About this file

36C25819B0002 0004 S02 - RFI 014_r1.pdf

View the file

Other files for this federal contract opportunity

Other files attached to LB - Remove & Replace Emergency Generator - LOCATION OF PERFORMANCE IS LONG BEACH, CA 90822, newest first.
File Type Posted
36C25819B0002-0008000.docx DOCX document
36C25819B0002-0007002.pdf PDF
36C25819B0002-0007001.pdf PDF
36C25819B0002-0007000.docx DOCX document
36C25819B0002-0006000.docx DOCX document
36C25819B0002-0006001.pdf PDF
36C25819B0002-0005000.docx DOCX document
36C25819B0002-0005001.pdf PDF
36C25819B0002-0004001.pdf PDF
36C25819B0002-0004000.docx DOCX document
36C25819B0002-0004003.pdf PDF
36C25819B0002-0004002.pdf PDF
36C25819B0002-0003000.docx DOCX document
36C25819B0002-0003001.pdf PDF
36C25819B0002-0003002.pdf PDF
36C25819B0002-0002000.docx DOCX document
36C25819B0002-0002001.pdf PDF
36C25819B0002_0001.docx DOCX document
S02_-_SOLICITATION_RFI_FORM_-_LB_-_Remove_Replace_Emergency_Generator.docx DOCX document
S02_-_IFB_-_TB_Pre-Construction_Testing_Requirement_-_LB_-_Remove_Replace_Emergency_Generator.docx DOCX document
36C25819B0002_1.docx DOCX document
S02_-_David_Bacon_Wage_Decision_-_General_Decision_Number_CA180033_11-02-2018_CA33_-_33_Pages.docx DOCX document
36C25819B0002-000.docx DOCX document
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI FORM

Contractor Name: D-Square Construction Address: 530 E 27th St., Tucson, AZ 85713 Phone/Fax: (520) 748-9371/(520) 748-9372 Send to: timothy.saffles@va.gov

RFI

(REQUEST FOR INFORMATION)

PROJECT NO.:

RFI NO.:

PROJECT NAME:

VA Long Beach D-B Remove & Replace

Emergency Generator

DATE REQUESTED:

12/28/18

SOLICITATION NO.:

36C25819

REFERENCE: N/A

DRAWING:

N/A

SPECIFICATION

SECTION:

Testing or special studies

DESCRIPTION OF PROBLEM OR INFORMATION BEING REQUESTED

Will the VA require any testing or special studies not specified in the RFP? Specifically we don’t see where the RFP is requiring arc flash studies, coordination study, power load study, etc. If it is established after award and during the design phase that the size and ratings of the generator specified and the current electrical system is not sufficient or meeting current/updated code requirements, will the size increase be handled as a changed condition, or is the contractor to assume the risk for the size of the generator in their bid? Please verify that currently the generator provides critical care transfer but not life safety transfer requirements and that rating can remain.

PROJECT MANAGER’S RESPONSE

An Arc Flash Study will need to be conducted for the ATS and the Disconnect in accordance with NFPA 70E: Standard for Electrical Safety in the Workplace and a completed Arc Flash

Label must be placed on the equipment and contain all criteria required by the guidelines.

Documentation of the study must be provided to the COR upon completion. The 600kW rating is sufficient and the current generator provides critical care transfer.

TRACKING NO.: AMENDMENT NO.: