Summary: VA Fresno Critical Room Recertification 2025 - Test, Adjust, and Balance Report

This document is a Certified Test, Adjust, and Balance (TAB) Report prepared by Equal Air Balance Company (NEBB Certified Firm #2910) for the Department of Veterans Affairs facility in Fresno, California on February 7, 2025. The report provides comprehensive testing, measurement, and certification of HVAC system performance across multiple critical care rooms and operational spaces within the VA Medical Center. Equal Air Balance Company is a NEBB-certified firm operating under License #1006492, with technicians A. Plyavinsh and J. Bueno conducting measurements in accordance with NEBB procedural standards. The work documents static pressures, air change rates (ACH), supply and exhaust CFM flows, and differential pressures for over 60 rooms across multiple floors, including operating rooms, isolation rooms, procedure rooms, emergency department spaces, and support facilities.

Key findings indicate several rooms exceed or fall short of designed air change specifications, with notable issues including: AHU-Surgical experiencing elevated external discharge static pressure of 4.86" (previously 3.61"), suggesting possible air restrictions; multiple sterile supply and observation/treatment rooms demonstrating insufficient supply airflow and inadequate air changes; 3A04A and 3A04B GI procedure rooms with insufficient exhaust flow; and room 3A15A (Housekeeping) with zero exhaust register flow, indicating possible disconnection. Pressure compliance varies significantly across spaces, with some rooms maintaining designed positive or negative pressurization while others deviate. The report includes detailed outlet-by-outlet measurements, calibration certificates for measurement instruments (micromanometer, hygronic manometer, digital strobe, and digital thermometer all calibrated in 2024), and NEBB certification documentation for the supervising professional and firm, valid through December 31, 2025.

View the file

Other files

File Type Posted
Amendment 0002 - Attachment 3.pdf PDF
36C26126Q0321 0002.docx DOCX document
Questions and Answers Document .docx DOCX document
Amendment 0002 - Attachment 2.pdf PDF
36C26126Q0321 0001.docx DOCX document
ATTACHMENT 2 - Room Schedule Air Test Adjust and Balance.pdf PDF
36C26126Q0321.docx DOCX document
ATTACHMENT 1 - Quality Assurance Surveillance Plan.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CERTIFIED TEST; ADJUST; BALANCE REPORT

Project Name:

Address:

City:

Architect: N/S

Engineer:

HVAC Contractor:

NEBB Certified TAB Firm: Equal Air Balance Company

Address: 357 East Arrow Highway, Suite 206

City: San Dimas, CA 91773

Certification Number: 2910

License #: 1006492

Date: 2/7/2025

A. Plyavinsh, J. Bueno

VA Fresno Critical Room Recertification

VA Fresno Critical Room Recertification 2025

2615 E. Clinton Avenue

Fresno, CA 93703-2223

N/S

Department of Veterans Affairs

EAB Job #: 25007

Technician:

AIR BALANCE REPORT IS NOT VALID WITHOUT NEBB STAMP ABOVE

accounts Snapshot

Project Name:

Certifying NEBB Qualified

TAB Supervisor:

Firm License Number:

Expiration Date: 8/31/2025

Firm Certification Number:

Expiration Date:

"THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM

MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN

ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL

SYSTEMS . ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB

TOLERANCES, ARE NOTED IN THE TEST - ADJUST - BALANCE REPORT PROJECT

SUMMARY."

357 E. Arrow Hwy. Suite 206

San Dimas, CA 91773

Phone (714) 637-3500

Fax (714) 637-3050

Web: www.equalairbalance.com

Specializing in testing and balancing of environmental systems

1006492

REPORT CERTIFICATION

VA Fresno Critical Room

Recertification 2025

Erik Dlugajczyk

12/31/2025

STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL

Symbol Sheet:

Report Summary: 2nd & 3rd Floors

Test & Balance Sheet:

Air Balance Summary Sheet:

Outlet Sheets:

Report Summary: All Floors

Air Balance Summary Sheet:

Test & Balance Sheet:

Outlet Sheets:

Report Summary Sheet:

Air Balance Summary Sheet:

Outlet Sheets:

Test & Balance Sheet:

Report Summary Sheet:

Test & Balance Sheet:

Certifications:

61 - 62

64 - 81

Table of Contents

VA Fresno Critical Room Recertification 2025

8 - 13

14 - 17

18 - 20

21 - 23

24 - 60

ACU Air Conditioning Unit LAT Leaving Air Temperature

AK Free Area Factor LD Linear Diffuser

ATM Atmosphere LFD Laminar Floor Diffuser

BHP Brake Horse Power LWT Leaving Water Temperature

CAV Constant Air Volume MAT Mixed Air Temperature

CD Ceiling Diffuser MB Mixing Box

CER Ceiling Exhaust Register NA Not Applicable

CFM Cubic Feet per Minute NI Not Installed

CHWR Chilled Water Return NL Not Listed

CHWS Chilled Water Supply NVL No Valid Location

CO Cooling Only NM Not Measured

CRR Ceiling Return Register NR Not Read

CSG Ceiling Supply Grille NS Not Specified

CWR Condenser Water Return OSA Outside Air

CWS Condenser Water Supply R.A Reverse Acting

D.A. Direct Acting RA Return Air

DNA Data Not Available RAG Return Air Grille

DO Duct Opening RAR Return Air Register

DT Duct Traverse RD Round Diffuser

EAG Exhaust Air Grille RH Re-Heat

EAR Exhaust Air Register RPM Revolutions per Minute

EAT Entering Air Temperature SA Supply Air

EF Exhaust Fan SAG Supply Air Grille

EG Exhaust Grille SAR Supply Air Register

ESP External Static Pressure SAV Supply Air Valve

EWT Entering Water Temperature SEF Smoke Evac Fan

EXH Exhaust SP Static Pressure

FC Fan Coil SW Sidewall

FLA Full Load Amps SWG Sidewall Grille

FP Fan Powered TBD To Be Determined

FPM Feet per Minute TSP Total Static Pressure

GEX General Exhaust T-STAT Thermostat

GF Grease Filter UA ULPA Filter

HF Hepa Filter V Volts

HP Horse Power VAV Variable Air Volume

HWR Hot Water Return VP Velocity Pressure

HWS Hot Water Supply WER Wall Exhaust Register

Air Symbol Sheet

(1)

(2)

(3)

(4)

(5)

(6)

PROJECT: VA Fresno Critical Room Recertification 2025

JOB #: 25007

DATE:SYSTEM:

357 East Arrow Highway Suite 206

San Dimas, CA 91773

(714) 637-3500

REPORT SUMMARY

A.P. / J. B. TECHNICIAN:

Fresno, CA 93703

Existing HVAC

2nd & 3rd Floor

2/7/2025

AREA SERVED:

LOCATION:

Room has 24.18 ACH and is designed for 20 ACH. The room is positively pressurized to the corridor and is designed to be positive.

2A13B Special Procedures (SPL):

2A04F Preparation Assembly and

Room has 24.38 ACH and is designed for 4 ACH. The room is positively pressurized to the corridor and is designed to be positive.

3A15 Decontamination Area:

Room has 25.68 ACH and is designed for 6 ACH. The room is negatively pressurized to the corridor and is designed to be negative.

3A15.1 Scope Processing:

Room has 30.05 ACH and is designed for 10 ACH. The room is negatively pressurized to the corridor and is designed to be negative.

3A15A Housekeeping:

Zero flow reading from exhaust register. Register possibly disconnected from exhaust system.

3A15B Restroom:

Room has 10.78 ACH and is designed for 10 ACH. The door to the restroom has been removed, unable to measure DP.

accounts Image accounts Text Box

CERTIFIED MEMBER - NATIONAL ENVIRONMENTAL BALANCING BUREAU

Date: 2/7/2025

Readings by: Job No.: 25007

REQUIRED ACTUAL

DELTA PRESS. DELTA PRESS. WHERE TAKEN

TO ADJACENT TO ADJACENT COMMENTS

ROOM (INCHES W.C) ROOM (INCHES W.C) AN/OR DATA

2A13B ( + ) 0.001" ( + ) 0.0352"

3A02F ( + ) 0.001" ( + ) 0.0103"

3A15 ( - ) 0.001" ( - ) 0.0127"

3A15.1 ( - ) 0.001" ( - ) 0.0082"

3A15A ( -) 0.001" ( - ) 0.00015" (1)

3A15B ( - ) 0.001" NA (2)

Notes:

(2) Restroom door has been removed. No pressure reading can be taken.

(1) 3A15A Housekeeping: Zero flow reading from exhaust register.

Restroom

Housekeeping

TEST AND BALANCE

VA Fresno Critical Room Recertification 2025

A. Plyavinsh, J. Bueno

ROOM

NO. # NAME

Special Procedures

Prep Assembly

Decontamination Area

Scope Processing accounts Image accounts

Air Balance Summary Job No.:

Date:

Job Name: Technician:

Job Location:

ROOM VOLUME PRESSURE PRESSURE SUPPLY SUPPLY SUPPLY EXH EXH EXH RETURN RETURN RETURN CODE MIN OA CODE MIN TOTAL

RM # ROOM NAME (CU.FT.) REQ. ACT. PLAN ACT. CFM +/- PLAN ACT. CFM +/- PLAN ACT CFM +/- AC/HR AC/HR

2A13B Special Procedures (SPL) 5562 P P NS 2242 NM NS 1235 NM NA NA NA NA 20 24.18

3A02F Preparation, Assembly and Sterilization Area 6826 P P NS 2546 NM NS 0 NM NA NA NA NA 4 22.38

3A15 Decontamination Area 3154 N N NS 660 NM NS 1350 NM NA NA NA NA 6 25.68

3A15.1 Scope Processing 605 N N NS 303 NM NS 245 NM NA NA NA NA 10 30.05

3A15A Housekeeping (2) 155 N N NS NA NM NS 0 NM NA NA NA NA 10 0.00

3A15B Restroom 601 N NA (1) NS 86 NM NS 108 NM NA NA NA NA 10 10.78

Notes:

(1) Restroom door has been removed. No pressure reading can be taken.

(2) Housekeeping area has zero CFM reading from Exhaust Register.

Fresno, CA 93703

AIR CHANGES

ACTUAL

357 East Arrow Highway Suite 206 San Dimas, CA 91773

(714) 637-3500

25007

2/7/2025

A. Plyavinsh, J. BuenoVA Fresno Critical Room Recertification 2025 accounts Image accounts

TEST AND BALANCE REPORT

DIFFUSER AND GRILLE TEST

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 2A13B / Special Procedures 1 24" x 24" 1.00 HF NS * 969 *

2A13B / Special Procedures 2 24" x 10" 1.670 HF NS NS 641 384

2A13B / Special Procedures 3 24" x 10" 1.670 HF NS NS 631 378

Total NS 2242

Exhaust 2A13B / Special Procedures E - 1 48" x 10" 3.33 SWG NS * 749 225

2A13B / Special Procedures E - 2 48" x 10" 3.33 SWG NS * 486 146

2A13B / Special Procedures E - 3 14" x 14" 1.00 SWG NS * 0 NS (1)

2A13B / Special Procedures E - 4 14" x 14" 1.00 SWG NS * 0 NS (1)

Total NS 1235

(+) 1007

Notes:

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

DESIGN ACTUAL

NOTES

(1) Zero flow reading from exhaust register. Register is capped accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A02F / Prep Assembly 1 14" x 14" 1.00 CD NS * 222 *

3A02F / Prep Assembly 2 14" x 14" 1.00 CD NS * 35 *

3A02F / Prep Assembly 3 14" x 14" 1.00 CD NS * 34 *

3A02F / Prep Assembly 4 14" x 14" 1.00 CD NS * 170 *

3A02F / Prep Assembly 5 14" x 14" 1.00 CD NS * 135 *

3A02F / Prep Assembly 6 14" x 14" 1.00 CD NS * 168 *

3A02F / Prep Assembly 7 14" x 14" 1.00 CD NS * 115 *

3A02F / Prep Assembly 8 12" x 8" 1.00 SWSG NS * 306 *

3A02F / Prep Assembly 9 12" x 8" 1.00 SWSG NS * 152 *

3A02F / Prep Assembly 10 12" x 8" 1.00 SWSG NS * 136 *

3A02F / Prep Assembly 11 12" x 8" 1.00 SWSG NS * 237 *

3A02F / Prep Assembly 12 12" x 8" 1.00 SWSG NS * 244 *

3A02F / Prep Assembly 13 12" x 8" 1.00 SWSG NS * 303 *

3A02F / Prep Assembly 14 12" x 8" 1.00 SWSG NS * 0 *

3A02F / Prep Assembly 15 11.25" x 7.25" 1.00 SWSG NS * 289 *

Total NS 2546

Return 3A02F / Prep Assembly 1 25.25" x 11.5" 1.00 SWR NS * 0 *

Total NS 0

( + ) 2,546

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A15 / Decontamination Area 1 18" x 18" 1.00 CD NS * 391 *

3A15 / Decontamination Area 2 16" x 16" 1.00 CD NS * 269 *

Total NS 660

Exhaust 3A15 / Decontamination Area E - 1 20" x 20" 1.00 EG NS * 1350 *

Total NS 1350

( - ) 690

Supply 3A15 / Decontamination Area 1 18" DIA 1.00 RG NS * 581 *

3A15 / Decontamination Area 2 18" DIA 1.00 RG NS * 615 *

Total NS 1,196 (1)

Return 3A15 / Decontamination Area R - 1 18" DIA 1.00 RG NS * 582 *

3A15 / Decontamination Area R - 2 18" DIA 1.00 RG NS * 575 *

Total NS 1,157 (1)

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

(1) This unit is a temp unit installed and 100% recirculation. Not included with AC/H calculation.

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A15.1 / Scope Processing 1 12" x 12" 1.00 CD NA * 303 *

Total NS 303

Exhaust 3A15.1 / Scope Processing E - 1 12" x 12" 1.00 EG NS * 245 *

Total NS 245

( + ) 58

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A15A / Housekeeping 1 6" x 4" 1.00 CD NS * 0 *

Total NS 0 (1)

Notes:

(1) Zero flow reading from exhaust grille, possibly disconnected from exhaust system.

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL 0

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A15B / Restroom 1 12" x 12" 1.00 CD NS * 86 *

Total NS 86

Exhaust 3A15B / Restroom E - 1 10" x 6" 1.00 EG NS * 108 *

Total NS 108

( - ) 22

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

(1) 2A09C Ultrasound #1:

(2) 3A014 Sterile Supply Room (GI Cabinet):

(3) 3A02E Clean Storage West:

(4) 3A02E Clean Storage East:

(5) 3A04A GI Procedure-1 EDG

(6) 3A04B GI Procedure-2 EDG:

(7) 3A04D Sterile Supply Room GI:

(8) 3A04G GI Procedure Room:

(9) 3B10A OR-1:

(10) 3B10D OR-2:

(11) 3B10I Sterile Supply:

Room has 8.67 ACH and is designed for 4 ACH. Room is positively pressurized to Ultrasound Suite and is designed to be positive.

Actual Room - Restroom. The room has 12.10 ACH and is designed for 4 ACH. The room is negatively pressurized to the corridor and is designed to be positive.

Room has 4.4 ACH and is designed for 4 ACH. Room is negatively pressurized to the corridor and is designed to be positive.

Room has 5.83 ACH and is designed for 4 ACH. Room is positively pressurized to the ramp and is designed to be positive.

Room has 5.12 ACH and is designed for 10 ACH. Room is negatively pressurized to the corridor. and is designed to be negative. Insufficient exhaust flow. Insufficient air changes.

Room has 7.33 ACH and is designed for 10 ACH. Room is positively pressurized to the corridor. and is designed to be negative. Insufficient exhaust flow. Insufficient air changes.

Room has 23.63 ACH and is designed for 20 ACH. Room is positively pressurized to the corridor and is designed to be positive. Room static set point of (+)0.02"w.c. is maintaining by motorized exhaust dampers. Measured space pressure is 0.0292"w.c.

Room has 4.66 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive.

Room has 6.8 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive.

Room has 14.16 ACH and is designed for 12 ACH. Room is negatively pressurized to the corridor and is designed to be negative.

Room has 23.07 ACH and is designed for 20 ACH. Room is positively pressurized to the corridor and is designed to be positive. Room static set point of (+)0.02"w.c. is maintaining by motorized exhaust dampers. Measured space pressure is 0.0257"w.c.

AREA SERVED: All Floors TECHNICIAN: A.P. / J. B.

357 East Arrow Highway Suite 206

San Dimas, CA 91773

(714) 637-3500

Report Summary

PROJECT: VA Fresno Critical Room Recertification 2025

LOCATION: Fresno, CA 93703 JOB #: 25007

SYSTEM: Existing HVAC DATE: 2/7/2025 accounts Image accounts

(12) 3B10J OR Equipment Storage:

(13) 3B10K OR-4:

(14) 3B10M OR-3:

(15) 4A45 Sterile Supply Room:

(16) 4A26 Sterile Supply Room:

(17) 4A27 Sterile Supply Room:

(18) 4B39 Sterile Supply Room:

(19) 4B46L Sterile Supply Room:

(20) 5A28 Isolation Room:

Room has 24.78 ACH and negative ( - ) 0.0917" in relation to the corridor.

Room has 24.54 ACH and is designed for 20 ACH. Room is positively pressurized to the corridor and is designed to be positive. Room static set point of (+)0.02"w.c. is maintaining by motorized exhaust dampers. Measured space pressure is 0.0258"w.c.

Room has 11.75 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive. Exhaust register is covered by tape.

Room has 8.25 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive.

Room has 9.04 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive.

Room has 9.52 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive.

Room has 15.29 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive.

Room has 20.17 ACH and is designed for 20 ACH. Room is positively pressurized to the corridor and is designed to be positive. Room static set point of (+)0.02"w.c. is maintaining by motorized exhaust dampers. Measured space pressure is 0.0204"w.c.

LOCATION: Fresno, CA 93703 JOB #: 25007

SYSTEM: Existing HVAC DATE: 2/7/2025

AREA SERVED: All Floors TECHNICIAN: A.P. / J. B.

Room has 5.23 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive.

357 East Arrow Highway Suite 206

San Dimas, CA 91773

(714) 637-3500

PROJECT: VA Fresno Critical Room Recertification 2025 accounts Image accounts

(21) 5A29 Ante Room:

(22) 5A30 Isolation Room:

(23) 5B19 Isolation Room:

(24) 5B19.1 Ante Room:

(25) 5B20 Isolation Room:

(26)

(27) B1B04 Gross Specimen Holding Area:

(28) B1B04A Autopsy:

(29) B1B05 Soiled Laundry Receiving and Sorting Room:

(30) B1B16 Laundry Room-Clean Side:

Room has 10. ACH and is designed for 6 ACH. Room is positively pressurized to the corridor (0.0021") and is designed to be negative.

Room has 16.13 ACH and is designed for 4 ACH. Room is positively pressurized to B1B04 and is designed to be positive.

Room has 15.94 ACH and is positive in relation to the isolation room 5A28 (0.0451"); positive in relation to the isolation room 5A30 (0.0201") and negative in relation to the corridor ( - ) 0.0557". Pressure monitor reads: ( - )

0.0219" W.C. Attempted to calibrate. Pressure value on monitor is fluctuating, can not be calibrated.

Room has 27.56 ACH with a design of 12 ACH. Room is negatively pressurized to the corridor and is designed to be negative.

Room has 16.06 ACH with a design of 12 ACH. Room is negatively pressurized to the corridor and is designed to be negative.

Room has 10.23 ACH positive in relation to the isolation room (0.0220") and design of 10 ACH); positive in relation to the isolation room (0.0301") and negative in relation to the corridor ( - )0.0110".

5B20.1 Ante Room:

Room has 10.02 ACH with design of 10 ACH and is positive in relation to the isolation room (0.0290"); positive in relation to the isolation room (0.0301") and negative in relation to the corridor ( - )0.0130".

There are no outlets installed.

Room has 25.73 ACH and is designed for 12 ACH. Room is negatively pressurized to B1B04 and is designed to be negative.

AREA SERVED: All Floors TECHNICIAN: A.P. / J. B.

The ISO Room has 26.48 ACH and negative ( - ) 0.0743" in relation to the corridor.

LOCATION: Fresno, CA 93703 JOB #: 25007

SYSTEM: Existing HVAC DATE: 2/7/2025

357 East Arrow Highway Suite 206

San Dimas, CA 91773

(714) 637-3500

PROJECT: VA Fresno Critical Room Recertification 2025 accounts Image accounts

(31) B1B16B Clean Laundry Storage Room:

(32) 2C06K Infusion Clinic:

(33) 2C15F Sterile Supply Room:

(34) 3C10W Sterile Supply Room:

(35) S0G8 Isolation Room:

(36)

(37) 2C08E Sterile Supply Room:

With the T-stat at 55 degrees the room is positively pressurized to the corridor and is designed to be negative.

When the T-stat is at 72 degrees the room has insufficient air changes with 5.23 ACH with a design of 6 ACH.

Insufficient exhaust flow. The room is negatively pressurized to the corridor with the T-stat at 72 degrees.

Room has 2.87 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive. Insufficient supply flow.

Room has 1.35 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive. Insufficient supply flow.

Room has 11.08 ACH and is designed for 4 ACH. Room is negatively pressurized to the corridor and is designed to be positive. Insufficient supply flow.

Room has 21.57 ACH and is designed for 12 ACH. At time of TAB: Med Air System at High speed. Room is negatively pressurized to the corridor and is designed to be negative.

S0G9 Isolation Room:

Room has 28.69 ACH and is designed for 12 ACH. At time of TAB: Med Air System at High speed. Room is negatively pressurized to the corridor and is designed to be negative.

AREA SERVED: All Floors TECHNICIAN: A.P. / J. B.

Room has 14.9 ACH and is designed for 4 ACH. Room is positively pressurized to the corridor and is designed to be positive.

LOCATION: Fresno, CA 93703 JOB #: 25007

SYSTEM: Existing HVAC DATE: 2/7/2025

357 East Arrow Highway Suite 206

San Dimas, CA 91773

(714) 637-3500

PROJECT: VA Fresno Critical Room Recertification 2025 accounts Image accounts

Job Name: Technician:

Job Location:

ROOM VOLUME PRESSURE PRESSURE SUPPLY SUPPLY SUPPLY EXH EXH EXH RETURN RETURN RETURN CODE MIN OA CODE MIN TOTAL

RM # ROOM NAME (CU.FT.) REQ. ACT. PLAN ACT. CFM +/- PLAN ACT. CFM +/- PLAN ACT CFM +/- AC/HR AC/HR

2A09C Ultrasound #1 1357 P P NS 196 NS NS 57 NS NA NA NA NA 4 8.67

3A014 Sterile Supply Room (GI Cabinet) (1) 372 P N NS 75 NS NS 85 NS NA NA NA NA 4 12.10

3A02E Clean Storage (West) 4270 P N NS 313 NS NS 0 NS NA NA NA NA 4 4.40

3A02E Clean storage Equip. Room (East) 5124 P P NS 498 NS NS 0 NS NA NA NA NA 4 5.83

3A04A GI Procedure-1 (EDG) (2) 1827 N N NS 136 NS NS 156 NS NA NA NA NA 10 5.12

3A04B GI Procedure-2 (EDG) (2) 1907 N P NS 349 NS NS 233 NS NA NA NA NA 10 7.33

3A04D Sterile Supply Room (GI) 406 P P NS 46 NS NS 0 NS NA NA NA NA 4 6.80

3A04G GI Procedure-3 (Bronch Room) 1720 N N NS 213 NS NS 406 NS 482 NA NA NA 12 14.16

3B10A OR 1 3937 P P NS 1514 NS NS 859 NS NA NA NA NA 20 23.07

3B10D OR 2 4196 P P NS 1652 NS NS 818 NS NA NA NA NA 20 23.63

3B10I OR Sterile Supply 876 P P NS 68 NS NS 53 NS NA NA NA NA 4 4.66

3B10J OR Equip Storage 3704 P P NS 323 NS NS 180 NS NA NA NA NA 4 5.23

Notes: (1) Actual: Room 3A14 is the restroom. Room is negative to the corridor.

(2) 3A04A and 3A04B GI procedure (EDG): Insufficient exhaust air flow. Insufficient air change rate.

Fresno, CA 93703

AIR CHANGES

ACTUAL

357 East Arrow Highway Suite 206 San Dimas, CA 91773

(714) 637-3500

25007

2/7/2025

A. Plyavinsh, J. BuenoVA Fresno Critical Room Recertification 2025 accounts Image accounts

Job Name: Technician:

Job Location:

ROOM VOLUME PRESSURE PRESSURE SUPPLY SUPPLY SUPPLY EXH EXH EXH RETURN RETURN RETURN CODE MIN OA CODE MIN TOTAL

RM # ROOM NAME (CU.FT.) REQ. ACT. PLAN ACT. CFM +/- PLAN ACT. CFM +/- PLAN ACT CFM +/- AC/HR AC/HR

3B10K OR 4 6851 P P NS 2,304 N/S NS 1,507 NS NA NA NA NA 20 20.17

3B10M OR 3 3574 P P NS 1461 NS NS 1011 NS NA NA NA NA 20 24.54

4A45 Sterile Supply Room (ENT) (1) 480 P P NS 94 NS NS 0 NS NA NA NA NA 4 11.75

4A26 Sterile Supply Room (Urology ambulatory) 1280 P P NS 176 NS NS 0 NS NA NA NA NA 4 8.25

4A27 Sterile Supply Room ( Surgical Clinic) 684 P P NS 103 NS NS 0 NS NA NA NA NA 4 9.04

4B39 Sterile Supply Room (Dermatology) 416 P P NS 66 NS NS 0 NS NA NA NA NA 4 9.52

4B46L Sterile Supply Room (Women's Clinic) 577 P P NS 147 NS NS 66 NS NA NA NA NA 4 15.29

5A28 Isolation Room 1804 N N NS 140 NS NS 580 NS NA NA NA NA 12 19.29

5A29 Ante Room 384 N N NS 102 NS NS 0 NS NA NA NA NA 10 15.94

5A30 Isolation Room 1500 N N NS 287 NS NS 697 NS NA NA NA NA 12 27.88

5B19 Isolation Room 1961 N N NS 246 NS NS 600 NS NA NA NA NA 12 16.06

5B19.1 Ante Room 393 N N NS 67 NS NS NA NS NA NA NA NA 10 10.23

5B20 Isolation Room 1260 N N NS 172 NS NS 579 NS NA NA NA NA 12 27.56

5B20.1 Ante Room 407 N N NS 68 NS NS NA NS NA NA NA NA 10 10.02

B1B04 Gross Specimen Holding Area (2) 1120 N N NS NA NS NS 0 NS NA NA NA NA 6 0.00

B1B04A Autopsy 1728 N N NS 304 NS NS 741 NS NA NA NA NA 12 25.73

(3)

B1B05 Soiled Laundry Receiving and Sorting Room 5413 N P NS 608 NS NS 902 NS NA NA NA NA 6 10.00

B1B16B Clean Laundry Storage Room 1180 P P NS 293 NS NS 0 NS NA NA NA NA 4 14.90

Notes: (1) 4A45 Sterile Supply Room (ENT): Exhaust register is covered by tape. Zero flow reading.

(2) No outlets installed in room.

(3) Insufficient exhaust flow.

Fresno, CA 93703

AIR CHANGES

ACTUAL

357 East Arrow Highway Suite 206 San Dimas, CA 91773

(714) 637-3500

25007

2/7/2025

A. Plyavinsh, J. BuenoVA Fresno Critical Room Recertification 2025 accounts Image accounts

Job Name: Technician:

Job Location:

ROOM VOLUME PRESSURE PRESSURE SUPPLY SUPPLY SUPPLY EXH EXH EXH RETURN RETURN RETURN CODE MIN OA CODE MIN TOTAL

RM # ROOM NAME (CU.FT.) REQ. ACT. PLAN ACT. CFM +/- PLAN ACT. CFM +/- PLAN ACT CFM +/- AC/HR AC/HR

B1B16 Laundry Room-Clean Side 18176 P P NS 4,886 NS NS 2832 NS NA NA NA NA 4 16.13

2C06K Infusion Clinic (1) 5463 N P NS 1,056 NS NS 460 NS NA NA NA NA 6 11.60

2C08E Sterile Supply Room (Cardiology) (2) 648 P P NS 31 NS NS 22 NS NA NA NA NA 4 2.87

2C15F Sterile Supply Room (Eye Clinic) (2) 1020 P P NS 23 NS NS 20 NS NA NA NA NA 4 1.35

3C10W Sterile Supply Room (Dental) 720 P N NS #REF! NS NS #REF! NS NA NA NA NA 4 #REF!

SO-G8 Isolation Room (B1C10) 1146 N N NS 181 NS NS 412 NS NA NA NA NA 12 21.57

SO-G9 Isolation Room (B1C11) 1146 N N NS #REF! NS NS #REF! NS NA NA NA NA 12 #REF!

Notes: (1) Insufficient exhaust flow. Insufficient air change rate. At time of test T-Stat set point is 55F.

(2) Insufficient supply flow. Insufficient air change rate.

Fresno, CA 93703

AIR CHANGES

ACTUAL

357 East Arrow Highway Suite 206 San Dimas, CA 91773

(714) 637-3500

25007

2/7/2025

A. Plyavinsh, J. BuenoVA Fresno Critical Room Recertification 2025 accounts Image accounts

REQUIRED ACTUAL

DELTA PRESS. DELTA PRESS. WHERE TAKEN

TO ADJACENT TO ADJACENT COMMENTS

ROOM (INCHES W.C) ROOM (INCHES W.C) AN/OR DATA

2A09C ( + ) 0.001" ( + ) 0.0031"

3A014 ( + ) 0.001" ( - ) 0.0012" (1)

3A02E(West) ( + ) 0.001" ( - ) 0.0028" (6)

3A02E(East) ( + ) 0.001" ( + ) 0.0179" (2)

3A04A ( - ) 0.001" ( - ) 0.0014" (3)

3A04B ( - ) 0.001" ( + ) 0.0031" (4)

3A04D ( + ) 0.001" ( + ) 0.0026" (5)

3A04G ( - ) 0.001" ( - ) 0.0048"

3B10A ( ++ ) 0.02" ( + ) 0.0257"

3B10D ( ++ ) 0.02" ( + ) 0.0292"

3B10I ( + ) 0.001" ( + ) 0.00136"

3B10J ( + ) 0.001" ( + ) 0.00246"

3B10K ( ++ ) 0.02" (+) 0.0204"

3B10M ( ++ ) 0.02" (+) 0.0258""

4A45 ( + ) 0.001" ( + ) 0.0044"

4A26 ( + ) 0.001" ( + ) 0.0007"

4A27 ( + ) 0.001" ( + ) 0.0001"

Notes:

(2) 3A02E (EAST): Room is positive to the ramp ( + )0.0268"

(3) 3A04A GI Procedure-1 (EDG): Insufficient exhaust air flow.

(4) 3A04B GI procedure-2 (EDG): Insufficient exhaust air flow.

Room is positively pressurized, designed to be negative.

(5) 3A04D Sterile Supply Room (GI): Insufficient (zero flow reading) exhaust air flow.

GI Procedure-2 (EDG)

(1) Actual: Room 3A14 is the restroom. Room is negative to corridor.

OR Equip Storage

OR4

Ultrasound #1

Restroom

Clean Storage Eq. Rm West

Clean Storage East

GI Procedure-1 (EDG)

Sterile Supply Room (GI)

GI Procedure-3 (Brunch Room)

OR1

OR2

OR3

OR Sterile Supply

Sterile Supply Room (ENT)

TEST AND BALANCE

VA Fresno Critical Room Recertification 2025

A. Plyavinsh, J. Bueno

ROOM

NO. # NAME

Sterile Supply Room (Urology ambulatory)

(6) The room is negatively pressurized to the corridor and is designed to be positive.

Ster. Supply Rm (Surg. Clinic) accounts Image accounts

REQUIRED ACTUAL

DELTA PRESS. DELTA PRESS. WHERE TAKEN

TO ADJACENT TO ADJACENT COMMENTS

ROOM (INCHES W.C) ROOM (INCHES W.C) AN/OR DATA

4A55 ( + ) 0.001" ( - ) 0.0032" (7)

4B39 ( + ) 0.001" ( + ) 0.0036"

4B46L ( + ) 0.001" ( + ) 0.0064"

5A28 ( - ) 0.001" ( - ) 0.0917"

5A29 ( - ) 0.001" ( - ) 0.0508" (8)

5A30 ( - ) 0.001" ( - ) 0.0743"

5B19 ( - ) 0.001" ( - ) 0.0248"

5B19.1 ( ) 0.001" ( - ) 0.0110" (9)

5B20 ( -- ) 0.001" ( - ) 0.0373"

5B20.1 ( ) 0.001" ( - ) 0.0130" (10)

B1B04 ( - ) 0.001" ( - ) 0.0040"

B1B04A ( - ) 0.001" ( - ) 0.108"

B1B05 ( - ) 0.001" ( + ) 0.0021" (11)

Notes:

(8) 5A29: The ante room is positive in relation to the isolation room 5A28 (0.0449"); positive in relation to the isolation room 5A30 (0.0276") and negative in relation to the corridor.

(9) 5B19.1: The ante room is positive in relation to the isolation room (0.0220") and negative

(10) 5B20.1: The ante room is positive in relation to the isolation room (0.0290") and negative in relation to the corridor ( - )0.0130".

(11) B1B05 Soiled Laundry: Space is open to laundry. Space is positively pressurized to corridor. Designed to be negative.

(7) 4A55 Sterile supply room: No registers installed. No ductwork above the ceiling.

5A29: Readings on pressure monitor reads is fluctuating, cannot be calibrated.

in relation to the corridor ( - )0.0110".

Soiled Lndr. Receive and Sort Rm

Autopsy

Sterile Supply Room (Podiatry)

Sterile Supply Room (Dermat.)

4B46L Ster. Supply Rm (Wom. Clin.)

Isolation Room

Ante

Isolation Room

Isolation Room

Ante

Isolation Room

Ante

Gross Specimen Holding Area

TEST AND BALANCE

VA Fresno Critical Room Recertification 2025

A. Plyavinsh, J. Bueno

ROOM

NO. # NAME

accounts Image accounts

REQUIRED ACTUAL

DELTA PRESS. DELTA PRESS. WHERE TAKEN

TO ADJACENT TO ADJACENT COMMENTS

ROOM (INCHES W.C) ROOM (INCHES W.C) AN/OR DATA

B1B16 ( + ) 0.001" ( + ) 0.0103"

B1B16B ( + ) 0.001" ( + ) 0.0512"

2C06K ( - ) 0.001" ( + ) 0.0088" (12)

2C08E ( + ) 0.001" ( + ) 0.0005"

2C15F ( + ) 0.001" ( + ) 0.0005"

3C10W ( + ) 0.001" ( - ) 0.0047" (13)

SOG8 ( -- ) 0.001" ( - ) 0.0026"

SOG9 ( -- ) 0.001" ( - ) 0.0542"

Notes:

(12) 2C06K Infusion clinic: Room is positive in relation to the corridor. Insufficient air change rate. Insufficient exhaust air flow. Condition: VAV on auto. Temperature Set Point (70F.)

Room is negative in relation to the corridor ( - )0.0003" W.C.).

(13) 3C10W Sterile Supply Rm(Dental): Room is negatively pressurized to corridor. Designed to be positive.

Isolation Room

Isolation Room

Sterile Supply Rm(Dental)

TEST AND BALANCE

VA Fresno Critical Room Recertification 2025

A. Plyavinsh, J. Bueno

ROOM

NO. # NAME

Laundry Room-Clean Side

Clean Laundry Storage Room

Infusion Clinic

Sterile Supply Rm (Cardiol.)

Sterile Supply Rm(Eye Clinic) accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 2A09C / Sterile Supply Room 1 24" x 24" 1.00 CD NS * 196 *

Total NS 196

Exhaust 2A09C / Sterile Supply Room E - 1 24" x 24" 1.00 EG NS * 57 *

Total NS 57

( + ) 139

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A014 / Restroom 1 12" x 12" 1.00 CD NS * 75 *

Total NS 75

Exhaust 3A014 / Restroom E - 1 12" x 12" 1.00 EG NS * 85 *

Total NS 85

( - ) 10

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A02E / Clean Storage (East) 1 5.5" x 9.5" 1.00 SWSG NS * 75 *

2 5.5" x 9.5" 1.00 SWSG NS * 219 *

3 5.5" x 9.5" 1.00 SWSG NS * 204 *

Total NS 498

( + ) 498

Supply 3A02E / Clean Storage 1 5.5" x 19.5" 1.00 SWSG NS * 194 *

Equip. Room (West) 2 5.5" x 19.5" 1.00 SWSG NS * 119 *

Total NS 313

( + ) 313

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A04A / GI Procedure-1 (EDG) 1 24" x 24" 1.00 CD NS * 136 *

Total NS 136

Exhaust 3A04A / GI Procedure-1 (EDG) E - 1 24" x 24" 1.00 EG NS * 156 *

Total NS 156

( - ) 20

Notes:

AIR TYPE ROOM OUTLET SIZE TYPE

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A04B / GI Procedure-1 (EDG) 1 24" x 24" 1.00 CD NS * 349 *

Total NS 349

Exhaust 3A04B / GI Procedure-1 (EDG) E - 1 24" x 24" 1.00 EG NS * 233 *

Total NS 233

( + ) 116

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A04D / Sterile Supply Room (GI) 1 24" x 24" 1.00 CD NS * 46 *

Total NS 46

Exhaust 3A04D / Sterile Supply Room (GI) E - 1 24" x 24" 1.00 EG NS * 0 *

Total NS 0 (1)

( + ) 46

Notes:

(1) As of 1/27/2025: Still Zero flow reading from exhaust register. No access to verify if duct is connected

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3A04G / GI Proced-3 (Bronch Rm) 1 24" x 24" 1.00 CD NS * 213 *

Total NS 213

Exhaust 3A04G / GI Proced-3 (Bronch Rm) E - 1 24" x 24" 1.00 EG NS * 0 *

Total NS 0

E(HEPA) 3A04G / GI Proced-3 (Bronch Rm) E - 2 24" x 48" 1.00 HEPA NS * 406 *

Total NS 406

( - ) 193

Notes:

NOTES

CFM DIFFERENTIAL

DESIGN ACTUAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3B10A OR1 1 25" x 20" 1.066 HEPA NS * 130 122

3B10A OR1 2 25" x 20" 1.066 HEPA NS * 133 125

3B10A OR1 3 25" x 20" 1.066 HEPA NS * 130 122

3B10A OR1 4 25" x 20" 1.066 HEPA NS * 127 119

3B10A OR1 5 25" x 20" 1.066 HEPA NS * 129 121

3B10A OR1 6 25" x 20" 1.066 HEPA NS * 127 119

3B10A OR1 7 25" x 20" 1.066 HEPA NS * 126 118

3B10A OR1 8 25" x 20" 1.066 HEPA NS * 124 116

3B10A OR1 9 25" x 20" 1.066 HEPA NS * 120 113

3B10A OR1 10 25" x 20" 1.066 HEPA NS * 123 115

3B10A OR1 11 25" x 20" 1.066 HEPA NS * 124 116

3B10A OR1 12 25" x 20" 1.066 HEPA NS * 122 114

Total 1646 1514 92%

Exhaust 3B10A OR1 E - 1 12" x 21.5" 1.00 EG NS * 137 *

3B10A OR1 E - 2 12" x 21.5" 1.00 EG NS * 93 *

3B10A OR1 E - 3 12" x 21.5" 1.00 EG NS * 316 *

3B10A OR1 E - 4 12" x 21.5" 1.00 EG NS * 313 *

Total NS 859

( + ) 655

Notes:

NOTES

CFM DIFFERENTIAL

DESIGN ACTUAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3B10D OR2 1 25" x 20" 1.066 HEPA NS * 145 136

3B10D OR2 2 25" x 20" 1.066 HEPA NS * 147 138

3B10D OR2 3 25" x 20" 1.066 HEPA NS * 144 135

3B10D OR2 4 25" x 20" 1.066 HEPA NS * 142 133

3B10D OR2 5 25" x 20" 1.066 HEPA NS * 135 127

3B10D OR2 6 25" x 20" 1.066 HEPA NS * 144 135

3B10D OR2 7 25" x 20" 1.066 HEPA NS * 133 125

3B10D OR2 8 25" x 20" 1.066 HEPA NS * 135 127

3B10D OR2 9 25" x 20" 1.066 HEPA NS * 139 130

3B10D OR2 10 25" x 20" 1.066 HEPA NS * 117 110

3B10D OR2 11 25" x 20" 1.066 HEPA NS * 134 126

3B10D OR2 12 25" x 20" 1.066 HEPA NS * 136 128

Total 1608 1652 103%

Exhaust 3B10D OR2 E - 1 12" x 21.5" 1.00 EG NS * 116 *

3B10D OR2 E - 2 12" x 21.5" 1.00 EG NS * 137 *

3B10D OR2 E - 3 12" x 21.5" 1.00 EG NS * 535 *

3B10D OR2 E - 4 12" x 21.5" 1.00 EG NS * 30 *

Total NS 818

( + ) 834

Notes:

NOTES

CFM DIFFERENTIAL

DESIGN ACTUAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3B10I / OR Sterile Supply 1 8" x 8" 1.00 CD NS * 68 *

Total NS 68

Exhaust 3B10I / OR Sterile Supply E - 1 11" x 11" 1.00 EG NS * 53 *

Total NS 53

( + ) 15

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3B10J / OR Equip Storage 1 14.5" x 14.5" 1.00 CD NS * 147 *

2 14.5" x 14.5" 1.00 CD NS * 176 *

Total NS 323

Exhaust 3B10J / OR Equip Storage E - 1 14" x 14" 1.00 ER NS * 180 *

Total NS 180

( + ) 143

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3B10K OR4 1 54.25" x 21.25" 1.066 HEPA NS * 256 240

3B10K OR4 2 54.25" x 21.25" 1.066 HEPA NS * 281 264

3B10K OR4 3 54.25" x 21.25" 1.066 HEPA NS * 365 342

3B10K OR4 4 54.25" x 21.25" 1.066 HEPA NS * 220 206

3B10K OR4 5 54.25" x 21.25" 1.066 HEPA NS * 286 268

3B10K OR4 6 54.25" x 21.25" 1.066 HEPA NS * 272 255

3B10K OR4 7 54.25" x 21.25" 1.066 HEPA NS * 205 192

3B10K OR4 8 54.25" x 21.25" 1.066 HEPA NS * 196 184

3B10K OR4 9 35.25" x 21.25" 1.066 HEPA NS * 81 76

3B10K OR4 10 35.25" x 21.25" 1.066 HEPA NS * 143 134

Total NS 2,304 (1)

Exhaust 3B10K OR4 1 21.25" x 11.25" 1.00 SWEG NS * 359 *

3B10K OR4 2 21.25" x 11.25" 1.00 SWEG NS * 369 *

3B10K OR4 3 21.25" x 11.25" 1.00 SWEG NS * 405 *

3B10K OR4 4 21.25" x 11.25" 1.00 SWEG NS * 374 *

Total NS 1,507

( + ) 797

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3B10M OR3 1 25" x 20" 1.066 HEPA NS * 120 113

3B10M OR3 2 25" x 20" 1.066 HEPA NS * 123 115

3B10M OR3 3 25" x 20" 1.066 HEPA NS * 130 122

3B10M OR3 4 25" x 20" 1.066 HEPA NS * 117 110

3B10M OR3 5 25" x 20" 1.066 HEPA NS * 122 114

3B10M OR3 6 25" x 20" 1.066 HEPA NS * 124 116

3B10M OR3 7 25" x 20" 1.066 HEPA NS * 116 109

3B10M OR3 8 25" x 20" 1.066 HEPA NS * 120 113

3B10M OR3 9 25" x 20" 1.066 HEPA NS * 118 111

3B10M OR3 10 25" x 20" 1.066 HEPA NS * 116 109

3B10M OR3 11 25" x 20" 1.066 HEPA NS * 125 117

3B10M OR3 12 25" x 20" 1.066 HEPA NS * 130 122

Total 1631 1461 90% (1)

Exhaust 3B10M OR3 E - 1 12" x 23" 1.00 EG NS * 131 *

3B10M OR3 E - 2 12" x 23" 1.00 EG NS * 76 *

3B10M OR3 E - 3 12" x 23" 1.00 EG NS * 496 *

3B10M OR3 E - 4 12" x 23" 1.00 EG NS * 308 *

Total NS 1011

( + ) 450

Notes:

(1) Room has 24.54 ACH

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 4A26 / Sterile Supply Rm 1 24" x 24" 1.00 CD NS * 176 *

(Urology ambulatory) Total NS 176

Exhaust 4A26 / Sterile Supply Rm (Urol.) E - 1 24" x 24" 1.00 EG NS * 0 *

RET Total NS 0

( + ) 176

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 4A27 / Strl Supply Rm (Cl.Sgr.) 1 24" x 24" 1.00 CD NS * 103 *

Total NS 103

Exhaust 4A27 / Strl Supply Rm (Cl.Sgr.) E - 1 24" x 24" 1.00 EG NS * 0 *

RET Total NS 0

( + ) 103

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 4A45 / Sterile Supply Room (ENT) 1 7.5" x 7.5" 1.00 CD NS * 94 *

Total NS 94

Exhaust 4A45 / Sterile Supply Room (ENT) E - 1 10" x 10" 1.00 EG NS * 0 *

Total NS 0 (1)

( - ) -94

Notes:

(1) Exhaust register is covered by tape. Zero flow reading.

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 4A55 / Sterile Supply Rm (Pdtr) 1 NS NS CD NS * 0 *

Total NS 0

Exhaust 4A55 / Sterile Supply Rm (Pdtr) E - 1 NS NS EG NS * 0 *

Total NS 0

(+ - ) 0

Notes:

(1) There are no outlets in the room. Room is negative to corridor.

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 4B39 Sterile Supply Rm (Derm.) 1 11" x 11" 1.00 CD NS * 66 *

Total NS 66

Exhaust 4B39 Sterile Supply Rm (Derm.) E - 1 8" x 8" 1.00 EG NS * 0 *

Total NS 0

( - ) -66

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 4B46L / Ster. Supply Rm (Wom. Clin.) 1 14" x 14" 1.00 CD NS * 147 *

Total NS 147

Exhaust 4B46L / Ster. Supply Rm (Wom. Clin.) E - 1 8" x 8" 1.00 EG NS * 66 *

Total NS 66

( + ) 81

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 5A28 / Isolation Room 1 24" x 24" 1.00 CD NS * 140 *

Total NS 140

Exhaust 5A28 / Isolation Room E - 1 37" x 2.5" 0.44 SWEG NS * 457 1038 (1)

E - 2 13" x 13" 1.00 EG NS * 123 *

Total NS 580

( - ) 440

Notes:

(1) Register is served by negative room pressure system.

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 5A29 / Ante 1 7.5" x 7.5" 1.00 CD NS * 102 *

Total NS 102

( + ) 102

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 5A30 / Isolation Room 1 24" x 24" 1.00 CD NS * 287 *

Total NS 287

Exhaust 5A30 / Isolation Room E - 1 37" x 2.5" 0.44 SWEG NS * 697 1584 (1)

5A30 / Isolation Room E - 2 13" x 13" 1.11 SWEG NS 0 0

Total NS 697

( - ) 410

Notes:

(1) Register is served by negative room pressure system.

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 5B19 / Isolation Room 1 13.25" x 13.25" 1.00 CD NS * 109 *

2 13.25" x 13.25" 1.00 CD NS * 137 *

Total NS 246

Exhaust 5B20 / Isolation Room E - 1 37" x 2.25" 0.38 SWEG NS * 600 1578

Total NS 600 (1)

( - ) 354

Notes:

(1) Register is served by negative room pressure system

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 5B19.1 Ante 1 11.25" x 11.25" 1.00 CD NS * 67 *

Total NS 67

( + ) 67

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 5B20 / Isolation Room 1 13.25" X 13.25" 1.00 CD NS * 172 *

2 13.25" X 13.25" 1.00 CD NS * 0 * (1)

Total NS 172

Exhaust 5B20 / Isolation Room E - 1 37" X 2.25" 0.38 SWEG NS * 579 1523 (2)

Total NS 579

( - ) 407

Notes:

(1) Supply register is capped by mechanical contractor. Zero CFM reading.

(2) Register is served by negative room pressure system

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 5B20.1 Ante 1 11.25" x 11.25" 1.00 CD NS * 68 *

Total NS 68

( + ) 68

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Exhaust B1B04 / Gross Specimen Hold. Area 1 NS NS EG NS * NS *

Total NS NS

( +- ) NS

Notes:

(1) Room has no outlets.

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply B1B04A / Autopsy 1 9.5" x 9.5" 1.00 SWSG NS * 229 *

2 9.5" x 9.5" 1.00 SWSG NS * 75 *

Total NS 304

Exhaust B1B04A / Autopsy E - 1 10" x 13" 1.00 SWEG NS * 280 *

E - 2 10" x 13" 1.00 SWEG NS * 248 *

E - 3 10" x 13" 1.00 SWEG NS * 213 *

Total NS 741

( - ) 437

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply B1B05 / Soiled Lndr Rcvng and Srtng Rm S - 1 34" x 11" 2.34 SWG NS * 400 171

S - 2 34" x 11" 2.34 CD NS * 208

S - 3 26" x 8" 1.00 SWG NS 0

Total NS 608

Exhaust B1B05 / Soiled Lndr Rcvng and Srtng Rm E - 1 24" x 24" 1.00 SWEG NS * 902

Total NS 902

( - ) 294

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply B1B16 / Laundry Room-Clean Side 1 24" x 24" 1.00 CD NS * 358 *

B1B16 / Laundry Room-Clean Side 2 24" x 24" 1.00 CD NS * 358 *

B1B16 / Laundry Room-Clean Side 3 24" x 24" 1.00 CD NS * 282 *

B1B16 / Laundry Room-Clean Side 4 24" x 24" 1.00 CD NS * 270 *

B1B16 / Laundry Room-Clean Side 5 24" x 24" 1.00 CD NS * 262 *

B1B16 / Laundry Room-Clean Side 6 24" x 24" 1.00 CD NS * 397 *

B1B16 / Laundry Room-Clean Side 7 24" x 24" 1.00 CD NS * 173 *

B1B16 / Laundry Room-Clean Side 8 24" x 24" 1.00 CD NS * 161 *

B1B16 / Laundry Room-Clean Side 9 24" x 24" 1.00 CD NS * 181 *

B1B16 / Laundry Room-Clean Side 10 24" x 24" 1.00 CD NS * 0 * (1)

B1B16 / Laundry Room-Clean Side 11 24" x 24" 1.00 CD NS * 902 *

B1B16 / Laundry Room-Clean Side 12 24" x 24" 1.00 CD NS * 0 * (1)

B1B16 / Laundry Room-Clean Side 13 34" x 24" 1.00 SG NS * 58 *

B1B16 / Laundry Room-Clean Side 14 6"DIA 1.00 SG NS * 544 *

B1B16 / Laundry Room-Clean Side 15 6"DIA 1.00 SG NS * 204 *

B1B16 / Laundry Room-Clean Side 16 6"DIA 1.00 SG NS * 323 *

B1B16 / Laundry Room-Clean Side 17 6"DIA 1.00 SG NS * 275 *

B1B16 / Laundry Room-Clean Side 18 6"DIA 1.00 SG NS * 138 *

Total NS 4,886

Exhaust B1B16 / Laundry Room-Clean Side E - 1 32" x 24" 1.00 EG NS * 921 *

E - 2 32" x 24" 1.00 EG NS * 844 *

E - 3 32" x 24" 1.00 EG NS * 848 *

E - 4 32" x 24" 1.00 EG NS * 503 *

E - 5 32" x 24" 1.00 EG NS * 0 * (1)

Total NS 3,116

( + ) 1,770

Notes:

(1) Register is disconnected from the system.

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply B1B16B / Clean Laundry Storage 1 18" x 7" 1.00 SWSG NS * 88 *

B1B16B / Clean Laundry Storage 2 8" x 7" 1.00 SWSG NS * 205 *

Total 293

( + ) 293

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 2C06K / Infusion ClB14:B37inic 1 24" x 24" 1.00 CD NS * 33 *

T-STAT 2C06K / Infusion ClB14:B37inic 2 24" x 24" 1.00 CD NS * 60 *

AT 70F. 2C06K / Infusion ClB14:B37inic 3 24" x 24" 1.00 CD NS * 68 *

2C06K / Infusion ClB14:B37inic 4 24" x 24" 1.00 CD NS * 71 *

Total 232

Exhaust 2C06K / Infusion Clinic E - 1 24" x 24" 1.00 EG NS * 125 *

2C06K / Infusion Clinic E - 2 24" x 24" 1.00 EG NS * 68 *

2C06K / Infusion Clinic E - 3 24" x 24" 1.00 EG NS * 135 *

2C06K / Infusion Clinic E - 4 24" x 24" 1.00 EG NS * 148 *

Total 476 (1)

( - ) 244

Supply 2C06K / Infusion Clinic 1 24" x 24" 1.00 CD NS * 137 *

T-STAT 2C06K / Infusion Clinic 2 24" x 24" 1.00 CD NS * 254 *

AT 55F. 2C06K / Infusion Clinic 3 24" x 24" 1.00 CD NS * 303 *

2C06K / Infusion Clinic 4 24" x 24" 1.00 CD NS * 362 *

Total 1,056

Exhaust 2C06K / Infusion Clinic E - 1 24" x 24" 1.00 EG NS * 130 *

2C06K / Infusion Clinic E - 2 24" x 24" 1.00 EG NS * 78 *

2C06K / Infusion Clinic E - 3 24" x 24" 1.00 EG NS * 148 *

2C06K / Infusion Clinic E - 4 24" x 24" 1.00 EG NS * 104 *

Total 460

( + ) 596 (2)

Notes:

(1) Room is serving by VAV. Negative to the corridor: ( - )0.0003".

(2) Room is serving by VAV. Negative to the corridor: ( + )0.0088".

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 2C08E / Sterile Supply Rm (Cardiol.) 1 24" x 24" 1.00 CD NS * 31 *

Total NS 31

Exhaust 2C08E / Sterile Supply Rm (Cardiol.) E - 1 24" x 24" 1.00 EG NS * 22 *

Total NS 22

( + ) 9

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 2C15F / Sterile Supply Rm(Eye Clinic) 1 24" x 24" 1.00 CD NS * 23 *

Total NS 23

Exhaust 2C15F / Sterile Supply Rm(Eye Clinic) E - 1 7" x 7" 1.00 EG NS * 20 *

Total NS 20

( + ) 3

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply 3C10W / Sterile Supply Rm (Dental) 1 24" X 24" 1.00 CD NS * 38 *

Total NS 38

Exhaust 3C10W / Sterile Supply Rm (Dental) E - 1 7" X 7" 1.00 DO NS * 133 * (1)

Total NS 133

( - ) 95

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

(1) Supply diffuser installed instead exhaust grill

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply SOG8 / Isolation Room 1 12" X 12" 1.00 CD NS * 181 *

Total NS 181

Exhaust SOG8 / Isolation Room E - 1 18" X 18" 1.00 EG NS * 412 * (1)

Total NS 412

( - ) 231

Notes:

(1) Register is served by negative room pressure system. At time of TAB: MedAir System at high speed.

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

Readings by: A. Plyavinsh, J. Bueno

AK % Of

FACTOR CFM FPM CFM FPM Design

Supply SOG9 / Isolation Room 1 12" X 12" 1.00 CD NS * 141 *

Total NS 141

Exhaust SOG9 / Isolation Room E - 1 18" X 18" 1.00 EG NS * 548 * (1)

Total NS 548

( - ) 407

Notes:

DESIGN ACTUAL

NOTES

CFM DIFFERENTIAL

(1) Register is served by negative room pressure system. At time of TAB: MedAir System at high speed.

VA Fresno Critical Room Recertification 2025

Job No.: 25007

Date: 2/7/2025

AIR TYPE ROOM OUTLET SIZE TYPE

accounts Image accounts

(1) 3C17G Same Day Procedure Room-2:

(2) 3C17H Same Day Procedure Room-1:

(3) 3C17J PACU Post Surgical Revovery Unit:

(4) B1B-1 Emergency Department Waiting Area:

(5) SOG1A Emergency Department Exam Room SO-G COR 1A:

(6) SOG1B Emergency Department Exam Room SO-G COR 1B:

(7) SO3G Emergency Department Exam Room SO-G 3:

(8) SO3G4 Trauma (Small) B1C06:

(9) SO3G5 Trauma (Large) B1C07:

(10) SO3G7 Oberservation/Treatment B1C09:

(11) Room has 4.45 ACH with a design of 6 ACH. Insufficient supply flow. Insufficient air changes.

Room has 10.12 ACH with a design of 6 ACH. Room is positive to the corridor and is designed to be negative.

Insufficient exhaust flow.

Room has 5.94 ACH with a design of 6 ACH. Insufficient supply flow. Insufficient air changes.

SOG10 Oberservation/Treatment B1C12:

Room has 4.02 ACH with a design of 6 ACH. The room is positively pressurized to the corridor and is designed to be positive. Insufficient supply flow.

Room has 4.08 ACH with a design of 12 ACH. The room is negatively pressurized to the ER Entrance and is designed to be negative. Insufficient exhaust flow.

Room has 4.66 ACH with a design of 6 ACH. Insufficient supply flow.

Room has 2.96 ACH with a design of 6 ACH. Insufficient supply flow.

Room has 4.83 ACH with a design of 15 ACH. Insufficient supply flow.

Room has 13.86 ACH with a design of 6 ACH. Room is positive to the corridor and is designed to be negative.

Insufficient exhaust flow.

Room has 7.05 ACH with a design of 15 ACH. The room is positively pressurized to the corridor and is designed to be positive. Insufficient supply flow.

LOCATION: Fresno, CA 93703 JOB #: 25007

SYSTEM: Existing HVAC DATE: 2/7/2025

AREA SERVED: All Floors TECHNICIAN: A.P. / J. B.

Room has 12.35 ACH with a design of 15 ACH. The room is positively pressurized to the corridor and is designed to be positive. Insufficient supply flow.

357 East Arrow Highway Suite 206

San Dimas, CA 91773

(714) 637-3500

Report Summary

PROJECT: VA Fresno Critical Room Recertification 2025 accounts Image accounts

(12) SOG11 Operation/Treatment B1C13:

(13) SOG12 Operation/Treatment B1C14:

(14) SOG14 Observation/Treatment B1C22:

(15) SOG15 Obersvation/Treatment B1C23:

(16)…