About this file

36C25819B0002 0007 S02 - RFI007_rev1 - DayTank_ANSWERED - 1 page - 02132019.pdf

View the file

Other files for this federal contract opportunity

Other files attached to LB - Remove & Replace Emergency Generator - LOCATION OF PERFORMANCE IS LONG BEACH, CA 90822, newest first.
File Type Posted
36C25819B0002-0008000.docx DOCX document
36C25819B0002-0007000.docx DOCX document
36C25819B0002-0007001.pdf PDF
36C25819B0002-0006000.docx DOCX document
36C25819B0002-0006001.pdf PDF
36C25819B0002-0005000.docx DOCX document
36C25819B0002-0005001.pdf PDF
36C25819B0002-0004001.pdf PDF
36C25819B0002-0004004.pdf PDF
36C25819B0002-0004000.docx DOCX document
36C25819B0002-0004003.pdf PDF
36C25819B0002-0004002.pdf PDF
36C25819B0002-0003001.pdf PDF
36C25819B0002-0003002.pdf PDF
36C25819B0002-0003000.docx DOCX document
36C25819B0002-0002000.docx DOCX document
36C25819B0002-0002001.pdf PDF
36C25819B0002_0001.docx DOCX document
S02_-_IFB_-_TB_Pre-Construction_Testing_Requirement_-_LB_-_Remove_Replace_Emergency_Generator.docx DOCX document
36C25819B0002_1.docx DOCX document
S02_-_David_Bacon_Wage_Decision_-_General_Decision_Number_CA180033_11-02-2018_CA33_-_33_Pages.docx DOCX document
S02_-_SOLICITATION_RFI_FORM_-_LB_-_Remove_Replace_Emergency_Generator.docx DOCX document
36C25819B0002-000.docx DOCX document
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI FORM

Contractor Name: D-Square Construction

Address: 530 E 27th St., Tucson, AZ 85713

Phone/Fax: {520) 748-9371/(520) 748-9372

Send to: timothy.saffles@va.gov

RFI

(REQUEST FOR INFORMATION)

PROJECT NO.: RFI NO.:

PROJECT NAME: VA Long Beach O-B DATE REQUESTED:

Remove & Replace

Emergency

Generator

SOLICITATION NO.:

36(25819

REFERENCE:

DRAWING: SPECIFICATION

N/A SECTION:

007_rev1

12/28/18

2/12/19

N/A

Day tank

DESCRIPTION OF PROBLEM OR INFORMATION BEING REQUESTED

Clarifying Question: Is it the intent of the project to supply a new 200gallon daytank with: 1.

Duplex supply pumps and duplex controls mounted on the daytank. or 2. Duplex controls only mounted on the daytank to signal an existing duplex pump controller mounted elsewhere. or

3. Duplex controller only connecting to existing duplex pumps mounted elsewhere on the property or within the existing underground storage tank.

PROJECT MANAGER'S RESPONSE

The 200 Gallon Day Tank needs to encompass duplex supply pumps and duplex controls. Most often it will come mounted to the day tank, but it does not need to be. The duplex supply pumps and duplex controls do need to be in the same room as the generator and must be incorporated into the 200 Gallon Day Tank system according to the manufacturers specifications.

TRACKING NO.: AMENDMENT NO.:

VA PROJECT ENGINEER/MANAGER: Liam Boccia DATE: 02/13/2019