36C26219B0001-0001003.xlsx
XLSX spreadsheet 43 KB Posted
- Attached to
- Fire Door Compliance Federal contract opportunity
- Solicitation number
- 36C26219B0001
About this file
36C26219B0001 0001 VA Loma Linda Fire Doors Deficiency List.xlsx
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26219C0088-000.docx | DOCX document | |
| 36C26219B0001-0002000.docx | DOCX document | |
| 36C26219B0001-0002001.pdf | ||
| 36C26219B0001-0002002.pdf | ||
| 36C26219B0001-0001001.pdf | ||
| 36C26219B0001-0001002.pdf | ||
| 36C26219B0001-0001000.docx | DOCX document | |
| 36C26219B0001-007.pdf | ||
| 36C26219B0001-008.pdf | ||
| 36C26219B0001-004.pdf | ||
| 36C26219B0001-001.pdf | ||
| 36C26219B0001-005.pdf | ||
| 36C26219B0001-002.doc | DOC document | |
| 36C26219B0001-006.pdf | ||
| 36C26219B0001-000.docx | DOCX document | |
| 36C26219B0001-003.pdf | ||
| 36C26219B0001_1.docx | DOCX document |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Loma 110518
| Account Name | Floor | Area/Room | Location | Additional Info | ID Date | Unique ID | Deficiency | Occupancy | References | Recommended Action (short) | TYPE |
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR | West entry doors, adjacent OR 1 | Adjust closer to overcome pressurization issue in area | 10/25/18 | 3C.4-1 | Smoke barrier door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.7.8(1) | Adjust self-closing device so that it holds door closed tight to door frame. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Ultrasound | Smoke Doors FD-234-4 | The center smoke seal prevents the doors from closing properly | 10/25/18 | 3C.4-2 | Smoke barrier door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.7.8(1) | Adjust self-closing device so that it holds door closed tight to door frame. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Stair 4 - Room 3A-01 | Bathroom adjacent Stair | N/A | 10/25/18 | 3B.4-10 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Adjust / repair hardware to provide for proper positive latching. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Equipment Room - Room 3D-17 | N/A | N/A | 10/25/18 | 3B.4-12 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Adjust / repair hardware to provide for proper positive latching. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | VA Police Administration | Corridor Smoke Doors | N/A | 10/25/18 | 3C.3-2 | Smoke barrier door not fitted to limit the passage of smoke. | Existing Health Care | NFPA 101: 8.5.4.1 | Adjust door frame to reduce the gap between meeting edges of the doors to <1/8”. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Chapel | Corridor Smoke Doors 1F-01 | N/A | 10/25/18 | 3C.3-3 | Smoke barrier door not fitted to limit the passage of smoke. | Existing Health Care | NFPA 101: 8.5.4.1 | Adjust door frame to reduce the gap between meeting edges of the doors to <1/8”. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-1 | Column Grid L-17 | N/A | 10/25/18 | 3C.4-7 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-1 | Column Grid L-17 | N/A | 10/25/18 | 3C.4-8 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-1 | Column Grid K-25 | N/A | 10/25/18 | 3C.4-9 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-3 | Column Grid G-25 | no latch hardware also. | 10/25/18 | 3C.4-10 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-5 | Column Grid F-25 | N/A | 10/25/18 | 3C.4-11 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-2 | Column Grid K-17 | N/A | 10/25/18 | 3C.4-12 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-4 | Column Grid K-17 | N/A | 10/25/18 | 3C.4-13 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-4 | Column Grid H-17 | N/A | 10/25/18 | 3C.4-14 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-6 | Column Grid F-17 | N/A | 10/25/18 | 3C.4-15 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-5 | Column Grid F-17 | N/A | 10/25/18 | 3C.4-16 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-8 | Column Grid E-17 | N/A | 10/25/18 | 3C.4-17 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-7 | Column Grid E-17 | N/A | 10/25/18 | 3C.4-18 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-8 | Column Grid F-9 | N/A | 10/25/18 | 3C.4-19 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 Interstitial | Smoke Compartment 4-5 | Column Grid H-25 | N/A | 10/25/18 | 3C.4-20 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 Interstitial | Smoke Compartment 3-2 | Column Grid N-17 | N/A | 10/25/18 | 3C.4-21 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 Interstitial | Smoke Compartment 3-6 | Column Grid F-17 | N/A | 10/25/18 | 3C.4-22 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 Interstitial | Smoke Compartment 3-8 | Column Grid F-9 | N/A | 10/25/18 | 3C.4-23 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 Interstitial | Smoke Compartment 3-5 | Column Grid H-25 | N/A | 10/25/18 | 3C.4-24 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 Interstitial | Smoke Compartment 3-5 | Column Grid G-25 | N/A | 10/25/18 | 3C.4-25 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 Interstitial | Smoke Compartment 3-7 | Column Grid E-25 | No door hardware also. | 10/25/18 | 3C.4-26 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 Interstitial | Smoke Compartment 2-4 | Column Grid K-17 | N/A | 10/25/18 | 3C.4-27 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | FD-233-2 | Smoke doors between zones 2-3 and 2-5 | Door doesn't close and latch properly | 10/25/18 | 3C.4-6 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-12 | Col A16 | Adjust door closer | 10/25/18 | 3C.4-28 | Smoke barrier door does not properly self- or automatically close. | Business | NFPA 101: 18.3.7.2 & 18.3.7.8 | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Loading Dock | Smoke Doors FD-262-1 | Blue door above ceiling to cat-walk. Door found in the open position | 10/25/18 | 3C.4-3 | Smoke barrier door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.7.8(1) | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Service Bay 4 | Smoke Doors FD-222-4 | The center smoke seal prevents the doors from closing properly | 10/25/18 | 3C.4-4 | Smoke barrier door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.7.8(1) | Adjust door so that it self-closes and latches properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Adjacent Stair 3 | Fire Doors FD-224-1 | N/A | 10/25/18 | 3A.4-1 | Door in fire barrier does not properly self- or automatically close. | Existing Health Care | NFPA 101: 8.3.3.3 | Adjust self-closing device so that it holds the access panel closed tight to door frame. | DOOR |
| K300 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-8 | Col F15/16 | Adjust door closer | 10/25/18 | 3A.4-5 | Door in fire barrier does not properly self- or automatically close. | Business | NFPA 101: 8.3.3.3 | Adjust self-closing device so that it holds the access panel closed tight to door frame. | DOOR |
| K300 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Palliative Care | Fire Doors FD-272-3 | N/A | 10/25/18 | 3A.4-2 | Door in fire barrier does not properly self- or automatically close. | Existing Health Care | NFPA 101: 8.3.3.3 | Adjust self-closing device so that it holds the access panel closed tight to door frame. | DOOR |
| K300 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Palliative Care - Room 1G-143 | Laundry Room | N/A | 10/25/18 | 3D.1-6 | Hazardous area door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.2.1.3 | Adjust self-closing device so that it holds the door closed tight to door frame. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Kitchen - Room 1C-07C | Trash Room | N/A | 10/25/18 | 3D.1-11 | Hazardous area door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.2.1.3 | Adjust self-closing device so that it holds the door closed tight to door frame. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR-Room 3F-33B | South side of OR's | N/A | 10/25/18 | 3D.1-4 | Hazardous area door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.2.1.3 | Disable the friction hold-open function of the closer. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Kitchen | Decon Room | N/A | 10/25/18 | 3C.4-5 | Smoke barrier door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.7.8(1) | Disable the friction hold-open function of the closer. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Emergency Department - Room 1A-632 | Storage Room | N/A | 10/25/18 | 3D.1-7 | Hazardous area door does not properly self- or automatically close. | Ambulatory Health Care | NFPA 101: 20/21.3.2.1 | Disable the friction hold-open function of the closer. | DOOR |
| K321 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Main Lobby | Sliding doors to Main Lobby | N/A | 10/25/18 | 4N.1-1 | More than one operation required to open a door. | Existing Health Care | NFPA 101: 7.2.1.5.10.2 | Disable the thumb turn latch on the inside of the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Pain Clinic - Room 3A-46 | Supply Room | N/A | 10/25/18 | 3D.1-5 | Hazardous area door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.2.1.3 | Install a self-closing device on the door. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | 2C-24A | Lab door | no closer | 10/25/18 | 3D.1-3 | Hazardous area door does not properly self- or automatically close. | Business | NFPA 101: 8.7.1.2 | Install a self-closing device on the door. | DOOR |
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-12 | Col D9/10 | No closer on door | 10/25/18 | 3A.4-4 | Door in fire barrier does not properly self- or automatically close. | Business | NFPA 101: 8.3.3.3 | Install a self-closing device on the door. | DOOR |
| K300 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-2 | Col K9/10 | no closer on door | 10/25/18 | 3A.4-6 | Door in fire barrier does not properly self- or automatically close. | Business | NFPA 101: 8.3.3.3 | Install a self-closing device on the door. | DOOR |
| K300 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Kitchen - Room 1C-37A | Storage Room | N/A | 10/25/18 | 3D.1-8 | Hazardous area door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.2.1.3 | Install a self-closing device on the door. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Kitchen - Room 1C-07A | Storage Room | N/A | 10/25/18 | 3D.1-10 | Hazardous area door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.2.1.3 | Install a self-closing device on the door. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Floor Sweeper Room - Room 1C-34 | Door to room | N/A | 10/25/18 | 3D.1-12 | Hazardous area door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.2.1.3 | Install a self-closing device on the door. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | Basement | Service Bay 5 | N/A | no closer on door | 10/25/18 | 3A.4-3 | Door in fire barrier does not properly self- or automatically close. | Business | NFPA 101: 8.3.3.3 | Install a self-closing device on the door. | DOOR |
| K300 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | Stair 5 | Door | Panic hardware on exit stair door | 10/25/18 | 3A.10-1 | Door within a means of egress not provided with proper fire exit hardware. | Existing Health Care | NFPA 101: Section 7.2.1.7.1 | Install approved fire exit hardware on the referenced door. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | 2B-144 | N/A | Panic hardware | 10/25/18 | 3A.10-2 | Door within a means of egress not provided with proper fire exit hardware. | Business | NFPA 101: Section 7.2.1.7.1 | Install approved fire exit hardware on the referenced door. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | 2B-141 | Corridor door | Panic hardware | 10/25/18 | 3A.10-3 | Door within a means of egress not provided with proper fire exit hardware. | Business | NFPA 101: Section 7.2.1.7.1 | Install approved fire exit hardware on the referenced door. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-4 | Col H16 | Pipe (possibly sprinkler) missing coupling on tee. | 10/25/18 | 5G.2-1 | Sprinkler system component not Listed or not installed per the Listing. | Business | NFPA 13: 6.1.1.2 | Install coupling per required manufacturer recommendations and listing | DOOR |
| K351 | |||||||||||
| LS.03.01.35 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Acute Psych Corridor | N/A | 46 ft dead end leading up to Acute Psych | 10/25/18 | 4BB.2-1 | Dead-end corridor exceeds maximum permitted length. | Existing Health Care | NFPA 101 : 19.2.5.2 | Install double doors to reduce dead-end corridor to allowable limit. | DOOR |
| K251 | |||||||||||
| LS.02.01.20 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | VA Police Corridor | Doors to ED - Doors FD-212-3 | N/A | 10/25/18 | 3A.5-2 | Fire doors have gaps/clearances exceeding the allowances per NFPA 80. | Existing Health Care | NFPA 80: 6.3.1.7.1 | Install Listed product to reduce clearance under the door to not exceed 3/4". | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | FD-225-1 | North Elev Lobby | Gap at door edge | 10/25/18 | 3A.5-1 | Fire doors have gaps/clearances exceeding the allowances per NFPA 80. | Existing Health Care | NFPA 80: 6.3.1.7.1 | Install Listed product to reduce the gap between meeting edges of doors. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | 4.00E-51 | Cardiology/EKG Suite doors | Suite door locked open, inactive leaf with no latching hardware and latch blocked with paper/tissues | 10/25/18 | 3B.4-1 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR-Room 3F-42 | Trash Room | N/A | 10/25/18 | 3B.4-3 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR | Storage Room | Room adjacent OR 1 | 10/25/18 | 3B.4-4 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR | Storage Room | Double doors across from OR 5 | 10/25/18 | 3B.4-5 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR-Sterile Core | Door into OR 1 | N/A | 10/25/18 | 3B.4-6 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR-Sterile Core | Door into OR 3 | N/A | 10/25/18 | 3B.4-7 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR-Sterile Core | Door into OR 4 | N/A | 10/25/18 | 3B.4-8 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | SICU-Door 3D-07 | N/A | Suite boundary doors | 10/25/18 | 3B.4-11 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Locker Room - Room C3-39A | N/A | Sliding glass door into Locker Room | 10/25/18 | 3B.4-13 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | SICU Procedure OR | N/A | New double doors into SICU | 10/25/18 | 3B.4-14 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Ultrasound - Door C3-51 | Corridor doors | Suite boundary doors into Ultrasound | 10/25/18 | 3B.4-9 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Install positive latching hardware on the double doors. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | ED | Double doors adjacent Dirty Utility 1A-634 | N/A | 10/25/18 | 3B.4-15 | Door separating room or suite from corridor does not properly latch. | Ambulatory Health Care | NFPA 80: 6.4.4.3 | Install positive latching hardware on the double doors. | DOOR |
| K363 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | VA Police Corridor | Doors to ED - Doors FD-212-3 | N/A | 10/25/18 | 3A.3-3 | Door in fire barrier does not properly latch. | Existing Health Care | NFPA 80: 6.4.4.3 | Modify the present smoke seal to allow bottom Fire Bolt to operate properly if required. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Fire Pump Room | N/A | N/A | 10/25/18 | 3A.1-19 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test result that door and frame are 60-minute rated - replace if necessary. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Stair 8 - Pipe Chase Room | Stair 8 Required Exit Passageway | N/A | 10/25/18 | 3A.1-16 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test result that door and frame are 90-minute rated - replace if necessary. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Stair 8 - AHU #44 Room | Stair 8 Required Exit Passageway | N/A | 10/25/18 | 3A.1-17 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test result that door and frame are 90-minute rated - replace if necessary. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Resident Quarters | Fire Doors C3-32 | Door into Residents Quarters - Frame label covered by continuous hinge | 10/25/18 | 3A.1-14 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door frame has a 90-minute rating- replace if necessary. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Stair 8 - Service Bay 8 | Stair 8 Required Exit Passageway | N/A | 10/25/18 | 3A.1-15 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door frame has a 90-minute rating- replace if necessary. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | 4.00E-04 | Cath Holding | Door not 90-min rated | 10/25/18 | 3A.1-5 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has 90-minute rating-replace door if necessary. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | 4A-05A | Exec Conf Room | No label on door in 2-hour barrier | 10/25/18 | 3A.1-6 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has 90-minute rating-replace door if necessary. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | 2B-144 | N/A | 60 min rated | 10/25/18 | 3A.1-10 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Obtain test results showing door has 90-minute rating-replace door if necessary. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | 2B-141 | Corridor door | 60 min rated | 10/25/18 | 3A.1-11 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Obtain test results showing door has 90-minute rating-replace door if necessary. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | Service Bay 2 | Door | No label | 10/25/18 | 3A.1-1 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | Service Bay 4 | Door | No label | 10/25/18 | 3A.1-2 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | Service Bay 5 | Door | No label | 10/25/18 | 3A.1-3 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | Service Bay 7 | Door | No label | 10/25/18 | 3A.1-4 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Service Bay 1 | N/A | No Label | 10/25/18 | 3A.1-20 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Service Bay 8 | N/A | No Label | 10/25/18 | 3A.1-21 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Service Bay 8 | N/A | 20 min door, no closer | 10/25/18 | 3A.1-7 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Service Bay 3 | N/A | No label on door | 10/25/18 | 3A.1-12 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Service Bay 5 | N/A | No label on door | 10/25/18 | 3A.1-13 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Service Bay 2 | N/A | No label on door | 10/25/18 | 3A.1-23 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Service Bay 1 | N/A | no label on door | 10/25/18 | 3A.1-24 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Service Bay 7 | N/A | no label on door | 10/25/18 | 3A.1-25 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Obtain test results showing door has a 45-minute fire rating- replace if necessary | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Service Bay 7 | Glass door towards Service Bay | N/A | 10/25/18 | 4X.7-3 | Door that could be mistaken for an exit is not provided with proper signage. | Existing Health Care | NFPA 101: 7.10.8.3.1 | Post a sign reading "NO EXIT" on or adjacent to the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.20 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | 4B-09 | N/A | Power operated suite door not positive latching. | 10/25/18 | 3B.4-2 | Door separating room or suite from corridor does not properly latch. | Existing Health Care | NFPA 101: 19.3.6.3.5, 19.3.6.3.6(1), 19.3.6.3.7 | Reactivate positive-latching hardware. | DOOR |
| K363 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Kitchen - Room 1C-33F | Ingredient Control Room | N/A | 10/25/18 | 3D.1-9 | Hazardous area door does not properly self- or automatically close. | Existing Health Care | NFPA 101: 19.3.2.1.3 | Reconnect the self-closing device to the door. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-1 | Col K23 | Door scraps on concrete floor and does not close | 10/25/18 | 3A.4-7 | Door in fire barrier does not properly self- or automatically close. | Business | NFPA 101: 8.3.3.3 | Rehang door or modify concrete floor (maintain required floor rating). | DOOR |
| K300 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Stair 5 | Door STR #5-1-2 | N/A | 10/25/18 | 3A.7-1 | The integrity of the fire door is compromised by holes/other damaged items. | Existing Health Care | NFPA 80: 5.2.15.4 | Re-install missing closer cover. | DOOR |
| K321 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-7 | Col E17 | Gap around frame | 10/25/18 | 3C.3-7 | Smoke barrier door not fitted to limit the passage of smoke. | Business | NFPA 101: 18.3.7.2 & 18.3.7.6 | Re-install smoke barrier door and frame or properly seal gap around frame | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-7 | Col D/E17 | Gap around frame filled with expanding foam | 10/25/18 | 3C.3-8 | Smoke barrier door not fitted to limit the passage of smoke. | Business | NFPA 101: 18.3.7.2 & 18.3.7.6 | Re-install smoke barrier door and frame or properly seal gap around frame | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 Interstitial | Smoke Compartment 2-5 | Column Grid F-17 | door and frame removed. | 10/25/18 | 3C.3-6 | Smoke barrier door not fitted to limit the passage of smoke. | Business | NFPA 101: 18.3.7.2 & 18.3.7.6 | Re-install smoke barrier door and frame. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 Interstitial | Smoke Compartment 2-6 | Column Grid F-17 | Door removed. | 10/25/18 | 3C.3-5 | Smoke barrier door not fitted to limit the passage of smoke. | Business | NFPA 101: 18.3.7.2 & 18.3.7.6 | Re-install smoke barrier door. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-7 | Col F25 | Missing door | 10/25/18 | 3C.3-9 | Smoke barrier door not fitted to limit the passage of smoke. | Business | NFPA 101: 18.3.7.2 & 18.3.7.6 | Re-install smoke barrier door. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-2 | Col L/M17 | gap around door with expanding foam | 10/25/18 | 3A.1-29 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Remove expanding foam and properly seal gap or remove and reinstall door. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | OR | Office door 3F-42 | Room no longer utilized as a storage room | 10/25/18 | 3B.8-1 | Corridor door not able to be closed with a pushing or pulling motion. | Existing Health Care | NFPA 101: 19.3.6.3.10* | Remove the self-closing device from the door. | DOOR |
| K363 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 4 | 4C-22B | N/A | Door does not latch properly | 10/25/18 | 3A.3-1 | Door in fire barrier does not properly latch. | Existing Health Care | NFPA 80: 6.4.4.3 | Repair the latching hardware to allow the door to close and latch properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Residents Quarters | Fire Doors - FD-214-1 | N/A | 10/25/18 | 3A.3-2 | Door in fire barrier does not properly latch. | Existing Health Care | NFPA 80: 6.4.4.3 | Repair the latching hardware to allow the door to close and latch properly. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-1 | Col L/M17 | Door does not properly latch | 10/25/18 | 3A.3-5 | Door in fire barrier does not properly latch. | Business | NFPA 80: 6.4.4.3 | Repair the latching hardware to allow the door to close and latch properly. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-1 | Stair 1 | door does not properly latch | 10/25/18 | 3A.3-6 | Door in fire barrier does not properly latch. | Business | NFPA 80: 6.4.4.3 | Repair the latching hardware to allow the door to close and latch properly. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-4 | Col K17 | Handle on door is broken | 10/25/18 | 3C.1-1 | Improper construction of smoke barrier door. | Business | NFPA 101: 18.3.7.2 & 18.3.7.6 | Repair/replace door handle. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-1 | Col L18 | No door | 10/25/18 | 3A.1-26 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Replace doors and frame with a door and frame having a 90-minute fire rating. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-1 | Col K/L18 | No door | 10/25/18 | 3A.1-27 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Replace doors and frame with a door and frame having a 90-minute fire rating. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 Intersticial | Smoke Compartment 1-1 | Col K25 | No door | 10/25/18 | 3A.1-28 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Replace doors and frame with a door and frame having a 90-minute fire rating. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Stair 8 - Glass Doors to 1 South | Stair 8 Required Exit Passageway | N/A | 10/25/18 | 3A.1-18 | Door assembly in fire barrier does not have the minimum required rating. | Existing Health Care | NFPA 101: 8.3.4.2 | Replace doors and frame with a door and frame having a 90-minute fire rating. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Palliative Care - Door PC-1S | East Smoke Doors | N/A | 10/25/18 | 2D.1-2 | Smoke barrier fire window assembly not properly rated. | Existing Health Care | NFPA 101: 8.5.4.5, 8.3.3.5 - 8.3.3.9 | Replace glass & frame assembly in smoke barrier with one having a minimum 20-minute rating. | DOOR |
| K379 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Palliative Care | West Smoke Doors | N/A | 10/25/18 | 2D.1-3 | Smoke barrier fire window assembly not properly rated. | Existing Health Care | NFPA 101: 8.5.4.5, 8.3.3.5 - 8.3.3.9 | Replace glass & frame assembly in smoke barrier with one having a minimum 20-minute rating. | DOOR |
| K379 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Radiology-Door 3E-28E | N/A | Glazing (glass) in door is painted and unable to determine rating. | 10/25/18 | 2D.1-1 | Smoke barrier fire window assembly not properly rated. | Existing Health Care | NFPA 101: 8.5.4.5, 8.3.3.5 - 8.3.3.9 | Replace glass in smoke barrier with material having a minimum 20-minute rating. | DOOR |
| K379 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 3 | Clinics | Smoke Doors FD-214-3 | Doors are warped and do not seal properly along center edge | 10/25/18 | 3C.3-1 | Smoke barrier door not fitted to limit the passage of smoke. | Business | NFPA 101: 18.3.7.2 & 18.3.7.6 | Replace the door. | DOOR |
| K374 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Elevator S3 | Doors towards Central Supply | Current situation creates a "dead-end" corridor for those occupants that do not have card reader access to the doors | 10/25/18 | 4M.1-1 | Door within the means of egress not unlocked from the direction of egress. | Existing Health Care | NFPA 101: 19.2.2.2.2 | Replace the existing lock with an approved delayed egress locking mechanism. | DOOR |
| K222 | |||||||||||
| LS.02.01.20 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Emergency Department | Doors between Lobby & ED - Doors FD-212-4 | N/A | 10/25/18 | 3A.3-4 | Door in fire barrier does not properly latch. | Existing Health Care | NFPA 80: 6.4.4.3 | Return the missing Fire Bolt on bottom of the door. | DOOR |
| K374 | |||||||||||
| LS.02.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Palliative Care - Room 1G-114 | 2 doors into room | Door frame is covered by a continuous hinge and door frame label not visible | 10/25/18 | 2K.1-1 | Hazardous area not properly enclosed. | Existing Health Care | NFPA 101: 19.3.2.1 | Verify fire rating of door frame. | DOOR |
| K321 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 1 | Palliative Care - Room 1G-112 | 2 doors into room | Door frame is covered by a continuous hinge and door frame label not visible | 10/25/18 | 2K.1-2 | Hazardous area not properly enclosed. | Existing Health Care | NFPA 101: 19.3.2.1 | Verify fire rating of door frame. | DOOR |
| K321 | |||||||||||
| LS.02.01.30 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Service Bay 6 | N/A | No Label | 10/25/18 | 3A.1-8 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Door assembly in fire barrier does not have the minimum required rating. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | Service Bay 4 | N/A | No label | 10/25/18 | 3A.1-9 | Door assembly in fire barrier does not have the minimum required rating. | Business | NFPA 101: 8.3.4.2 | Door assembly in fire barrier does not have the minimum required rating. | DOOR |
| K374 | |||||||||||
| LS.03.01.10 | |||||||||||
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | 2F-25 | N/A | No closer or latch on both doors | 10/25/18 | 3D.1-1 | Hazardous area door does not properly self- or automatically close. | Business | NFPA 101: 8.7.1.2 | Hazardous area door does not properly self- or automatically close. | DOOR |
| VA Loma Linda (Formerly: VA Medical Center-Loma Linda) | 2 | 2F-27B | N/A | No closer | 10/25/18 | 3D.1-2 | Hazardous area door does not properly self- or automatically close. | Business | NFPA 101: 8.7.1.2 | Hazardous area door does not properly self- or automatically close. | DOOR |
| GRAND TOTAL | |
| Phase 2. Vendor will install all doors and/or hardware to ensure compliance. The vendor will provide all required oversight. Daily project logs will be completed and turned in at the end of each day for COR review. Weekly reports will also be submitted documenting project progress, line items completed, in progress, parts status, pending completion, upcoming schedules, and/or issues. | |
| NFPA reports and checklists will be completed and submitted daily and weekly. Doors which are not listed as rated will be rated. Doors listed as rated which are no longer visible will be addressed and fixed to ensure labeling. |
In the event that the vendor discovers a door which are listed as rated but not actually rated will be addressed on a case-by-case basis.
No changes will be made without COR consent.
| The vendor will provide patch and paint and carpentry, if needed. | |||||
| DR1 | Interior Doors | CS Acrovyn | Flush Door, Square Edge | Door Slab and Door Edge Classic Maple #372 | |
| Lite Kit - Standard Metal (NR 90min) Painted (DE761 Cochise or SIM.) | per Architectural Door Schedule | Public (Front of House) Interior Doors | Continuous Aluminum Privacy Hinge |
Office doors do not have closers, unless required by fire code.
| DR2 | Interior Doors | Graham, Assa Abloy | Flush Door with Stainless Steel Door Kick | #100 Clear | |
| Plain Sliced White Maple | per Architectural Door Schedule | Employee (Back of House) Interior Doors | Formaldehyde-Free Adhesives Continuous Aluminum Privacy Hinge |
Office doors do not have closers, unless required by fire code.
File details come from the government source that posted it.