36C24618R0839-004.pdf

PDF 7 MB Posted

Attached to
Project 659-16-103, Replace Campus Fire Alarm System Federal contract opportunity
Solicitation number
36C24618R0839
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

36C24618R0839 CONTRACT ATTACHMENT A - DRAWINGS FILE 3 - 03-Sheets_FD117-131.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Project 659-16-103, Replace Campus Fire Alarm System, newest first.
File Type Posted
36C24618R0839-0003002.pdf PDF
36C24618R0839-0003001.pdf PDF
36C24618R0839-0003000.docx DOCX document
36C24618R0839-0002001.pdf PDF
36C24618R0839-0002000.docx DOCX document
36C24618R0839-013.docx DOCX document
36C24618R0839-008.pdf PDF
36C24618R0839-012.pdf PDF
36C24618R0839-009.pdf PDF
36C24618R0839-002.pdf PDF
36C24618R0839-006.pdf PDF
36C24618R0839-001.docx DOCX document
36C24618R0839-014.pdf PDF
36C24618R0839-005.pdf PDF
36C24618R0839-003.pdf PDF
36C24618R0839-010.pdf PDF
36C24618R0839-007.pdf PDF
36C24618R0839-011.pdf PDF
36C24618R0839-000.docx DOCX document
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OFFICE

30363036

OFFICE-RN

30373037

OFFICE- VJO

30383038

OFFICE

30353035

OFFICE-SW

COORD

30333033

OFFICE- PSA

30393039

BREAK ROOM

30323032

WOMEN TLT

30403040

OFFICE- SWS

30223022

OFFICE- SWS

30233023

OFFICE- SWS

30243024 OFFICE- SWS

30253025

OFFICE- SWS

30263026

OFFICE- SWS

30213021

OFFICE- SWS

30203020

OFFICE- SWS

30193019

OFFICE- SWS

30183018

HAC

30173017

OFFICE-

PRIMARY CARE

30153015

OFFICE- CHIEF

SWS

30143014

OFFICE- ASST

CHIEF SWS

30133013

OFFICE- AO

30123012

HCMI PSA

30103010

COPY ROOM

30093009

OFFICE- GPD

30083008

OFFICE- GPD

30073007

OFFICE- GPD

30063006

OFFICE- GPD

30053005 MEN

30043004

MEN TLT

COMM

OFFICE-

ADDICTION

SPECIALIST

OFFICE-

OUTREACH

OFFICE

WOMEN

30923092

OFFICE

30553055

HAS/PSA

30033003

WAITING

30543054

WAITING

26 SF

VEND

HA

LL

W

AY

CORRIDOR

C302C302

VESTIBULE

30023002

PATIENT

CHECK-IN

30013001

CORRIDOR

C301

EXISTING

DINING

CORRIDOR

C305C305

STOR

HALLWAY

30163016

HALLWAY

30293029

ROOM

ELEC

FEC

CWT OFFICE

FUTURE

30653065

BREAK ROOM

30643064

CWT OFFICE

FUTURE

30663066

CWT OFFICE

FUTURE

30683068

CONFERENCE

30733073

OFFICE-VOC

REHAB 1

30753075

OFFICE-VOC

REHAB 2

30763076

OFFICE-VOC

REHAB 3

30773077

OFFICE-VOC

REHAB 4

30783078

OFFICE-VOC

REHAB 5

30793079

OFFICE-VOC

REHAB 6

30803080

OFFICE-MA

REHAB 1

30813081

OFFICE

30823082

EXAM TLT

30833083

HAC

30693069

EXAM- PA

OFFICE

30843084

SAS GROUP

ROOM

30853085

OFFICE-

PSYCHIATRIST

30863086

MED

30873087OFFICE

30883088

OFFICE- OP/SAS

SOCIAL WORK

30893089

OFFICE- OP/SAS

MENTAL

HEALTH

30903090

OFFICE- OP/SAS

MENTAL

HEALTH

30913091

STAFF TLT

30633063

STAFF TLT

30623062

OFFICE- OP/SAS

SOCIAL WORK

30583058

OFFICE

30573057

CODE BLUE

30563056

CORRIDOR

C306C306

HALLWAY

30743074

PASSAGE

31123112

STOR

30593059

COMM

30603060

HALLWAY

30613061

ELEC

30703070

FEC

30733073

MY HEALTHY

VET

3001B3001B

OFFICE EQUIP

30673067

MOP

3052A

F F F

F

F

F

F

F F F

F

F

F

F

F

FF

F F

F

F

F

F

F

F F

F F

F

F

F

F

F

F

F

F

FF

F

F

F S

F S

F

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

SF

S

F S

F S

F S

F S

F S

F S

F S

F S

F S F

S

F

FF

F S

F S

F

A A

TP

F S

KHFS

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD117

BLDG 4 THIRD FLOOR

EXISTING/DEMOLITION 4

1 BLDG 4 THIRD FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

DEMOLITION NOTES

KEYED NOTES #

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

1. REPLACE AATP (NOTIFIER XPIQ) WITH A NACP

AND A DAA. RECONFIGURE NAC AND SPEAKER

CIRCUITS AS REQUIRED.

DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8

6/25/2018

B WING CENTER WING CENTER WING A WING

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

FF

F

FF

FC

FC

F F

F

F

EPR

EAR

FC

A A

TP

TC

XN

XN

XN

XN

XN XN

XN

XN

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD118

BLDG 4 FOURTH FLOOR AND PENTHOUSE

EXISTING/DEMO 4

1 BLDG 4 FOURTH FLOOR

3/32" = 1'

2 BLDG 4 B-WING PENTOUSE

3/32" = 1' 3 BLDG 4 CENTER PENTOUSE

3/32" = 1' 4 BLDG 4 A-WING PENTOUSE

3/32" = 1'

HEALTH CARE OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

1. REPLACE AATP (NOTIFIER XPIQ) WITH A NACP

AND A DAA. RECONFIGURE NAC AND SPEAKER

CIRCUITS AS REQUIRED.

G032

VENDING STORAGE

G033

CANTEEN STORAGE

G031

MOBILE STORAGE

G052

OFFICE

G032A

CONCESSION ROOM

GO30A

OFFICE

G030

CANTEEN OFFICE

G029

RETAIL SALES

G026

STORAGE

G025

CHILLER

G024

REFRIG.

GO73

REFRIG.

G021

OFFICE

G017

KITCHEN

G018

DISHWASHING

G006

CART WASH

ENTRY

G003

STORAGE

G004

FREEZER

G005

DEEP FREEZE

G001

ELECT. CLOSET

G036

UNEXCAVATED AREA

G035

STAIRS

G016

ELE LOBBY

G010

REFRIG

G012

STORAGE

G017B

OFFICE

G017A

OFFICE

G040

LOCKER

G037

LOCKER

G038

SHWR

G041

SHWR

G042

SHWR

G043

LOCKER

G045

LOCKER

G047

SHWR

G043

MECHANICAL

G050

LOUNGE

1050A

STORAGE

G051

TOILET

G049

STAIRS

G027

FAC

G009

CLOSET

G020

FAC

1050B

VENDING

G007

ELECTRICAL

G048A

MECH.

G052A

MECHANICAL

G031A

CANTEEN STORAGE

G044

ELEV MEC RM

GO53

ELECT. CLOSET

GO28

CORRIDOR

G046

CORRIDOR

G003A

FREEZER

G034

F S

F

SF

S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

F

F

F

F

F

FACP A

A

TP

EPR

EAR

F

F F S

F

F F

KHFS

F

FB

FOER

FOER

MATCHLINE

KHFS

XN

XD

XD

XD

XD

XD

XR

F

F F

CHILLER PLANT

SHOP

LOCKER

OFFICE

SHW/TLT

100A

COMPUTER ROOM

100B

TOILET

TC

F

F

F S

F S

F S

F S

F

F

M A

TC

H

LI

N

E F S

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD119

BLDG 5 GROUND FLOOR, BLDG 31, BLDG 35

EXISTING/DEMOLITION 5

1 BLDG 5 GROUND FLOOR

3/32" = 1'

2 BLDG 31

3/32" = 1'

BUSINESS OCCUPANCY

FULLY SPRINKLERED

INDUSTRIAL OCCUPANCY

FULLY SPRINKLERED

3 BLDG 35

3/32" = 1' INDUSTRIAL OCCUPANCY

NOT SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

1. DEMOLISH EXISTING FACP. EXTEND EXISTING

SLC CIRCUITS TO NEW LOCATION.

2. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).

EXTEND EXISTING NAC AND SPEAKER CIRCUITS

TO NEW NACP AND DAA LOCATION.

REFRIG

VEG PREP

MECH. ROOM

DRY STORAGE

SUPPLY REFRIG

GARB. REFR

WASH RM

CART CHAR.

RECEIV. VEST.

OFFICE

MOP

CLOSET

CORRIDOR

BIOMED SHOP

DARK RM

CLOSET

CLOSET

1021A

OFFICE

1021B

OFFICE

OFFICE

TOLIET

1021C

OFFICE

CLOSET

OFFICE

TOILET

CLOSET

STAIRS

REFRIG

FREEZOR

STORAGE

1012A

TELE. ROOM

FAC

CORRIDOR

MECH. ROOM

STAIRS

M/F TOILET

TRAVEL

AGENT CASH

CORR

WAITING

STORAGE

202 SF

CONFERENCE

403 SF

CORRIDOR

C102

90 SF

STORAGE

200 SF

RECEPTION

183 SF

OFFICE

250SF

OFFICE

109 SF

OFFICE

OFFICE

CLOSET

23 SF

1056A

279 SF

STORAGE

116 SF

OFFICE

135 SF

STORAGE

84 SF

LOUNGE

94 SF

OFFICE

80 SF

OFFICE

102 SF

OFFICE

MEDICAL MEDIA

327 SF

403 SF

CORRIDOR

C103

403 SF

CORRIDOR

C101

STORAGE

CORRIDOR

CORRIDOR

CORRIDOR

M. TLT

F. TLT

LOBBY

F/A CABINET

CORRIDOR

376TO BUILDING 2

ROOF ROOF

BUILDING 2BUILDING 5 FIRST FLOOR

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

F

F

F F

F F

F

F

F

F

F

F

F

F S

FAAP

F

F

TC

F

F S

F S

FSCP

F

F

F S

~60'

EPR

EAR

XN

XN

XN

XN

XR

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD120

BLDG 5 FIRST FLOOR

EXISTING/DEMOLITION 5

1 BLDG 5 FIRST FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

SOUTH WINGNORTH WING

G065

PIPE SPACE

G064

PIPE SPACE

G013

PIPE SPACE

G009

PIPE SPACE

C O

R R

ID

O

R

OFFICE 9

OFFICE 10

OFFICE 11

OFFICE 12

OFFICE 13 SUPPORT

OFFICE 8

OFFICE 7

OFFICE 6

OFFICE 5

OFFICE 4

OFFICE 3

OFFICE 2

C O

R R

ID

O

R

TOUCH DOWN

RESOURCE RM

WOMENS ROOM

MENS ROOM

RECEPTION

STORAGE

CONFERENCE RM

OFFICE 1

G

C

O R

R

ID

O R

G023

CORRIDOR

G041

BREAK ROOM

G039

OFFICE

G032

OFFICE

G

B

LO

O

D /B

IO

LO

G

IC

FR

E

E

ZE

R /F

R

ID

G E

G035

OFFICE

G037

OFFICE

G040

IRB

G038

EXAM ROOM

G036

EXAM ROOM

G034

EXAM ROOM

G

C

O R

R

ID

O R

G033 Waiting

G021

CORRIDOR

G030

OFFICE

G028

COPY ROOM

G031

RCO

G

C

O R

R

ID

O R

G025

FEMALE

TOILET

G026

MALE

TOILET

G029

MECH

ROOM

G083

OFFICE

G043

COPY ROOM

G051

BREAK ROOM

G046

CORRIDOR

G047

CORRIDOR

G052

M. TOILET

G050

F. TOLET

G048

CORRIDOR

G053

OFFICE

G049

OFFICE

G054

OFFICE

G014

OFFICE

G015

OFFICE

G019A

FEC

G068

FEC

G059

RECORDS STORAGE

G017

FEC

G069

MECHANICAL ROOM

G070

BILLIARD ROOM

G080

OFFICE

G086

BREAK ROOM

G072

FAC

G008

PIPE SPACE

G002

MECHANICAL ROOM

G019

CORRIDOR

G001

STAIRS

190 G003

STOR.

G

P

IP

E T

R E

N C

H

G004

STORAGE

G006

STORAGE

G007

STORAGE

G010

TOILET

G011

TOILET

G012

STORAGE

G063A

STORAGE

G027

FAN ROOM

G016

WAITING

G042

OPEN OFFICE

G018

OFFICE

G066

CORRIDOR

G071

BOWLING ALLEY

G079

MECHANICAL

G078

STAIRS

G075

CORRIDOR

G073

PIPE SPACE

G076

STOR.

G074

PEST CONT.

G077

CORRIDOR

G087

STORAGE

G085

STORAGE

F

F

F

F

F

F

F

F

F

F

F

F F S

F

F F S

F S

F

F

F S

F S

F S F

FF

F

F

F

F S

F S

F S

F S

F S

F

F

FF

S

F

F S

F S

F

F

F S

F F

FF

S

F S

F

F

F

F S

F

F S

F S

F

F S

F S

F S

F

SF

F S

FFB

NAC

XN XN

XN

XN

G062

MECHANICAL ROOM

G063

CHLORINE ROOM

F F S

F

F S

F XN XN

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD121

BLDG 6 GROUND FLOOR AND BASEMENT

EXISTING/DEMOLITION 6

1 BLDG 6 GROUND FLOOR

3/32" = 1'

2 BLDG 6 BASEMENT

3/32" = 1'

ASSEMBLY OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

PATIENT LIBRARY

OFFICE

OFFICE

SEWING RM

LOUNGE

OFFICE

AMER LEGION

DAV OFFICE

VFW OFFICE

STORAGE

PATIENT LIBRARY

OFFICE

OFFICE

F. TOILET

M. TOILET

MECH RM

F. TLT.

M. TLT.

REC OFFICE

REC OFFICE

OFFICE

OFFICE

ELEC ROOM

LOBBY

LEARNING CENTER

M. TLT

W. TLT.

CANTEEN

STORAGE

BARBER SHOP

WAITING RM

OFFICE

CANTEEN DINING RM

CANTEEN KITCHEN

1082A

CANTEEN STO

1082B

REFRIG

STAIRS

REC STORAGE

1085A

REC STORAGE

REC KITCHEN

SOCIAL ROOM

REC OFFICE

REC OFFICE

GYM

FAC

FAC

OFFICE

STAIRS

LIBRARY OFFICE

CLOSET

STORAGE

STORAGE

OFFICE

OFFICE

EQUIP RM

BRK RM

LOBBY

1042A

STAIRS

VESTIBULE

VESTIBULE

ORCH. STAGE

STAGE

STAIRS HALL

STAIR HALL

FAC

STAIRS

PASSAGEWAY

STAIRS

ELEC CLO

1089B

ELEC CLO

LOBBY

DISH RM

CORR

FAC

1084A

ELECT.

CANTEEN DINING RM

FAC

COATS

UTIL.

FAC

LOBBY

TO FAN RM

TO GRID

M004

FAN ROOM

UPSTAIRS

M005

FAN ROOM

UPSTAIRS

OFFICE

1047A

TOILET

1042B

Stor.

1011A

STORE RM

CORR

FAC

E

LE

C C

L

1098A

FAC

1046A

STORAGE

TELLER

1056A

CLASS ROOM

1056B

CLASS ROOM

LIBRARY WING CENTER WING

T H

E A

T R

E W

E S T

CANTEEN WING

CENTER WING

T H

E A

T R

E W

IN

G

CENTER WING

CENTER WING

ELEVATOR

EQUIP. RM.

MECHANICAL ENG.

STAIRS

MECH. EQUIP.

REC STORAGE

STORAGE

F

F

F

F

F

F

F

F

F

F

F F

F

F

F F

F

F

F

F F

FF

F

F

F S

F S

FF

S

F F S

F

SF

S

F

SF

S

FAAP

F

F S

F S

F

F S

F S

F

KHFS

FF

F

F S

FFF

S

F S

F S

F S

F S

F

F

F

AATPFA

C

P

EPR

EAR

F

F

FF

S

F S

XN

XN

XN

XN

XN

XN

XN

XN

XN XN

XNXN

XN XN XN

XN

XN XN

XD

XD

XD

XR

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD122

BLDG 6 FIRST FLOOR

EXISTING/DEMOLITION 6

1 BLDG 6 FIRST FLOOR

3/32" = 1'

ASSEMBLY OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

1. DEMOLISH EXISTING FACP. EXTEND EXISTING

SLC CIRCUITS TO NEW FACP LOCATION.

2. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).

EXTEND EXISTING NAC AND SPEAKER CIRCUITS

TO NEW NACP AND DAA LOCATION.

1011A

WELLNESS

MECHANICAL

EXAM

STORAGE

77 1023

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

DRIVER TRAINING

BREAK ROOM

EQUIPMENT STORAGE

OFFICE

STORAGE

MECH. RM

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

TOILET

LAB

OFFICE/STORAGE

EXAM

EXAM

EXAM

EXAM

MECHANICAL

PROSTHETICS STORAGE

STORAGE

1011A

F. LOCKER

M. LOCKER

HAC

M. TLT

M. TLT

M. LOCKER RM

OFFICE

OFFICE

CHIEF/CONF

OFFICE

OFFICE

TOILET

SHW RM

HAC

TOILET

TOILET

67 1124

GEN STORAGE

ELEC. CLS

EXAM

FAC

WAITING

KINNESIOTHERAPY

RECEPT.

OCC. THERAPY

WORK ROOM

FAC

PIPE SPACE

TLT

OFFICE

CORRIDOR

CORRIDOR

CORRIDOR

LOBBY

CORRIOR

FEC

CORRIOR

CORRIOR

CORRIOR

CORRIDOR

CORRIOR

CORRIOR

1054A

OFFICE

GOO1

MECHANICAL ROOM

PIPE

TOILET

PIPE SPACE

TO BUILDING 10

T O

B U

IL

D

IN

G

F F S

F S

F S

F S F

S F S

F S

F S

F S

F S

F

SF

S

F S

F

FF

F

FFFF

F

F

FA

C

PA

A

TP TC

F

F

F

F

F

F

F

F F

F F

F S

F

F

F

FB

FB

~50'

XN

XN XN

XN

XN

XD

XN

PROSTHETICS

STORAGE GREENHOUSE

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD123

BLDG 7, BLDG 24, BLDG 30

EXISTING/DEMOLITION 7, 24, 30

1 BLDG 7 FIRST FLOOR

3/32" = 1'

2 BLDG 7 BASEMENT

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

3 BLDG 24 STORAGE

3/32" = 1' 4 BLDG 30

3/32" = 1' STORAGE OCCUPANCY

NOT SPRINKLERED

STORAGE OCCUPANCY

NOT SPRINKLERED

BUSINESS OCCUPANCY

FULLY SPRINKLERED

INDUSTRIAL OCCUPANCY

FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

1. REPLACE FACP. EXISTING BACKBOX/CABINET MAY

BE RE-USED IN-PLACE IF ADEQUATELY-SIZED.

PROVIDE NEW FIBER PATCH PANEL.

2. REPLACE AATP (NOTIFIER XPIQ) WITH NACP AND

DAA. RECONFIGURE NAC AND SPEAKER CIRCUIT

AS REQUIRED.

ELEV MACHINE

ROOM

A001

ELEVATOR 1

S1

ELEVATOR 2

S2

ELEVATOR LOBBY

AC001

EPR

EAR

EST

ESTPSF

F S

F F S F

S

F F

DN

A1

STAIR

A135 PATIENT ROOM 15

A134

DOUBLE PATIENT

ROOM 14

A133

BATHROOM 15

A134A

BATHROOM 14

A133A

SECLUSION

A131

ANTE ROOM

A131A

TLT

A131B

SINGLE PATIENT

ROOM 13

A122

BATHROOM 12

A124A

BATHROOM 13

A122A

SINGLE PATIENT

ROOM 12

A124

DOUBLE PATIENT

ROOM 11

A126

BATHROOM 11

A126A

BATHROOM 10

A129A

DOUBLE PATIENT

ROOM 10

A129

SINGLE PATIENT

ROOM 9

A127

BATHROOM 8

A125A

BATHROOM 9

A127A

PATIENT ROOM 8

A125

SCREENED

PORCH 2

A123

GROUP ROOM

A121

BARIATRIC

BATHROOM 7

A112A

BREAK

A108

LAUNDRY

STORAGE

A110

BARIATRIC

PATIENT ROOM 7

A112

SINGLE PATIENT

ROOM 6

A114

BATHROOM 6

A114A

BATHROOM 5

A116A

SINGLE PATIENT

ROOM 5

A116

DOUBLE PATIENT

ROOM 4

A118

BATHROOM 4

A118A

TV AREA

A117

BATHROOM 3

A115A

DOUBLE PATIENT

ROOM 3

A115

SINGLE PATIENT

ROOM 2

A113

BATHROOM 1

A111A

BATHROOM 2

A113A

PATIENT ROOM 1

A111

SCREENED

PORCH 1

A109LAUNDRY

A107

SECURE

VESTIBULE

A101

FAMILY

CONFERENCE

A102

CONSULT 1

A104

HALL

AC110

CONSULT 2

A106

OFFICE 7

A158

OFFICE 3

A159

OFFICE 4

A160

OFFICE 5

A161

ELEVATOR

VESTIBULE

A175

OFFICE 2

A156

OFFICE 1

A155

STAFF BREAK

A154

OFFICE 12

A153

OFFICE 11

A152

OFFICE 10

A151

OFFICE 9

A150 WARD CLERK

A120C

WORK ROOM

A120B

TEAM ROOM

A141

CLEAN STORAGE

A142

ST TLT

A144B

ST TLT

A144A

STAFF LOCKERS

A144

MEDICATION

A120A

CLEAN LINEN

A140

QUIET ROOM

A130SHOWER

A132

CORRIDOR

AC104

ELECTRICAL 3

A146

COMM

A171

ELEVATOR 2

S2

ELEVATOR 1

S1

OFFICE 8

A157

OFFICE 6

A162

PATIENT

PROPERTY

A163

DAY

AC102B

DINING

AC103A

DAY

AC103B

SERVICE

CORRIDOR

AC106

PUBLIC

CORRIDOR

AC111

SOILED UTILITY

A145 HAC

A143

AIR HANDLER

ROOM

A172

LOBBY

A100

EXAM

A103

SERVING

A105

ELEVATOR

MACHINE ROOM

A170

STAIR 1

AS101

HALL

AC105

NURSING

STATION

A120

PATIENT

CORRIDOR

AC103

HALL

AC107

HALL

AC108

HALL

AC109

PATIENT

CORRIDOR

AC102 DINING

AC102A

ELECTRICAL 1

A173

ELECTRICAL 2

A174

GROUP ROOM

CLOSET

A121A

PATIENT

CORRIDOR

AC101

CORRIDOR

AC104A

A105A

ABOVE

SUB PORCH

(GROUP)

A121B

TV AREA

A128

STANDPIPE

CHASE

AS101A

ELEVATOR

P1

ELEVATOR

P2

ENTRY

VESTIBULE

SECURITY

OPEN TO ABOVE

OPEN

TO

ABOVE

HAS OFFICE

AL

IG

N

UP

TO BUILDING 4

TO BUILDING 4

UP

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S F

S F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S F

S

F S F

S F S

F S

F S

F S

F S

F F

F F F

F

F

F

F

FF F

F

F

F

F

FF

F S

F

FF

FA

C

P

F S

F S

F

F

F F

F S

F S

F F F

F S

F S

F

F S

F

F

SF

F

SF

FACP

F F

F

F F

F F

F

F S

F S

F S

F S

F S

F S

F

F F

F

F

F F F

F S

F F

F

F S

F

F

F

F S

F S

F

F

F

F F S

FC

F F

F

N A

C

EPR

EAR

EICN

EST

ESTPS

EST

EST

EST

~15'

~15'

1. FIRE ALARM SYSTEM SHALL NOT BE DEMOLISHED.

ALL DEVICES AND COMPONENTS SHALL REMAIN.

SHOWN HERE FOR REFERENCE ONLY.

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD124

BLDG 8 GROUND AND FIRST FLOOR

EXISTING/DEMOLITION 8

1 BLDG 8 GROUND FLOOR

3/32" = 1'

2 BLDG 8 FIRST FLOOR

3/32" = 1'

HEALTH CARE OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

UPDN

DN

DOUBLE

PATIENT ROOM

A229

TV AREA

A228

SCREENED

PORCH 1

A209

PATIENT ROOM

A211

BATHROOM 1

A211A

SINGLE

PATIENT ROOM

A213

BATHROOM 2

A213A DOUBLE

PATIENT ROOM

A215

BATHROOM 3

A215A

TV AREA

A217

DOUBLE

PATIENT ROOM

A218

BATHROOM 4

A218A

SINGLE

PATIENT ROOM

A216

BATHROOM 5

A216A

SINGLE

PATIENT ROOM

A214

BATHROOM 6

A214A

BARIATRIC

PATIENT ROOM

A212

BARIATRIC

BATHROOM 7

A212A

Clean Linen A210

Nourish A208

GROUP ROOM

A221

GROUP ROOM

CLOSET

A221A

SUB PORCH

(GROUP)

A221B

SCREENED

PORCH 2

A223

PATIENT ROOM

A225

SINGLE

PATIENT ROOM

A227

BATHROOM 9

A227A

BATHROOM 8

A225A

BATHROOM 10

A229A

BATHROOM 11

A226A

DOUBLE

PATIENT ROOM

A226

SINGLE

PATIENT ROOM

A224

BATHROOM 12

A224A

BATHROOM 13

A222A

SINGLE

PATIENT ROOM

A222

TLT

A231B

ANTE ROOM

A231A

SECLUSION

A231DOUBLE

PATIENT ROOM

A233

BATHROOM 14

A233A

BATHROOM 15

A234A

PATIENT ROOM

A234

ELECTRICAL 3

A246

SOILED UTILITY

A245

SHOWER

A232

HAC

A243

QUIET ROOM

A230

STAFF

LOCKERS

A244

STAFF BREAK

A254

OFFICE 12

A253

OFFICE 11

A252

OFFICE 10

A251

OFFICE 9

A250

CLEAN

STORAGE

A242

TEAM ROOM

A241 WORK ROOM

A220B

WARD CLERK

A220C

MEDICATION

A220A

ST TLT

A244B

ST TLT

A244A

NURSING

STATION

A220

OFFICE 1

A255

OFFICE 2

A256 OFFICE 8

A257

PATIENT

PROPERTY

A263

OFFICE 7

A258

OFFICE 6

A262

OFFICE 3

A259

OFFICE 4

A260

OFFICE 5

A261 FAMILY

CONFERENCE

A202

CONSULT 1

A204

CONSULT 2

A206

SERVING

A205

EXAM

A203

SECURE

VESTIBULE

A201

COMM

A271

AIR HANDLER

ROOM

A272

DAY

AC202B

DINING

AC202A

DINING

AC203A

DAY

AC203B

PATIENT

CORRIDOR

AC202

LAUNDRY

A207

PATIENT

CORRIDOR

AC203

HALL

AC207

HALL

AC208

HALL

AC210

HALL

AC209

CORRIDOR

AC204

CORRIDOR

AC204A

HALL

AC205 CLEAN LINEN

A240

SERVICE

CORRIDOR

AC206

ELEVATOR

VESTIBULE

A275

STORAGE

A276

STORAGE

A273A

FEMALE PUBLIC

TOILET

A277

STAIR 1

AS201

EXIST.

ELEVATOR 2

P2

EXIST.

ELEVATOR 1

P1

MALE PUBLIC

TOILET

A278

GROUP ROOM

A273

PUBLIC

CORRIDOR

AC211

ELEVATOR

VESTIBULE

A274

EXIST ELEV

S1

EXIST ELEV

S2

STAIR 2

AS202

HAC

A280PUBLIC

CORRIDOR

AC212

A205-A

OPEN TO BELOW

OPEN TO BELOW

FUTURE

CONFERENCE

ROOM

A279

FF

F S

F

F S

F S

F S

F S

F S

F S

F S

F

SF

S F S

F S

F S

F S

F S

F S

F S F

S

F S

F S

F

SF

S F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S F

S

F S

F

F

F

F

F

F

F

F F

F F

F

F

F

F

F

F

F

F

F F

F

FF

F

F

F

F

F S

F S

F S

F S

F S

F S

F S

F S

FF

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F S

F

F S

F

F S

FC

F

F

N A

C

1. FIRE ALARM SYSTEM SHALL NOT BE DEMOLISHED.

ALL DEVICES AND COMPONENTS TO REMAIN. SHOWN

HERE FOR REFERENCE ONLY.

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD125

BLDG 8 SECOND FLOOR

EXISTING/DEMOLITION 8

1 BLDG 8 SECOND FLOOR

3/32" = 1'

HEALTH CARE OCCUPANCY - FULLY SPRINKLERED

DEMOLITION NOTES

SINGLE

PATIENT ROOM

A316

BATHROOM 5

A316A

SINGLE

PATIENT ROOM

A314

BATHROOM 6

A314A

BARIATRIC

PATIENT ROOM

A312

PAT TLT

A310

CLEAN

LINEN

A308

GROUP ROOM

CLOSET

A321A

EXERCISE

ROOM

A323

PATIENT ROOM

A325

SINGLE

PATIENT ROOM

A322

TLT

A331B

ANTE ROOM

A331A

QUIET ROOM

A330

OFFICE 9

A350

TEAM ROOM

A341 WORK ROOM

A320B

MEDICATION

A320A

DAY

AC302B

WARD CLERK

A320C

GROUP ROOM

A321

BARIATRIC

BATHROOM

A312A

DINING

AC302A

CLEAN LINEN

A340

DINING

AC303A

NURSE

STATION

A320

PATIENT

CORRIDOR

AC303

SECLUSION

A331

DN

AIR HANDLER

ROOM

A372

STORAGE

A373A

MALE PUBLIC

TOILET

A378

GROUP ROOM

A373

EXIST

ELEVATOR 1

P1

EXIST.

ELEVATOR 2

P2

ELEVATOR

VESTIBULE

A374

PUBLIC

CORRIDOR

AC312

STAIR 2

AS302

HAC

A380

FEMALE TOILET

A377

EXIST ELEV

S1

EXIST ELEV

S2

DOUBLE

PATIENT ROOM

A329

TV AREA

A328

SCREENED

PORCH 1

A309

PATIENT ROOM

A311

BATHROOM 1

A311A

SINGLE

PATIENT ROOM

A313

BATHROOM 2

A313A DOUBLE

PATIENT ROOM

A315

BATHROOM 3

A315A

TV AREA

A317

DOUBLE

PATIENT ROOM

A318

BATHROOM 4

A318A

SINGLE

PATIENT ROOM

A327

BATHROOM 9

A327A

BATHROOM 8

A325A

BATHROOM 10

A329A

BATHROOM 11

A326A

DOUBLE

PATIENT ROOM

A326

SINGLE

PATIENT ROOM

A324

BATHROOM 12

A324A

BATHROOM 13

A322A

DOUBLE

PATIENT ROOM

A333

BATHROOM 14

A333A

BATHROOM 15

A334A

ELECTRICAL 3

A346

SOILED UTILITY

A345

SHOWER

A332

HAC

A343

STAFF

LOCKERS

A344

STAFF BREAK

A354

OFFICE 12

A353

OFFICE 11

A352

OFFICE 10

A351

CLEAN

STORAGE

A342

ST TLT

A344B

ST TLT

A344A

OFFICE 1

A355

OFFICE 2

A356 OFFICE 8

A357

PATIENT

PROPERTY

A363

OFFICE 7

A358

OFFICE 6

A362

OFFICE 3

A359

OFFICE 4

A360

OFFICE 5

A361 FAMILY

CONFERENCE

A302

CONSULT 1

A304

CONSULT 2

A306

EXAM

A303

LAUNDRY

A307

HALL

AC307

HALL

AC308

HALL

AC310

HALL

AC309

CORRIDOR

AC304A

HALL

AC305

SERVICE

CORRIDOR

AC306

ELEVATOR

VESTIBULE

A375

PATIENT ROOM

A334

PUBLIC

CORRIDOR

AC311

STAIR 1

AS301

COMM

A371

SECURE

VESTIBULE

A301

SERVING

A305

CORRIDOR

AC304

DAY

AC303B

PATIENT

CORRIDOR

AC302

A305-A

F S

F

F S

F S

F

SF

S F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

FC

F S

F S

F S

F S

F S

F S

F S

F S

F S F

S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

SF

S

F S

F S

F S

F S

F S

F S

F S

F

SF

S F S

F S

F S

F

F

F

F

F

F

F

F

F

F

F

F

F F

F S

F

F

F

F

F F

F

F

F

F

F F

F

F

F

F

F S

F

F

F

F S

F

F F

F

F

F

FF

F

F

F

F

F S

F

F F

F F

F

F F

F

F

F F

N A

C

1. FIRE ALARM SYSTEM SHALL NOT BE DEMOLISHED.

ALL DEVICES AND COMPONENTS TO REMAIN. SHOWN

HERE FOR REFERENCE ONLY.

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD126

BLDG 8 THIRD FLOOR

EXISTING/DEMOLITION 8

1 BLDG 8 THIRD FLOOR

3/32" = 1'

HEALTH CARE OCCUPANCY - FULLY SPRINKLERED

DEMOLITION NOTES

G03

LARGE CLASSROOM

G14B

M. TOILET

G17

OPEN OFFICE

G17A

STORAGE

G18

MECH ROOM

G18A

MECH

G19

MECHANICAL EQUIPMENT

G12

OFFICE

G11

OFFICE

130G10

OFFICE

G09

OFFICE

G06

OFFICE

G01

OFFICE/DINING

G02

KITCHEN

G07 Office

G05 Bathrm

G14

WAITING

G13

OFFICE

G14A

F. TOILET

G21

ENG

G20

ENG

G08

CORRIDOR

G22

CORRIDOR

G15

FAC

G16

STAIR

G04

CORRIDOR

G26

BREAK/OFFICE

G25

MECHANICAL RM

G16A

STORAGE

G03B

SPRINKLER RM

ENTRY

VESTIBULE

G001

CORRIDOR

G002G002

DN

MAIN

ELEC

G-40 Crawl

Space

Crawl 2

F

F

FACP

F F S

FB

F S

F S

F

FA

A

PF

NACP

DAA

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD127

BLDG 11 GROUND FLOOR

EXISTING/DEMOLITION 11

1 BLDG 11 GROUND FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND NO TAG ARE

EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

RESIDENT

ROOM

A103

RESIDENT

ROOM

A102

RESIDENT

BATHROOM

A104

RESIDENT

BATHROOM

A105

RESIDENT

ROOM

A107

RESIDENT

ROOM (2)

A106

RESIDENT

ROOM

A108

RESIDENT

ROOM

A109

RESIDENT

BATHROOM

A111

RESIDENT

BATHROOM

A110

OFFICE -

AT(2)

A112

STAFF

WORK

AREA

A114

NUTRITION

A133

LAUNDRY

A135

RESIDENT

BATHROOM

A138

RESIDENT

ROOM (2)

A140

RESIDENT

ROOM

A142

RESIDENT

BATHROOM

A144

RESIDENT

ROOM

A146

RESIDENT

ROOM

A147

RESIDENT

BATHROOM

A145

RESIDENT

ROOM

A143

RESIDENT

ROOM

A141

RESIDENT

BATHROOM

A139

RESIDENT

ROOM

A137

REC

B108

WOMEN'S

TOILET

A117MEN'S

TOILET

A116

TELECOM

A115

RESIDENT

ROOM

A113

PHONE

ROOM

A136

NURSE

MGR.

B106

OFFICE

B107

VESTIBULE

A131

VESTIBULE

A131

GROUP

B110

DINING

B117

KITCHEN

B114

PANTRY

B116

OFFICE -

PA

B125

EXAM

B124

STAFF

WORK

AREA

B126

MEDS

B127

ELEVATOR

B128

STAIR

B131

STORAGE

B132

WAITING

B146

RECEPTION

B145

SHOWER

B144

EXAM

B141

OFFICE -

DR

B140

FAMILY

ROOM

B150

FAMILY

ROOM

B151

PEDS

FAMILY

ROOM

B152

WOMEN'S

TOILET

B134

MEN'S

TOILET

B136

WOMEN'S

TOILET

B137

WOMEN'S

LOUNGE

B138

ELEC

B130

CODE

SUPPLY

B129

ADMIT

NURSE

B118

OFFICE

B120

SMALL

GROUP

B122

OFFICE -

MANAGER

B123

GROUP

B153

GROUP

B154

FITNESS

CENTER

B155

CONFERENCE

B160

JANITOR

B115

STAFF

WOMEN'S

TOILET

B112

STAFF

MEN'S

TOILET

B111

BREAK

B113

VESTIBULE

B121

TOILET

B143

TOILET

B142

MEN'S

TOILET

B133

WC

STORAGE

B135

OFFICE -

SW

B166

OFFICE -

SW

B165

OFFICE -

SW

B164

TELECOM

B162

STORAGE

B163

GROUP

B109

ELEVATOR

LOBBY

B147

MEN'S

TOILET

C115

WOMEN'S

TOILET

C116

TELECOM

C114

RESIDENT

ROOM

C112

RESIDENT

BATHROOM

C110

RESIDENT

ROOM

C108

RESIDENT

ROOM (2)

C106

RESIDENT

BATHROOM

C104

RESIDENT

ROOM

C102 RESIDENT

ROOM

C103

RESIDENT

BATHROOM

C105

RESIDENT

ROOM

C107

RESIDENT

ROOM

C109

RESIDENT

BATHROOM

C111

OFFICE -

AT (2)

C113

STAFF

WORK

AREA

C117

DEN

C120

LIBRARY

C119

ELEC

C124

SOILED

UTILITY &

LINEN

C122

CLEAN

SUPPLY

C123

RESIDENT

ROOM

C126

RESIDENT

BATHROOM

C128

RESIDENT

ROOM

C130

RESIDENT

ROOM

C129

RESIDENT

BATHROOM

C127

RESIDENT

ROOM

C125

VESTIBULE

C131

CLEAN

LINEN

C149

H.A.C.

C150

OFFICE

C151

RESIDENT

ROOM

C155

RESIDENT

BATHROOM

C157

RESIDENT

ROOM

C159

OFFICE

C152

RESIDENT

BATHROOM

C153

RESIDENT

ROOM

C154

RESIDENT

ROOM

C156

RESIDENT

BATHROOM

C158

RESIDENT

ROOM

C160

RESIDENT

ROOM

C162

RESIDENT

BATHROOM

C164

RESIDENT

ROOM

C166

RESIDENT

ROOM

C165

RESIDENT

BATHROOM

C163

RESIDENT

ROOM

C161

RESIDENT

ROOM

C146

RESIDENT

BATHROOM

C144

RESIDENT

ROOM

C142

RESIDENT

ROOM (2)

C140

RESIDENT

BATHROOM

C138

LAUNDRY

C135

NUTRITION

C133

LIVING

ROOM

C134

PHONE

ROOM

C136

RESIDENT

ROOM

C137

RESIDENT

BATHROOM

C139

RESIDENT

ROOM

C141

RESIDENT

ROOM

C143

RESIDENT

BATHROOM

C145

RESIDENT

ROOM

C147

STORAGE

B156

STAFF

BREAK

B157

MEN'S

STAFF

TOILET

B158

WOMEN'S

STAFF

TOILET

B159

OFFICE -

SW

B167

DN

ELEC

AXXX

F

F

F F

F

FFF

F

F

F

F

F F

F

F

F

F

F F

F

F

F F

F

F F

F F

F F

F F

FF

F

F

F

F F

F

F F

F

F

F F F

F

F F

F

F F

F

F

F

F F

F

F

F F

F

F

F

F

F

F

F

FF

F

F

F

F

F

F F

FF

F

F F

F

F

F

F F

F F

F

F

F

F

F

F F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

FF

F F F F

F

F F

FFF

FF

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

RL

F

FF

F

F F

F

F

F F

F F FF

F

F

F

F

F

F

F

F

F FA

A

P

F

F

F

F F

F

F F

F F

FACP

F

F

F

F

F

F

EC

M A

TC

H

LI

N

E

XN

XN

XN

XN

XN

XN

XN

XN

XN

XN

XN

XN

XN

XN

LIBRARY

A119

DEN

A120

LIVING

ROOM

A134

CONFERENCE ROOM

F F F

F

F

F

F

F

M A

TC

H

LI

N

E

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD128

BLDG 11 FIRST FLOOR

EXISTING/DEMOLITION 11

1 BLDG 11 FIRST FLOOR (ALL DEVICES TO REAMIN)

3/32" = 1'

FULLY SPRINKLERED

DEMOLITION NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATIONS SHALL BE ACCESSIBLE, WITH

HEIGHT ACCORDING TO NOTES AND

SPECIFICATIONS.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

GROUP ROOM

GROUP ROOM

BREAK RM

93 101

BATHROOM

BATHROOM

HOUSE KEEPING

ELEC

OFFICE

WAITING ROOM

RECEPTION

OFFICE

OFFICE

STAFF BATH

STAFF BATH

R R R R R R

RRRRRR

R

R

R R

R

R

F

F

F

F

F F

F

F

FA

C

P

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

GROUP ROOM

GROUP ROOM

BREAK RM

BATHROOM

BATHROOM

EMS

ELEC

OFFICE

WAITING ROOM

RECEPTION

OFFICE

OFFICE

STAFF BATH

STAFF BATH

R R R R

R

F F

F

F S

F

FF

F

F

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CALL CENTER

GROUP ROOM

Med/Inject

BATHROOM

BATHROOM

EMS

ELEC

BREAK RM

WAITING ROOM

RECEPTION

OFFICE

OFFICE

STAFF BATH

STAFF BATH

CORRIDOR

F F

F

F

F S

F S

F S

F

F

F

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD129

BLDG 11A, BLDG 11B, BLDG 11C

EXISTING/DEMOLITION 11

1 BLDG 11A

1/8" = 1' 1 BLDG 11B

1/8" = 1' 1 BLDG 11C

1/8" = 1'

BUSINESS OCCUPANCY - NOT SPRINKLERED

GENERAL NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

CONFERENCE ROOM

KITCHEN

ELECTRICAL 109

HW TANK

ARMORY

SECRETARY

HALLWAY

HALLWAY

COMMUNICATION

102B

KITCHEN

CLOS.

TOILET

CLOS.

STAIRS

102A

HALLWAY

R

XD

OFFICE

OFFICE

OFFICE

BATH

BATH

CLOSET

CLOSET

OFFICE

LOCKERS

CLOS

CLOSET

CLOSET

CORRIDOR

STAIRS

R

XD

CONFERENCE

KITCHEN

DINING

BEDROOM

JANITOR

ADA TOILET

FEMALE

TOILET

HALL

118 OFFICE

ADA TOILET

LIVING

MECH.

LAUNDRY

COMPUTER

LOBBY

STAIR

MECH.

IT

119SCREENED

PORCH

F

F

F

F

F

F

F

F

F

FF

F

F

F F

F

FA

C

P

XD

XD

XDXD

XD

XD

XD

DN

BEDROOM

BEDROOM

BEDROOM

FEMALE

BEDROOM

TOILET

BEDROOM

BEDROOM

TOILET

TOILET

STORAGE

TOILET

BEDROOM

TOILET

STORAGE

LAUNDRY

HALL

217F

F

FXD XD

CONFERENCE RM

CONFERENCE RM

KITCHEN

KITCHEN

LAUNDRY

LAUNDRY

VESTIBULE

KENNEL

STORAGE

VESTIBULE

TOILET

106A

TOILET

CLOSET

CLOSET

U P

U P

R R

XD XD

M LOCKER RM.

M. BEDROOM

OFFICE

OFFICE

OFFICE

W. BEDROOM / LOCKER

BATH

BATH

PASSAGE

PASSAGE

D N

D N

R R

XD XD

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD130

BLDG 12, BLDG 14W, BLDG 14E

EXISTING/DEMOLITION 12, 14E, 14W

1 BLDG 12 FIRST FLOOR

1/8" = 1'

2 BLDG 12 SECOND FLOOR

1/8" = 1'

3 BLDG 14E FIRST FLOOR

1/8" = 1'

4 BLDG 14E SECOND FLOOR

1/8" = 1'

5 BLDG 14W FIRST FLOOR

1/8" = 1'

6 BLDG 14W SECOND FLOOR

1/8" = 1' RESIDENTIAL OCCUPANCY

FULLY SPRINKLERED

RESIDENTIAL OCCUPANCY

FULLY SPRINKLERED

RESIDENTIAL OCCUPANCY

FULLY SPRINKLERED

RESIDENTIAL OCCUPANCY

FULLY SPRINKLERED

BUSINESS OCCUPANCY

FULLY SPRINKLERED

BUSINESS OCCUPANCY

FULLY SPRINKLERED

GENERAL NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

9. FOR BUILDING 14E, STROBES SHOWN AS DEMO

SHALL BE REPLACED WITH SPEAKER-STROBES

IN THE SAME LOCATION.

B01

MECH. ROOM

B02

TRANSFORMER RM

BEDROOM

BEDROOM

BEDROOM

ELECTRICAL ROOM

KITCHEN

LOUNGE

READING ROOM

LOBBY

UNISEX B/R

BEDROOM

LOBBY

LAUNDRY

BEDROOM

BEDROOM

132A

BEDROOM

BEDROOM

BEDROOM

BEDROOM

ENTRY

STAIRS

CLOSET

STAIRS

BATH

BATH

CLOSET

CLOSET

CLOSET

BATH

BATH

BATH

BATH

BATH

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

13 114

CLOSET

CLOSET

105A

CLOSET

149B

FEC

F

F

F

F

F F F

F F

F

F

F

F F

F

F

F

F F

F

F

FFFF

FACPEP

F

FF F

F

F F

FB

FACP

F F

F

F

E P

BEDROOM

BATH

CORRIDOR

STAIRWELL

BEDROOM

CLOSET

BATH

BEDROOM

BEDROOM

BATH

47 216

STORAGE

LA/ OIT

ELECTRIC CLOSET

TELE CLST

BATH

BEDROOM

BATH

BEDROOM

210 203

BEDROOM

BATH

STAIRS

TOILET

BEDROOM

BATH

CLOSET

BEDROOM

LAUNDRY

BEDROOM

KITCHEN

BATH

BEDROOM

BEDROOM

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

F F F F

F

F F F

F

F

F

FF

F

F

F

FF

F

F F

F

F

F

F

F

F

FF

NACP

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD131

BLDG 13 EXISTING/DEMOLITION

2 BLDG 13 SECOND FLOOR

3/32" = 1'1 BLDG 13 FIRST FLOOR

3/32" = 1'

3 BLDG 13 BASEMENT

3/32" = 1'

RESIDENTIAL OCCUPANCY - NOT SPRINKLERED

GENERAL NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.