36C26219B0001-0001003.xlsx

XLSX spreadsheet 43 KB Posted

Attached to
Fire Door Compliance Federal contract opportunity
Solicitation number
36C26219B0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

36C26219B0001 0001 VA Loma Linda Fire Doors Deficiency List.xlsx

View the file

Other files for this federal contract opportunity

Other files attached to Fire Door Compliance, newest first.
File Type Posted
36C26219C0088-000.docx DOCX document
36C26219B0001-0002000.docx DOCX document
36C26219B0001-0002001.pdf PDF
36C26219B0001-0002002.pdf PDF
36C26219B0001-0001001.pdf PDF
36C26219B0001-0001002.pdf PDF
36C26219B0001-0001000.docx DOCX document
36C26219B0001-007.pdf PDF
36C26219B0001-008.pdf PDF
36C26219B0001-004.pdf PDF
36C26219B0001-001.pdf PDF
36C26219B0001-005.pdf PDF
36C26219B0001-002.doc DOC document
36C26219B0001-006.pdf PDF
36C26219B0001-000.docx DOCX document
36C26219B0001-003.pdf PDF
36C26219B0001_1.docx DOCX document
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Loma 110518

Account NameFloorArea/RoomLocationAdditional InfoID DateUnique IDDeficiencyOccupancyReferencesRecommended Action (short)TYPE
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3ORWest entry doors, adjacent OR 1Adjust closer to overcome pressurization issue in area10/25/183C.4-1Smoke barrier door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.7.8(1)Adjust self-closing device so that it holds door closed tight to door frame.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3UltrasoundSmoke Doors FD-234-4The center smoke seal prevents the doors from closing properly10/25/183C.4-2Smoke barrier door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.7.8(1)Adjust self-closing device so that it holds door closed tight to door frame.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Stair 4 - Room 3A-01Bathroom adjacent StairN/A10/25/183B.4-10Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Adjust / repair hardware to provide for proper positive latching.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Equipment Room - Room 3D-17N/AN/A10/25/183B.4-12Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Adjust / repair hardware to provide for proper positive latching.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1VA Police AdministrationCorridor Smoke DoorsN/A10/25/183C.3-2Smoke barrier door not fitted to limit the passage of smoke.Existing Health CareNFPA 101: 8.5.4.1Adjust door frame to reduce the gap between meeting edges of the doors to <1/8”.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1ChapelCorridor Smoke Doors 1F-01N/A10/25/183C.3-3Smoke barrier door not fitted to limit the passage of smoke.Existing Health CareNFPA 101: 8.5.4.1Adjust door frame to reduce the gap between meeting edges of the doors to <1/8”.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-1Column Grid L-17N/A10/25/183C.4-7Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-1Column Grid L-17N/A10/25/183C.4-8Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-1Column Grid K-25N/A10/25/183C.4-9Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-3Column Grid G-25no latch hardware also.10/25/183C.4-10Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-5Column Grid F-25N/A10/25/183C.4-11Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-2Column Grid K-17N/A10/25/183C.4-12Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-4Column Grid K-17N/A10/25/183C.4-13Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-4Column Grid H-17N/A10/25/183C.4-14Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-6Column Grid F-17N/A10/25/183C.4-15Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-5Column Grid F-17N/A10/25/183C.4-16Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-8Column Grid E-17N/A10/25/183C.4-17Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-7Column Grid E-17N/A10/25/183C.4-18Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-8Column Grid F-9N/A10/25/183C.4-19Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4 InterstitialSmoke Compartment 4-5Column Grid H-25N/A10/25/183C.4-20Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3 InterstitialSmoke Compartment 3-2Column Grid N-17N/A10/25/183C.4-21Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3 InterstitialSmoke Compartment 3-6Column Grid F-17N/A10/25/183C.4-22Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3 InterstitialSmoke Compartment 3-8Column Grid F-9N/A10/25/183C.4-23Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3 InterstitialSmoke Compartment 3-5Column Grid H-25N/A10/25/183C.4-24Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3 InterstitialSmoke Compartment 3-5Column Grid G-25N/A10/25/183C.4-25Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3 InterstitialSmoke Compartment 3-7Column Grid E-25No door hardware also.10/25/183C.4-26Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2 InterstitialSmoke Compartment 2-4Column Grid K-17N/A10/25/183C.4-27Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2FD-233-2Smoke doors between zones 2-3 and 2-5Door doesn't close and latch properly10/25/183C.4-6Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-12Col A16Adjust door closer10/25/183C.4-28Smoke barrier door does not properly self- or automatically close.BusinessNFPA 101: 18.3.7.2 & 18.3.7.8Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Loading DockSmoke Doors FD-262-1Blue door above ceiling to cat-walk. Door found in the open position10/25/183C.4-3Smoke barrier door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.7.8(1)Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Service Bay 4Smoke Doors FD-222-4The center smoke seal prevents the doors from closing properly10/25/183C.4-4Smoke barrier door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.7.8(1)Adjust door so that it self-closes and latches properly.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Adjacent Stair 3Fire Doors FD-224-1N/A10/25/183A.4-1Door in fire barrier does not properly self- or automatically close.Existing Health CareNFPA 101: 8.3.3.3Adjust self-closing device so that it holds the access panel closed tight to door frame.DOOR
K300
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-8Col F15/16Adjust door closer10/25/183A.4-5Door in fire barrier does not properly self- or automatically close.BusinessNFPA 101: 8.3.3.3Adjust self-closing device so that it holds the access panel closed tight to door frame.DOOR
K300
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Palliative CareFire Doors FD-272-3N/A10/25/183A.4-2Door in fire barrier does not properly self- or automatically close.Existing Health CareNFPA 101: 8.3.3.3Adjust self-closing device so that it holds the access panel closed tight to door frame.DOOR
K300
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Palliative Care - Room 1G-143Laundry RoomN/A10/25/183D.1-6Hazardous area door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.2.1.3Adjust self-closing device so that it holds the door closed tight to door frame.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Kitchen - Room 1C-07CTrash RoomN/A10/25/183D.1-11Hazardous area door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.2.1.3Adjust self-closing device so that it holds the door closed tight to door frame.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3OR-Room 3F-33BSouth side of OR'sN/A10/25/183D.1-4Hazardous area door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.2.1.3Disable the friction hold-open function of the closer.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1KitchenDecon RoomN/A10/25/183C.4-5Smoke barrier door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.7.8(1)Disable the friction hold-open function of the closer.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Emergency Department - Room 1A-632Storage RoomN/A10/25/183D.1-7Hazardous area door does not properly self- or automatically close.Ambulatory Health CareNFPA 101: 20/21.3.2.1Disable the friction hold-open function of the closer.DOOR
K321
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Main LobbySliding doors to Main LobbyN/A10/25/184N.1-1More than one operation required to open a door.Existing Health CareNFPA 101: 7.2.1.5.10.2Disable the thumb turn latch on the inside of the door.DOOR
K363
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Pain Clinic - Room 3A-46Supply RoomN/A10/25/183D.1-5Hazardous area door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.2.1.3Install a self-closing device on the door.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)22C-24ALab doorno closer10/25/183D.1-3Hazardous area door does not properly self- or automatically close.BusinessNFPA 101: 8.7.1.2Install a self-closing device on the door.DOOR
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-12Col D9/10No closer on door10/25/183A.4-4Door in fire barrier does not properly self- or automatically close.BusinessNFPA 101: 8.3.3.3Install a self-closing device on the door.DOOR
K300
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-2Col K9/10no closer on door10/25/183A.4-6Door in fire barrier does not properly self- or automatically close.BusinessNFPA 101: 8.3.3.3Install a self-closing device on the door.DOOR
K300
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Kitchen - Room 1C-37AStorage RoomN/A10/25/183D.1-8Hazardous area door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.2.1.3Install a self-closing device on the door.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Kitchen - Room 1C-07AStorage RoomN/A10/25/183D.1-10Hazardous area door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.2.1.3Install a self-closing device on the door.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Floor Sweeper Room - Room 1C-34Door to roomN/A10/25/183D.1-12Hazardous area door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.2.1.3Install a self-closing device on the door.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)BasementService Bay 5N/Ano closer on door10/25/183A.4-3Door in fire barrier does not properly self- or automatically close.BusinessNFPA 101: 8.3.3.3Install a self-closing device on the door.DOOR
K300
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4Stair 5DoorPanic hardware on exit stair door10/25/183A.10-1Door within a means of egress not provided with proper fire exit hardware.Existing Health CareNFPA 101: Section 7.2.1.7.1Install approved fire exit hardware on the referenced door.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)22B-144N/APanic hardware10/25/183A.10-2Door within a means of egress not provided with proper fire exit hardware.BusinessNFPA 101: Section 7.2.1.7.1Install approved fire exit hardware on the referenced door.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)22B-141Corridor doorPanic hardware10/25/183A.10-3Door within a means of egress not provided with proper fire exit hardware.BusinessNFPA 101: Section 7.2.1.7.1Install approved fire exit hardware on the referenced door.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-4Col H16Pipe (possibly sprinkler) missing coupling on tee.10/25/185G.2-1Sprinkler system component not Listed or not installed per the Listing.BusinessNFPA 13: 6.1.1.2Install coupling per required manufacturer recommendations and listingDOOR
K351
LS.03.01.35
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Acute Psych CorridorN/A46 ft dead end leading up to Acute Psych10/25/184BB.2-1Dead-end corridor exceeds maximum permitted length.Existing Health CareNFPA 101 : 19.2.5.2Install double doors to reduce dead-end corridor to allowable limit.DOOR
K251
LS.02.01.20
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1VA Police CorridorDoors to ED - Doors FD-212-3N/A10/25/183A.5-2Fire doors have gaps/clearances exceeding the allowances per NFPA 80.Existing Health CareNFPA 80: 6.3.1.7.1Install Listed product to reduce clearance under the door to not exceed 3/4".DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4FD-225-1North Elev LobbyGap at door edge10/25/183A.5-1Fire doors have gaps/clearances exceeding the allowances per NFPA 80.Existing Health CareNFPA 80: 6.3.1.7.1Install Listed product to reduce the gap between meeting edges of doors.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)44.00E-51Cardiology/EKG Suite doorsSuite door locked open, inactive leaf with no latching hardware and latch blocked with paper/tissues10/25/183B.4-1Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3OR-Room 3F-42Trash RoomN/A10/25/183B.4-3Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3ORStorage RoomRoom adjacent OR 110/25/183B.4-4Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3ORStorage RoomDouble doors across from OR 510/25/183B.4-5Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3OR-Sterile CoreDoor into OR 1N/A10/25/183B.4-6Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3OR-Sterile CoreDoor into OR 3N/A10/25/183B.4-7Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3OR-Sterile CoreDoor into OR 4N/A10/25/183B.4-8Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3SICU-Door 3D-07N/ASuite boundary doors10/25/183B.4-11Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Locker Room - Room C3-39AN/ASliding glass door into Locker Room10/25/183B.4-13Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3SICU Procedure ORN/ANew double doors into SICU10/25/183B.4-14Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the door.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Ultrasound - Door C3-51Corridor doorsSuite boundary doors into Ultrasound10/25/183B.4-9Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Install positive latching hardware on the double doors.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3EDDouble doors adjacent Dirty Utility 1A-634N/A10/25/183B.4-15Door separating room or suite from corridor does not properly latch.Ambulatory Health CareNFPA 80: 6.4.4.3Install positive latching hardware on the double doors.DOOR
K363
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1VA Police CorridorDoors to ED - Doors FD-212-3N/A10/25/183A.3-3Door in fire barrier does not properly latch.Existing Health CareNFPA 80: 6.4.4.3Modify the present smoke seal to allow bottom Fire Bolt to operate properly if required.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Fire Pump RoomN/AN/A10/25/183A.1-19Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test result that door and frame are 60-minute rated - replace if necessary.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Stair 8 - Pipe Chase RoomStair 8 Required Exit PassagewayN/A10/25/183A.1-16Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test result that door and frame are 90-minute rated - replace if necessary.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Stair 8 - AHU #44 RoomStair 8 Required Exit PassagewayN/A10/25/183A.1-17Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test result that door and frame are 90-minute rated - replace if necessary.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Resident QuartersFire Doors C3-32Door into Residents Quarters - Frame label covered by continuous hinge10/25/183A.1-14Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door frame has a 90-minute rating- replace if necessary.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Stair 8 - Service Bay 8Stair 8 Required Exit PassagewayN/A10/25/183A.1-15Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door frame has a 90-minute rating- replace if necessary.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)44.00E-04Cath HoldingDoor not 90-min rated10/25/183A.1-5Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has 90-minute rating-replace door if necessary.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)44A-05AExec Conf RoomNo label on door in 2-hour barrier10/25/183A.1-6Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has 90-minute rating-replace door if necessary.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)22B-144N/A60 min rated10/25/183A.1-10Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Obtain test results showing door has 90-minute rating-replace door if necessary.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)22B-141Corridor door60 min rated10/25/183A.1-11Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Obtain test results showing door has 90-minute rating-replace door if necessary.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4Service Bay 2DoorNo label10/25/183A.1-1Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4Service Bay 4DoorNo label10/25/183A.1-2Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4Service Bay 5DoorNo label10/25/183A.1-3Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)4Service Bay 7DoorNo label10/25/183A.1-4Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Service Bay 1N/ANo Label10/25/183A.1-20Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Service Bay 8N/ANo Label10/25/183A.1-21Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Service Bay 8N/A20 min door, no closer10/25/183A.1-7Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Service Bay 3N/ANo label on door10/25/183A.1-12Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Service Bay 5N/ANo label on door10/25/183A.1-13Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Service Bay 2N/ANo label on door10/25/183A.1-23Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Service Bay 1N/Ano label on door10/25/183A.1-24Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Service Bay 7N/Ano label on door10/25/183A.1-25Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Obtain test results showing door has a 45-minute fire rating- replace if necessaryDOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Service Bay 7Glass door towards Service BayN/A10/25/184X.7-3Door that could be mistaken for an exit is not provided with proper signage.Existing Health CareNFPA 101: 7.10.8.3.1Post a sign reading "NO EXIT" on or adjacent to the door.DOOR
K363
LS.02.01.20
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)44B-09N/APower operated suite door not positive latching.10/25/183B.4-2Door separating room or suite from corridor does not properly latch.Existing Health CareNFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7Reactivate positive-latching hardware.DOOR
K363
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Kitchen - Room 1C-33FIngredient Control RoomN/A10/25/183D.1-9Hazardous area door does not properly self- or automatically close.Existing Health CareNFPA 101: 19.3.2.1.3Reconnect the self-closing device to the door.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-1Col K23Door scraps on concrete floor and does not close10/25/183A.4-7Door in fire barrier does not properly self- or automatically close.BusinessNFPA 101: 8.3.3.3Rehang door or modify concrete floor (maintain required floor rating).DOOR
K300
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Stair 5Door STR #5-1-2N/A10/25/183A.7-1The integrity of the fire door is compromised by holes/other damaged items.Existing Health CareNFPA 80: 5.2.15.4Re-install missing closer cover.DOOR
K321
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-7Col E17Gap around frame10/25/183C.3-7Smoke barrier door not fitted to limit the passage of smoke.BusinessNFPA 101: 18.3.7.2 & 18.3.7.6Re-install smoke barrier door and frame or properly seal gap around frameDOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-7Col D/E17Gap around frame filled with expanding foam10/25/183C.3-8Smoke barrier door not fitted to limit the passage of smoke.BusinessNFPA 101: 18.3.7.2 & 18.3.7.6Re-install smoke barrier door and frame or properly seal gap around frameDOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2 InterstitialSmoke Compartment 2-5Column Grid F-17door and frame removed.10/25/183C.3-6Smoke barrier door not fitted to limit the passage of smoke.BusinessNFPA 101: 18.3.7.2 & 18.3.7.6Re-install smoke barrier door and frame.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2 InterstitialSmoke Compartment 2-6Column Grid F-17Door removed.10/25/183C.3-5Smoke barrier door not fitted to limit the passage of smoke.BusinessNFPA 101: 18.3.7.2 & 18.3.7.6Re-install smoke barrier door.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-7Col F25Missing door10/25/183C.3-9Smoke barrier door not fitted to limit the passage of smoke.BusinessNFPA 101: 18.3.7.2 & 18.3.7.6Re-install smoke barrier door.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-2Col L/M17gap around door with expanding foam10/25/183A.1-29Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Remove expanding foam and properly seal gap or remove and reinstall door.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3OROffice door 3F-42Room no longer utilized as a storage room10/25/183B.8-1Corridor door not able to be closed with a pushing or pulling motion.Existing Health CareNFPA 101: 19.3.6.3.10*Remove the self-closing device from the door.DOOR
K363
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)44C-22BN/ADoor does not latch properly10/25/183A.3-1Door in fire barrier does not properly latch.Existing Health CareNFPA 80: 6.4.4.3Repair the latching hardware to allow the door to close and latch properly.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Residents QuartersFire Doors - FD-214-1N/A10/25/183A.3-2Door in fire barrier does not properly latch.Existing Health CareNFPA 80: 6.4.4.3Repair the latching hardware to allow the door to close and latch properly.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-1Col L/M17Door does not properly latch10/25/183A.3-5Door in fire barrier does not properly latch.BusinessNFPA 80: 6.4.4.3Repair the latching hardware to allow the door to close and latch properly.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-1Stair 1door does not properly latch10/25/183A.3-6Door in fire barrier does not properly latch.BusinessNFPA 80: 6.4.4.3Repair the latching hardware to allow the door to close and latch properly.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-4Col K17Handle on door is broken10/25/183C.1-1Improper construction of smoke barrier door.BusinessNFPA 101: 18.3.7.2 & 18.3.7.6Repair/replace door handle.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-1Col L18No door10/25/183A.1-26Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Replace doors and frame with a door and frame having a 90-minute fire rating.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-1Col K/L18No door10/25/183A.1-27Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Replace doors and frame with a door and frame having a 90-minute fire rating.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1 IntersticialSmoke Compartment 1-1Col K25No door10/25/183A.1-28Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Replace doors and frame with a door and frame having a 90-minute fire rating.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Stair 8 - Glass Doors to 1 SouthStair 8 Required Exit PassagewayN/A10/25/183A.1-18Door assembly in fire barrier does not have the minimum required rating.Existing Health CareNFPA 101: 8.3.4.2Replace doors and frame with a door and frame having a 90-minute fire rating.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Palliative Care - Door PC-1SEast Smoke DoorsN/A10/25/182D.1-2Smoke barrier fire window assembly not properly rated.Existing Health CareNFPA 101: 8.5.4.5, 8.3.3.5 - 8.3.3.9Replace glass & frame assembly in smoke barrier with one having a minimum 20-minute rating.DOOR
K379
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Palliative CareWest Smoke DoorsN/A10/25/182D.1-3Smoke barrier fire window assembly not properly rated.Existing Health CareNFPA 101: 8.5.4.5, 8.3.3.5 - 8.3.3.9Replace glass & frame assembly in smoke barrier with one having a minimum 20-minute rating.DOOR
K379
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3Radiology-Door 3E-28EN/AGlazing (glass) in door is painted and unable to determine rating.10/25/182D.1-1Smoke barrier fire window assembly not properly rated.Existing Health CareNFPA 101: 8.5.4.5, 8.3.3.5 - 8.3.3.9Replace glass in smoke barrier with material having a minimum 20-minute rating.DOOR
K379
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)3ClinicsSmoke Doors FD-214-3Doors are warped and do not seal properly along center edge10/25/183C.3-1Smoke barrier door not fitted to limit the passage of smoke.BusinessNFPA 101: 18.3.7.2 & 18.3.7.6Replace the door.DOOR
K374
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Elevator S3Doors towards Central SupplyCurrent situation creates a "dead-end" corridor for those occupants that do not have card reader access to the doors10/25/184M.1-1Door within the means of egress not unlocked from the direction of egress.Existing Health CareNFPA 101: 19.2.2.2.2Replace the existing lock with an approved delayed egress locking mechanism.DOOR
K222
LS.02.01.20
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Emergency DepartmentDoors between Lobby & ED - Doors FD-212-4N/A10/25/183A.3-4Door in fire barrier does not properly latch.Existing Health CareNFPA 80: 6.4.4.3Return the missing Fire Bolt on bottom of the door.DOOR
K374
LS.02.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Palliative Care - Room 1G-1142 doors into roomDoor frame is covered by a continuous hinge and door frame label not visible10/25/182K.1-1Hazardous area not properly enclosed.Existing Health CareNFPA 101: 19.3.2.1Verify fire rating of door frame.DOOR
K321
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)1Palliative Care - Room 1G-1122 doors into roomDoor frame is covered by a continuous hinge and door frame label not visible10/25/182K.1-2Hazardous area not properly enclosed.Existing Health CareNFPA 101: 19.3.2.1Verify fire rating of door frame.DOOR
K321
LS.02.01.30
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Service Bay 6N/ANo Label10/25/183A.1-8Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Door assembly in fire barrier does not have the minimum required rating.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)2Service Bay 4N/ANo label10/25/183A.1-9Door assembly in fire barrier does not have the minimum required rating.BusinessNFPA 101: 8.3.4.2Door assembly in fire barrier does not have the minimum required rating.DOOR
K374
LS.03.01.10
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)22F-25N/ANo closer or latch on both doors10/25/183D.1-1Hazardous area door does not properly self- or automatically close.BusinessNFPA 101: 8.7.1.2Hazardous area door does not properly self- or automatically close.DOOR
VA Loma Linda (Formerly: VA Medical Center-Loma Linda)22F-27BN/ANo closer10/25/183D.1-2Hazardous area door does not properly self- or automatically close.BusinessNFPA 101: 8.7.1.2Hazardous area door does not properly self- or automatically close.DOOR
GRAND TOTAL
Phase 2. Vendor will install all doors and/or hardware to ensure compliance. The vendor will provide all required oversight. Daily project logs will be completed and turned in at the end of each day for COR review. Weekly reports will also be submitted documenting project progress, line items completed, in progress, parts status, pending completion, upcoming schedules, and/or issues.
NFPA reports and checklists will be completed and submitted daily and weekly. Doors which are not listed as rated will be rated. Doors listed as rated which are no longer visible will be addressed and fixed to ensure labeling.

In the event that the vendor discovers a door which are listed as rated but not actually rated will be addressed on a case-by-case basis.

No changes will be made without COR consent.

The vendor will provide patch and paint and carpentry, if needed.
DR1Interior DoorsCS AcrovynFlush Door, Square EdgeDoor Slab and Door Edge Classic Maple #372
Lite Kit - Standard Metal (NR 90min) Painted (DE761 Cochise or SIM.)per Architectural Door SchedulePublic (Front of House) Interior DoorsContinuous Aluminum Privacy Hinge

Office doors do not have closers, unless required by fire code.

DR2Interior DoorsGraham, Assa AbloyFlush Door with Stainless Steel Door Kick#100 Clear
Plain Sliced White Mapleper Architectural Door ScheduleEmployee (Back of House) Interior DoorsFormaldehyde-Free Adhesives Continuous Aluminum Privacy Hinge

Office doors do not have closers, unless required by fire code.