Amendment 0002 - Attachment 2.pdf
PDF 2 MB Posted
- Attached to
- H241--AIR TEST/BALANCE (TAB) SERVICE
- Solicitation number
- 36C26126Q0321
About this file
This document is a Certified Test, Adjust and Balance (TAB) Report prepared by Systems Service Mechanical, Inc. for the Community Living Center Phase I project located at 2615 East Clinton Ave, Fresno, CA 93793, dated July 18, 2018. The report certifies that air distribution and hydronic distribution systems have been tested, adjusted, and balanced in accordance with NEBB (National Environmental Balancing Bureau) Procedural Standards and project specifications. The TAB work was performed by NEBB Certified Professional Steve Santos (Registration No. 2938, expiration date 3/31/2019) and submitted by Systems Service Mechanical, Inc., located at 39215 Skyline Dr, Oakhurst, CA 93644. The architect is Polytech Associates, Inc., and the engineer is Mazzetti & Associates. The HVAC contractor was New England Sheet Metal.
The report documents comprehensive testing of systems including AHU-1 (Huntair 20-ton unit), two exhaust/return fans (EF-2 and RF-1), 27 VAV boxes serving various zones, multiple pumps for primary and secondary heating circuits, and associated balance valves and control systems. Final measured flows achieved approximately 98-101% of design specifications across most zones, with VAV cooling design flows ranging from 45 CFM to 1,025 CFM per zone. Primary heating pumps (PHWP-1 and PHWP-2) delivered 56 GPM at 9.25 feet of head; secondary heating pumps (SHWP-1 and SHWP-2) delivered 54 GPM at 30 feet of head operating at 36 Hz. The report includes detailed instrument calibration records with calibration dates through 2019, shop drawings, performance curves, and general notes addressing VAV calibration procedures, ductwork balancing, and seasonal limitations affecting heating system testing.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0002 - Attachment 3.pdf | ||
| Amendment 0002 - Attachment 1.pdf | ||
| 36C26126Q0321 0002.docx | DOCX document | |
| Questions and Answers Document .docx | DOCX document | |
| 36C26126Q0321 0001.docx | DOCX document | |
| ATTACHMENT 2 - Room Schedule Air Test Adjust and Balance.pdf | ||
| 36C26126Q0321.docx | DOCX document | |
| ATTACHMENT 1 - Quality Assurance Surveillance Plan.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CERTIFIED TEST, ADJUST AND
BALANCE REPORT
DATE 7/18/2018
PROJECT Community Living Center Phase I ADDRESS 2615 East Clinton Ave
Fresno, CA. 93793
ARCHITECT Polytech Associates, Inc ADDRESS 235 Pne Street, 17th Floor
San Francisco, CA 94104
PHONE 415 397 3117 FAX 415 397 1517
ENGINEER Mazzetti & Associates ADDRESS 220 Montgomeery Street, Suite 650
San Francisco, CA 94104
PHONE 415 632 3266 FAX
HVAC
CONTRACTOR New England Sheet Metal
ADDRESS 2731 South Cherry Ave.
Fresno, CA 93706
PHONE 559 268 7375 FAX
NEBB TAB FIRM Systems Service Mechanical, Inc.
ADDRESS 39215 Skyline Dr.
Oakhurst, CA. 93644 (559) 779-2634
TAB CERT. NO. 2938
E-MAIL steve@ssmechtab.com mailto:steve.ssmech@sti.net
TABLE of CONTENT
COVER PAGE 1
TOC 2
CERTIFCATION 3
GENERAL NOTES 4
SHOP DRAWING 5-6
AIR APPARATUS REPORT 7
FAN TEST REPORT 8
VAV INOUT REPORT 9-11
INOUT REPORT 12
PUMP TEST & BALANCE REPORT 13-18
INSTRUMENT CERTIFICATION 19-21
ABBREVIATION PAGE 22
Systems Service Mechanical CERTIFICATION PROJECT Community Living Center Phase I ADDRESS 2615 East Clinton Ave
Fresno, CA. 93793
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENT AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST-ADJUST-BALANCE
REPORT PROJECT SUMMARY.
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS
HAVE BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING,
ADJUSTING BALANCING OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
NEBB TAB FIRM
REG. NO. 2938 CERTIFIED BY Steve Santos DATE 7/18/2018
(Air Tab Supervisor)
THE HYDRONIC DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING
BALANCING OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
NEBB TAB FIRM
REG. NO. 2938 CERTIFIED BY Steve Santos DATE 7/18/2018
(Hydronic Tab Supervisor)
SUBMITTED & CERTIFIED BY:
NEBB TAB FIRM Systems Service Mechanical, Inc.
TAB SUPERVISOR Steve Santos
REG. NO. 2938 SIGNATURE DATE 7/18/2018
EXP. DATE 3/31/2019
FORM 2 /12.98 PAGE 3
SYSTEMS SERVICE MECHANICAL, INC.
HVAC Test, Adjust and Balancing
39215 Skyline Drive., Oakhurst, CA. 93644 CCL# 669679 Ph (559) 779-2634 Fax (559) 683-6426
NEBB Certified Professional # 2938 steve.ssmech@sti.net
GENERAL NOTES
All VAV boxes were calibrated via EMS program for their maximum / minimum setpoints, distribution after the box was proportionally balanced. Once all boxes calibrated they were forced to cooling max and AH fan speed adjusted to satisfy all zones cooling setpoint, with only two or three boxes damper at 100% open. Duct static pressure set to control VFD.
Outside air damper opened to allow Phase I minimum OSA and ductwork above unit was measured via pitot tube traverse. Return fan tracking speed set when supply fan at operating speed. Return duct distribution proportionally balanced. Supply air and return air totals derived from flowhood tabulation, OSA will not typically equal exactly the difference between SA & RA & OSA reading
EF 2 serving general exhaust was ran and ductwork balanced to the required flows.
Heating pumps serving boilers were reduced down to the design flows from the triple duty valve at inlet to boiler. VFD operating speed remained at 60hz.
Secondary heating pumps were tested per NEBB procedures at full speed and throttling valve was used to verify pumps requirement. Throttling reopen and VFD ran to deliver the required flows to phase I requirement, 36hz
Reheat coils balancing valves were proportionally balanced. Due to seasonal condition boiler was not ran and no heating water and heating air temperatures available.
::::::::::::::::: :: .. ·.·.·.·.··o·····.·.
r•••· ::::/::/:::. :�W}:/
LOOBY
FIREPLACE
FLUE
8"x8"
�V>ti/BOILER "iC..,,lJ ROOM
@fil Bl r:::=:J
----. 12·x12•
---30"x30"
ELECTRICAL
ROON
[illjJ i
D]
CHILLERYARO i I 1 ·' I ' I J I . I• · ·• I I :�i I I .�R I I I I I I I I L __________ _i
Al
S9
S10
S1
S2
S3
S4
S5
S6
S7
S8
S11
S12
S13
S14 S15
S16
S17
S18
S19S20
S21
S23
NA
S24
S25 S26
S27 S28
S29
S30
S31
S33
S32
R34
R35
R36
R37
R39
R40
R41
R42
R43
R44
R45
R46
R47
R48
R49 E50
E51
E52
R43
E54
E55
E56
E57
E58
E59
E60
Systems Service Mechanical, Inc. AIR APPARATUS
REPORT
PROJECT VA Community Living Center SYSTEM / UNIT AHU 1
LOCATION Fresno, CA
UNIT DATA MOTOR DATA
Make / Model No. Huntair / 30461 001 Make / Frame Toshiba / 184t
Type / Size CW/HW / 20 tons H.P. / RPM 4) 6.5 / 1740
Serial Number NA Volts / Phase / Hertz 460 / 3 / 60
Arr. / Class 4) BI SWSI / I F.L. Amps / S.F. 8.9 / 1.15
Discharge Plenum Make Sheave Direct Drive
Make Sheave Direct Drive Sheave Diam. / Bore Direct Drive
Sheave Diam. / Bore Direct Drive Sheave Center Distance Direct Drive
No. Belts / Make / Size Direct Drive
No. Filters / Type / Size 12 / MERV8 / 24x24x2
12 / MERV14 / 24x24x12
FAN DESIGN DESIGN ACTUAL
Total CFM 8000 8046 External Discharge S.P. NA 1.67
Total S.P. NA 2.49 External Suction S.P. NA 0.63
Fan RPM 1740 1145 Fan Discharge S.P. NA 1.67
External S.P. NA 2.3 Fan Suction S.P. NA 0.82
Motor Volts 460 467/467/468 Reheat Coil Delta S.P. NA NA
Motor Amps 8.9 6.9 / 6.9 / 6.8 Cooling Coil & PHC Delta S.P. NA 0.59
Outside Air CFM ( Min ) 2535 2610 Filters Delta S.P. NA 0.13
Return Air CFM 7460 7212 VFD Hertz 60 39.5
Outside Air Damper Position NA 35% open
Ambient Temp. 105 79 / 60
Entering Air DB / WB 80 / 64 74 / 61
Leaving Air DB / WB NA 55 / 53
EWT / LWT (F) 45 / 55 43 / 58
REMARKS:
TEST DATE 7/18/2018 READINGS BY Steve Santos
FORM 5 / 12.98 PAGE 7
TEST DATA TEST DATAOUTLET
TOTAL
Systems Service Mechanical, Inc. FAN TEST
PROJECT VA Community Living Center Phase 1, Fresno, CA
FAN DATA FAN NO. EF - 2 FAN NO. RF - 1 FAN NO.
Location
Service
Manufacturer
Model Number
Serial Number
Type / Class
Motor Make / Style
Motor HP/RPM/Frame
Volts/Phase/Hertz
F.L. Amps/S.F.
Motor Sheave Make
Motor Sheave Diam./Bore
Fan Sheave Make
Fan Sheave Diam./Bore
No. Belts/Make/Size
Sheave Center Distance
TEST DATA FAN DESIGN INLET TOTAL FAN DESIGN INLET TOTAL FAN DESIGN INLET TOTAL
CFM 880 873 7330 7212
Fan RPM 2100 2070 1750 704
S.P. In/Out NA .67 / .0 NA .6 / .03
Total S.P. 1 0.67 NA 0.63
Voltage 460 469/470/469 460 471/471/470
Amperage 1.1 1.0 / 1.1 / 1.0 4) 4.0 5.9
VFD Speed NA NA 60 24
REMARKS
TEST DATE 7/3/2018 READINGS BY Steve Santos
FORM 6 / 12.98 PAGE 8
Mechanical Room
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Direct Drive
460 / 3 / 60
AH 1
Huntair
30476 001
NA
4) BI SWSI / I
Toshiba / ODP
5.0 / 1760 / 182T
1VP36 / 5/8"
Power Drive
AK30 / 3/4"
1 / Carlisle / 4L210
4) 4.0 / 1.15
6.5"
Power Drive
Roof
General Exhaust
Marathon / ODP
3/4 / 1750 / 56
460 / 3 / 60
1.1 / 1.15
Greenheck
CUBE 101 HP 5X
15445494
BI SWSI / I
Systems Service Mechanical VAV IN OUT
PROJECT VA Community Living Center Phase 1, Fresno, CA
AREA NO. KIND SIZE AK COOLING
DESIGN PRELIM COOLING
FINAL
PERCENT
OF DESIGN
Htg. MAX.
DESIGN
Htg. MAX
FINAL
AHU 1
SAV 1-12
Lobby S1 CD 8 x 8 1.00 255 121 241 95 140 Lobby S2 CD 8 x 8 1.00 260 191 270 104 146 Lobby S3 SWG 12 x 10 1.00 255 407 265 104 148 Lobby S4 SWG 12 x 10 1.00 255 429 251 98 141
Total 1025 1148 1027 100 562 575
SAV 1-13
Stair Well S5 CD 18 x 8 1.00 450 440 460 102 460 Storage 1E20 S6 SWG 6 x 6 1.00 45 200 80 178 80 Utility 1E15 S7 CD 8" Dia. 1.00 175 50 179 102 179
Total 670 690 719 107 670 719
SAV 1-14
Electrical Rm 1E21 S8 SWG 22 x 22 1.00 740 680 739 100 739
Total 740 680 739 100 740
SAV 1-15
Resident Bed 1D01 S9 CD 10" Dia. 1.00 290 289 100 141
Total 290 0 289 100 145 141
SAV 1-16
Resident Bed 1D02 S10 CD 10" Dia. 1.00 290 278 292 101 142
Total 290 278 292 101 145 142
SAV 1-17
Kitchen 1D03A S11 SWG 16 x 8 1.00 390 59 382 98 206 Kitchen 1D03A S12 SWG 18 x 10 1.00 520 810 534 103 255
Total 910 869 916 101 455 461
REMARKS
TEST DATE READINGS BY Steve Santos
FORM 2 / 12.98 PAGE 9
7/3/2018
PROJECT VA Community Living Center Phase 1, Fresno, CA
AREA NO. KIND SIZE AK COOLING
DESIGN PRELIM COOLING
FINAL
PERCENT
OF DESIGN
Htg. MAX.
DESIGN
Htg. MAX
FINAL
AHU 1
SAV 1-18
Resident Bed 1D04 S13 CD 10" Dia. 1.00 290 288 99 146
Total 290 0 288 99 145 146
SAV 1-19
Resident Bed 1D05 S14 CD 10" Dia. 1.00 290 279 96 144
Total 290 0 279 96 145 144
SAV 1-20
Corridor 1D-1 S15 CD 10" Dia. 1.00 310 279 308 99 132 Storage 1D13 S16 CD 6" Dia. 1.00 25 85 26 104 0 Nurse Station 1D14 S17 CD 6" Dia. 1.00 75 101 74 99 36 Corridor 1D-1 S18 CD 10" Dia. 1.00 310 248 302 97 136
Total 720 713 710 99 310 328
SAV 1-21
Medication 1D10 S19 CD 8" Dia. 1.00 150 114 152 101 69 Clean Linen 1D11A S20 CD 6" Dia. 1.00 75 59 78 104 37 Corridor 1D01 S21 CD 6" Dia. 1.00 25 85 27 108 0
Total 250 258 257 103 100 106
SAV 1-22
Nurses Break 1D15 S22 CD 10" Dia. 1.00 315 305 309 98 162
Total 315 305 309 98 160 162
FORM 2 / 12.98 PAGE 10
PROJECT VA Community Living Center Phase 1, Fresno, CA
AREA NO. KIND SIZE AK COOLING
DESIGN PRELIM COOLING
FINAL
PERCENT
OF DESIGN
Htg. MAX.
DESIGN
Htg. MAX
FINAL
AHU 1
SAV 1-23
Living Room 1D16 S24 Lin 8" Dia. 1.00 125 111 130 104 74 Living Room 1D16 S25 Lin 8" Dia. 1.00 125 105 122 98 70 Living Room 1D16 S26 Lin 8" Dia. 1.00 125 99 125 100 76 Living Room 1D16 S27 Lin 8" Dia. 1.00 125 88 120 96 71 Living Room 1D16 S28 SWG 16 x 8 1.00 250 454 260 104 140 Living Room 1D16 S29 SWG 16 x 8 1.00 250 395 252 101 135
Total 1000 1252 1009 101 555 566
SAV 1-24
Resident Bed 1D17 S30 CD 10" Dia. 1.00 290 287 99 150
Total 290 0 287 99 145 150
SAV 1-25
Resident Bed 1D18 S31 CD 10" Dia. 1.00 290 290 100 144
Total 290 0 290 100 145 144
SAV 1-26
Data Rm 1E17 S32 CD 12" Dia. 1.00 500 477 505 101 256
Total 500 477 505 101 250 256
SAV 1-27
Laundry Rm 1E18 S33 CD 8" Dia. 1.00 130 143 130 100 66
Total 130 143 130 100 65 66
FORM 2 / 12.98 PAGE 11
Systems Service Mechanical, Inc. IN OUT
PROJECT VA Community Living Center Phase 1, Fresno, CA
AREA NO. KIND SIZE AK DESIGN PRELIM FINAL COMMENTS
AHU 1 Returns Lobby R34 SWR 30 x10 1.50 1115 960 1092 98 Mech Rm R35 SWR 18 x 10 1.00 450 1100 434 96 Electrical Rm 1E21 R36 SWR 16 x 16 1.56 740 1205 760 103 Data Rm 1E17 R37 CR 14" Dia. 0.78 500 400 496 99 Resident Bed 1D01 R38 CR 8" Dia. 1.00 215 220 203 94 Resident Bed 1D02 R39 CR 8" Dia. 1.00 215 135 203 94 Dining Room 1D03 R40 SWR 30 x 12 1.00 910 955 908 100 Resident Bed 1D04 R41 CR 8" Dia. 1.00 215 127 211 98 Resident Bed 1D05 R42 CR 8" Dia. 1.00 215 197 221 103 Nurses Break 1D15 R43 CR 8" Dia. 1.00 215 202 219 102 Living Room 1D16 R44 SWR 30 x 12 1.00 1100 900 1056 96 Resident Bed 1D17 R45 CR 8" Dia. 1.00 215 202 203 94 Resident Bed 1D18 R46 CR 8" Dia. 1.00 215 168 211 98 Corridor 1D-1 R47 CR 12" Dia. 1.00 510 428 496 97 Corridor 1D-1 R48 CR 12" Dia. 1.00 500 469 499 100
Total 7330 7668 7212 98
EF -2
Resident Bed 1D01a E49 CR 6" Dia. 1.00 75 73 76 101 Resident Bed 1D02a E50 CR 6" Dia. 1.00 75 53 70 93 Resident Bed 1D04a E51 CR 6" Dia. 1.00 75 93 81 108 Resident Bed 1D05a E52 CR 6" Dia. 1.00 75 71 78 104 Soiled Utility 1D11b E53 CR 6" Dia. 1.00 75 71 73 97 Staff Toilet 1D11c E54 CR 6" Dia. 1.00 75 96 73 97 House Keeping 1D11d E55 CR 6" Dia. 1.00 75 85 70 93 Toilet E56 CR 6" Dia. 1.00 75 88 76 101 Resident Bed 1D17a E57 CR 6" Dia. 1.00 75 118 77 103 Resident Bed 1D18a E58 CR 6" Dia. 1.00 75 131 78 104 Laundry 1E18 E59 CR 6" Dia. 1.00 130 68 121 93
Totsl 880 947 873 99
REMARKS
TEST DATE READINGS BY Steve Santos
FORM 2 / 12.98 PAGE 12
PERCENT
of DESIGN
Systems Service Mechanical PUMP TEST
PROJECT VA Community Living Center Phase 1, Fresno, CA
PUMP DATA PUMP NO. PHWP - 1 PUMP NO. PHWP - 2 PUMP NO.
Location
Service
Manufacturer
Model Number
Serial Number
GPM / Ft.Hd.
Req. NPSH
Pump RPM
Impeller Diam.
Motor Mfr. / Frame
Motor HP / RPM
Volts / Phase / Hertz
F.L. Amps / S.F.
Seal Type
Pump Off Pressure
Valve Shut Diff.
Actual Impeller Diam.
Valve Open Diff.
Valve Open GPM
Final Discharge Press.
Final Suction Press.
Final Delta P
Final GPM
Voltage
Amperage
VFD Speed
REMARKS
TEST DATE 7/18/2018 READINGS BY Steve Santos
FORM 8 / 8.99 PAGE 13
3.5"
3.5'
50.75'
41.5'
9.25'
0.64
41.5'
0.64
.8 / 1.15
CeramicCeramic
9.25'
3.5"
3.5'
18 psi
13'
18 psi
13'
50.75'
.8 / 1.15
NA
3.5"
Baldor / 56C
3.5"
Baldor / 56C
1/2 / 1725
460 / 3 / 60
1/2 / 1725
460 / 3 / 60
NA
Mechanical Room
Primary / Boilers
Bell & Gossett
60 3x5.25 3.5" BF
PH018592 A
54 / 10'
PH018592 B
54 / 10'
Mechanical Room
Primary / Boilers
Bell & Gossett
60 3x5.25 3.5" BF
Systems Service Mechanical PUMP TEST
PROJECT VA Community Living Center Phase 1, Fresno, CA
PUMP DATA PUMP NO. SHWP - 1 PUMP NO. SHWP - 2 PUMP NO.
Location
Service
Manufacturer
Model Number
Serial Number
GPM / Ft.Hd.
Req. NPSH
Pump RPM
Impeller Diam.
Motor Mfr. / Frame
Motor HP / RPM
Volts / Phase / Hertz
F.L. Amps / S.F.
Seal Type
Pump Off Pressure
Valve Shut Diff.
Actual Impeller Diam.
Valve Open Diff.
Valve Open GPM
Final Discharge Press.
Final Suction Press.
Final Delta P
Final GPM
Voltage
Amperage
VFD test speed
PH I operating Spd
REMARKS
TEST DATE 7/18/2018 READINGS BY Steve Santos
FORM 8 / 8.99 PAGE 14
36hz 36hz
1.3 1.5
60hz 60hz
54 54
456 457
46' 48'
30' 30'
70 70
76' 78'
5.75" 5.75"
20.9' 20.9'
NA NA
37' 37'
1.6 / 1.15 1.6 / 1.15
Ceramic Ceramic
1.0 / 1760 1.0 / 1760
460 / 3 / 60 460 / 3 / 60
5.75" 5.75"
Baldor / 143t Baldor / 143t
4' 4'
1760 1760
PH018594 A PH018594 B
54 / 30' 54 / 30'
Bell & Gossett Bell & Gossett e1510 1.25 AD e1510 1.25 AD
Mechanical Room Mechanical Room
Reheat Coils Reheat Coils
B-160L x
SERIES e-1510 1800 RPM SYNCHRONOUS SPEED
Series e-1510
Series e-1510 x
Systems Service Mechanical BALANCE VALVE/FLOW
METER TEST REPORT
PROJECT VA Community Living Center Phase 1, Fresno, CA
AREA SIZE MODEL DESIGN ACTUAL ACTUAL ACTUAL NOTES
GPM VALVE VALVE GPM
SETPOINT P.D.
AHU -1
Cooling Coil CB4F B&G 94 15.00 6.8' 95
Heating Water
PHC - 1 CV 3.8 Griswold 4 100% 38" 3
SAV 1-12 CV 1.9 Griswold 2.1 50% 22" 2
SAV 1-13 CV 1.9 Griswold 1.2 20% 10" 1.3
SAV 1-15 CV 1.9 Griswold 0.7 50% 11" 0.8
SAV 1-16 CV 1.9 Griswold 0.6 60% 25" 0.7
SAV 1-17 CV 1.9 Griswold 1.6 50% 10" 1.6
SAV 1-18 CV 1.9 Griswold 0.6 50% 11" 0.7
SAV 1-19 CV 1.9 Griswold 0.6 50% 18" 0.7
SAV 1-20 CV 1.9 Griswold 1 50% 11" 1.1
SAV 1-21 CV 1.9 Griswold 0.5 50% 12" 0.6
SAV 1-22 CV 1.9 Griswold 1 50% 20" 1.1
SAV 1-23 CV 1.9 Griswold 1.9 100% 40" 1.8
SAV 1-24 CV 1.9 Griswold 0.6 30% 11" 0.7
SAV 1-25 CV 1.9 Griswold 0.6 30% 10" 0.7
SAV 1-27 CV 1.9 Griswold 0.5 10% 10" 0.7
REMARKS
TEST DATE READINGS BY Steve Santos
FORM 2 / 12.98 PAGE 17
7/18/2018
Systems Service Mechanical, Inc.
Table 1. Required Instrumentsation for Air & Hydronic Certification
FUNCTION
RANGE
MINIMUM
ACCURACY &
RESOLUTION
CALIBRATION
DATE
(Requirement)
Name/ Type (12 Months)
1% +/- RPM Manufact. & Model Serial No. H.250132 2/8/2019
(12 Months)
Name/ Type
Manufact. & Model Serial No. 6070691 2/8/2019
Name/ Type (12 Months)
Manufact. & Model Serial No. 6070691 2/8/2019
Name/ Type
Manufact. & Model Serial No. 6070691 2/8/2019
Electrical Measurement
Name/ Type (6 Months)
Manufact. & Model Serial No. 73953486 2/8/2019
Name/ Type
Manufact. & Model Serial No. 73953486 2/8/2019
Clamp Meter
Clamp Meter
2% +/- reading &
0.1 Ampere
Fluke 52
INSTRUMENT INFORMATION
Digital Tachometer
2% +/- READING
minus40 to 240 deg
Extech Instruments 461995
1% of Reading & 0.2 deg.F.
1% of Reading & 0.2 deg.F.
1% of Reading & 0.2 deg.F.
minus40 to 240 deg minus40 to 240 deg
Digital Thermometer / with probes
Fluke 52
Rotating Measuring
Digital Thermometer / with probes
0 to 100 AmpsAmpere
AIR
Immersion
Contact
Volts
Fluke 52
0 to 600 VAC
Temperature Measurement
0 to 5000 RPM
Fluke #36
Digital Thermometer / with thermo
2% +/- reading & 1 volt Fluke #36
Systems Service Mechnical, Inc.
Table 2. Required Instrumentsation for Air & Hydronic Certification
FUNCTION RANGE
MINIMUM
ACCURACY &
RESOLUSION
CALIBRATION
DATE
(Requirement)
5% +/- in w.g. Name/ Type (12 Months)
Manufact. & Model Serial No. M92163 2/8/2019
Name/ Type
Air Pressure 0 to 10.00 in. w.g. Manufact. & Model Serial No. M92163 2/8/2019 Measurememt
Name/ Type
Manufact. & Model Serial No. M92163 2/8/2019
Name/ Type
Manufact. & Model Serial No. M92163 2/8/2019
18 in. NA Name/ Type
Manufact. & Model Serial No. NA NA Pitot Tube
(2 Required ) 36 in. NA Name/ Type
Manufact. & Model Serial No. NA NA
Name/ Type (12 Months)
Measuring 50 to 2500 FPM 20 fpm Manufact. & Model Serial No. CP237357 10/27/2017
Name/ Type (12 Months)
10 to 90% RH 3% RH Range Manufact. & Model Serial No. 11118499 2/8/2019 1% Resolusion
Name/ Type (12 Months)
Digital 5 CFM Manufact. & Model Serial No. M92163 2/8/2019
PAG 20E
INSTRUMENT INFORMATION
Micromanometer
Shortridge ADM 870
Micromanometer
Dwyer
Micromanometer
Shortridge ADM 870
Micromanometer
Shortridge ADM 870
Shortridge ADM 870
Dwyer / 18"
Dwyer
Dwyer / 36"
Shortridge ADM 870
Alnor Anemometer
RVA 801
Precision Psychrometer
Extech RH 390
Shortridge Flow Hood
0.01 in w.g. < 1 in w.g.
0.1 in w.g. > 1 in w.g.
5% +/- reading &
Air Volume Measurememt
(Direct Readings Hood)
Minimum Range 100 to 2000 CFM
5% +/- Reading
Air Velocity Minimum Range
Humidity Measurememt
Systems Service Mechanical, Inc.
Table 3. Required Instrumentation for Hydronic Certification
FUNCTION RANGE
MINIMUM
ACCURACY &
RESOLUSION
CALIBRATION
DATE
(Requirement)
Name/ Type (12 Months)
Manufact. & Model Serial No. W12128 3/20/2018
Name/ Type
Manufact. & Model Serial No. W12128 3/20/2018
Name/ Type
Manufact. & Model Serial No. W12128 3/20/2018
Name/ Type
Manufact. & Model Serial No. W12128 3/20/2018
Name/ Type
Manufact. & Model Serial No. W12128 3/20/2018
INSTRUMENT INFORMATION
Hydro Data Digital Micromanometer
Shortridge 250
Hydro Data Digital Micromanometer
Shortridge 250
Hydro Data Digital Micromanometer
Shortridge 250
Hydro Data Digital Micromanometer 0 to 100ft
Shortridge 250
Hydro Data Digital Micromanometer
Shortridge 250
2% of Reading &
1.0 psi.
2% of Reading &
2.5 psi.
2% of Reading & 1.0ft w.g.
Hydronic Drfferential Pressure
Measurenent
2% of Reading & 1.0 in w.g
Hydronic Pressure
Measuremet
2% of Reading &
0.5 psi.
30 HG to 60
Psi.
0 TO 100 PSI.
0 to 100 in w.g.
0 TO 200 PSI.
ABBREVIATION
AFF ABOVE FINISH FLOOR LWT LEAVING WATER TEMPERATURE
AMB AMBIENT LIN LINEAR DIFFUSER
BDD BACKDRAFT DAMPER MAX MAXIMUM
BHP BRAKE HORSEPOWER MBH THOUSAND BTU PER HOUR
BTUH BTU PER HOUR MIN MINIMUM
CD CEILING DIFFUSER NC NORMALLY CLOSED
CG CEILING GRILL NA NOT AVAILABLE
CR CEILING REGISTER OSA OUTSIDE AIR
CFM CUBIC FEET PRE HOUR OD OUTSIDE DIAMETER
DIA DIAMETER OV OUTLET VELOCITY
DL DRUM LOUVER PRV PRESSURE REDUCING VALVE
DWDI DOUBLE WIDE DOUBLE INLET
E EXHAUST AIR GRILL PSI POUNDS PER SQUARE INCH
EAT ENTER AIR TEMPERATURE PSIG PSI GAUGE
EDB ENTER DRY BULB QTY QUANTITY
EER ENERGY EFFICIENCY RATIO R RETURN AIR DIFFUSER/GRILL
EFF EFFICIENCY RH RELATIVE HUMIDITY
ENT ENTERING S SUPPLY AIR DIFFUSER/GRILL
ESP EXTERNAL STATIC PRESSURE SS STAINLESS STEEL
EWB ENTERING WET BULB SWG SIDE WALL GRILL
EWT ENTERING WATER TEMPERATURE SWSI SINGLE WIDE SINGLE INLET FAN
(E) EXISTING TG TRANSFER GRILL
FA FREE AREA TSP TOTAL STATIC PRESSURE
FC FORWARD CURVE FAN TYP TYPICAL
FT FEET TW THROW AWAY FILTERS
FG FLOOR GRILL UNO UNLESS NOTED OTHERWISE
FF FINISHED FLOOR V/PH/HZ VOLTS / PHASE / HERTZ
FLA FULL LOAD AMPERES VD VOLUME DAMPER
FPM FEET PER MINUTE VTR VENT THROUGH ROOF
FV FACE VELOCITY W WIDTH
GPM GALLONS PER MINUTE W/ WITH
HP HORSEPOWER WB WET BULB
HX HEAT EXCHANGER WG WATER GAUGE
ID INSIDE DIAMETER WPH WATER PRESSURE DROP
IN INCHES
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LDB LEAVING WET BULB TEMPERATURE
| SSM cover |
| Sheet1 |
| TABLE OF CONTENT |
| SSM certifi |
| Sheet1 |
| SSM general notes |
| Floor Plan |
| SSM appara |
| Sheet1 |
| SSM fan |
| Sheet1 |
| SSM VAVinout |
| Sheet1 |
| Sheet1 (2) |
| Sheet1 (3) |
| SSM new Inout |
| Sheet1 |
| SSM flowmeter |
| Sheet1 |
| Balance Valve |
| SSM Calibration |
| Table 1 |
| Table 2 |
| Table 3 |
| TAB ABBREVIATIONS |
| Sheet1 |
| SSM pumps.pdf |
| Sheet1 |
| Sheet1 (2) |