36C24618R0839-011.pdf
PDF 6 MB Posted
- Attached to
- Project 659-16-103, Replace Campus Fire Alarm System Federal contract opportunity
- Solicitation number
- 36C24618R0839
About this file
36C24618R0839 CONTRACT ATTACHMENT A - DRAWINGS FILE 10 - 10-Sheets_FA144-FA601.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24618R0839-0003001.pdf | ||
| 36C24618R0839-0003000.docx | DOCX document | |
| 36C24618R0839-0003002.pdf | ||
| 36C24618R0839-0002000.docx | DOCX document | |
| 36C24618R0839-0002001.pdf | ||
| 36C24618R0839-004.pdf | ||
| 36C24618R0839-013.docx | DOCX document | |
| 36C24618R0839-008.pdf | ||
| 36C24618R0839-012.pdf | ||
| 36C24618R0839-009.pdf | ||
| 36C24618R0839-001.docx | DOCX document | |
| 36C24618R0839-014.pdf | ||
| 36C24618R0839-005.pdf | ||
| 36C24618R0839-003.pdf | ||
| 36C24618R0839-010.pdf | ||
| 36C24618R0839-007.pdf | ||
| 36C24618R0839-002.pdf | ||
| 36C24618R0839-006.pdf | ||
| 36C24618R0839-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Stair
Stair
Resident
2C128
Resident
2C130
Bath
2C130A
Bath
2C128A
Resident
2C131
Bath
2C131A
Bath
2C127A
Resident
2C127
Bath
2C132A
Bariatric
2C132
Resident
2C126
Bath
2C126A Bath
2C125A
Resident
2C125 Resident
2C124
Bath
2C124A
Living Room
2C121
Meds
2C122
Soiled
2C134
Telecom
2C135
Elec
2C136
Office/ Consult
2C118
Laundry
2C119
Resident
2C117
Bath
2C117A
Break
2C103
Staff Tlt
2C102
Equip
2C104
Passage
2C105HK
2C107
Clean
2C106 Bariatric
2C108
Bath
2C108A
Resident
2C116
Bath
2C116A Bath
2C115A
Resident
2C115 Resident
2C114
Bath
2C114A
Bath
2C109A
Resident
2C109 Resident
2C110
Bath
2C110A
WC/ Stretcher
2C111
WC/ Stretcher
2B155
Resident
2C112 Resident
2C113
Bath
2C113A Bath
2C112A
Formal Dining
Room
2A102 Chute
Vestibule
2A104
Vending
2A105
MATTRESS
STORAGE
2A101
Elec
2A100
Mech
2C133 Pantry
2C100A
Kitchen
2C100
Lounge
2B154
Dining Room
2C120 Nurse Work
2C123
Resident Kitchen
2C101
Resident
2B128
Bath
2B128A
Sitting Area
2B131Living Room
2B132
Meds
2B130 Nurse Work Area
2B129
Soiled
2B105
Elec
2B104 Tele
2B103 Private Dining
2B101
Office/ Consult
2B100
Kichen
2B152 Dining Room
2B150
Pantry
2B151 Resident Kitchen
2B149
Laundry
2B134 Nurse Office
2B133
Resident
2B135
Bath
2B135A
Break
2B148
Equip
2B145
Passage
2B146
Staff Toilet
2B147
Resident
2B136
Bath
2B136A
HK
2B143 Clean
2B144
Resident
2B137 Bath
2B137A
Resident
2B138
Bath
2B138A
Resident
2B139
Bath
2B139A Resident
2B140
Bath
2B140A
Resident
2B142
Bath
2B142A
Resident
2B141
Corridor
C2-19
Bath
2B141A
Room
2B153
Conference Room
2A126B
Conference Room
2A126A
Office
2A121
Toilet
2A122 Toilet
2A123
Office Suite
2A103
GEN STORAGE
2A126C
Tele
2A128
Corridor
C2-16A
Linen
2B146A
Linen
2C105A
Bridge
2E102
Corridor
C2-13
Elevator Lobby
C2-1
Corridor
C2-25
Corridor
C2-26 Corridor
C2-22
Corridor
C2-16
Corridor
C2-20
Elevator
P20
Elevator
P21
Elevator
S23
OFFICE
2A126
UP DN
Stair
Closet
2A101A
Closet
2A102A
Janitor
2A103B
Resident
2D125Bath
2D125A
Soiled
2D134
Elec
2D135 Tele
2D136
Private Dining
2D137Office/
Consult
2D138
Kitchen
2D100
Pantry
2D100A
Meds
2D123
Living Room
2D122
Office/
Consult
2D121 Laundry
2D120
Break
2D103
Equip
2D104
Passage
2D105
Staff Tlt
2D103A Bath
2D119A Resident
2D119
Resident
2D118Bath
2D118A
Resident
2D117 Bath
2D117A
HK
2D107
Clean
2D106
Bariatric
2D108 Bath
2D108A
Resident
2D116 Bath
2D116A Bath
2D109AResident
2D109
Resident
2D110
Bath
2D110A
Resident
2D115 Bath
2D115A
Resident
2D114 Bath
2D114A WC/ Stretcher
2D111
Storage
2C129
Nurse Work
2D124
Sitting Room
2D139
Dining Room
2D101 Resident
Kitchen
2D102
Linen
2D105A
Lounge
2D112
Corridor
C2-31
Corridor
C2-28
Elevator
P24
Vestibule
2D113
FEC-1
MATCHLINE FA144/FA145
MATCHLINE FA144/FA145
MATCHLINE FA144/FA145
MATCHLINE FA144/FA145
HEAT DETECTOR (FIXED)
F F F F F F F F F F
F F
F F F F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F F S
F
F
F
F S
KHFS
KHFS
FAAP
F
HEAT DETECTOR (FIXED)
F
F
F
F
F
F
F
F
F
F
F
F
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S F
S
F S
F S
F S
F S
F S
F S F
S
F S
F S
F S
F S F
S
F S
F S
F S
F S
FS
FS
FS
FS
FS
FS
FS
FS
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F
FS
F S
F S
F S
F S
NACP
DAA
1. AATP REPLACEMENT PANELS SHALL BE CIRCUITED
TO THE SAME CIRCUIT AS THE AATPs.
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FA144
BLDG 42 SECOND FLOOR EAST
1 BLDG 42 SECOND FLOOR EAST
3/32"= 1'
HEALTH CARE OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
ELECTRICAL POWER NOTES
1. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
2. WHERE NEW DEVICES ARE SHOWN, LOCATE THE
NEAREST JUNCTION BOX WITH THE SLC, NAC,
OR SPEAKER CIRCUIT AND INTERCEPT AND
EXTEND CIRCUIT TO THE NEW DEVICE
LOCATION.
3. VERIFY ALL CEILING TYPES BEFORE WORK.
REPLACE ANY CEILING DAMAGE AND PAINT TO
MATCH EXISTING.
4. ALL EXISTING DEVICES TO REMAIN. PROVIDE
NEW DEVICES AS SHOWN. CONNECT OLD
CIRCUITS AND NEW CIRCUITS TO NEW FACP.
DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8
6/25/2018
Closet
2A120 Office
2A119
Office
2A118
Office
2A117
Office
2A116
Stair
GM Breakroom
2A106
Supply Closet
2A111 Office
2A112
Office
2A113
Office
2A114
Office
2A115
Copy Room
2A110
Men's Locker/
Toilet
2A109
Women's Locker/
Toilet
2A107
Room
2A108
Vending
2A105
Resident
2B109
Resident
2B110
Bath
2B109A
Bath
2B110A
Elec
2B111 Mechanical
2B112Corridor
C2-42
Equip
2B113
Equip
2B114
Bath
2B115A
Corridor
C2-44Bath
2B122A Bath
2B121A
Bath
2B120A Bath
2B119A
Bath
2B118A
Bath
2B117A
Bath
2B116A
Lounge
2B123 Corridor
C2-43
Corridor
C2-17 Storage
2B107A Snoezelen Room
2B107
Corridor
C2-41
Mechanical
2B106
Bath
2B124A
Resident
2B124
Resident
2B125 Bath
2B125A
Resident
2B126
Bath
2B126A
Bath
2B127A
Resident
2B127
Resident
2B128
Bath
2B128A
Meds
2B130 Nurse Work Area
2B129
Soiled
2B105
Elec
2B104 Tele
2B103 Private Dining
2B101
Office/ Consult
2B100
Mechanical
2A124
Office
2A121
Toilet
2A122 Toilet
2A123
Elevator Lobby
C2-1
Stair
Stair
Resident
2B120
Resident
2B121
Resident
2B122 Resident
2B115
Resident
2B116
Resident
2B117
Resident
2B119
Resident
2B118
Corridor
C2-7
Corridor
C2-8
Corridor
C2-9
Waiting
C2-5
Secretary
C2-6
Corridor
C2-2
Secretary
C2-4 Lobby
C2-3
Elevator
P20
Elevator
P21
DN
Stair
Bariatric
2D132
Bath
2D132A
Bath
2D131A Resident
2D131
Resident
2D130 Bath
2D130A
Resident
2D129Bath
2D129A
Resident
2D128Bath
2D128A
Resident
2D127 Bath
2D127A
Bath
2D126A Resident
2D126
Resident
2D125Bath
2D125A
Mechanical
2D133
Soiled
2D134
Elec
2D135 Tele
2D136
Private Dining
2D137Office/
Consult
2D138
Meds
2D123
2D122
Nurse Work
2D124
Corridor
C2-32
FEC-1
MATCHLINE FA144/FA145
MATCHLINE FA144/FA145
MATCHLINE FA144/FA145
MATCHLINE FA144/FA145
F
F
F
F
F
F
F
F
F
F
F F
F
F
F
F
F
F
F
F S
F S
F S
F
F
NACP
NACP
FAAP
F
F
F
F
F
F
F
F
F
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
FS
FS
FS
F S
F S
F S
F S
FS
FS
FS
FS
FS
FS
FS
FS
FS
FS
F S
F S
FS
FS
F S
F S
F S
F S
F S
F S
F S
F S
F S F
S F S
FS
FF
F
F S
F S
F
FS
F S
FA122
TO B
LD
G 6
NACP
DAA
1. AATP REPLACEMENT PANELS SHALL BE CIRCUITED
TO THE SAME CIRCUIT AS THE AATPs.
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FA145
BLDG 42 SECOND FLOOR WEST
1 BLDG 42 SECOND FLOOR WEST
3/32"= 1'
HEALTH CARE OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
#KEYED NOTES
ELECTRICAL POWER NOTES
1. REPLACE AATP (NOTIFIER XPIQ) WITH A NACP
AND DAA. RECONFIGURE NAC AND SPEAKER
CIRCUITS AS REQUIRED.
1. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
2. WHERE NEW DEVICES ARE SHOWN, LOCATE THE
NEAREST JUNCTION BOX WITH THE SLC, NAC,
OR SPEAKER CIRCUIT AND INTERCEPT AND
EXTEND CIRCUIT TO THE NEW DEVICE
LOCATION.
3. VERIFY ALL CEILING TYPES BEFORE WORK.
REPLACE ANY CEILING DAMAGE AND PAINT TO
MATCH EXISTING.
4. ALL EXISTING DEVICES TO REMAIN. PROVIDE
NEW DEVICES AS SHOWN. CONNECT OLD
CIRCUITS AND NEW CIRCUITS TO NEW FACP.
PLAY ROOM
MEDITATION
GAME ROOM
FAMILY ROOM
EQUIPEMENT
BREAK RM
PHY OFF
NP OFF
COORD OFF
NUR MGR OFF
SW OFF
FLEX OFF
WELCOME CTR.
DINING ROOM
VESTIBULE
LOBBY
KITCHEN
FAMILY KITCHEN
SOILED UTILITY
HK
FAM SUITE
116A
FAM BATH
NURSE
CORR
CLEAN SUP
TELECOM
MEDS
MECHANICAL
EM ELECT
NORM ELEC
CHAPLAIN
EQUIP. STORAGE
CORR
12B
BATH
QUIET RM
PASSAGE
66 146
LAUNDRY
NURSE
PASSAGE
BATHTIQUE
TLT
TLT
TLT
PASSAGE
TLT
TLT
OFFICE
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
11B
BATH
10B
BATH
9B
BATH
8B
BATH
7B
BATH
ELECTRICAL CLT
LIVING ROOM
783 104
CORR
NURSE
CORR
CORR
RESIDENT ROOM
6B
BATH
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
5B
BATH
4B
BATH
3B
BATH
2B
BATH
1B
BATH
PASS
CORR
MECHANICAL
KENNEL
SECURITY CLOSET
115A
LINENS
Corr
124 BUILDING 42
FACP
NACP
TO BLDG 42FIBER
PLAY ROOM
MEDITATION
GAME ROOM
FAMILY ROOM
EQUIPEMENT
BREAK RM
PHY OFF
NP OFF
COORD OFF
NUR MGR OFF
SW OFF
FLEX OFF
WELCOME CTR.
DINING ROOM
VESTIBULE
LOBBY
KITCHEN
FAMILY KITCHEN
SOILED UTILITY
HK
FAM SUITE
116A
FAM BATH
NURSE
CORR
CLEAN SUP
TELECOM
MEDS
MECHANICAL
EM ELECT
NORM ELEC
CHAPLAIN
EQUIP. STORAGE
CORR
12B
BATH
QUIET RM
PASSAGE
66 146
LAUNDRY
NURSE
PASSAGE
BATHTIQUE
TLT
TLT
TLT
PASSAGE
TLT
TLT
OFFICE
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
11B
BATH
10B
BATH
9B
BATH
8B
BATH
7B
BATH
ELECTRICAL CLT
LIVING ROOM
783 104
CORR
NURSE
CORR
CORR
RESIDENT ROOM
6B
BATH
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
RESIDENT ROOM
5B
BATH
4B
BATH
3B
BATH
2B
BATH
1B
BATH
PASS
CORR
MECHANICAL
KENNEL
SECURITY CLOSET
115A
LINENS
Corr
124 BUILDING 42
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F F
F
FF
F
F
F
F
FA
C
P
FA
A
P
FAAP
FAAP
Fco
Fco
Fco
N A
C P
KHFS
FS
FS
FS
FS
FS
FS
FS
FS
FS
FS
FS
FS
FS
FS
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
FS
F S
F S
F S
F S
FS
FS
F
F
F
F
F
F
FS
1. WHERE NEW DEVICES ARE SHOWN, LOCATE THE
NEAREST JUNCTION BOX WITH THE SLC, NAC, OR
SPEAKER CIRCUIT AND INTERCEPT AND EXTEND
CIRCUIT TO THE NEW DEVICE LOCATION.
2. PROVIDE NEW FIBER PATCH PANEL AND
CONNECTIONS FOR FACP.
3. VERIFY ALL CEILING TYPES BEFORE WORK. REPLACE
ANY CEILING DAMAGE AND PAINT TO MATCH
EXISTING.
4. ALL EXISTING DEVICES TO REMAIN. PROVIDE NEW
DEVICES AS SHOWN. CONNECT OLD CIRCUITS AND
NEW CIRCUITS TO NEW FACP.
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FA146
BLDG 43
1 BLDG 43
3/32"= 1'
HEALTH CARE OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
#KEYED NOTES
1. PROVIDE FIBER BOX, PATCH PANEL, PATCH
CORDS AND RELATED MATERIAL. SEE DETAILS
ON FA501 FOR MORE INFO.
2. EXTEND ALL CKT TO NEW NACP & FACP.
BUILDING FLOOR
BUILDING WALL
HDPE CONDUIT
BY DIRECTIONAL BORE
PULL BACK CONDUIT
DIRECTLY FROM
CRAWLSPACE
SUPPORT ARMORED FIBER TO
STRUCTURE EVERY 54" MIN
(TIE SECURELY - DO NOT LAY LOOSE)
CONDUIT SHALL BE SUPPORTED TO
STRUCTURE IN TWO PLACES MINIMUM
ARMORED
FIBER CABLE
FLOOR JOISTS/FRAMING
(TYP)
WHERE CRAWLSPACE BECOMES
INACCESSIBLE TO INSTALL
SUPPORTS, ARMORED FIBER CABLE
SHALL BE FISHED ALONG GRADE GRADE
PROVIDE SUFFICIENT SLACK WHILE PULLING TO
PREVENT EXCEEDING MINIMUM CABLE IN-USE RADIUS
CABLE
SUPPORT (TYP)
FIBER CRAWLSPACE INSTALLATION NOTES
1. ARMORED FIBER CABLE SHALL BE INSTALLED IN MIN
1-1/2" CONDUIT OR PER 2014 NEC 350.30.
2. WHERE NOT INSTALLED IN CONDUIT, ARMORED FIBER
CABLE SHALL BE SUPPORTED EVERY 54" MINIMUM OR
SHALL BE CONTINUOUSLY SUPPORTED BY UNISTRUT
SPANNING STRUCTURAL MEMBERS.
3. WHEN PASSING ARMORED FIBER CABLE THROUGH
INACCESSIBLE SPACES, CABLE MAY BE FISHED ALONG
GROUND.
PROVIDE FIRE-RATED CONDUIT PENETRATION
THROUGH FLOOR OR WALL. WHERE EXPOSED,
ARMORED FIBER CABLE SHALL CONTINUE IN MIN
1-1/2" CONDUIT TO DESTINATION
POLYMER CONCRETE
UNDERGROUND ENCLOSURE
(HAND HOLE)
6" MIN
LID LABELED 'SIGNAL'
PVC OR HDPE CONDUIT
CONNECTOR
RIGID PVC CONDUIT ELBOW (MIN RADIUS
PER NEC OR MINIMUM CABLE INSTALLATION
BEND RADIUS, WHICHEVER IS GREATER)
PROVIDE 5% GRADE
MIN 36" ON ALL SIDES
4" MIN
6" MIN
COMPACTED BACKFILL
#5-7 STONE
STUB UP MIN 2" ABOVE GRAVEL.
SEAL WITH NON-HARDENING DUCT SEAL TO
PREVENT GRAVEL FROM ENTERING CONDUIT.
ARMORED FIBER
MC CABLE CONNECTOR
NIPPLE TO FIRE
ALARM EQUIPMENT
FIRE ALARM EQUIPMENT
DOUBLE-DOOR WALL MOUNT
FIBER OPTIC PATCH PANEL,
PANDUIT OPTICOM FWME4 OR
EQUAL. FACTORY-PAINTED RED.
PROVIDE LOCK; KEY TO FIRE
ALARM PANEL KEY. FIBER PATCH CORDS
ALL STRANDS SHALL BE
TERMINATED ON THE
FIBER COUPLERS IN THE
FIBER PATCH PANEL
CONNECTION TO FIBER CARD
PROVIDE ADDITIONAL PATCH
CORDS TO CONNECT
ADDITIONAL CARDS.
LOOP 48" MIN.
TIE OR CLIP TO PREVENT UNWINDING.
DO NOT REMOVE OUTER JACKET UNTIL
AFTER WINDING.
NOTES:
1. ALL CABLES SHALL BE NEATLY DRESSED.
2. EACH FIBER-CONNECTED EQUIPMENT LOCATION
SHALL BE PROVIDED WITH A WALL-MOUNTED PATCH
PANEL. EXISTING PANELS RECEIVING NEW FIBER
CONNECTION SHALL BE PROVIDED WITH A NEW
PATCH PANEL.
3. WHERE FIBER-CONNECTED FIRE ALARM EQUIPMENT
IS SEPARATED BY GREATER THAN 6', A SEPARATE
PATCH PANEL AND TWO SEGMENTS OF ARMOR
FIBER SHALL BE PROVIDED.
WHERE EXPOSED, ARMORED FIBER
SHALL BE ROUTED IN CONDUIT
PROVIDE LOOP PRIOR TO
EACH TERMINATION
FASTEN LOOP SECURELY
ARMORED FIBER SHALL EXIT CONDUIT
PRIOR TO CONNECTION TO CABINET
(EXPOSED 6" MAX)
WHERE INSTALLED ABOVE CEILING,
ARMORED FIBER MAY BE WITHOUT CONDUIT.
SUPPORT PER 2014 NEC 350.30
LOCATE LOOP ABOVE CEILING OR
BELOW FLOOR (IN CRAWLSPACE)
WHERE PRACTICABLE.
LOCATE LOOP ABOVE CEILING OR
BELOW FLOOR (IN CRAWLSPACE)
WHERE PRACTICABLE.
CEILING
FLOOR
FIBER PATCH PANEL (TYP)
FIRE ALARM EQUIPMENT (TYP)
ARMORED FIBER MAY
EXIT CONDUIT AT
MINIMUM DISTANCE
REQUIRED TO SATISFY
IN-USE BEND RADIUS
CONTINUE TO NEXT
FIRE ALARM EQUIPMENT
CONTINUE TO NEXT
FIRE ALARM EQUIPMENT
CEILING
FLOOR
WHERE ARMORED FIBER
MUST BE EXPOSED IN
ACCESSIBLE AREA,
SECURELY SUPPORT
EVERY 6" MIN
UNDER NO CIRCUMSTANCES SHALL
ARMORED FIBER RISE THROUGH
FLOOR WITHOUT CONDUIT.
1. PROVIDE SLACK LOOPS ACCORDING TO THE FOLLOWING:
1.1. MAINTAIN MANUFACTURER'S RECOMMENDED
MINIMUM IN-USE BEND RADIUS FOR ALL LOOPS
AND TURNS INTO EQUIPMENT.
1.2. EACH LOOP SHALL BE TIED AND SUPPORTED
SECURELY. SUPPORTS AND TIES IN UNDERGROUND
ENCLOSURES SHALL BE NON-CORROSIVE.
1.3. LOOPS SHALL BE CONCEALED OR OUT-OF-REACH
WHERE PRACTICABLE.
1.4. FOR EACH SEGMENT OF ARMORED FIBER RUN,
PROVIDE 5% OF THE LENGTH OF THE RUN IN LOOPS
(5' LOOP FOR EVERY 100' RUN), WITH MIN 10' LOOP
PRIOR TO EACH TERMINATION, WHICHEVER IS
GREATER. LOOPS EVERY 500' MIN. PROVIDE
ADDITIONAL BOXES IF REQUIRED.SUBMIT
PROPOSED LOOP LOCATIONS AND LENGTHS.
2. UNLESS OTHERWISE NOTED ALL ABOVE-GROUND
CONDUIT, BOXES, AND COVERS SHALL BE RED. EXISTING
CONDUIT SHALL BE USED IN-PLACE, BUT THEY SHALL BE
PAINTED RED. (REMOVED CONDUIT SHALL NOT BE
RE-INSTALLED.)
3. ARMORED FIBER OUTER JACKET SHALL BE RED.
4. INSTALLATION BY LOCATION SHALL BE AS FOLLOWS:
4.1. ABOVE CEILINGS:
4.1.1. ARMORED FIBER SHALL BE INSTALLED IN 1-1/2"
CONDUIT OR INSTALLED PER 2014 NEC 350.30.
4.1.2. WHERE INSTALLED PER 2014 NEC 350.30,
ARMORED CABLE SHALL BE SECURELY
SUPPORTED TO STRUCTURE OR
CONSTRUCTED SUPPORT. ARMORED FIBER
SHALL NOT BE SUPPORTED BY PIPING,
CONDUIT, OR DUCT AND SHALL NOT BE LAID
ON CEILING TILE.
4.2. OPEN AND EXPOSED CEILINGS:
4.2.1. ARMORED FIBER SHALL BE INSTALLED IN 1-1/2"
CONDUIT.
4.2.2. IN FINISHED AREAS, CONDUIT AND BOXES
SHALL BE PAINTED TO MATCH CEILING.
4.2.3. IN INDUSTRIAL TYPE AND UNFINISHED AREAS
(SUCH AS MECHANICAL ROOMS, ELECTRICAL
ROOMS, AND TELCO ROOMS.) CONDUIT,
BOXES, AND COVERS SHALL BE RED.
4.3. EXISTING RACEWAYS:
4.3.1. WHERE INSTALLED IN EXISTING RACEWAYS
SHARED BY OTHER SYSTEMS, THE RACEWAY
SHALL NOT BE PAINTED RED.
4.3.2. AT EACH PULL POINT, AN EMBOSSED OR
ENGRAVED METAL IDENTIFICATION TAG WHICH
READS "FIRE ALARM" SHALL BE TIED TO THE
FIRE ALARM FIBER CABLE.
4.4. NEW UNDERGROUND RACEWAYS:
4.4.1. SHALL BE BY DIRECTIONAL BORE OR OTHER
APPROVED MEANS. HAND HOLES SHALL BE
PROVIDED AS REQUIRED TO ENSURE PULLING
TENSION DOES NOT EXCEED THAT
RECOMMENDED BY THE MANUFACTURER. SEE
HAND HOLE DETAIL.
4.4.2. CONDUIT SIZE AND QUANTITY SHALL BE AS
INDICATED ON SITE PLAN.
4.4.3. IN EACH MAN HOLE OR HAND HOLE, USE
NON-CORROSIVE WIRE TO TIE EMBOSSED OR
ENGRAVED NON-CORROSIVE METAL TAG TO
ARMORED FIBER. FOR MAN HOLES, PROVIDE
TWO TAGS PER FIBER SEGMENT, LOCATED AT
EACH CONDUIT ENTRY. FOR HAND HOLES,
PROVIDE ONE TAG.
4.4.4. WHERE BORING INTO CRAWLSPACE, SEE
CRAWLSPACE INSTALLATION DETAIL.
4.5. CRAWLSPACES:
4.5.1. SEE CRAWLSPACE INSTALLATION DETAIL.
5. IN ALL CASES WHERE FIBER IS INSTALLED BELOW 8' AFF
AND EXPOSED, FIBER SHALL BE INSTALLED IN CONDUIT.
6. WHERE TWO SEGMENTS OF FIBER CABLE FOLLOW THE
SAME ROUTE THROUGH A BUILDING OR TUNNEL, THEY
SHALL BE PHYSICALLY SEPARATED BY 36" MIN. WHERE
36" IS NOT POSSIBLE, MAINTAIN AS MUCH PHYSICAL
SEPARATION AS POSSIBLE.
7. SUBMIT FIBER ROUTE AND RACEWAY TYPE AND COLOR
FOR EACH AREA.
8. ALL FIBER CABLING ROUTED THROUGH WALLS OR
FLOORS SHALL BE PROVIDED WITH A CONDUIT SLEEVE.
9. PROVIDE FIRE STOPPING FOR ALL SLEEVES.
10. PROVIDE 25' FIBER LOOP EVERY 400'.
FIBER INSTALLATION NOTES
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
1 ARMORED FIBER TYPICAL INSTALLATION
NTS
FA-501
DETAILS
2 PATCH PANEL INSTALLATION
NTS4 TYPICAL CRAWLSPACE ARMORED FIBER INSTALLATION
NTS
3 TYPICAL HAND HOLE INSTALLATION
NTS
TO ADDITIONAL
SPRINKLER DEVICES
TO ADDITIONAL
INITIATING
DEVICES
TO SMOKE DAMPERS
NEW
FIRE ALARM
CONTROL
PANEL (FACP)
DACT
SPRINKLER FLOW AND
TAMPER SWITCH DEVICES
TO ADDITIONAL FIRE
ALARM SPEAKERS
CONTROL RELAY
FOR AUTO DOORS
(TYPICAL)
FIRE ALARM RISER NOTES
1. FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH ACCESS CONTROL SYSTEM TO
ALLOW EGRESS DURING ALARM CONDITIONS. COORDINATE BETWEEN ACCESS CONTROL
SYSTEM AND FIRE ALARM SYSTEM MANUFACTURERS.
2. ALL FIRE ALARM WIRING SHALL BE IN FACTORY PAINTED RED CONDUIT.
3. ALL WIRING SHALL BE AS RECOMMENDED BY MANUFACTURER.
4. PROVIDE SEPARATE OUTPUT SIGNALS TO AIR HANDLER UNIT CONTROLLER FOR
INDIVIDUAL UNIT SHUT-DOWN.
5. PROVIDE ZONE ADAPTER MODULES TO CONNECT NON-ADDRESSABLE DEVICES SUCH AS
FLOW AND TAMPER SWITCHES, DOOR HOLD-OPEN DEVICES, AND CONTROL SIGNALS.
6. PROVIDE POWER SUPPLY AND/OR NAC (NOTIFICATION APPLIANCE CIRCUIT) PANEL AS
REQUIRED FOR ADDITIONAL DEVICES.
7. PROVIDE POWER AMPLIFIERS FOR ALL SPEAKERS.
8. THE NEW FIRE ALARM SYSTEM SHALL MATCH THE EXISTING NOTIFIER FIRE ALARM
SYSTEM, FUNCTIONS, OPERATIONS, AND PROGRAMMING.
9. PROVIDE ADDRESSABLE RELAY MODULES FOR:
A. ELEVATOR PRIMARY RECALL
B. ELEVATOR ALTERNATE RECALL
C. IN CAB NOTIFICATIONS
10. PROVIDE ADDRESSABLE CONTROL MODULES FOR:
A. ELEVATOR EMERGENCY SHUNT TRIP
11. PROVIDE ADDRESSABLE INTERFACE MODULES FOR:
A. ELEVATOR EMERGENCY SHUNT TRIP POWER SUPERVISION
SECURITY
SYSTEM
INTERCONNECT
FIRE ALARM
SYSTEM REMOTE
ANNUNCIATOR NEW
FIRE
ALARM
PANEL
NAC
PANEL
TO
ADDITIONAL
FIRE
ALARM
DEVICES
TO ADDITIONAL
INDICATING
APPLIANCES
TO ADDITIONAL DOOR
HOLDER DEVICES
EPR
TO ADDITIONAL
ELEVATOR RECALLS
F S
F S
F S
FIBER
ELEVATOR RECALL DEVICES
F S
F
NETWORK
COMMAND
CONSOLE
KITCHEN HOOD
F
EPR
12. PROVIDE COPPER BUILDING ENTRANCE PROTECTION FOR ALL CABLING ENTERING AND
EXISTING THE BUILDING PER MANUFACTURERS RECOMMENDATION.
EXISTING
FACP
NEW FB
FIBER
FIBER BOX
FACP-18
17C 17B 17A
FACP-21A
21B
FACP-11A
11B
11C
FACP-14E
14W
SLC-LOOP,
NAC CIRCUIT, AND/OR
SPEAKER CIRCUIT
(TYP)
FACP-21
FACP-05
NACP-31
NACP
NACP
EXISTING FACP
NEW
FIBER BOX
TO EXISTING
DEVICE
TO EXISTING
DEVICE
NEW 12
STRAND
FIBER
FANCC-04
FACP-13
FACP-04 FACP-19
FACP-01
FANA-12
FACP-14E
FACP-02
FACP-03
FACP-09
FACP-20
FACP-05
FACP-06
FACP-42 FACP-43FACP-07FACP-18 FANA-18
FACP-15
FACP-11A
FACP-11
FACP-08
FACP-21AFANA-21
FACP-21
NOTES:
1. EACH LINE REPRESENTS 12-STRAND INDOOR/OUTDOOR ARMORED FIBER-OPTIC CABLING.
TWO STRANDS ARE FOR CONNECTION TO THE FIRE ALARM EQUIPMENT, 10 ARE SPARE.
2. RACEWAY TYPE AND RUN DISTANCES PRESENTED HERE ARE APPROXIMATE AND FOR
REFERENCE ONLY. CONTRACTOR SHALL DETERMINE EXACT ROUTING, RACEWAY TYPE,
AND INSTALLATION METHODS REQUIRED FOR ALL FIBER-OPTIC CABLING.
3. SEE SITE PLAN AND BUILDING PLANS FOR ROUTING.
4. NO ALTERATION TO LOOP ARRANGEMENT IS PERMITTED WITHOUT PRIOR APPROVAL BY
THE ENGINEER AND THE VA.
5. SEE DETAILS ON FA501 FOR FIBER BOXES, PATCH PANELS & SELECTED MATERIAL FOR
EACH FIRE ALARM PANEL.
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FA-601
FIBER INTERCONNECTION DIAGRAM
1 FIRE ALARM TYPICAL RISER DIAGRAM
NTS
3 COPPER INTERCONNECTION DIAGRAM (NACP)
NTS
5 EXISTING FIRE ALARM TYPICAL RISER
NTS
MATRIX NOTES:
1. NEW EQUIPMENT = N
2. EXISTING TO REMAIN = E
3. NOTE A: FED FROM BLDG 5
4. NOTE B= FED FROM BLDG 11A
5. NOTE C= FED FROM BLDG 14E
6. NOTE D= FED FROM BLDG 17
7. NOTE E1= FED FROM BLDG 18
8. NOTE F= FED FROM BLDG 21A
9. NOTE G= NEW FIBER CABLES,
PATCH PANELS, FIBER BOXES,
PATCH CORDS, TERMINATIONS,
CONNECTION & TESTING.
4 BUILDING-CAMPUS ALARM MATRIX
NTS
2 FIBER INTERCONNECTION DIAGRAM
NTS
6 FIRE ALARM MATRIX
NTS
| 15-447-FA143 B42F1 East, West-FA143.pdf |
| Sheets and Views |
| FA143 |
| 15-447-FA601 FIBER INTERCONNECTION-FA601.pdf |
| Sheets and Views |
| FA601 |
| 15-447-FA501 DETAILS-FA501.pdf |
| Sheets and Views |
| FA501 |
| 15-447-FA146 B43-FA146.pdf |
| Sheets and Views |
| FA146 |
| 15-447-FA145 B42F2 East, West-FA145.pdf |
| Sheets and Views |
| FA145 |
| 15-447-FA144 B42F2 East, West-FA144.pdf |
| Sheets and Views |
| FA144 |
| 15-447-FA144 B42F2 East, West-FA144.pdf |
| Sheets and Views |
| FA144 |
| 2018-06-26T04:52:41-0700 | |
| DocuSign, Inc. | |
| Digitally verifiable PDF exported from www.docusign.com |
File details come from the government source that posted it.