36C24618R0839-002.pdf
PDF 1 MB Posted
- Attached to
- Project 659-16-103, Replace Campus Fire Alarm System Federal contract opportunity
- Solicitation number
- 36C24618R0839
About this file
36C24618R0839 CONTRACT ATTACHMENT A - DRAWINGS FILE 1 - 01-Sheets_GI001-GI002_and_FI001.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24618R0839-0003001.pdf | ||
| 36C24618R0839-0003000.docx | DOCX document | |
| 36C24618R0839-0003002.pdf | ||
| 36C24618R0839-0002000.docx | DOCX document | |
| 36C24618R0839-0002001.pdf | ||
| 36C24618R0839-004.pdf | ||
| 36C24618R0839-013.docx | DOCX document | |
| 36C24618R0839-008.pdf | ||
| 36C24618R0839-012.pdf | ||
| 36C24618R0839-009.pdf | ||
| 36C24618R0839-001.docx | DOCX document | |
| 36C24618R0839-014.pdf | ||
| 36C24618R0839-005.pdf | ||
| 36C24618R0839-003.pdf | ||
| 36C24618R0839-010.pdf | ||
| 36C24618R0839-007.pdf | ||
| 36C24618R0839-011.pdf | ||
| 36C24618R0839-006.pdf | ||
| 36C24618R0839-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REPLACE/UPGRADE CAMPUS FIRE ALARM SYSTEM
PROJECT NO. 659-16-103
GENERAL INFORMATION
GI001 COVER SHEET
GI002 SITE KEY PLAN
FIRE ALARM INFORMATION
FI001 FIRE ALARM GENERAL NOTES, LEGENDS,
ABBREVIATIONS, AND DEMO NOTES
FIRE ALARM EXISTING/DEMOLITION
FD101 FIBER-OPTIC SITE PLAN EXISTING/DEMOLITION
FD102 BLDG 1 EXISTING/DEMOLITION
FD103 BLDG 2 GROUND FLOOR EXISTING/DEMOLITION
FD104 BLDG 2 FIRST FLOOR EXISTING/DEMOLITION
FD105 BLDG 2 SECOND FLOOR EXISTING/DEMOLITION
FD106 BLDG 2 THIRD FLOOR EXISTING/DEMOLITION
FD107 BLDG 2 FOURTH FLOOR EXISTING/DEMOLITION
FD108 BLDG 2 FIFTH FLOOR AND PENTHOUSE
EXISTING/DEMOLITION
FD109 BLDG 3 AND 20 GROUND FLOOR EXISTING/DEMOLITION
FD110 BLDG 3 FIRST FLOOR EXISTING/DEMOLITION
FD111 BLDG 3 SECOND FLOOR EXISTING/DEMOLITION
FD112 BLDG 3 THIRD FLOOR EXISTING/DEMOLITION
FD113 BLDG 3 FOURTH FLOOR AND PENTHOUSE
EXISTING/DEMOLITION
FD114 BLDG 4 GROUND FLOOR AND BLDG 36
EXISTING/DEMOLITION
FD115 BLDG 4 FIRST FLOOR EXISTING/DEMOLITION
FD116 BLDG 4 SECOND FLOOR EXISTING/DEMOLITION
FD117 BLDG 4 THIRD FLOOR EXISTING/DEMOLITION
FD118 BLDG 4 FOURTH FLOOR AND PENTHOUSE
EXISTING/DEMOLITION
FD119 BLDG 5 GROUND FLOOR, BLDG 31, BLDG 35
EXISTING/DEMOLITION
FD120 BLDG 5 FIRST FLOOR EXISTING/DEMOLITION
FD121 BLDG 6 GROUND FLOOR AND BASEMENT
EXISTING/DEMOLITION
FD122 BLDG 6 FIRST FLOOR EXISTING/DEMOLITION
FD123 BLDG 7, BLDG 24, BLDG 30 EXISTING/DEMOLITION
FD124 BLDG 8 GROUND AND FIRST FLOOR
EXISTING/DEMOLITION
FD125 BLDG 8 SECOND FLOOR EXISTING/DEMOLITION
FD126 BLDG 8 THIRD FLOOR EXISTING/DEMOLITION
FD127 BLDG 11 GROUND FLOOR EXISTING/DEMOLITION
FD128 BLDG 11 FIRST FLOOR EXISTING/DEMOLITION
FD129 BLDG 11A, BLDG 11B, BLDG 11C EXISTING/DEMOLITION
FD130 BLDG 12, BLDG 14W, BLDG 14E EXISTING/DEMOLITION
FD131 BLDG 13 EXISTING/DEMOLITION
FD132 BLDG 15 EXISTING/DEMOLITION
FD133 BLDG 16 EXISTING/DEMOLITION
FD134 BLDG 17, BLDG 28, BLDG 32, BLDG 33
EXISTING/DEMOLITION
FD135 BLDG 18, BLDG 17A, BLDG 17B, BLDG 17C
EXISTING/DEMOLITION
FD136 BLDG 19 EXISTING/DEMOLITION
FD137 BLDG 21 GROUND FLOOR AND BLDG 37
EXISTING/DEMOLITION
FD138 BLDG 21 FIRST FLOOR EXISTING/DEMOLITION
FD139 BLDG 21 SECOND FLOOR AND PENTHOUSE
EXISTING/DEMOLITION
FD140 BLDG 21A, BLDG 21B EXISTING/DEMOLITION
FD141 BLDG 42 GROUND FLOOR EXISTING/DEMOLITION
FD142 BLDG 42 FIRST FLOOR EAST EXISTING/DEMOLITION
FD143 BLDG 42 FIRST FLOOR WEST EXISTING/DEMOLITION
FD144 BLDG 42 SECOND FLOOR EAST EXISTING/DEMOLITION
FD145 BLDG 42 SECOND FLOOR WEST EXISTING/DEMOLITION
FD146 BLDG 43 EXISTING/DEMOLITION
FD601 FIBER INTERCONNECTION EXISTING/DEMOLITION
FIRE ALARM NEW
FA101 NEW FIRE ALARM SYSTEM FIBER ROUTING
FA102 BLDG 1 GROUND, FIRST, SECOND FLOOR
FA103 BLDG 2 GROUND FLOOR
FA104 BLDG 2 FIRST FLOOR
FA105 BLDG 2 SECOND FLOOR
FA106 BLDG 2 THIRD FLOOR
FA107 BLDG 2 FOURTH FLOOR
FA108 BLDG 2 FIFTH FLOOR AND PENTHOUSE
FA109 BLDG 3 AND 20 GROUND FLOOR AND BLDG 34
FA110 BLDG 3 FIRST FLOOR
FA111 BLDG 3 SECOND FLOOR
FA112 BLDG 3 THIRD FLOOR
FA113 BLDG 3 FOURTH FLOOR AND PENTHOUSE
FA114 BLDG 4 GROUND FLOOR AND BLDG 36
FA115 BLDG 4 FIRST FLOOR
FA116 BLDG 4 SECOND FLOOR
FA117 BLDG 4 THIRD FLOOR
FA118 BLDG 4 FOURTH FLOOR AND PENTHOUSE
FA119 BLDG 5 GROUND FLOOR, BLDG 31, BLDG 35
FA120 BLDG 5 FIRST FLOOR
FA121 BLDG 6 GROUND FLOOR
FA122 BLDG 6 FIRST FLOOR AND BASEMENT
FA123 BLDG 7, BLDG 24, BLDG 30
FA124 BLDG 8 GROUND AND FIRST FLOOR
FA125 BLDG 8 SECOND FLOOR
FA126 BLDG 8 THIRD FLOOR
FA127 BLDG 11 GROUND FLOOR
FA128 BLDG 11 FIRST FLOOR
FA129 BLDG 11A, BLDG 11B, BLDG 11C
FA130 BLDG 12, BLDG 14W, BLDG 14E
FA131 BLDG 13
FA132 BLDG 15
FA133 BLDG 16
FA134 BLDG 17, BLDG 28, BLDG 32, BLDG 33
FA135 BLDG 18, BLDG 17A, BLDG 17B, BLDG 17C
FA136 BLDG 19
FA137 BLDG 21 GROUND FLOOR AND BLDG 37
FA138 BLDG 21 FIRST FLOOR
FA139 BLDG 21 SECOND FLOOR AND PENTHOUSE
FA140 BLDG 21A, BLDG 21B
FA141 BLDG 42 GROUND FLOOR
FA142 BLDG 42 FIRST FLOOR EAST
FA143 BLDG 42 FIRST FLOOR WEST
FA144 BLDG 42 SECOND FLOOR EAST
FA145 BLDG 42 SECOND FLOOR WEST
FA146 BLDG 43
FA501 DETAILS
FA601 FIBER INTERCONNECTION DIAGRAM, FIRE ALARM RISER
DIAGRAM
1601 BRENNER AVE, SALISBURY, NORTH CAROLINA 28144
W.G. HEFNER VA MEDICAL CENTER
COVER SHEET
GI001
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
SHEET LIST
BID DEDUCT NOTES
A. SURVEY: BEFORE WORK IS STARTED, THE CONTRACTOR SHALL MAKE A
THOROUGH SURVEY WITH THE COR , OF AREAS OF BUILDINGS IN WHICH
ALTERATIONS OCCUR AND AREAS WHICH ARE ANTICIPATED ROUTES OF
ACCESS, AND FURNISH A REPORT, SIGNED BY BOTH, TO THE COR. THIS
REPORT SHALL LIST BY ROOMS AND SPACES:
1. EXISTING CONDITION AND TYPES OF RESILIENT FLOORING, DOORS,
WINDOWS, WALLS AND OTHER SURFACES NOT REQUIRED TO BE
ALTERED THROUGHOUT AFFECTED AREAS OF BUILDINGS.
2. EXISTENCE AND CONDITIONS OF ITEMS SUCH AS PLUMBING FIXTURES
AND ACCESSORIES, ELECTRICAL FIXTURES, EQUIPMENT, VENETIAN
BLINDS, AND SHADES, REQUIRED BY DRAWINGS TO BE EITHER REUSED
OR RELOCATED, OR BOTH.
3. SHALL NOTE DISCREPANCIES BETWEEN DRAWINGS AND EXISTING
CONDITIONS AT SITE.
4. SHALL DESIGNATE AREAS FOR WORKING SPACE, MATERIAL STORAGE
AND ROUTES OF ACCESS TO AREAS WITHIN BUILDINGS WHERE
ALTERATIONS OCCUR AND WHICH HAVE BEEN AGREED UPON BY
CONTRACTOR AND COR.
B. ITEMS REQUIRED BY DRAWINGS TO BE EITHER REUSED OR RELOCATED
OR BOTH, FOUND DURING THIS SURVEY TO BE NONEXISTENT, OR IN
OPINION OF COR , TO BE IN SUCH CONDITION THAT THEIR USE IS
IMPOSSIBLE OR IMPRACTICAL, SHALL BE FURNISHED OR REPLACED BY
CONTRACTOR WITH NEW ITEMS IN ACCORDANCE WITH SPECIFICATIONS
WHICH WILL BE FURNISHED BY GOVERNMENT. PROVIDED THE CONTRACT
WORK IS CHANGED BY REASON OF THIS SUBPARAGRAPH, THE CONTRACT
SHALL BE MODIFIED ACCORDINGLY, UNDER PROVISIONS OF CLAUSE
ENTITLED "DIFFERING SITE CONDITIONS" (FAR 52.236-2) AND "CHANGES"
(FAR 52.243-4 AND VAAR 852.236-88).
C. RE-SURVEY: THIRTY DAYS BEFORE EXPECTED PARTIAL OR FINAL
INSPECTION DATE, THE CONTRACTOR AND COR TOGETHER SHALL MAKE
A THOROUGH RE-SURVEY OF THE AREAS OF BUILDINGS INVOLVED.
SUBMIT A REPORT ON CONDITIONS THEN EXISTING, OF RESILIENT
FLOORING, DOORS, WINDOWS, WALLS AND OTHER SURFACES AS
COMPARED WITH CONDITIONS OF SAME AS NOTED IN FIRST CONDITION
SURVEY REPORT:
1. RE-SURVEY REPORT SHALL ALSO LIST DAMAGE CAUSED BY
CONTRACTOR TO SUCH FLOORING AND OTHER SURFACES, DESPITE
PROTECTION MEASURES; AND, SHALL FORM BASIS FOR DETERMINING
EXTENT OF REPAIR WORK REQUIRED OF CONTRACTOR TO RESTORE
DAMAGE CAUSED BY CONTRACTOR'S WORKERS IN EXECUTING WORK
OF THIS CONTRACT.
D. PROTECTION: PROVIDE THE FOLLOWING PROTECTIVE MEASURES:
1. WHEREVER EXISTING ROOF SURFACES ARE DISTURBED THEY SHALL
BE PROTECTED AGAINST WATER INFILTRATION. IN CASE OF LEAKS,
THEY SHALL BE REPAIRED IMMEDIATELY UPON DISCOVERY.
2. TEMPORARY PROTECTION AGAINST DAMAGE FOR PORTIONS OF
EXISTING STRUCTURES AND GROUNDS WHERE WORK IS TO BE DONE,
MATERIALS HANDLED AND EQUIPMENT MOVED OR RELOCATED.
3. PROTECTION OF INTERIOR OF EXISTING STRUCTURES AT ALL TIMES,
FROM DAMAGE, DUST AND WEATHER INCLEMENCY. WHEREVER WORK
IS PERFORMED, FLOOR SURFACES THAT ARE TO REMAIN IN PLACE
SHALL BE ADEQUATELY PROTECTED PRIOR TO STARTING WORK, AND
THIS PROTECTION SHALL BE MAINTAINED INTACT UNTIL ALL WORK IN
THE AREA IS COMPLETED.
BID ALTERNATES
1. (DEDUCT ALTERNATE ITEM NO. 1): PROVIDE ALL WORK PER BASE BID ABOVE
EXCEPT: DELETE WORK ASSOCIATED WITH NEW FIRE ALARM WORK IN BUILDING
4. (THE MAIN TERMINAL EQUIPMENT LOCATED IN G022-4, CONDUIT FOR FIBER
LOOP, FIBER CABLE, PATCH PANELS, PATCH CORDS, FIBER BOXES,
TERMINATIONS, CONNECTIONS TO THE NEW FIRE ALARM FIBER LOOP, BORING
SHALL REMAIN IN BASE BID). ALL WORK SHALL INCLUDE FINAL CLEANUP,
COMPLETION OF ANY PUNCH LIST ITEMS, TESTING AND TRAINING.
2. (DEDUCT ALTERNATE ITEM NO. 2): PROVIDE ALL WORK PER ALTERNATE NO. 1
ABOVE EXCEPT: DELETE NEW FIRE ALARM WORK IN BUILDING 12. (CONDUIT FOR
FIBER LOOP, FIBER CABLE, PATCH PANELS, PATCH CORDS, FIBER BOXES,
TERMINATIONS, CONNECTIONS TO NEW FIRE ALARM FIBER LOOP, BORING SHALL
REMAIN IN BASE BID). ALL WORK SHALL INCLUDE FINAL CLEANUP, COMPLETION
OF ANY PUNCH LIST ITEMS, TESTING AND TRAINING.
3. (DEDUCT ALTERNATE ITEM NO. 3): PROVIDE ALL WORK PER ALTERNATE NO. 2
ABOVE EXCEPT: DELETE NEW FIRE ALARM WORK IN BUILDING 15. (CONDUIT FOR
FIBER LOOP, FIBER CABLE, PATCH PANELS, PATCH CORDS, FIBER BOXES,
TERMINATIONS, CONNECTIONS TO NEW FIRE ALARM FIBER LOOP, BORING SHALL
REMAIN IN BASE BID). ALL WORK SHALL INCLUDE FINAL CLEANUP, COMPLETION
OF ANY PUNCH LIST ITEMS, TESTING AND TRAINING.
4. (DEDUCT ALTERNATE ITEM NO. 4): PROVIDE ALL WORK PER ALTERNATE NO. 3
ABOVE EXCEPT: DELETE NEW FIRE ALARM WORK IN BUILDING 1. (CONDUIT FOR
FIBER LOOP, FIBER CABLE, PATCH PANELS, PATCH CORDS, FIBER BOXES,
TERMINATIONS, CONNECTIONS TO NEW FIRE ALARM FIBER LOOP, BORING SHALL
REMAIN IN BASE BID). ALL WORK SHALL INCLUDE FINAL CLEANUP, COMPLETION
OF ANY PUNCH LIST ITEMS, TESTING AND TRAINING.
5. (DEDUCT ALTERNATE ITEM NO. 5): PROVIDE ALL WORK PER ALTERNATE NO. 4
ABOVE EXCEPT: DELETE NEW FIRE ALARM WORK IN BUILDING 5.(LEAVE NEW
HEAD END IN BASE WITH ALL CONDUIT FOR FIBER LOOP, FIBER CABLE, PATCH
PANELS, PATCH CORDS, FIBER BOXES, TERMINATIONS, CONNECTIONS TO NEW
FIRE ALARM FIBER LOOP, BORING SHALL REMAIN IN BASE BID) ALL WORK SHALL
INCLUDE FINAL CLEANUP, COMPLETION OF ANY PUNCH LIST ITEMS, TESTING
AND TRAINING.
DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8
6/25/2018
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
VICINITY MAP
AutoCAD SHX Text
NTS
AutoCAD SHX Text
CAMPUS LOCATION
AutoCAD SHX Text
CAMPUS LOCATION
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text N
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text 23894
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text
SEAL
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text L
AutoCAD SHX Text E
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
1 SITE KEY PLAN
1" = 100'
GI002
SITE KEY PLAN
ADMINISTRATION BUILDING
G. M. & S BUILDING
OUTPATIENT CLINICS
MENTAL HEALTH OFFICES
MAIN KITCHEN
RECREATION BUILDING
R.M.S & CORE CLINIC BUILDING
PATIENT TREATMENT (MENTAL HEALTH)
PARKING GARAGE
N.C. VETERANS HOME
MENTAL HEALTH OFFICES
MENTAL HEALTH OFFICES
MENTAL HEALTH OFFICES
CALL CENTER
POLICE HEADQUARTERS
STUDENT LODGING
E&W CWT HOMELESS AND POLICE
ADMIN
LAUNDRY
WAREHOUSE
BOILER PLANT
CHAPEL
CLINIC LAB
LOGISTICS, IRM, ENDOSCOPE, PODIATRY,
ONCOLOGY, SLEEP CLINIC
FEE BASIS
ENGINEERING
FLAG POLE
R.M.&S STORAGE
R.M.&S STORAGE
ENGINEERING PAINT SHOP
R.M.&S. STORAGE
GREENHOUSE
CHILLER PLANT
GENERATOR BUILDING
SWITCHGEAR BUILDING
GENERATOR BUILDING
GENERATOR BUILDING
GENERATOR BUILDING
GENERATOR BUILDING
GENERATOR BUILDING
PICNIC SHELTER
GROUNDS STORAGE SHELTER
NCA SHELTER
GEROPSYCHIATRIC BUILDING
HOSPICE BUILDING
GATES
BUILDING LEGEND
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
11A.
11B.
11C.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
21A.
21B.
22.
24.
25.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
NO
RT
H
DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8
6/25/2018
AutoCAD SHX Text
STREET
AutoCAD SHX Text
HEDRICK
AutoCAD SHX Text
AVENUE
AutoCAD SHX Text
BRENNER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 11A
AutoCAD SHX Text 11C
AutoCAD SHX Text 11B
AutoCAD SHX Text
AutoCAD SHX Text 14E
AutoCAD SHX Text 14W
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 21B
AutoCAD SHX Text 21A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 17A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 17B
AutoCAD SHX Text 17C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text N
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text L
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FI001
FIRE ALARM GENERAL NOTES, LEGENDS,
ABBREVIATIONS, AND DEMO NOTES
DEVICE MODIFIERS
R RESIDENTIAL
K INSTITUTIONAL
LK LOCKABLE/LOCK BOX
WP WEATHERPROOF
# W SPEAKER WATTAGE
# cd STROBE CANDELA
F
FF F
F F
F S
F S
F S
F S
F F
F F
FACP
F F
MANUAL PULL STATION
ABORT SWITCH
SMOKE DETECTOR
HEAT DETECTOR (FIXED)
SMOKE DETECTOR BEAM
FLOW SWITCH
TAMPER SWITCH
POST INDICATOR VALVE
PRESSURE SWITCH
DUCT SMOKE DETECTOR
REMOTE TEST KEYED SWITCH/ALARM
INDICATOR LIGHT
HORN
HORN/STROBE
SPEAKER
SPEAKER/STROBE
BELL
BUZZER
CHIME
DOOR HOLD
SMOKE DAMPER
FIRE DAMPER
SMOKE/FIRE DAMPERZONE ADDRESSABLE MODULE
INDIVIDUAL ADDRESSABLE MODULE FIRE FIGHTER PHONE
FIRE ALARM DEVICE AND EQUIPMENT SYMBOL LEGEND
FIRE ALARM EQUIPMENT
FIRE ALARM EQUIPMENT AND SOME DEVICES ARE SHOWN ON PLANS BY ABBREVIATIONS WITHIN A BOX.
FOR EXAMPLE: IS A FIRE ALARM CONTROL PANEL.
ABBREVIATIONS USED ARE BELOW, ALONG WITH THEIR DEFINITIONS.
AATP ANALOG AUDIO TRANSPONDER
PANEL
BAT FIRE ALARM BATTERIES
CHR FIRE ALARM BATTERY CHARGER
CR CONTROL MODULE RELAY
DAA DIGITAL AUDIO AMPLIFIER
DACT DIGITAL ALARM COMMUNICATOR
TRANSMITTER
DC DAMPER CONTROL
EAR ELEVATOR ALTERNATE RECALL
EC ELEVATOR CONTROLLER
EP ELECTRICAL PANEL
EST EMERGENCY SHUNT TRIP
ESTPS ELEVATOR EMERGENCY SHUNT TRIP
POWER SUPERVISION
EICN ELEVATOR IN-CAB NOTIFICATION
EPR ELEVATOR PRIMARY RECALL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FANA FIRE ALARM NETWORK
ANNUNCIATOR
FANCC FIRE ALARM NETWORK COMMAND
CONSOLE
FAP FIRE ALARM PRINTER
FAPS FIRE ALARM POWER SUPPLY
FAR FIRE ALARM RECORDER
FATD FIRE ALARM TELEPHONE DIALER
FB FIBER OPTICS BREAKOUT BOX
FC FAN CONTROL
FOER FIBER-OPTIC EXTENDER/REPEATER
FPCP FIRE PUMP CONTROL PANEL
FSCP FIRE SUPPRESSION SYSTEM
CONTROL PANEL
FR FAN STOP RELAY
KHFS KITCHEN HOOD FIRE SUPPRESSION
SYSTEM
LCD MONITOR WITH KEYBOARD -
OPERATOR'S TERMINAL
MM MONITORING MODULE
MR MONITORING MODULE W/ RELAY
NAC NOTIFICATION APPLIANCE CIRCUIT
NACP NOTIFICATION APPLIANCE CIRCUIT
PANEL
PC PERSONAL COMPUTER
PSCP PAGING SYSTEM CONTROL PANEL
PSRA PAGING SYSTEM REMOTE AMPLIFIER
RM ADDRESSABLE RELAY MODULE
RL REMOTE INDICATOR LAMP
RLCP REMOTELY LOCATED CONTROL
PANEL
RP RELAY PANEL
SR FIRE SHUTTER RELAY
TC FIRE ALARM TERMINAL CABINET
UPS UNINTERRUPTIBLE POWER SUPPLY
DESCRIPTION
DEVICE HEIGHT ABBREVIATIONS
UNLESS OTHERWISE NOTED, HEIGHTS OF
WALL-MOUNTED DEVICES ARE OC AFF.
ABBREVIATIONS USED TO MODIFY LISTED
HEIGHT HERE AND IN PLANS:
OC TO CENTER OF DEVICE
OP TO HEIGHEST OPERABLE PART
TP TO TOP OF DEVICE
BM TO BOTTOM OF DEVICE
BFC BELOW FINISHED CEILING
ADF ABOVE DOOR FRAME
AFF ABOVE FINISHED FLOOR
78" OP
48" OP
SYMBOLHEIGHTDESCRIPTIONSYMBOLHEIGHT DEVICE HEIGHT NOTES
1. WALL-MOUNTED AUDIBLE NOTIFICATION
APPLIANCES SHALL BE MIN 90" AFF TP AND
MAX 6" BFC TP, WHICHEVER IS LOWER.
FOR COMBINATION AUDIBLE/VISIBLE
APPLIANCES, HEIGHT REQUIREMENTS FOR
VISIBLE DEVICES TAKE PRECEDENCE.
2. SIDEWALL SPOT-TYPE HEAT DETECTORS
SHALL BE MIN 4" BFC AND MAX 12" BFC.
CEILING SPOT-TYPE DETECTORS SHALL BE
MAX 12" BFC.
NOTE 1
80" BM
MIN
12" BFC
MAX
NOTE 2
42" MIN OP
48" MAX OP
42" MIN OP
48" MAX OP FF
INDIVIDUAL ADDRESSABLE MODULE
WITH RELAY
STROBE
DOOR HOLD/CLOSER
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 1
WALL TYPE LEGEND
ZONE DIVIDER
SMOKE BARRIER
1-HOUR RATED
2-HOUR RATED
AMPERE
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPS INTERRUPTING CAPACITY
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
CONDUIT
CANDELA
CIRCUIT
CONCRETE MASONRY UNIT
COPPER
DEEP
DIGITAL ALARM COMMUNICATOR TRANSMITTER
DEDICATED CIRCUIT
EQUIPMENT GROUND
ELECTRICAL METALLIC TUBING
EXISTING
EXTERIOR
FULL LOAD AMPS
FLEXIBLE METAL CONDUIT
GROUNDING ELECTRODE CONDUCTOR
GROUND FAULT CIRCUIT INTERRUPTER
GALVANIZED RIGID STEEL
HIGH
HORSEPOWER
INTERNATIONAL BUILDING CODE
ISOLATED GROUND
KILOWATT
MAXIMUM
MAIN BONDING JUMPER
METAL-CLAD CABLE
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MAIN DISTRIBUTION PANEL
MINIMUM
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL FIRE PROTECTION ASSOCIATION
NOT TO SCALE
ON CENTER
PHOTOCELL
RELOCATED
SIGNALING LINE CIRCUIT
SURGE PROTECTION DEVICE
SUBSURFACE UTILITY ENGINEERING
TOTAL CONNECTED LOAD
TOTAL DEMAND LOAD
TYPICAL
UNDERWRITERS LABORATORIES
UNLESS NOTED OTHERWISE
UNINTERRUPTIBLE POWER SUPPLY
WEATHERPROOF
TRANSFORMER
A,AMP
AFC
AFF
AFG
AIC
ATS
AWG
BFF
BFG
C cd
CKT
CMU
CU
D
DACT
DED
EG
EMT
EX
EXT
FLA
FMC
GEC
GFI
GRS
H
HP
IBC
IG
KW
MAX
MBJ
MC
MCA
MCB
MDP
MIN
MLO
MOCP
N
NEC
NFPA
NTS
OC
PC
R
SLC
SPD
SUE
TCL
TDL
TYP
UL
UNO
UPS
WP
XFMR
ELECTRICAL ABBREVIATIONS
1. ALL ELECTRICAL DEVICES, FIXTURES, AND
EQUIPMENT SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT
SPECIFICATIONS, THE MANUFACTURER'S
RECOMMENDED INSTALLATION PROCEDURES,
ALL APPLICABLE CODES, AMERICANS WITH
DISABILITIES ACT AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES,
FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR
DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR
PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS,
FLOORS, CEILING, AND ROOFS IN ACCORDANCE
WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT
AND APPLICABLE BUILDING CODES. WALL
RATINGS SHOWN ARE BASED ON EXISTING
DRAWINGS. CONTRACTOR SHALL VERIFY
CONSTRUCTION RATINGS (REGARDLESS OF
WHETHER SHOWN ON PLANS) AND PROVIDE
PENETRATION ASSEMBLIES SUITABLE FOR THE
PARTICULAR CONSTRUCTION.
4. VERIFY CEILING SYSTEMS AND PROVIDE
MOUNTING ACCESSORIES, TRIMS AND ALL
REQUIRED MOUNTING HARDWARE TO SUIT THE
PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND
BUILDING INTERIOR UTILITIES DURING
CONSTRUCTION.
6. ALL CONDUIT SHALL BE GRS OR EMT UNLESS
OTHERWISE NOTED.
7. ALL ELECTRICAL MATERIALS, DEVICES,
APPLIANCES AND EQUIPMENT SHALL BE
LABEL-LISTED BY AN APPROVED THIRD PARTY
TESTING AGENCY.
8. IN CASE OF CONFLICTS OR DISCREPANCIES
WITHIN OR AMONG THE CONTRACT DRAWINGS,
THE BETTER QUALITY, MORE STRINGENT
REQUIREMENTS OR GREATER QUANTITY OF
WORK, AS DETERMINED BY THE VA, SHALL BE
PROVIDED.
9. ALL PHASING SHALL BE COORDINATED WITH THE
COR.
10. ALL RACEWAY IN FINISHED AREAS SHALL BE
CONCEALED EXCEPT FOR IN AREAS WHERE
EXPOSED RACEWAY ALREADY EXISTS. ALL
EXPOSED RACEWAY SHALL BE APPROVED BY THE
VA PRIOR TO INSTALLATION.
11. ALL WORK SHALL MEET THE LATEST NEC.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY
CEILING DAMAGE.
13. CONTRACTOR SHALL SURVEY THE AREA OF
WORK BEFORE BEGINNING WORK.
14. ALL WORK SHALL BE COORDINATE WITH COR.
15. ANY SYSTEM OUTAGES SHALL BE COORDINATED
BY COR.
16. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY
DAMAGE TO SIDEWALKS, PLANTING AREAS,
STREETS, AND DRIVEWAYS.
17. CONTRACTOR SHALL SEAL DUCT WORK AFTER
THE DUCT DETECTOR WORK.
GENERAL NOTES
1. ALL FIRE ALARM EQUIPMENT POWER CIRCUITS
SHALL BE AS STATED ON DRAWINGS FOR EACH
BUILDING, 2-12 AWG, 12 AWG EG, 3/4" C. EXISTING
RACEWAY MAY BE REUSED IN-PLACE. REMOVED
RACEWAY SHALL NOT BE RE-INSTALLED. WHERE
NOT REUSED, RACEWAY AND ALL APPURTENANCES
SHALL BE DEMOLISHED AND ALL PENETRATIONS
SEALED.
2. FOR LONG RUNS, INCREASE WIRE SIZE AS
REQUIRED TO ENSURE NOT GREATER THAN 3%
VOLTAGE DROP FROM THE PANEL TO THE LOAD.
3. PROVIDE A TOGGLE SWITCH WITH LOCKABLE
COVER FOR ALL NEW AND EXISTING FACP, NACP,
DAA, AND OTHER FIRE ALARM EQUIPMENT 120V
POWER CIRCUIT. EACH SWITCH SHALL BE LABELED
WITH AN ENGRAVED PHENOLIC LABEL IDENTIFUING
THE EQUIPMENT SERVED (EXISTING TOGGLE
SWITCH MAY BE REUSED) COORDINATE WITH COR.
4. EACH 120V-POWERED FIRE ALARM EQUIPMENT
SHALL BE LABELED WITH ENGRAVED PHENOLIC
LABEL FOR SOURCE OF POWER (PANEL AND
CIRCUIT).
5. EXPOSED RACEWAY SHALL BE PAINTED TO MATCH
WALL OR CEILING.
6. EACH JUNCTION BOX SHALL BE VISIBLY LABELED
WITH BLACK PERMANENT MARKER FOR VOLTAGE
AND CIRCUIT. EXPOSED JUNCTION BOXES IN
FINISHED AREAS SHALL BE LABELED WITH PRINTED
ADHESIVE LABEL.
7. PROVIDE NEW TYPED PANEL SCHEDULES FOR EACH
PANEL, COMBINING EXISTING DIRECTORIES AND
CIRCUITS MODIFIED BY THIS PROJECT. TWO COPIES
OF EACH NEW PANEL SCHEDULE SHALL BE
PROVIDED TO THE VA ELECTRIC SHOP.
8. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED
PER THE PANEL, BREAKER, OR PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
9. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL
OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
10. ALL ELECTRICAL POWER WIRE TERMINATIONS
SHALL BE RATED FOR 75 DEGREES C.
11. ALL ELECTRICAL POWER CONDUCTORS SHALL HAVE
THHN/THWN INSULATION, UNLESS OTHERWISE
NOTED.
12. CONTRACTOR SHALL VERIFY ALL ELECTRICAL
POWER, PANELS, BREAKERS TO EACH FIRE ALARM
EQUIPMENT. SURVEY ALL ELECTRICAL WORK
BEFORE BEGINNING OF WORK.
ELECTRICAL POWER NOTES
BID DEDUCT SMOKE DETECTOR12" BFC
MAX
1. ALL EXISTING CONDITIONS, INCLUDING DEVICES,
EQUIPMENT, AND ROUTING, ARE BASED ON BEST
AVAILABLE INFORMATION FROM EXISTING
DRAWINGS AND SURVEYAND/OR VISUAL
INSPECTION. VERIFY ALL EXISTING CONDITIONS,
INCLUDING TRACING AND IDENTIFYING ALL FIRE
ALARM DEVICES, EQUIPMENT, RACEWAY AND
CIRCUITS IN THE AREA OF WORK.
2. EXISTING RACEWAY MAY BE REUSED IN-PLACE.
RACEWAY AND BOXES SHALL BE PAINTED RED OR
PROVIDED WITH A LABEL WHICH READS 'FIRE
ALARM' MIN EVERY 10'. WHERE RACEWAY IS NOT
REUSED, REMOVE ALL ACCESSIBLE RACEWAY AND
APPURTENANCES FROM ALL PORTIONS OF THE
AREA OF WORK INCLUDING WALLS, CEILINGS, AND
FLOORS. INACCESSIBLE RACEWAY SHALL BE
ABANDONED ONLY BY COR APPROVAL.
3. WHERE FLUSH-MOUNTED DEVICES ARE REMOVED
FROM WALLS AND THE RACEWAY AND BOX IS
INACCESSIBLE FOR REMOVAL, CUT OFF AND CAP
RACEWAY ABOVE CEILING AND PROVIDE
STAINLESS-STEEL COVER PLATE FOR BOX.
4. WHERE RACEWAY IS REMOVED FROM AN EXISTING
RATED ASSEMBLY, THE REMAINING PENETRATION
SHALL BE PATCHED TO MAINTAIN THE RATING OF
THE ASSEMBLY.
5. REPLACE ALL CEILING TILES DAMAGED AS A RESULT
OF THE FIRE ALARM SYSTEM WORK. CEILING TILES
FROM WHICH DEVICES ARE REMOVED MAY BE
REUSED IN THE SAME OR OTHER AREAS FOR NEW
DEVICES, PROVIDED THE CEILING TILE MATCHES
THE AREA AND IS NOT DAMAGED IN ANY OTHER
WAY. ALL NEW CEILING TILES SHALL MATCH
EXISTING STYLE, TEXTURE, AND COLOR.
DEMOLITION NOTES
1. VISIBLE NOTIFICATION DEVICES SHALL BE
INSTALLED ON THE WALL UNLESS WALL
CONSTRUCTION PROHIBITS FLUSH-MOUNTED
DEVICES AND CONDUIT WITHIN WALL, SUCH AS
PLASTER WALLS. CEILING-MOUNTED INSTALLATION
OF VISIBLE NOTIFICATION DEVICES SHALL RECEIVE
PRIOR APPROVAL BY THE COR.
2. NO AREA SHALL BE WITHOUT FULL FIRE ALARM
PROTECTION. SHOULD AN AREA NEED TO BE
WITHOUT FULL FIRE ALARM PROTECTION,
COORDINATE WITH THE COR AND PROVIDE 24-HOUR
FIRE WATCH.
3. COORDINATE EXACT DEVICE LOCATIONS WITH ALL
EXISTING CEILING FIXTURES SUCH AS LIGHTS,
DIFFUSERS, AND SPRINKLER HEADS.
4. VISUAL NOTIFICATIONS SETUP.
a. RESTROOMS : 15cd
b. CORRIDORS : 75cd
c. OFFICES(LARGE) : 75cd
d. LOUNGES : 75cd
e. CONFERENCE ROOMS : 75cd
f. WAITING AREAS : 75cd
g. PATIENT ROOMS: 110cd
5. ALL SPEAKERS SHALL BE SETUP AT A MINIMUM OF
1/2W EXCEPT AS NOTED. ADJUST AS NEEDED BASED
ON AREA NOISE LEVEL.
6. PROVIDE SMOKE AND HEAT DETECTOR WITHIN 24"
OF A SPRINKLER HEAD IN EACH ELEVATOR ROOM.
CONTRACTOR SHALL SURVEY AREA OF WORK
BEFORE BEGINNING WORK.
7. CONTRACTOR SHALL PROVIDE REMOTE TEST KEYED
SWITCH WITH INDICATOR LIGHT FOR EACH
DETECTOR AND LOCATE AT AN ACCESSIBLE
LOCATION. VERIFY EXACT LOCATION WITH COR.
8. REPLACE EXISTING FIRE ALARM SYSTEM
EQUIPMENT AS SHOWN AND RE-TERMINATE
EXISTING WIRING TO THE NEW PANELS. LABEL AND
TEST PER CODE AND VA STANDARDS.
FIRE ALARM SYSTEM NOTESTUNNEL DEVICE SCHEDULE
PROVIDE THE FOLLOWING DEVICES IN EACH TUNNEL AS SHOWN BELOW
(CONTRACTOR SHALL VERIFY AND COORDINATE WITH COR)
TUNNEL PULL STATIONS SPEAKERS/STROBES TUNNEL
LENGTH
FROM BUILDING 21
TO BUILDING 8
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±390'
FROM BUILDING 4
TO BUILDING 19
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±200'
FROM BUILDING 4
TO BUILDING 2
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±190'
FROM BUILDING 2
TO BUILDING 20 & 3
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±195'
FROM BUILDING 2
TO BUILDING 5
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±120'
FROM BUILDING 5
TO BUILDING 7
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±210'
FROM BUILDING 7
TO PULLBOX AT
BUILDING 10
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±255'
FROM BUILDING 31
TO BUILDING 6
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±315'
FROM BUILDING 6
TO BUILDING 42
AT EACH EXIT/ENTRANCE TO
TUNNEL. WITHIN 5' OF
EXIT/ENTRANCE
EVERY 100' AND WITHIN
15' OF EXIT/ENTRANCE ±330'
1. PROVIDE THE NEW COMPLETE FIBER OPTIC LOOP:
a. CONDUIT AND CONDUIT SUPPORT.
b. BORING AND SURVEY.
c. SLEEVES AND FIRE STOPPING.
d. FIBER CABLES, PATCH PANELS, AND FIBER BOXES.
e. TERMINATION AND LABELING.
f. TESTING OF THE NEW FIBER OPTIC LOOP.
2. INSTALL NEW FIRE ALARM CONTROL PANELS FOR EACH BUILDING.
3. INSTALL NEW FIRE ALARM NOTIFICATION APPLIANCE CIRCUIT
PANELS FOR EACH BUILDING.
4. INSTALL NEW FIRE ALARM DIGITAL AUDIO AMPLIFIERS FOR EACH
BUILDING.
5. INSTALL NEW FIRE ALARM ANNUNCIATORS PANEL FOR EACH
BUILDING.
6. INSTALL NEW FIRE ALARM NETWORK ANNUNCIATORS WHEN
SHOWN.
7. INSTALL NEW FIRE ALARM NETWORK COMMAND CONSOLES WHEN
SHOWN.
8. INSTALL NEW FIRE ALARM PANELS WHEN SHOWN.
9. INSTALL NEW FIRE ALARM LCD MONITORS WITH KEYBOARD
OPERATOR'S TERMINALS WHEN SHOWN.
10. INSTALL NEW FIRE ALARM DIGITAL ALARM COMMUNICATOR
TRANSMITTERS WHEN SHOWN.
11. INSTALL NEW FIRE ALARM PRINTER WHEN SHOWN.
12. INSTALL NEW FIRE ALARM PC WHEN SHOWN.
13. INSTALL EMERGENCY POWER AS SHOWN.
14. INSTALL NEW FIRE ALARM DEVICES AS SHOWN.
15. TERMINATE AND CONNECT NEW FIRE ALARM DEVICES AS SHOWN.
16. INSTALL NEW CONDUIT AND WIRING FOR ALL NEW DEVICES.
17. TEST EXISTING WIRING BEFORE FACP IN REPLACED.
18. REMOVE AND REPLACE EXISTING FACP AS SHOWN WITH NEW
PANEL.
19. ALL WORK SHALL BE COORDINATED WITH COR.
20. TEST NEW FACP AND NEW DEVICES.
21. PROGRAM NEW FACP AND NEW DEVICES PER VA
RECOMMENDATIONS.
22. CONTRACTOR SHALL PERFORM WORK ON ONE BUILDING AT A
TIME, ALL WORK SHALL BE COORDINATED WITH COR.
23. TEST AND COMMISSION EACH BUILDING FIRE ALARM SYSTEM
COMPLETE.
24. AFTER ALL BUILDINGS FIRE ALARM SYSTEM IS INSTALLED, TEST
THE ENTIRE CAMPUS FIRE ALARM SYSTEM AND FIBER LOOP AND
PROVIDE TEST RESULTS TO VA.
25. THE ABOVE PHASING IS A GUIDELINE FOR THE CONTRACTOR.
FIBER PHASING SHALL BE REVIEWED AND APPROVED BY VA COR.
26. CONTRACTOR SHALL SCHEDULE PHASING MEETING AND PROGRAM
MEETING WITH COR.
PHASING GUIDELINES
DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8
6/25/2018
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text N
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text L
| 01-Sheets GI001-GI002 |
| 15-447-GI001-GI001 |
| Sheets and Views |
| GI001 |
| 15-447-GI002-SITE KEY PLAN-GI002 |
| Sheets and Views |
| GI002 |
| 02-Sheet FI001 |
| Sheets and Views |
| FI001 |
| 15-447-GI001-GI001.pdf |
| Sheets and Views |
| GI001 |
| 2018-06-26T04:52:41-0700 | |
| DocuSign, Inc. | |
| Digitally verifiable PDF exported from www.docusign.com |
File details come from the government source that posted it.