20 Return 1 09:28:05 Pass 41 RTU 17 Supply 1 09:28:08 Pass 42 RTU 17 Return 1 09:28:11 Pass 43 RTU 15 Supply 1 09:28:14 Pass 44 RTU 15 Return 1 09:28:17 Pass 45 RTU 9 Supply 1 09:28:20 Pass 46 RTU 9 Return 1 09:28:24 Pass 47 RTU 8 Supply 1 09:28:27 Pass 48 RTU 8 Return 1 09:29:41 Pass 29 RTU 5 Supply 1 09:45:05 Pass 30 RTU 5 Return 1 09:45:06 Pass
Loop 1:
Manual pull station: EP 3
Device ID Location Floor Time Result Notes
68 SW WHS Exit 1 09:26:42 Pass 9 Office South Exit 1 09:26:48 Pass 10 Main Entry 1 09:26:51 Pass 11 Office North Exit 1 09:26:55 Pass 14 Loading Dock 1 09:27:05 Pass 16 Smokers Exit 1 09:27:07 Pass 17 Receiving Entry 1 09:27:11 Pass 19 WHSE Exit 1 09:27:14 Pass 18 H Keeping Exit 1 09:45:01 Pass 21 South Center Exit 1 09:45:03 Pass 22 SE Exit 1 09:45:05 Pass
Tamper switch: EP 1
Device ID Location Floor Time Result Notes
12 Tamper 1 09:26:57 Pass Water flow switch: EP 2
Device ID Location Floor Time Result Notes
13 Waterflow 1 09:27:01 Pass Photo electric smoke detector: EP 3
Device ID Location Floor Time Result Notes
15 FACP Room 1 09:45:00 Pass