RFI FORM
Contractor Name: Johnson Danforth Address: 10298 Robb St. Denver CO 80021 Phone/Fax: 720-638-2016 Send to: timothy.saffles@va.gov
RFI
(REQUEST FOR INFORMATION)
PROJECT NO.:
600-19-104
RFI NO.:
PROJECT NAME:
Remove & Replace Emergency Generator
DATE REQUESTED:
2/6/19
SOLICITATION NO.:
36C25819B0002
REFERENCE:
DRAWING:
SPECIFICATION
SECTION:
DESCRIPTION OF PROBLEM OR INFORMATION BEING REQUESTED
Do we need to run new cable for the remote annunciator?
If so, then where exactly is room 18C in Building 5?
PROJECT MANAGER’S RESPONSE
Yes, as the SOW indicates: Contractor will provide and install all conduit, boxes, fittings, straps, connectors, wire, and all other parts and materials needed to facilitate the attachment of the New Generator to the Remote Annunciator Module in accordance with
NFPA 70: National Electric Code guidelines. All penetrations containing conduit will be fire caulked and any damages incurred during installation shall be repaired by the contractor at no cost to the VA. The conduit run will be approximately 320’ from the Generator to Building-
5 Room-18C, Boiler Shop. Room 18C is in the basement of Building 5 Boiler Plant.
TRACKING NO.: AMENDMENT NO.:
VA PROJECT ENGINEER/MANAGER: Liam Boccia
DATE: 02/06/2019