36C26219B0001-001.pdf
PDF 182 KB Posted
- Attached to
- Fire Door Compliance Federal contract opportunity
- Solicitation number
- 36C26219B0001
About this file
36C26219B0001 S02 Solicitation Attachment 1 Fire Door Deficiencies.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26219C0088-000.docx | DOCX document | |
| 36C26219B0001-0002000.docx | DOCX document | |
| 36C26219B0001-0002001.pdf | ||
| 36C26219B0001-0002002.pdf | ||
| 36C26219B0001-0001003.xlsx | XLSX spreadsheet | |
| 36C26219B0001-0001001.pdf | ||
| 36C26219B0001-0001002.pdf | ||
| 36C26219B0001-0001000.docx | DOCX document | |
| 36C26219B0001-007.pdf | ||
| 36C26219B0001-008.pdf | ||
| 36C26219B0001-004.pdf | ||
| 36C26219B0001-005.pdf | ||
| 36C26219B0001-002.doc | DOC document | |
| 36C26219B0001-006.pdf | ||
| 36C26219B0001-000.docx | DOCX document | |
| 36C26219B0001-003.pdf | ||
| 36C26219B0001_1.docx | DOCX document |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Account Name Floor Area/Room Location Additional Info ID Date Unique
ID Deficiency Occupa ncy References Recommended Action
(short) TYPE
NFPA 101:
19.3.7.8(1)
K374
LS.02.01.30
NFPA 101:
19.3.7.8(1)
K374
LS.02.01.30
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
8.5.4.1
K374
LS.02.01.30
NFPA 101:
8.5.4.1
K374
LS.02.01.30
10/25/2018 3C.4-1 Smoke barrier door does not properly self-or automatically close.
Existing Health Care
Adjust self-closing device so that it holds door closed tight to door frame.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 OR
West entry doors, adjacent
OR 1
Adjust closer to overcome pressurization issue in area
10/25/2018 3B.4-10
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Adjust / repair hardware to provide for proper positive latching.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Stair 4 - Room 3A-01
Bathroom adjacent Stair N/A
10/25/2018 3C.4-2 Smoke barrier door does not properly self-or automatically close.
Existing Health Care
Adjust self-closing device so that it holds door closed tight to door frame.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Ultrasound Smoke Doors
FD-234-4
The center smoke seal prevents the doors from closing properly
10/25/2018 3C.3-2 Smoke barrier door not fitted to limit the passage of smoke.
Existing Health Care
Adjust door frame to reduce the gap between meeting edges of the doors to <1/8”.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
VA Police Administratio n
Corridor Smoke Doors N/A
10/25/2018 3B.4-12
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Adjust / repair hardware to provide for proper positive latching.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Equipment Room - Room 3D-17
N/A N/A
10/25/2018 3C.3-3 Smoke barrier door not fitted to limit the passage of smoke.
Existing Health Care
Adjust door frame to reduce the gap between meeting edges of the doors to <1/8”.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Chapel Corridor Smoke Doors 1F-01 N/A
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
10/25/2018 3C.4-7 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-1
Column Grid L- 17 N/A
10/25/2018 3C.4-9 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-1
Column Grid K- 25 N/A
10/25/2018 3C.4-8 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-1
Column Grid L- 17 N/A
10/25/2018 3C.4-11 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-5
Column Grid F- 25 N/A
10/25/2018 3C.4-10 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-3
Column Grid G-no latch hardware also.
10/25/2018 3C.4-13 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-4
Column Grid K- 17 N/A
10/25/2018 3C.4-12 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-2
Column Grid K- 17 N/A
18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
10/25/2018 3C.4-15 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-6
Column Grid F- 17 N/A
10/25/2018 3C.4-14 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-4
Column Grid H- 17 N/A
10/25/2018 3C.4-17 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-8
Column Grid E- 17 N/A
10/25/2018 3C.4-16 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-5
Column Grid F- 17 N/A
10/25/2018 3C.4-19 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-8
Column Grid F-9 N/A
10/25/2018 3C.4-18 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-7
Column Grid E- 17 N/A
10/25/2018 3C.4-20 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 4-5
Column Grid H- 25 N/A
18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
10/25/2018 3C.4-21 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 3-2
Column Grid N- 17 N/A
10/25/2018 3C.4-23 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 3-8
Column Grid F-9 N/A
10/25/2018 3C.4-22 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 3-6
Column Grid F- 17 N/A
10/25/2018 3C.4-25 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 3-5
Column Grid G- 25 N/A
10/25/2018 3C.4-24 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 3-5
Column Grid H- 25 N/A
10/25/2018 3C.4-27 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 2-4
Column Grid K- 17 N/A
10/25/2018 3C.4-26 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 3-7
Column Grid E-
No door hardware also.
18.3.7.8
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.8
K374
LS.02.01.30
NFPA 101:
19.3.7.8(1)
K374
LS.02.01.30
NFPA 101:
19.3.7.8(1)
K374
LS.02.01.30
NFPA 101:
8.3.3.3
K300
LS.02.01.10
NFPA 101:
8.3.3.3
K300
LS.03.01.10
10/25/2018 3C.4-28 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-12
Col A16 Adjust door closer
10/25/2018 3C.4-6 Smoke barrier door does not properly self-or automatically close.
Business Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 FD-233-2
Smoke doors between zones 2- 3 and 2-5
Door doesn't close and latch properly
10/25/2018 3C.4-4 Smoke barrier door does not properly self-or automatically close.
Existing Health Care
Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Service Bay
Smoke Doors
FD-222-4
The center smoke seal prevents the doors from closing properly
10/25/2018 3C.4-3 Smoke barrier door does not properly self-or automatically close.
Existing Health Care
Adjust door so that it self-closes and latches properly. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Loading Dock
Smoke Doors
FD-262-1
Blue door above ceiling to cat-walk. Door found in the open position
10/25/2018 3A.4-5 Door in fire barrier does not properly self-or automatically close.
Business
Adjust self-closing device so that it holds the access panel closed tight to door frame.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-8
Col F15/16 Adjust door closer
10/25/2018 3A.4-1 Door in fire barrier does not properly self-or automatically close.
Existing Health Care
Adjust self-closing device so that it holds the access panel closed tight to door frame.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Adjacent Stair 3
Fire Doors FD- 224-1 N/A
8.3.3.3
K300
LS.02.01.10
NFPA 101:
19.3.2.1.3
K321
LS.02.01.10
NFPA 101:
19.3.2.1.3
K321
LS.02.01.10
NFPA 101:
19.3.2.1.3
K321
LS.02.01.10
NFPA 101:
19.3.7.8(1)
K374
LS.02.01.30
NFPA 101:
20/21.3.2.1
K321
LS.03.01.10
NFPA 101:
7.2.1.5.10.2
K363
10/25/2018 3D.1-6 Hazardous area door does not properly self-or automatically close.
Existing Health Care
Adjust self-closing device so that it holds the door closed tight to door frame.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Palliative Care - Room 1G-143
Laundry Room N/A
10/25/2018 3A.4-2 Door in fire barrier does not properly self-or automatically close.
Existing Health Care
Adjust self-closing device so that it holds the access panel closed tight to door frame.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Palliative Care
Fire Doors FD- 272-3 N/A
10/25/2018 3D.1-4 Hazardous area door does not properly self-or automatically close.
Existing Health Care
Disable the friction hold-open function of the closer. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 OR-Room 3F- 33B
South side of OR's N/A
10/25/2018 3D.1-11 Hazardous area door does not properly self-or automatically close.
Existing Health Care
Adjust self-closing device so that it holds the door closed tight to door frame.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Kitchen - Room 1C- 07C
Trash Room N/A
10/25/2018 3D.1-7 Hazardous area door does not properly self-or automatically close.
Ambulat ory Health Care
Disable the friction hold-open function of the closer. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Emergency Department - Room 1A-
Storage Room N/A
10/25/2018 3C.4-5 Smoke barrier door does not properly self-or automatically close.
Existing Health Care
Disable the friction hold-open function of the closer. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Kitchen Decon Room N/A
10/25/2018 4N.1-1 More than one operation required to open a door.
Existing Health Care
Disable the thumb turn latch on the inside of the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center Loma
1 Main Lobby Sliding doors to Main Lobby N/A
LS.02.01.30
19.3.2.1.3
K321
LS.02.01.10
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 2C-24A Lab door no closer 10/25/2018 3D.1-3 Hazardous area door does not properly self-or automatically close.
Business NFPA 101:
8.7.1.2
Install a self-closing device on the door. DOOR
NFPA 101:
8.3.3.3
K300
LS.03.01.10
NFPA 101:
8.3.3.3
K300
LS.03.01.10
NFPA 101:
19.3.2.1.3
K321
LS.02.01.10
NFPA 101:
19.3.2.1.3
K321
LS.02.01.10
NFPA 101:
19.3.2.1.3
K321
LS.02.01.10
10/25/2018 3D.1-5 Hazardous area door does not properly self-or automatically close.
Existing Health Care
Install a self-closing device on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Pain Clinic - Room 3A-46 Supply Room N/A
Center-Loma Linda)
10/25/2018 3A.4-6 Door in fire barrier does not properly self-or automatically close.
Business Install a self-closing device on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-2
Col K9/10 no closer on door
10/25/2018 3A.4-4 Door in fire barrier does not properly self-or automatically close.
Business Install a self-closing device on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-12
Col D9/10 No closer on door
10/25/2018 3D.1-10 Hazardous area door does not properly self-or automatically close.
Existing Health Care
Install a self-closing device on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Kitchen - Room 1C- 07A
Storage Room N/A
10/25/2018 3D.1-8 Hazardous area door does not properly self-or automatically close.
Existing Health Care
Install a self-closing device on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Kitchen - Room 1C- 37A
Storage Room N/A
10/25/2018 3D.1-12 Hazardous area door does not properly self-or automatically close.
Existing Health Care
Install a self-closing device on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Floor Sweeper Room - Room 1C-34
Door to room N/A
8.3.3.3
K300
LS.03.01.10
NFPA 101:
Section 7.2.1.7.1
K374
LS.02.01.10
NFPA 101:
Section 7.2.1.7.1
K374
LS.02.01.10
NFPA 101:
Section 7.2.1.7.1
K374
LS.02.01.10
NFPA 13:
6.1.1.2
K351
LS.03.01.35
NFPA 101 :
19.2.5.2
K251
LS.02.01.20
NFPA 80:
6.3.1.7.1
K321
10/25/2018 3A.4-3 Door in fire barrier does not properly self-or automatically close.
Business Install a self-closing device on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Basemen t
Service Bay 5 N/A no closer on door
10/25/2018 3A.10-2
Door within a means of egress not provided with proper fire exit hardware.
Business Install approved fire exit hardware on the referenced door.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 2B-144 N/A Panic hardware
10/25/2018 3A.10-1
Door within a means of egress not provided with proper fire exit hardware.
Existing Health Care
Install approved fire exit hardware on the referenced door.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 Stair 5 Door Panic hardware on exit stair door
10/25/2018 5G.2-1
Sprinkler system component not Listed or not installed per the Listing.
Business Install coupling per required manufacturer recommendations and listing
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-4
Col H16 Pipe (possibly sprinkler) missing coupling on tee.
10/25/2018 3A.10-3
Door within a means of egress not provided with proper fire exit hardware.
Business Install approved fire exit hardware on the referenced door.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 2B-141 Corridor door Panic hardware
10/25/2018 3A.5-2
Fire doors have gaps/clearances exceeding the allowances per NFPA 80.
Existing Health Care
Install Listed product to reduce clearance under the door to not exceed 3/4".
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 VA Police Corridor
Doors to ED - Doors FD-212-3 N/A
10/25/2018 4BB.2-1
Dead-end corridor exceeds maximum permitted length.
Existing Health Care
Install double doors to reduce dead-end corridor to allowable limit.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Acute Psych Corridor N/A
46 ft dead end leading up to Acute Psych
LS.02.01.10
NFPA 80:
6.3.1.7.1
K321
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
10/25/2018 3B.4-1
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 4.00E-51 Cardiology/EKG Suite doors
Suite door locked open, inactive leaf with no latching hardware and latch blocked with paper/tissues
10/25/2018 3A.5-1
Fire doors have gaps/clearances exceeding the allowances per NFPA 80.
Existing Health Care
Install Listed product to reduce the gap between meeting edges of doors.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 FD-225-1 North Elev Lobby Gap at door edge
10/25/2018 3B.4-4
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 OR Storage Room Room adjacent
OR 1
10/25/2018 3B.4-3
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 OR-Room 3F- 42 Trash Room N/A
10/25/2018 3B.4-6
Door separating room or suite from corridor does not properly
Existing Health C
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical 3 OR-Sterile
Core Door into OR 1 N/A
10/25/2018 3B.4-5
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 OR Storage Room Double doors across from OR 5
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
does not properly latch. Care hardware on the door.VA Medical
Center-Loma Linda)
Core
10/25/2018 3B.4-8
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 OR-Sterile Core Door into OR 4 N/A
10/25/2018 3B.4-7
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 OR-Sterile Core Door into OR 3 N/A
10/25/2018 3B.4-13
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Locker Room
- Room C3- 39A
N/A Sliding glass door into Locker Room
10/25/2018 3B.4-11
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 SICU-Door 3D-07 N/A Suite boundary doors
10/25/2018 3B.4-9
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the double doors.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Ultrasound - Door C3-51 Corridor doors
Suite boundary doors into Ultrasound
10/25/2018 3B.4-14
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Install positive latching hardware on the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
SICU
Procedure
OR
N/A New double doors into SICU
6.4.4.3
K363
LS.03.01.10
NFPA 80:
6.4.4.3
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
10/25/2018 3A.3-3 Door in fire barrier does not properly latch.
Existing Health Care
Modify the present smoke seal to allow bottom Fire Bolt to operate properly if required.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 VA Police Corridor
Doors to ED - Doors FD-212-3 N/A
10/25/2018 3B.4-15
Door separating room or suite from corridor does not properly latch.
Ambulat ory Health Care
Install positive latching hardware on the double doors.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 ED
Double doors adjacent Dirty Utility 1A-634
N/A
10/25/2018 3A.1-16
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test result that door and frame are 90-minute rated - replace if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Stair 8 - Pipe Chase Room
Stair 8 Required Exit Passageway
N/A
10/25/2018 3A.1-19
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test result that door and frame are 60-minute rated - replace if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Fire Pump Room N/A N/A
10/25/2018 3A.1-14
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door frame has a 90-minute rating- replace if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Resident Quarters
Fire Doors C3-
Door into Residents Quarters - Frame label covered by continuous hinge
10/25/2018 3A.1-17
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test result that door and frame are 90-minute rated - replace if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Stair 8 - AHU #44 Room
Stair 8 Required Exit Passageway
N/A
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.03.01.10
NFPA 101:
8.3.4.2
K374
LS.03.01.10
10/25/2018 3A.1-5
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has 90-minute rating-replace door if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 4.00E-04 Cath Holding Door not 90-min rated
10/25/2018 3A.1-15
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door frame has a 90-minute rating- replace if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Stair 8 - Service Bay
Stair 8 Required Exit Passageway
N/A
10/25/2018 3A.1-10
Door assembly in fire barrier does not have the minimum required rating.
Business Obtain test results showing door has 90-minute rating-replace door if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 2B-144 N/A 60 min rated
10/25/2018 3A.1-6
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has 90-minute rating-replace door if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 4A-05A Exec Conf Room
No label on door in 2-hour barrier
10/25/2018 3A.1-11
Door assembly in fire barrier does not have the minimum required rating.
Business Obtain test results showing door has 90-minute rating-replace door if necessary.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 2B-141 Corridor door 60 min rated
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
10/25/2018 3A.1-1
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 Service Bay 2 Door No label
10/25/2018 3A.1-3
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 Service Bay 5 Door No label
10/25/2018 3A.1-2
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 Service Bay 4 Door No label
10/25/2018 3A.1-20
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Service Bay 1 N/A No Label
10/25/2018 3A.1-4
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 Service Bay 7 Door No label
10/25/2018 3A.1-21
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Service Bay 8 N/A No Label
K374
LS.02.01.10
NFPA 101:
8.3.4.2
K374
LS.03.01.10
NFPA 101:
8.3.4.2
K374
LS.03.01.10
NFPA 101:
8.3.4.2
K374
LS.03.01.10
NFPA 101:
8.3.4.2
K374
LS.03.01.10
NFPA 101:
8.3.4.2
K374
LS.03.01.10
10/25/2018 3A.1-7
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Service Bay 8 N/A 20 min door, no closer
10/25/2018 3A.1-13
Door assembly in fire barrier does not have the minimum required rating.
Business Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Service Bay 5 N/A No label on door
10/25/2018 3A.1-12
Door assembly in fire barrier does not have the minimum required rating.
Business Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Service Bay 3 N/A No label on door
10/25/2018 3A.1-24
Door assembly in fire barrier does not have the minimum required rating.
Business Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Service Bay 1 N/A no label on door
10/25/2018 3A.1-23
Door assembly in fire barrier does not have the minimum required rating.
Business Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Service Bay 2 N/A No label on door
10/25/2018 3A.1-25
Door assembly in fire barrier does not have the minimum required rating.
Business Obtain test results showing door has a 45-minute fire rating- replace if necessary
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Service Bay 7 N/A no label on door
7.10.8.3.1
K363
LS.02.01.20
NFPA 101:
19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7
K363
LS.02.01.10
NFPA 101:
19.3.2.1.3
K321
LS.02.01.10
NFPA 101:
8.3.3.3
K300
LS.03.01.10
NFPA 80:
5.2.15.4
K321
LS.02.01.10
NFPA 101:
18.3.7.2 & 18.3.7.6
K374
LS.02.01.30
10/25/2018 4X.7-3
Door that could be mistaken for an exit is not provided with proper signage.
Existing Health Care
Post a sign reading "NO EXIT" on or adjacent to the door.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Service Bay
Glass door towards Service Bay
N/A
10/25/2018 3D.1-9 Hazardous area door does not properly self-or automatically close.
Existing Health Care
Reconnect the self-closing device to the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Kitchen - Room 1C- 33F
Ingredient Control Room N/A
10/25/2018 3B.4-2
Door separating room or suite from corridor does not properly latch.
Existing Health Care
Reactivate positive-latching hardware. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 4B-09 N/A Power operated suite door not positive latching.
10/25/2018 3A.7-1
The integrity of the fire door is compromised by holes/other damaged items.
Existing Health Care
Re-install missing closer cover. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Stair 5 Door STR #5-1- 2 N/A
10/25/2018 3A.4-7 Door in fire barrier does not properly self-or automatically close.
Business Rehang door or modify concrete floor (maintain required floor rating).
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-1
Col K23 Door scraps on concrete floor and does not close
10/25/2018 3C.3-7 Smoke barrier door not fitted to limit the passage of smoke.
Business Re-install smoke barrier door and frame or properly seal gap around frame
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-7
Col E17 Gap around frame
18.3.7.6
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.6
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.6
K374
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.6
K374
LS.02.01.30
NFPA 101:
8.3.4.2
K374
LS.03.01.10
NFPA 101:
19.3.6.3.10*
K363
LS.02.01.30
NFPA 80:
6.4.4.3
K374
LS.02.01.10
10/25/2018 3C.3-8 Smoke barrier door not fitted to limit the passage of smoke.
Business Re-install smoke barrier door and frame or properly seal gap around frame
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-7
Col D/E17 Gap around frame filled with expanding foam
10/25/2018 3C.3-5 Smoke barrier door not fitted to limit the passage of smoke.
Business Re-install smoke barrier door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 2-6
Column Grid F- 17 Door removed.
10/25/2018 3C.3-6 Smoke barrier door not fitted to limit the passage of smoke.
Business Re-install smoke barrier door and frame. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Interstitial
Smoke Compartmen t 2-5
Column Grid F-door and frame removed.
10/25/2018 3A.1-29
Door assembly in fire barrier does not have the minimum required rating.
Business Remove expanding foam and properly seal gap or remove and reinstall door.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-2
Col L/M17 gap around door with expanding foam
10/25/2018 3C.3-9 Smoke barrier door not fitted to limit the passage of smoke.
Business Re-install smoke barrier door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-7
Col F25 Missing door
10/25/2018 3A.3-1 Door in fire barrier does not properly latch.
Existing Health Care
Repair the latching hardware to allow the door to close and latch properly.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
4 4C-22B N/A Door does not latch properly
10/25/2018 3B.8-1
Corridor door not able to be closed with a pushing or pulling motion.
Existing Health Care
Remove the self-closing device from the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 OR Office door 3F-
Room no longer utilized as a storage room
6.4.4.3
K374
LS.02.01.10
NFPA 80:
6.4.4.3
K374
LS.03.01.10
NFPA 80:
6.4.4.3
K374
LS.03.01.10
NFPA 101:
18.3.7.2 & 18.3.7.6
K374
LS.02.01.30
NFPA 101:
8.3.4.2
K374
LS.03.01.10
NFPA 101:
8.3.4.2
K374
LS.03.01.10
10/25/2018 3A.3-5 Door in fire barrier does not properly latch.
Business Repair the latching hardware to allow the door to close and latch properly.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-1
Col L/M17 Door does not properly latch
10/25/2018 3A.3-2 Door in fire barrier does not properly latch.
Existing Health Care
Repair the latching hardware to allow the door to close and latch properly.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Residents Quarters
Fire Doors - FD- 214-1 N/A
10/25/2018 3C.1-1 Improper construction of smoke barrier door. Business Repair/replace door handle. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-4
Col K17 Handle on door is broken
10/25/2018 3A.3-6 Door in fire barrier does not properly latch.
Business Repair the latching hardware to allow the door to close and latch properly.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-1
Stair 1 door does not properly latch
10/25/2018 3A.1-27
Door assembly in fire barrier does not have the minimum required rating.
Business
Replace doors and frame with a door and frame having a 90-minute fire rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-1
Col K/L18 No door
10/25/2018 3A.1-26
Door assembly in fire barrier does not have the minimum required rating.
Business
Replace doors and frame with a door and frame having a 90-minute fire rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-1
Col L18 No door
K374
LS.03.01.10
NFPA 101:
8.3.4.2
K374
LS.02.01.10
NFPA 101:
8.5.4.5, 8.3.3.5
- 8.3.3.9
K379
LS.02.01.30
NFPA 101:
8.5.4.5, 8.3.3.5
- 8.3.3.9
K379
LS.02.01.30
NFPA 101:
8.5.4.5, 8.3.3.5
- 8.3.3.9
K379
LS.02.01.30
NFPA 101:
18.3.7.2 & 18.3.7.6
K374
10/25/2018 3A.1-18
Door assembly in fire barrier does not have the minimum required rating.
Existing Health Care
Replace doors and frame with a door and frame having a 90-minute fire rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Stair 8 - Glass Doors to 1 South
Stair 8 Required Exit Passageway
N/A
10/25/2018 3A.1-28
Door assembly in fire barrier does not have the minimum required rating.
Business
Replace doors and frame with a door and frame having a 90-minute fire rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Intersticia l
Smoke Compartmen t 1-1
Col K25 No door
10/25/2018 2D.1-3 Smoke barrier fire window assembly not properly rated.
Existing Health Care
Replace glass & frame assembly in smoke barrier with one having a minimum 20-minute rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Palliative Care
West Smoke Doors N/A
10/25/2018 2D.1-2 Smoke barrier fire window assembly not properly rated.
Existing Health Care
Replace glass & frame assembly in smoke barrier with one having a minimum 20-minute rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Palliative Care - Door
PC-1S
East Smoke Doors N/A
10/25/2018 3C.3-1 Smoke barrier door not fitted to limit the passage of smoke.
Business Replace the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma
3 Clinics Smoke Doors
FD-214-3
Doors are warped and do not seal properly along center edge
10/25/2018 2D.1-1 Smoke barrier fire window assembly not properly rated.
Existing Health Care
Replace glass in smoke barrier with material having a minimum 20-minute rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
3 Radiology- Door 3E-28E N/A
Glazing (glass) in door is painted and unable to determine rating.
LS.02.01.30
19.2.2.2.2
K222
LS.02.01.20
NFPA 80:
6.4.4.3
K374
LS.02.01.10
NFPA 101:
19.3.2.1
K321
LS.02.01.30
NFPA 101:
19.3.2.1
K321
LS.02.01.30
NFPA 101:
8.3.4.2
K374
LS.03.01.10
NFPA 101:
8.3.4.2
K374
Center Loma Linda) center edge
10/25/2018 3A.3-4 Door in fire barrier does not properly latch.
Existing Health Care
Return the missing Fire Bolt on bottom of the door. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Emergency Department
Doors between Lobby & ED - Doors FD-212-4
N/A
10/25/2018 4M.1-1
Door within the means of egress not unlocked from the direction of egress.
Existing Health Care
Replace the existing lock with an approved delayed egress locking mechanism.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
1 Elevator S3 Doors towards Central Supply
Current situation creates a "dead-end" corridor for those occupants that do not have card reader access to the doors
10/25/2018 2K.1-2 Hazardous area not properly enclosed.
Existing Health Care
Verify fire rating of door frame. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Palliative Care - Room 1G-112
2 doors into room
Door frame is covered by a continuous hinge and door frame label not visible
10/25/2018 2K.1-1 Hazardous area not properly enclosed.
Existing Health Care
Verify fire rating of door frame. DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
Palliative Care - Room 1G-114
2 doors into room
Door frame is covered by a continuous hinge and door frame label not visible
10/25/2018 3A.1-9
Door assembly in fire barrier does not have the minimum required rating.
Business Door assembly in fire barrier does not have the minimum required rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Service Bay 4 N/A No label
10/25/2018 3A.1-8
Door assembly in fire barrier does not have the minimum required rating.
Business Door assembly in fire barrier does not have the minimum required rating.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 Service Bay 6 N/A No Label
LS.03.01.10
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 2F-25 N/A No closer or latch on both doors 10/25/2018 3D.1-1
Hazardous area door does not properly self-or automatically close.
Business NFPA 101:
8.7.1.2
Hazardous area door does not properly self- or automatically close.
DOOR
VA Loma Linda (Formerly:
VA Medical Center-Loma Linda)
2 2F-27B N/A No closer 10/25/2018 3D.1-2 Hazardous area door does not properly self-or automatically close.
Business NFPA 101:
8.7.1.2
Hazardous area door does not properly self- or automatically close.
DOOR
GRAND TOTAL
Phase 2. Vendor will install all doors and/or hardware to ensure compliance. The vendor will provide all required oversight. Daily project log NFPA reports and checklists will be completed and submitted daily and weekly. Doors which are not listed as rated will be rated. Doors liste
In the event that the vendor discovers a door which are listed as rated but not actually rated will be addressed on a case-by-case basis.
No changes will be made without COR consent.
The vendor will provide patch and paint and carpentry, if needed.
Linda)
DR1 S Acrovy
Flush Door, Square Edge and Door Edge Classic Maple #372 Lite Kit ‐ Standard Metal (NR 90min) per Architectural
Door Schedule
(Front of
House
Interi or
Doors
Continuous Aluminum Privacy Hinge Office doors do not have closers, unless required by fire code.
DR2 am, Assa
Flush Door with Stainless Steel Door
Kick
#100 Clear Plain Sliced White Maple per Architectural
Door Schedule
Emplo yee (Back of
House
Interi
Formaldehyde‐ Free Adhesives Continuous Aluminum Privacy Hinge Office doors do not have closers, gs will be completed and turned in at the end of each day for COR review. Weekly reports will also be submitted documenting project progr ed as rated which are no longer visible will be addressed and fixed to ensure labeling ress, line items completed, in progress, parts status, pending completion, upcoming schedules, and/or issues.