36C24618R0839-004.pdf
PDF 7 MB Posted
- Attached to
- Project 659-16-103, Replace Campus Fire Alarm System Federal contract opportunity
- Solicitation number
- 36C24618R0839
About this file
36C24618R0839 CONTRACT ATTACHMENT A - DRAWINGS FILE 3 - 03-Sheets_FD117-131.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24618R0839-0003002.pdf | ||
| 36C24618R0839-0003001.pdf | ||
| 36C24618R0839-0003000.docx | DOCX document | |
| 36C24618R0839-0002001.pdf | ||
| 36C24618R0839-0002000.docx | DOCX document | |
| 36C24618R0839-013.docx | DOCX document | |
| 36C24618R0839-008.pdf | ||
| 36C24618R0839-012.pdf | ||
| 36C24618R0839-009.pdf | ||
| 36C24618R0839-002.pdf | ||
| 36C24618R0839-006.pdf | ||
| 36C24618R0839-001.docx | DOCX document | |
| 36C24618R0839-014.pdf | ||
| 36C24618R0839-005.pdf | ||
| 36C24618R0839-003.pdf | ||
| 36C24618R0839-010.pdf | ||
| 36C24618R0839-007.pdf | ||
| 36C24618R0839-011.pdf | ||
| 36C24618R0839-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OFFICE
30363036
OFFICE-RN
30373037
OFFICE- VJO
30383038
OFFICE
30353035
OFFICE-SW
COORD
30333033
OFFICE- PSA
30393039
BREAK ROOM
30323032
WOMEN TLT
30403040
OFFICE- SWS
30223022
OFFICE- SWS
30233023
OFFICE- SWS
30243024 OFFICE- SWS
30253025
OFFICE- SWS
30263026
OFFICE- SWS
30213021
OFFICE- SWS
30203020
OFFICE- SWS
30193019
OFFICE- SWS
30183018
HAC
30173017
OFFICE-
PRIMARY CARE
30153015
OFFICE- CHIEF
SWS
30143014
OFFICE- ASST
CHIEF SWS
30133013
OFFICE- AO
30123012
HCMI PSA
30103010
COPY ROOM
30093009
OFFICE- GPD
30083008
OFFICE- GPD
30073007
OFFICE- GPD
30063006
OFFICE- GPD
30053005 MEN
30043004
MEN TLT
COMM
OFFICE-
ADDICTION
SPECIALIST
OFFICE-
OUTREACH
OFFICE
WOMEN
30923092
OFFICE
30553055
HAS/PSA
30033003
WAITING
30543054
WAITING
26 SF
VEND
HA
LL
W
AY
CORRIDOR
C302C302
VESTIBULE
30023002
PATIENT
CHECK-IN
30013001
CORRIDOR
C301
EXISTING
DINING
CORRIDOR
C305C305
STOR
HALLWAY
30163016
HALLWAY
30293029
ROOM
ELEC
FEC
CWT OFFICE
FUTURE
30653065
BREAK ROOM
30643064
CWT OFFICE
FUTURE
30663066
CWT OFFICE
FUTURE
30683068
CONFERENCE
30733073
OFFICE-VOC
REHAB 1
30753075
OFFICE-VOC
REHAB 2
30763076
OFFICE-VOC
REHAB 3
30773077
OFFICE-VOC
REHAB 4
30783078
OFFICE-VOC
REHAB 5
30793079
OFFICE-VOC
REHAB 6
30803080
OFFICE-MA
REHAB 1
30813081
OFFICE
30823082
EXAM TLT
30833083
HAC
30693069
EXAM- PA
OFFICE
30843084
SAS GROUP
ROOM
30853085
OFFICE-
PSYCHIATRIST
30863086
MED
30873087OFFICE
30883088
OFFICE- OP/SAS
SOCIAL WORK
30893089
OFFICE- OP/SAS
MENTAL
HEALTH
30903090
OFFICE- OP/SAS
MENTAL
HEALTH
30913091
STAFF TLT
30633063
STAFF TLT
30623062
OFFICE- OP/SAS
SOCIAL WORK
30583058
OFFICE
30573057
CODE BLUE
30563056
CORRIDOR
C306C306
HALLWAY
30743074
PASSAGE
31123112
STOR
30593059
COMM
30603060
HALLWAY
30613061
ELEC
30703070
FEC
30733073
MY HEALTHY
VET
3001B3001B
OFFICE EQUIP
30673067
MOP
3052A
F F F
F
F
F
F
F F F
F
F
F
F
F
FF
F F
F
F
F
F
F
F F
F F
F
F
F
F
F
F
F
F
FF
F
F
F S
F S
F
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F
SF
S
F S
F S
F S
F S
F S
F S
F S
F S
F S F
S
F
FF
F S
F S
F
A A
TP
F S
KHFS
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD117
BLDG 4 THIRD FLOOR
EXISTING/DEMOLITION 4
1 BLDG 4 THIRD FLOOR
3/32" = 1'
BUSINESS OCCUPANCY - FULLY SPRINKLERED
DEMOLITION NOTES
KEYED NOTES #
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
1. REPLACE AATP (NOTIFIER XPIQ) WITH A NACP
AND A DAA. RECONFIGURE NAC AND SPEAKER
CIRCUITS AS REQUIRED.
DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8
6/25/2018
B WING CENTER WING CENTER WING A WING
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
FF
F
FF
FC
FC
F F
F
F
EPR
EAR
FC
A A
TP
TC
XN
XN
XN
XN
XN XN
XN
XN
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD118
BLDG 4 FOURTH FLOOR AND PENTHOUSE
EXISTING/DEMO 4
1 BLDG 4 FOURTH FLOOR
3/32" = 1'
2 BLDG 4 B-WING PENTOUSE
3/32" = 1' 3 BLDG 4 CENTER PENTOUSE
3/32" = 1' 4 BLDG 4 A-WING PENTOUSE
3/32" = 1'
HEALTH CARE OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
KEYED NOTES #
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
1. REPLACE AATP (NOTIFIER XPIQ) WITH A NACP
AND A DAA. RECONFIGURE NAC AND SPEAKER
CIRCUITS AS REQUIRED.
G032
VENDING STORAGE
G033
CANTEEN STORAGE
G031
MOBILE STORAGE
G052
OFFICE
G032A
CONCESSION ROOM
GO30A
OFFICE
G030
CANTEEN OFFICE
G029
RETAIL SALES
G026
STORAGE
G025
CHILLER
G024
REFRIG.
GO73
REFRIG.
G021
OFFICE
G017
KITCHEN
G018
DISHWASHING
G006
CART WASH
ENTRY
G003
STORAGE
G004
FREEZER
G005
DEEP FREEZE
G001
ELECT. CLOSET
G036
UNEXCAVATED AREA
G035
STAIRS
G016
ELE LOBBY
G010
REFRIG
G012
STORAGE
G017B
OFFICE
G017A
OFFICE
G040
LOCKER
G037
LOCKER
G038
SHWR
G041
SHWR
G042
SHWR
G043
LOCKER
G045
LOCKER
G047
SHWR
G043
MECHANICAL
G050
LOUNGE
1050A
STORAGE
G051
TOILET
G049
STAIRS
G027
FAC
G009
CLOSET
G020
FAC
1050B
VENDING
G007
ELECTRICAL
G048A
MECH.
G052A
MECHANICAL
G031A
CANTEEN STORAGE
G044
ELEV MEC RM
GO53
ELECT. CLOSET
GO28
CORRIDOR
G046
CORRIDOR
G003A
FREEZER
G034
F S
F
SF
S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F
F
F
F
F
F
FACP A
A
TP
EPR
EAR
F
F F S
F
F F
KHFS
F
FB
FOER
FOER
MATCHLINE
KHFS
XN
XD
XD
XD
XD
XD
XR
F
F F
CHILLER PLANT
SHOP
LOCKER
OFFICE
SHW/TLT
100A
COMPUTER ROOM
100B
TOILET
TC
F
F
F S
F S
F S
F S
F
F
M A
TC
H
LI
N
E F S
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD119
BLDG 5 GROUND FLOOR, BLDG 31, BLDG 35
EXISTING/DEMOLITION 5
1 BLDG 5 GROUND FLOOR
3/32" = 1'
2 BLDG 31
3/32" = 1'
BUSINESS OCCUPANCY
FULLY SPRINKLERED
INDUSTRIAL OCCUPANCY
FULLY SPRINKLERED
3 BLDG 35
3/32" = 1' INDUSTRIAL OCCUPANCY
NOT SPRINKLERED
GENERAL NOTES
KEYED NOTES #
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
1. DEMOLISH EXISTING FACP. EXTEND EXISTING
SLC CIRCUITS TO NEW LOCATION.
2. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).
EXTEND EXISTING NAC AND SPEAKER CIRCUITS
TO NEW NACP AND DAA LOCATION.
REFRIG
VEG PREP
MECH. ROOM
DRY STORAGE
SUPPLY REFRIG
GARB. REFR
WASH RM
CART CHAR.
RECEIV. VEST.
OFFICE
MOP
CLOSET
CORRIDOR
BIOMED SHOP
DARK RM
CLOSET
CLOSET
1021A
OFFICE
1021B
OFFICE
OFFICE
TOLIET
1021C
OFFICE
CLOSET
OFFICE
TOILET
CLOSET
STAIRS
REFRIG
FREEZOR
STORAGE
1012A
TELE. ROOM
FAC
CORRIDOR
MECH. ROOM
STAIRS
M/F TOILET
TRAVEL
AGENT CASH
CORR
WAITING
STORAGE
202 SF
CONFERENCE
403 SF
CORRIDOR
C102
90 SF
STORAGE
200 SF
RECEPTION
183 SF
OFFICE
250SF
OFFICE
109 SF
OFFICE
OFFICE
CLOSET
23 SF
1056A
279 SF
STORAGE
116 SF
OFFICE
135 SF
STORAGE
84 SF
LOUNGE
94 SF
OFFICE
80 SF
OFFICE
102 SF
OFFICE
MEDICAL MEDIA
327 SF
403 SF
CORRIDOR
C103
403 SF
CORRIDOR
C101
STORAGE
CORRIDOR
CORRIDOR
CORRIDOR
M. TLT
F. TLT
LOBBY
F/A CABINET
CORRIDOR
376TO BUILDING 2
ROOF ROOF
BUILDING 2BUILDING 5 FIRST FLOOR
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F
F
F
F F
F F
F
F
F
F
F
F
F
F S
FAAP
F
F
TC
F
F S
F S
FSCP
F
F
F S
~60'
EPR
EAR
XN
XN
XN
XN
XR
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD120
BLDG 5 FIRST FLOOR
EXISTING/DEMOLITION 5
1 BLDG 5 FIRST FLOOR
3/32" = 1'
BUSINESS OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
SOUTH WINGNORTH WING
G065
PIPE SPACE
G064
PIPE SPACE
G013
PIPE SPACE
G009
PIPE SPACE
C O
R R
ID
O
R
OFFICE 9
OFFICE 10
OFFICE 11
OFFICE 12
OFFICE 13 SUPPORT
OFFICE 8
OFFICE 7
OFFICE 6
OFFICE 5
OFFICE 4
OFFICE 3
OFFICE 2
C O
R R
ID
O
R
TOUCH DOWN
RESOURCE RM
WOMENS ROOM
MENS ROOM
RECEPTION
STORAGE
CONFERENCE RM
OFFICE 1
G
C
O R
R
ID
O R
G023
CORRIDOR
G041
BREAK ROOM
G039
OFFICE
G032
OFFICE
G
B
LO
O
D /B
IO
LO
G
IC
FR
E
E
ZE
R /F
R
ID
G E
G035
OFFICE
G037
OFFICE
G040
IRB
G038
EXAM ROOM
G036
EXAM ROOM
G034
EXAM ROOM
G
C
O R
R
ID
O R
G033 Waiting
G021
CORRIDOR
G030
OFFICE
G028
COPY ROOM
G031
RCO
G
C
O R
R
ID
O R
G025
FEMALE
TOILET
G026
MALE
TOILET
G029
MECH
ROOM
G083
OFFICE
G043
COPY ROOM
G051
BREAK ROOM
G046
CORRIDOR
G047
CORRIDOR
G052
M. TOILET
G050
F. TOLET
G048
CORRIDOR
G053
OFFICE
G049
OFFICE
G054
OFFICE
G014
OFFICE
G015
OFFICE
G019A
FEC
G068
FEC
G059
RECORDS STORAGE
G017
FEC
G069
MECHANICAL ROOM
G070
BILLIARD ROOM
G080
OFFICE
G086
BREAK ROOM
G072
FAC
G008
PIPE SPACE
G002
MECHANICAL ROOM
G019
CORRIDOR
G001
STAIRS
190 G003
STOR.
G
P
IP
E T
R E
N C
H
G004
STORAGE
G006
STORAGE
G007
STORAGE
G010
TOILET
G011
TOILET
G012
STORAGE
G063A
STORAGE
G027
FAN ROOM
G016
WAITING
G042
OPEN OFFICE
G018
OFFICE
G066
CORRIDOR
G071
BOWLING ALLEY
G079
MECHANICAL
G078
STAIRS
G075
CORRIDOR
G073
PIPE SPACE
G076
STOR.
G074
PEST CONT.
G077
CORRIDOR
G087
STORAGE
G085
STORAGE
F
F
F
F
F
F
F
F
F
F
F
F F S
F
F F S
F S
F
F
F S
F S
F S F
FF
F
F
F
F S
F S
F S
F S
F S
F
F
FF
S
F
F S
F S
F
F
F S
F F
FF
S
F S
F
F
F
F S
F
F S
F S
F
F S
F S
F S
F
SF
F S
FFB
NAC
XN XN
XN
XN
G062
MECHANICAL ROOM
G063
CHLORINE ROOM
F F S
F
F S
F XN XN
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD121
BLDG 6 GROUND FLOOR AND BASEMENT
EXISTING/DEMOLITION 6
1 BLDG 6 GROUND FLOOR
3/32" = 1'
2 BLDG 6 BASEMENT
3/32" = 1'
ASSEMBLY OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
PATIENT LIBRARY
OFFICE
OFFICE
SEWING RM
LOUNGE
OFFICE
AMER LEGION
DAV OFFICE
VFW OFFICE
STORAGE
PATIENT LIBRARY
OFFICE
OFFICE
F. TOILET
M. TOILET
MECH RM
F. TLT.
M. TLT.
REC OFFICE
REC OFFICE
OFFICE
OFFICE
ELEC ROOM
LOBBY
LEARNING CENTER
M. TLT
W. TLT.
CANTEEN
STORAGE
BARBER SHOP
WAITING RM
OFFICE
CANTEEN DINING RM
CANTEEN KITCHEN
1082A
CANTEEN STO
1082B
REFRIG
STAIRS
REC STORAGE
1085A
REC STORAGE
REC KITCHEN
SOCIAL ROOM
REC OFFICE
REC OFFICE
GYM
FAC
FAC
OFFICE
STAIRS
LIBRARY OFFICE
CLOSET
STORAGE
STORAGE
OFFICE
OFFICE
EQUIP RM
BRK RM
LOBBY
1042A
STAIRS
VESTIBULE
VESTIBULE
ORCH. STAGE
STAGE
STAIRS HALL
STAIR HALL
FAC
STAIRS
PASSAGEWAY
STAIRS
ELEC CLO
1089B
ELEC CLO
LOBBY
DISH RM
CORR
FAC
1084A
ELECT.
CANTEEN DINING RM
FAC
COATS
UTIL.
FAC
LOBBY
TO FAN RM
TO GRID
M004
FAN ROOM
UPSTAIRS
M005
FAN ROOM
UPSTAIRS
OFFICE
1047A
TOILET
1042B
Stor.
1011A
STORE RM
CORR
FAC
E
LE
C C
L
1098A
FAC
1046A
STORAGE
TELLER
1056A
CLASS ROOM
1056B
CLASS ROOM
LIBRARY WING CENTER WING
T H
E A
T R
E W
E S T
CANTEEN WING
CENTER WING
T H
E A
T R
E W
IN
G
CENTER WING
CENTER WING
ELEVATOR
EQUIP. RM.
MECHANICAL ENG.
STAIRS
MECH. EQUIP.
REC STORAGE
STORAGE
F
F
F
F
F
F
F
F
F
F
F F
F
F
F F
F
F
F
F F
FF
F
F
F S
F S
FF
S
F F S
F
SF
S
F
SF
S
FAAP
F
F S
F S
F
F S
F S
F
KHFS
FF
F
F S
FFF
S
F S
F S
F S
F S
F
F
F
AATPFA
C
P
EPR
EAR
F
F
FF
S
F S
XN
XN
XN
XN
XN
XN
XN
XN
XN XN
XNXN
XN XN XN
XN
XN XN
XD
XD
XD
XR
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD122
BLDG 6 FIRST FLOOR
EXISTING/DEMOLITION 6
1 BLDG 6 FIRST FLOOR
3/32" = 1'
ASSEMBLY OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
KEYED NOTES #
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
1. DEMOLISH EXISTING FACP. EXTEND EXISTING
SLC CIRCUITS TO NEW FACP LOCATION.
2. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).
EXTEND EXISTING NAC AND SPEAKER CIRCUITS
TO NEW NACP AND DAA LOCATION.
1011A
WELLNESS
MECHANICAL
EXAM
STORAGE
77 1023
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
DRIVER TRAINING
BREAK ROOM
EQUIPMENT STORAGE
OFFICE
STORAGE
MECH. RM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
TOILET
LAB
OFFICE/STORAGE
EXAM
EXAM
EXAM
EXAM
MECHANICAL
PROSTHETICS STORAGE
STORAGE
1011A
F. LOCKER
M. LOCKER
HAC
M. TLT
M. TLT
M. LOCKER RM
OFFICE
OFFICE
CHIEF/CONF
OFFICE
OFFICE
TOILET
SHW RM
HAC
TOILET
TOILET
67 1124
GEN STORAGE
ELEC. CLS
EXAM
FAC
WAITING
KINNESIOTHERAPY
RECEPT.
OCC. THERAPY
WORK ROOM
FAC
PIPE SPACE
TLT
OFFICE
CORRIDOR
CORRIDOR
CORRIDOR
LOBBY
CORRIOR
FEC
CORRIOR
CORRIOR
CORRIOR
CORRIDOR
CORRIOR
CORRIOR
1054A
OFFICE
GOO1
MECHANICAL ROOM
PIPE
TOILET
PIPE SPACE
TO BUILDING 10
T O
B U
IL
D
IN
G
F F S
F S
F S
F S F
S F S
F S
F S
F S
F S
F
SF
S
F S
F
FF
F
FFFF
F
F
FA
C
PA
A
TP TC
F
F
F
F
F
F
F
F F
F F
F S
F
F
F
FB
FB
~50'
XN
XN XN
XN
XN
XD
XN
PROSTHETICS
STORAGE GREENHOUSE
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD123
BLDG 7, BLDG 24, BLDG 30
EXISTING/DEMOLITION 7, 24, 30
1 BLDG 7 FIRST FLOOR
3/32" = 1'
2 BLDG 7 BASEMENT
3/32" = 1'
BUSINESS OCCUPANCY - FULLY SPRINKLERED
3 BLDG 24 STORAGE
3/32" = 1' 4 BLDG 30
3/32" = 1' STORAGE OCCUPANCY
NOT SPRINKLERED
STORAGE OCCUPANCY
NOT SPRINKLERED
BUSINESS OCCUPANCY
FULLY SPRINKLERED
INDUSTRIAL OCCUPANCY
FULLY SPRINKLERED
GENERAL NOTES
KEYED NOTES #
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
1. REPLACE FACP. EXISTING BACKBOX/CABINET MAY
BE RE-USED IN-PLACE IF ADEQUATELY-SIZED.
PROVIDE NEW FIBER PATCH PANEL.
2. REPLACE AATP (NOTIFIER XPIQ) WITH NACP AND
DAA. RECONFIGURE NAC AND SPEAKER CIRCUIT
AS REQUIRED.
ELEV MACHINE
ROOM
A001
ELEVATOR 1
S1
ELEVATOR 2
S2
ELEVATOR LOBBY
AC001
EPR
EAR
EST
ESTPSF
F S
F F S F
S
F F
DN
A1
STAIR
A135 PATIENT ROOM 15
A134
DOUBLE PATIENT
ROOM 14
A133
BATHROOM 15
A134A
BATHROOM 14
A133A
SECLUSION
A131
ANTE ROOM
A131A
TLT
A131B
SINGLE PATIENT
ROOM 13
A122
BATHROOM 12
A124A
BATHROOM 13
A122A
SINGLE PATIENT
ROOM 12
A124
DOUBLE PATIENT
ROOM 11
A126
BATHROOM 11
A126A
BATHROOM 10
A129A
DOUBLE PATIENT
ROOM 10
A129
SINGLE PATIENT
ROOM 9
A127
BATHROOM 8
A125A
BATHROOM 9
A127A
PATIENT ROOM 8
A125
SCREENED
PORCH 2
A123
GROUP ROOM
A121
BARIATRIC
BATHROOM 7
A112A
BREAK
A108
LAUNDRY
STORAGE
A110
BARIATRIC
PATIENT ROOM 7
A112
SINGLE PATIENT
ROOM 6
A114
BATHROOM 6
A114A
BATHROOM 5
A116A
SINGLE PATIENT
ROOM 5
A116
DOUBLE PATIENT
ROOM 4
A118
BATHROOM 4
A118A
TV AREA
A117
BATHROOM 3
A115A
DOUBLE PATIENT
ROOM 3
A115
SINGLE PATIENT
ROOM 2
A113
BATHROOM 1
A111A
BATHROOM 2
A113A
PATIENT ROOM 1
A111
SCREENED
PORCH 1
A109LAUNDRY
A107
SECURE
VESTIBULE
A101
FAMILY
CONFERENCE
A102
CONSULT 1
A104
HALL
AC110
CONSULT 2
A106
OFFICE 7
A158
OFFICE 3
A159
OFFICE 4
A160
OFFICE 5
A161
ELEVATOR
VESTIBULE
A175
OFFICE 2
A156
OFFICE 1
A155
STAFF BREAK
A154
OFFICE 12
A153
OFFICE 11
A152
OFFICE 10
A151
OFFICE 9
A150 WARD CLERK
A120C
WORK ROOM
A120B
TEAM ROOM
A141
CLEAN STORAGE
A142
ST TLT
A144B
ST TLT
A144A
STAFF LOCKERS
A144
MEDICATION
A120A
CLEAN LINEN
A140
QUIET ROOM
A130SHOWER
A132
CORRIDOR
AC104
ELECTRICAL 3
A146
COMM
A171
ELEVATOR 2
S2
ELEVATOR 1
S1
OFFICE 8
A157
OFFICE 6
A162
PATIENT
PROPERTY
A163
DAY
AC102B
DINING
AC103A
DAY
AC103B
SERVICE
CORRIDOR
AC106
PUBLIC
CORRIDOR
AC111
SOILED UTILITY
A145 HAC
A143
AIR HANDLER
ROOM
A172
LOBBY
A100
EXAM
A103
SERVING
A105
ELEVATOR
MACHINE ROOM
A170
STAIR 1
AS101
HALL
AC105
NURSING
STATION
A120
PATIENT
CORRIDOR
AC103
HALL
AC107
HALL
AC108
HALL
AC109
PATIENT
CORRIDOR
AC102 DINING
AC102A
ELECTRICAL 1
A173
ELECTRICAL 2
A174
GROUP ROOM
CLOSET
A121A
PATIENT
CORRIDOR
AC101
CORRIDOR
AC104A
A105A
ABOVE
SUB PORCH
(GROUP)
A121B
TV AREA
A128
STANDPIPE
CHASE
AS101A
ELEVATOR
P1
ELEVATOR
P2
ENTRY
VESTIBULE
SECURITY
OPEN TO ABOVE
OPEN
TO
ABOVE
HAS OFFICE
AL
IG
N
UP
TO BUILDING 4
TO BUILDING 4
UP
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S F
S F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S F
S
F S F
S F S
F S
F S
F S
F S
F F
F F F
F
F
F
F
FF F
F
F
F
F
FF
F S
F
FF
FA
C
P
F S
F S
F
F
F F
F S
F S
F F F
F S
F S
F
F S
F
F
SF
F
SF
FACP
F F
F
F F
F F
F
F S
F S
F S
F S
F S
F S
F
F F
F
F
F F F
F S
F F
F
F S
F
F
F
F S
F S
F
F
F
F F S
FC
F F
F
N A
C
EPR
EAR
EICN
EST
ESTPS
EST
EST
EST
~15'
~15'
1. FIRE ALARM SYSTEM SHALL NOT BE DEMOLISHED.
ALL DEVICES AND COMPONENTS SHALL REMAIN.
SHOWN HERE FOR REFERENCE ONLY.
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD124
BLDG 8 GROUND AND FIRST FLOOR
EXISTING/DEMOLITION 8
1 BLDG 8 GROUND FLOOR
3/32" = 1'
2 BLDG 8 FIRST FLOOR
3/32" = 1'
HEALTH CARE OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
UPDN
DN
DOUBLE
PATIENT ROOM
A229
TV AREA
A228
SCREENED
PORCH 1
A209
PATIENT ROOM
A211
BATHROOM 1
A211A
SINGLE
PATIENT ROOM
A213
BATHROOM 2
A213A DOUBLE
PATIENT ROOM
A215
BATHROOM 3
A215A
TV AREA
A217
DOUBLE
PATIENT ROOM
A218
BATHROOM 4
A218A
SINGLE
PATIENT ROOM
A216
BATHROOM 5
A216A
SINGLE
PATIENT ROOM
A214
BATHROOM 6
A214A
BARIATRIC
PATIENT ROOM
A212
BARIATRIC
BATHROOM 7
A212A
Clean Linen A210
Nourish A208
GROUP ROOM
A221
GROUP ROOM
CLOSET
A221A
SUB PORCH
(GROUP)
A221B
SCREENED
PORCH 2
A223
PATIENT ROOM
A225
SINGLE
PATIENT ROOM
A227
BATHROOM 9
A227A
BATHROOM 8
A225A
BATHROOM 10
A229A
BATHROOM 11
A226A
DOUBLE
PATIENT ROOM
A226
SINGLE
PATIENT ROOM
A224
BATHROOM 12
A224A
BATHROOM 13
A222A
SINGLE
PATIENT ROOM
A222
TLT
A231B
ANTE ROOM
A231A
SECLUSION
A231DOUBLE
PATIENT ROOM
A233
BATHROOM 14
A233A
BATHROOM 15
A234A
PATIENT ROOM
A234
ELECTRICAL 3
A246
SOILED UTILITY
A245
SHOWER
A232
HAC
A243
QUIET ROOM
A230
STAFF
LOCKERS
A244
STAFF BREAK
A254
OFFICE 12
A253
OFFICE 11
A252
OFFICE 10
A251
OFFICE 9
A250
CLEAN
STORAGE
A242
TEAM ROOM
A241 WORK ROOM
A220B
WARD CLERK
A220C
MEDICATION
A220A
ST TLT
A244B
ST TLT
A244A
NURSING
STATION
A220
OFFICE 1
A255
OFFICE 2
A256 OFFICE 8
A257
PATIENT
PROPERTY
A263
OFFICE 7
A258
OFFICE 6
A262
OFFICE 3
A259
OFFICE 4
A260
OFFICE 5
A261 FAMILY
CONFERENCE
A202
CONSULT 1
A204
CONSULT 2
A206
SERVING
A205
EXAM
A203
SECURE
VESTIBULE
A201
COMM
A271
AIR HANDLER
ROOM
A272
DAY
AC202B
DINING
AC202A
DINING
AC203A
DAY
AC203B
PATIENT
CORRIDOR
AC202
LAUNDRY
A207
PATIENT
CORRIDOR
AC203
HALL
AC207
HALL
AC208
HALL
AC210
HALL
AC209
CORRIDOR
AC204
CORRIDOR
AC204A
HALL
AC205 CLEAN LINEN
A240
SERVICE
CORRIDOR
AC206
ELEVATOR
VESTIBULE
A275
STORAGE
A276
STORAGE
A273A
FEMALE PUBLIC
TOILET
A277
STAIR 1
AS201
EXIST.
ELEVATOR 2
P2
EXIST.
ELEVATOR 1
P1
MALE PUBLIC
TOILET
A278
GROUP ROOM
A273
PUBLIC
CORRIDOR
AC211
ELEVATOR
VESTIBULE
A274
EXIST ELEV
S1
EXIST ELEV
S2
STAIR 2
AS202
HAC
A280PUBLIC
CORRIDOR
AC212
A205-A
OPEN TO BELOW
OPEN TO BELOW
FUTURE
CONFERENCE
ROOM
A279
FF
F S
F
F S
F S
F S
F S
F S
F S
F S
F
SF
S F S
F S
F S
F S
F S
F S
F S F
S
F S
F S
F
SF
S F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S F
S
F S
F
F
F
F
F
F
F
F F
F F
F
F
F
F
F
F
F
F
F F
F
FF
F
F
F
F
F S
F S
F S
F S
F S
F S
F S
F S
FF
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F S
F
F S
F
F S
FC
F
F
N A
C
1. FIRE ALARM SYSTEM SHALL NOT BE DEMOLISHED.
ALL DEVICES AND COMPONENTS TO REMAIN. SHOWN
HERE FOR REFERENCE ONLY.
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD125
BLDG 8 SECOND FLOOR
EXISTING/DEMOLITION 8
1 BLDG 8 SECOND FLOOR
3/32" = 1'
HEALTH CARE OCCUPANCY - FULLY SPRINKLERED
DEMOLITION NOTES
SINGLE
PATIENT ROOM
A316
BATHROOM 5
A316A
SINGLE
PATIENT ROOM
A314
BATHROOM 6
A314A
BARIATRIC
PATIENT ROOM
A312
PAT TLT
A310
CLEAN
LINEN
A308
GROUP ROOM
CLOSET
A321A
EXERCISE
ROOM
A323
PATIENT ROOM
A325
SINGLE
PATIENT ROOM
A322
TLT
A331B
ANTE ROOM
A331A
QUIET ROOM
A330
OFFICE 9
A350
TEAM ROOM
A341 WORK ROOM
A320B
MEDICATION
A320A
DAY
AC302B
WARD CLERK
A320C
GROUP ROOM
A321
BARIATRIC
BATHROOM
A312A
DINING
AC302A
CLEAN LINEN
A340
DINING
AC303A
NURSE
STATION
A320
PATIENT
CORRIDOR
AC303
SECLUSION
A331
DN
AIR HANDLER
ROOM
A372
STORAGE
A373A
MALE PUBLIC
TOILET
A378
GROUP ROOM
A373
EXIST
ELEVATOR 1
P1
EXIST.
ELEVATOR 2
P2
ELEVATOR
VESTIBULE
A374
PUBLIC
CORRIDOR
AC312
STAIR 2
AS302
HAC
A380
FEMALE TOILET
A377
EXIST ELEV
S1
EXIST ELEV
S2
DOUBLE
PATIENT ROOM
A329
TV AREA
A328
SCREENED
PORCH 1
A309
PATIENT ROOM
A311
BATHROOM 1
A311A
SINGLE
PATIENT ROOM
A313
BATHROOM 2
A313A DOUBLE
PATIENT ROOM
A315
BATHROOM 3
A315A
TV AREA
A317
DOUBLE
PATIENT ROOM
A318
BATHROOM 4
A318A
SINGLE
PATIENT ROOM
A327
BATHROOM 9
A327A
BATHROOM 8
A325A
BATHROOM 10
A329A
BATHROOM 11
A326A
DOUBLE
PATIENT ROOM
A326
SINGLE
PATIENT ROOM
A324
BATHROOM 12
A324A
BATHROOM 13
A322A
DOUBLE
PATIENT ROOM
A333
BATHROOM 14
A333A
BATHROOM 15
A334A
ELECTRICAL 3
A346
SOILED UTILITY
A345
SHOWER
A332
HAC
A343
STAFF
LOCKERS
A344
STAFF BREAK
A354
OFFICE 12
A353
OFFICE 11
A352
OFFICE 10
A351
CLEAN
STORAGE
A342
ST TLT
A344B
ST TLT
A344A
OFFICE 1
A355
OFFICE 2
A356 OFFICE 8
A357
PATIENT
PROPERTY
A363
OFFICE 7
A358
OFFICE 6
A362
OFFICE 3
A359
OFFICE 4
A360
OFFICE 5
A361 FAMILY
CONFERENCE
A302
CONSULT 1
A304
CONSULT 2
A306
EXAM
A303
LAUNDRY
A307
HALL
AC307
HALL
AC308
HALL
AC310
HALL
AC309
CORRIDOR
AC304A
HALL
AC305
SERVICE
CORRIDOR
AC306
ELEVATOR
VESTIBULE
A375
PATIENT ROOM
A334
PUBLIC
CORRIDOR
AC311
STAIR 1
AS301
COMM
A371
SECURE
VESTIBULE
A301
SERVING
A305
CORRIDOR
AC304
DAY
AC303B
PATIENT
CORRIDOR
AC302
A305-A
F S
F
F S
F S
F
SF
S F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F
FC
F S
F S
F S
F S
F S
F S
F S
F S
F S F
S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F S
F
SF
S
F S
F S
F S
F S
F S
F S
F S
F
SF
S F S
F S
F S
F
F
F
F
F
F
F
F
F
F
F
F
F F
F S
F
F
F
F
F F
F
F
F
F
F F
F
F
F
F
F S
F
F
F
F S
F
F F
F
F
F
FF
F
F
F
F
F S
F
F F
F F
F
F F
F
F
F F
N A
C
1. FIRE ALARM SYSTEM SHALL NOT BE DEMOLISHED.
ALL DEVICES AND COMPONENTS TO REMAIN. SHOWN
HERE FOR REFERENCE ONLY.
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD126
BLDG 8 THIRD FLOOR
EXISTING/DEMOLITION 8
1 BLDG 8 THIRD FLOOR
3/32" = 1'
HEALTH CARE OCCUPANCY - FULLY SPRINKLERED
DEMOLITION NOTES
G03
LARGE CLASSROOM
G14B
M. TOILET
G17
OPEN OFFICE
G17A
STORAGE
G18
MECH ROOM
G18A
MECH
G19
MECHANICAL EQUIPMENT
G12
OFFICE
G11
OFFICE
130G10
OFFICE
G09
OFFICE
G06
OFFICE
G01
OFFICE/DINING
G02
KITCHEN
G07 Office
G05 Bathrm
G14
WAITING
G13
OFFICE
G14A
F. TOILET
G21
ENG
G20
ENG
G08
CORRIDOR
G22
CORRIDOR
G15
FAC
G16
STAIR
G04
CORRIDOR
G26
BREAK/OFFICE
G25
MECHANICAL RM
G16A
STORAGE
G03B
SPRINKLER RM
ENTRY
VESTIBULE
G001
CORRIDOR
G002G002
DN
MAIN
ELEC
G-40 Crawl
Space
Crawl 2
F
F
FACP
F F S
FB
F S
F S
F
FA
A
PF
NACP
DAA
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD127
BLDG 11 GROUND FLOOR
EXISTING/DEMOLITION 11
1 BLDG 11 GROUND FLOOR
3/32" = 1'
BUSINESS OCCUPANCY - FULLY SPRINKLERED
GENERAL NOTES
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND NO TAG ARE
EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
RESIDENT
ROOM
A103
RESIDENT
ROOM
A102
RESIDENT
BATHROOM
A104
RESIDENT
BATHROOM
A105
RESIDENT
ROOM
A107
RESIDENT
ROOM (2)
A106
RESIDENT
ROOM
A108
RESIDENT
ROOM
A109
RESIDENT
BATHROOM
A111
RESIDENT
BATHROOM
A110
OFFICE -
AT(2)
A112
STAFF
WORK
AREA
A114
NUTRITION
A133
LAUNDRY
A135
RESIDENT
BATHROOM
A138
RESIDENT
ROOM (2)
A140
RESIDENT
ROOM
A142
RESIDENT
BATHROOM
A144
RESIDENT
ROOM
A146
RESIDENT
ROOM
A147
RESIDENT
BATHROOM
A145
RESIDENT
ROOM
A143
RESIDENT
ROOM
A141
RESIDENT
BATHROOM
A139
RESIDENT
ROOM
A137
REC
B108
WOMEN'S
TOILET
A117MEN'S
TOILET
A116
TELECOM
A115
RESIDENT
ROOM
A113
PHONE
ROOM
A136
NURSE
MGR.
B106
OFFICE
B107
VESTIBULE
A131
VESTIBULE
A131
GROUP
B110
DINING
B117
KITCHEN
B114
PANTRY
B116
OFFICE -
PA
B125
EXAM
B124
STAFF
WORK
AREA
B126
MEDS
B127
ELEVATOR
B128
STAIR
B131
STORAGE
B132
WAITING
B146
RECEPTION
B145
SHOWER
B144
EXAM
B141
OFFICE -
DR
B140
FAMILY
ROOM
B150
FAMILY
ROOM
B151
PEDS
FAMILY
ROOM
B152
WOMEN'S
TOILET
B134
MEN'S
TOILET
B136
WOMEN'S
TOILET
B137
WOMEN'S
LOUNGE
B138
ELEC
B130
CODE
SUPPLY
B129
ADMIT
NURSE
B118
OFFICE
B120
SMALL
GROUP
B122
OFFICE -
MANAGER
B123
GROUP
B153
GROUP
B154
FITNESS
CENTER
B155
CONFERENCE
B160
JANITOR
B115
STAFF
WOMEN'S
TOILET
B112
STAFF
MEN'S
TOILET
B111
BREAK
B113
VESTIBULE
B121
TOILET
B143
TOILET
B142
MEN'S
TOILET
B133
WC
STORAGE
B135
OFFICE -
SW
B166
OFFICE -
SW
B165
OFFICE -
SW
B164
TELECOM
B162
STORAGE
B163
GROUP
B109
ELEVATOR
LOBBY
B147
MEN'S
TOILET
C115
WOMEN'S
TOILET
C116
TELECOM
C114
RESIDENT
ROOM
C112
RESIDENT
BATHROOM
C110
RESIDENT
ROOM
C108
RESIDENT
ROOM (2)
C106
RESIDENT
BATHROOM
C104
RESIDENT
ROOM
C102 RESIDENT
ROOM
C103
RESIDENT
BATHROOM
C105
RESIDENT
ROOM
C107
RESIDENT
ROOM
C109
RESIDENT
BATHROOM
C111
OFFICE -
AT (2)
C113
STAFF
WORK
AREA
C117
DEN
C120
LIBRARY
C119
ELEC
C124
SOILED
UTILITY &
LINEN
C122
CLEAN
SUPPLY
C123
RESIDENT
ROOM
C126
RESIDENT
BATHROOM
C128
RESIDENT
ROOM
C130
RESIDENT
ROOM
C129
RESIDENT
BATHROOM
C127
RESIDENT
ROOM
C125
VESTIBULE
C131
CLEAN
LINEN
C149
H.A.C.
C150
OFFICE
C151
RESIDENT
ROOM
C155
RESIDENT
BATHROOM
C157
RESIDENT
ROOM
C159
OFFICE
C152
RESIDENT
BATHROOM
C153
RESIDENT
ROOM
C154
RESIDENT
ROOM
C156
RESIDENT
BATHROOM
C158
RESIDENT
ROOM
C160
RESIDENT
ROOM
C162
RESIDENT
BATHROOM
C164
RESIDENT
ROOM
C166
RESIDENT
ROOM
C165
RESIDENT
BATHROOM
C163
RESIDENT
ROOM
C161
RESIDENT
ROOM
C146
RESIDENT
BATHROOM
C144
RESIDENT
ROOM
C142
RESIDENT
ROOM (2)
C140
RESIDENT
BATHROOM
C138
LAUNDRY
C135
NUTRITION
C133
LIVING
ROOM
C134
PHONE
ROOM
C136
RESIDENT
ROOM
C137
RESIDENT
BATHROOM
C139
RESIDENT
ROOM
C141
RESIDENT
ROOM
C143
RESIDENT
BATHROOM
C145
RESIDENT
ROOM
C147
STORAGE
B156
STAFF
BREAK
B157
MEN'S
STAFF
TOILET
B158
WOMEN'S
STAFF
TOILET
B159
OFFICE -
SW
B167
DN
ELEC
AXXX
F
F
F F
F
FFF
F
F
F
F
F F
F
F
F
F
F F
F
F
F F
F
F F
F F
F F
F F
FF
F
F
F
F F
F
F F
F
F
F F F
F
F F
F
F F
F
F
F
F F
F
F
F F
F
F
F
F
F
F
F
FF
F
F
F
F
F
F F
FF
F
F F
F
F
F
F F
F F
F
F
F
F
F
F F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
FF
F F F F
F
F F
FFF
FF
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
RL
F
FF
F
F F
F
F
F F
F F FF
F
F
F
F
F
F
F
F
F FA
A
P
F
F
F
F F
F
F F
F F
FACP
F
F
F
F
F
F
EC
M A
TC
H
LI
N
E
XN
XN
XN
XN
XN
XN
XN
XN
XN
XN
XN
XN
XN
XN
LIBRARY
A119
DEN
A120
LIVING
ROOM
A134
CONFERENCE ROOM
F F F
F
F
F
F
F
M A
TC
H
LI
N
E
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD128
BLDG 11 FIRST FLOOR
EXISTING/DEMOLITION 11
1 BLDG 11 FIRST FLOOR (ALL DEVICES TO REAMIN)
3/32" = 1'
FULLY SPRINKLERED
DEMOLITION NOTES
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATIONS SHALL BE ACCESSIBLE, WITH
HEIGHT ACCORDING TO NOTES AND
SPECIFICATIONS.
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORRIDOR
GROUP ROOM
GROUP ROOM
BREAK RM
93 101
BATHROOM
BATHROOM
HOUSE KEEPING
ELEC
OFFICE
WAITING ROOM
RECEPTION
OFFICE
OFFICE
STAFF BATH
STAFF BATH
R R R R R R
RRRRRR
R
R
R R
R
R
F
F
F
F
F F
F
F
FA
C
P
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORRIDOR
GROUP ROOM
GROUP ROOM
BREAK RM
BATHROOM
BATHROOM
EMS
ELEC
OFFICE
WAITING ROOM
RECEPTION
OFFICE
OFFICE
STAFF BATH
STAFF BATH
R R R R
R
F F
F
F S
F
FF
F
F
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CALL CENTER
GROUP ROOM
Med/Inject
BATHROOM
BATHROOM
EMS
ELEC
BREAK RM
WAITING ROOM
RECEPTION
OFFICE
OFFICE
STAFF BATH
STAFF BATH
CORRIDOR
F F
F
F
F S
F S
F S
F
F
F
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD129
BLDG 11A, BLDG 11B, BLDG 11C
EXISTING/DEMOLITION 11
1 BLDG 11A
1/8" = 1' 1 BLDG 11B
1/8" = 1' 1 BLDG 11C
1/8" = 1'
BUSINESS OCCUPANCY - NOT SPRINKLERED
GENERAL NOTES
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
CONFERENCE ROOM
KITCHEN
ELECTRICAL 109
HW TANK
ARMORY
SECRETARY
HALLWAY
HALLWAY
COMMUNICATION
102B
KITCHEN
CLOS.
TOILET
CLOS.
STAIRS
102A
HALLWAY
R
XD
OFFICE
OFFICE
OFFICE
BATH
BATH
CLOSET
CLOSET
OFFICE
LOCKERS
CLOS
CLOSET
CLOSET
CORRIDOR
STAIRS
R
XD
CONFERENCE
KITCHEN
DINING
BEDROOM
JANITOR
ADA TOILET
FEMALE
TOILET
HALL
118 OFFICE
ADA TOILET
LIVING
MECH.
LAUNDRY
COMPUTER
LOBBY
STAIR
MECH.
IT
119SCREENED
PORCH
F
F
F
F
F
F
F
F
F
FF
F
F
F F
F
FA
C
P
XD
XD
XDXD
XD
XD
XD
DN
BEDROOM
BEDROOM
BEDROOM
FEMALE
BEDROOM
TOILET
BEDROOM
BEDROOM
TOILET
TOILET
STORAGE
TOILET
BEDROOM
TOILET
STORAGE
LAUNDRY
HALL
217F
F
FXD XD
CONFERENCE RM
CONFERENCE RM
KITCHEN
KITCHEN
LAUNDRY
LAUNDRY
VESTIBULE
KENNEL
STORAGE
VESTIBULE
TOILET
106A
TOILET
CLOSET
CLOSET
U P
U P
R R
XD XD
M LOCKER RM.
M. BEDROOM
OFFICE
OFFICE
OFFICE
W. BEDROOM / LOCKER
BATH
BATH
PASSAGE
PASSAGE
D N
D N
R R
XD XD
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD130
BLDG 12, BLDG 14W, BLDG 14E
EXISTING/DEMOLITION 12, 14E, 14W
1 BLDG 12 FIRST FLOOR
1/8" = 1'
2 BLDG 12 SECOND FLOOR
1/8" = 1'
3 BLDG 14E FIRST FLOOR
1/8" = 1'
4 BLDG 14E SECOND FLOOR
1/8" = 1'
5 BLDG 14W FIRST FLOOR
1/8" = 1'
6 BLDG 14W SECOND FLOOR
1/8" = 1' RESIDENTIAL OCCUPANCY
FULLY SPRINKLERED
RESIDENTIAL OCCUPANCY
FULLY SPRINKLERED
RESIDENTIAL OCCUPANCY
FULLY SPRINKLERED
RESIDENTIAL OCCUPANCY
FULLY SPRINKLERED
BUSINESS OCCUPANCY
FULLY SPRINKLERED
BUSINESS OCCUPANCY
FULLY SPRINKLERED
GENERAL NOTES
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.
9. FOR BUILDING 14E, STROBES SHOWN AS DEMO
SHALL BE REPLACED WITH SPEAKER-STROBES
IN THE SAME LOCATION.
B01
MECH. ROOM
B02
TRANSFORMER RM
BEDROOM
BEDROOM
BEDROOM
ELECTRICAL ROOM
KITCHEN
LOUNGE
READING ROOM
LOBBY
UNISEX B/R
BEDROOM
LOBBY
LAUNDRY
BEDROOM
BEDROOM
132A
BEDROOM
BEDROOM
BEDROOM
BEDROOM
ENTRY
STAIRS
CLOSET
STAIRS
BATH
BATH
CLOSET
CLOSET
CLOSET
BATH
BATH
BATH
BATH
BATH
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
13 114
CLOSET
CLOSET
105A
CLOSET
149B
FEC
F
F
F
F
F F F
F F
F
F
F
F F
F
F
F
F F
F
F
FFFF
FACPEP
F
FF F
F
F F
FB
FACP
F F
F
F
E P
BEDROOM
BATH
CORRIDOR
STAIRWELL
BEDROOM
CLOSET
BATH
BEDROOM
BEDROOM
BATH
47 216
STORAGE
LA/ OIT
ELECTRIC CLOSET
TELE CLST
BATH
BEDROOM
BATH
BEDROOM
210 203
BEDROOM
BATH
STAIRS
TOILET
BEDROOM
BATH
CLOSET
BEDROOM
LAUNDRY
BEDROOM
KITCHEN
BATH
BEDROOM
BEDROOM
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
F F F F
F
F F F
F
F
F
FF
F
F
F
FF
F
F F
F
F
F
F
F
F
FF
NACP
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked:
Building Number
A/E Project Number
Drawing Number
Drawn:
Revisions: Date
ENGINEERS/ARCHITECT:
W.G. (BILL) HEFNER VAMC
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
659-16-103
Architect
PROJECT LEAD
Fire Alarm, Electrical Engineer
VAMC SALISBURY
1601 Brenner Ave, Salisbury, NC 28144
100% CONSTRUCTION DOCUMENTS
SCBRSB11 DEC 2017
15-447REPLACE/UPGRADE CAMPUS
FIRE ALARM SYSTEM
(919) 858-7420 Consulting Group, PA www.acg-pa.com
Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ
ARCHITECTURAL
23894
SEAL
FD131
BLDG 13 EXISTING/DEMOLITION
2 BLDG 13 SECOND FLOOR
3/32" = 1'1 BLDG 13 FIRST FLOOR
3/32" = 1'
3 BLDG 13 BASEMENT
3/32" = 1'
RESIDENTIAL OCCUPANCY - NOT SPRINKLERED
GENERAL NOTES
1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET IN HALF-TONE AND WITH NO TAG
ARE EXISTING-TO-REMAIN.
2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XD' ARE TO BE
DEMOLISHED.
3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XN' ARE TO BE
REPLACED.
4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN
ON THIS SHEET WITH THE TAG 'XR' ARE TO BE
RELOCATED.
5. SEE CORRESPONDING 'FA' SHEET FOR NEW
DEVICE LOCATIONS.
6. WHERE NEW WALL DEVICES ARE NOT LOCATED
IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE
STAINLESS STEEL BLANK COVER FOR BOX. CUT
OFF CONDUIT ABOVE CEILING AND REMOVE TO
NEAREST JUNCTION BOX.
7. WHERE NEW CEILING DEVICES ARE NOT
LOCATED IN EXACTLY THE SAME LOCATION AS A
PREVIOUSLY-DEMOLISHED DEVICE, REPLACE
CEILING TILE TO MATCH EXISTING TILES.
REMOVE CONDUIT AND WIRE TO THE NEAREST
JUNCTION BOX.
8. REPLACE ALL EXISTING DUCT DETECTORS AND
ASSOCIATED KEY SWITCHES. NEW KEY SWITCH
LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT
ACCORDING TO NOTES AND SPECIFICATIONS.