36C26219B0001-0001002.pdf
PDF 160 KB Posted
- Attached to
- Fire Door Compliance Federal contract opportunity
- Solicitation number
- 36C26219B0001
About this file
36C26219B0001 0001 S05 RFI # 1- 6.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26219C0088-000.docx | DOCX document | |
| 36C26219B0001-0002001.pdf | ||
| 36C26219B0001-0002002.pdf | ||
| 36C26219B0001-0002000.docx | DOCX document | |
| 36C26219B0001-0001003.xlsx | XLSX spreadsheet | |
| 36C26219B0001-0001001.pdf | ||
| 36C26219B0001-0001000.docx | DOCX document | |
| 36C26219B0001-007.pdf | ||
| 36C26219B0001-002.doc | DOC document | |
| 36C26219B0001-006.pdf | ||
| 36C26219B0001-008.pdf | ||
| 36C26219B0001-004.pdf | ||
| 36C26219B0001-001.pdf | ||
| 36C26219B0001-005.pdf | ||
| 36C26219B0001-000.docx | DOCX document | |
| 36C26219B0001-003.pdf | ||
| 36C26219B0001_1.docx | DOCX document |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(D Square Construction) 530 E. 27th St, Tucson, AZ 85713
(520) 748-9371 Fax (888) 543-8500
R.F.I.
(REQUEST FOR INFORMATION)
Project #: None RFI #:
Project Name: Fire Door Compliance Date Requested:
Solicitation No.: 36C26219B0001 Reference:
Drawing: Specification Section:
DESCRIPTION OF PROBLEM OR INFORMATION REQUESTED
Please be a specific as possible.
OWNER RESPONSE
OWNER TRACKING No.: AMEND No.:
VA Project Engineer/Manager: Date:
03/08/19
Attachment 1
N/A N/A
Many of the doors noted on the Attachment 1 Correction List have a “Recommended Action” stating “Obtain test result that door and frame are XX-minute rated – replace if necessary”.
Does the VA have a testing agency, or the qualifications required for the testing agency that would be approved to perform this testing?
Project #: None RFI #:
Project Name: Fire Door Compliance Date Requested:
Solicitation No.: 36C26219B0001 Reference:
Drawing: Specification Section:
DESCRIPTION OF PROBLEM OR INFORMATION REQUESTED
Attachment 1
N/A N/A
Many of the doors noted on the Attachment 1 Correction List have a “Recommended Action” stating “Obtain test result that door and frame are XX-minute rated – replace if necessary”.
How are the Contractors to bid this action? It will not be known if the door needs replacing until the testing is performed. Should the Contractor include the full cost of replacing every door / frame / hardware set for all of the doors that require this action or will doors requiring replacement be considered a differing condition that will be handled with a contract modification?
Project #: None RFI #:
Project Name: Fire Door Compliance Date Requested:
Solicitation No.: 36C26219B0001 Reference:
Drawing: Specification Section:
DESCRIPTION OF PROBLEM OR INFORMATION REQUESTED
Painting of Doors
N/A N/A
Will all of the doors require new paint? If only some will require repainting, how will this be determined prior to the bid?
Project #: None RFI #:
Project Name: Fire Door Compliance Date Requested:
Solicitation No.: 36C26219B0001 Reference:
Drawing: Specification Section:
DESCRIPTION OF PROBLEM OR INFORMATION REQUESTED
Lead-based Paint
N/A N/A
Will lead-based paint be expected to be encountered during the course of work for this project?
Project #: None RFI #:
Project Name: Fire Door Compliance Date Requested:
Solicitation No.: 36C26219B0001 Reference:
Drawing: Specification Section:
DESCRIPTION OF PROBLEM OR INFORMATION REQUESTED
Door Deficiencies List
N/A N/A
The Attachment 1 Door Deficiencies List appears to have been converted from an Excel file into a PDF file and there are numerous blank pages at the end and also several of the cells have been cut off and cannot be read. Will the VA provide a clear copy of this list that is not cut off or missing information?
| RFI 001 |
| RFI 002 |
| RFI 003 |
| RFI 004 |
| RFI 005 |
| RFI 006 |